1. NETWORK CONFIGURATIONS
n definition
Standard IEC 38 defines voltage ratings as follows:
- Low voltage (LV)
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings
are: 400 V - 690 V - 1000 V (at 50 Hz)
- Medium voltage (MV)
For a phase-to-phase voltage between 1000 V and 35 kV. The standard ratings
are: 3.3 kV - 6.6 kV - 11 kV - 22 kV - 33 kV
- High voltage (HV)
For a phase-to-phase voltage between 35 kV and 230 kV. The standard ratings
are: 45 kV - 66 kV - 110 kV - 132 kV - 150 kV - 220 kV.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
25
supply source
HV consumer
substation
internal
production
HV
MV
main MV distribution switchboard
MV load
MV load
MV load
MV internal distribution
network
secondary MV
distribution switchboards
MV
MV
MV
MV
LV
LV
LV
LV
LV switchboards
and LV distribution
LV
load
LV
load
T&D
6 883 427/AE
26
HV busbar
NC
NC
NC
NC
to main MV switchboard
Figure 1-2: single fed HV consumer substation
advantage:
drawback:
N.B.:
Reduced cost
Low availability
the isolators associated with the HV circuit-breakers have not been shown.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
27
devices
operated
by the
utility
NC
source 2
NC
NC
HV busbar
NC
NC
HV
HV
MV
MV
NC
NC
to main MV switchboard
Figure 1-3: dual fed HV consumer substation
operating mode:
- normal:
- disturbed: If one source is lost, the other provides the total power supply.
advantages:
- good availability in that each source can supply the entire network
- maintenance of the busbar possible while it is still partially operating
drawbacks:
- more costly solution than the single power supply system
- only allows partial operation of the busbar if maintenance is being carried out on it
N.B.:
the isolators associated with the HV circuit-breakers have not been shown.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
28
source 2
NC
NC
NC
NO
NO
NC
BB1
coupler
NC or NO
HV double
busbar
BB2
NC
NO NC
NO NO
Out1
NC
Out2
NC
NC NO
NC
Out3
NC
Out4
NC
HV
HV
MV
MV
NC
NC
to main MV switchboard
operating mode:
- normal:
- disturbed: If one source is lost the other provides the total power supply.
If a fault occurs on a busbar (or maintenance is carried out on it), the bus
coupler circuit-breaker is tripped and the other busbar feeds all the outgoing
lines.
advantages :
- good supply availability
- highly flexible use for the attribution of sources and loads and for busbar maintenance
- busbar transfer possible without interruption (when the busbars are coupled, it is possible to
operate an isolator if its adjacent isolator is closed).
drawback:
- more costly in relation to the single busbar system
N.B.:
the isolators associated with the HV circuit-breakers have not been shown.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
30
overhead line
NC
The substation is fed by a single circuit tee-off from an MV distribution (cable or line). Up to
transformer ratings of 160 kVA this type of MV service is very common in rural areas. It has
one supply source via the utility.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
31
NC
NC
NC
underground
cable ring main
Ring main units (RMU) are normally connected to form an MV ring main or interconnectordistributor, such that the RMU busbars carry the full ring main or interconnector current.
This arrangement provides the user with a two-source supply, thereby reducing considerably
any interruption of service due to system faults or switching operations by the supply authority.
The main application for RMU's is in public-supply MV underground cable networks in urban
areas.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
32
NC
NO
NC
parallel
underground-cable
utility
When an MV supply connection to two lines or cables originating from the same busbar of a
substation is possible, a similar MV switchboard to that of an RMU is commonly used.
The main operational difference between this arrangement and that of an RMU is that the two
incoming panels are mutually interlocked, such that only one incoming switch can be closed at
a time, i.e. its closure prevents that of the other.
On loss of power supply, the closed incoming switch must be opened and the (formerly open)
switch can then be closed. The sequence may be carried out manually or automatically. This
type of switchboard is used particularly in networks of high load density and in rapidly
expanding urban areas supplied by MV underground cable systems.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
33
NC
NC
NC
NC
MV
MV
NC
NC
CT
NC
VT
LV
LV
MV feeders
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
34
the isolators and drawout systems which allow maintenance to be carried out on the installation
have not been shown on the diagrams.
MV feeders
operation: if the supply source is lost, the busbar is put out of service until the fault is
repaired.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
35
NC
source 2
NC or NO
MV busbar
MV feeders
operation: both sources can operate in parallel or one source can back up the other. If a fault
occurs on the busbar (or maintenance is carried out on it), the outgoing feeders are no longer
fed.
source 2
NC
NC or NO
MV busbar
MV feeders
Figure 1-11: 2 bus sections with coupler, 2 supply sources
operation: the coupler circuit-breaker can be held closed or open. If it is open, each source
feeds one bus section. If one source is lost, the coupler circuit-breaker is closed and the other
source feeds both bus sections.
If a fault occurs on a bus section (or maintenance is carried out on it), only one part of the
outgoing feeders is no longer fed.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
36
source 1
source 2
NC or NO
NC
source 3
NC
MV busbar
MV feeders
operation: the three sources can operate in parallel or one source can back up the other two.
If If a fault occurs on a bus section (or maintenance is carried out on it), the outgoing feeders
are no longer fed.
source 3
source 2
NC
NC
NC or NO
NC
NC or NO
MV busbar
MV feeders
operation: both bus coupler circuit-breakers can be kept open or closed. If they are open,
each supply source feeds its own bus section. If one source is lost, the associated coupler
circuit-breaker is closed, one source feeds 2 bus sections and the other feeds one bus section.
If a fault occurs on one bus section (or if maintenance is carried out on it), only one part of the
outgoing feeders is no longer fed.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
37
source 2
NC
NC
BB1
coupler
NO
BB2
NC
NC
Out1
Out2
NC
NC
Out3
Out4
MV double
busbar
MV feeders
operation: The coupler circuit-breaker is held open during normal operation. Each source can
feed one or other of the busbars via its two drawout circuit-breaker cubicles. For economic
reasons, there is only one circuit-breaker for the two drawout cubicles which are installed
alongside one another. It is thus easy to move the circuit-breaker from one cubicle to the other.
Thus, if source 1 is to feed busbar BB2, the circuit-breaker is moved into the other cubicle
associated with source 1.
The same principle is used for the outgoing feeders. Thus, there are two drawout cubicles and
only one circuit-breaker associated with each outgoing feeder. Each outgoing feeder can be
fed by one or other of the busbars depending on where the circuit-breaker is positioned. For
example, source 1 feeds busbar BB1 and feeders Out1 and Out2. Source 2 feeds busbar BB2
and feeders Out3 and Out4.
If one source is lost, the coupler circuit-breaker is closed and the other source provides the
total power supply.
If a fault occurs on one of the busbars (or maintenance is carried out on it), the coupler circuitbreaker is opened and each circuit-breaker is placed on the busbar in service, so that all the
outgoing feeders are fed.
The drawback of the "duplex" system is that it does not allow automatic switching. If a fault
occurs, each changeover lasts several minutes and requires the busbars to be de-energized.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
38
n 2 busbars, 2 connections per outgoing feeder, 2 supply sources (see fig. 1-15)
source 1
source 2
NC
NC
NC
NO
NO
NC
BB1
coupler
NO
MV double
busbar
BB2
NO
NC NO
Out1
NC NC
Out2
NO NC
Out3
NO
Out4
MV feeders
operation: the coupler circuit-breaker is held open during normal operation. Each outgoing
feeder can be fed by one or other of the busbars depending on the state of the isolators which
are associated with it and only one isolator per outgoing feeder must be closed.
For example, source 1 feeds busbar BB1 and feeders Out1 and Out2.
Source 2 feeds busbar BB2 and feeders Out3 and Out4.
If one source is lost, the coupler circuit-breaker is closed and the other source provides the
total power supply.
If a fault occurs on a busbar (or maintenance is carried out on it), the coupler circuit-breaker is
opened and the other busbar feeds all the outgoing feeders.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
39
source 1
source 2
NC
NC
NC
NO
NO
NC
BB1
NO
NO
NC
NO NC
Out1
NO
CB1
NO
CB2
2 MV double
NO bus switchboards
NO
Out2
NC NO
Out3
NC
BB2
Out4
MV feeders
operation: this arrangement is almost identical to the previous one (2 busbars, 2 connections
per feeder, 2 supply sources). The splitting up of the double busbars into two switchboards
with coupler (via CB1 and CB2) provides greater operating flexibility. Each busbar feeds a
smaller number of feeders during normal operation.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
40
source 2
NC
NO
main MV switchboard
switchboard1
switchboard2
MV
MV
LV
LV
Figure 1-17: MV single fed radial network
- the transformers and switchboards 1 and 2 are fed by a single source and there is no back-up
supply
- this structure should be used when availability is not a high requirement and it is often adopted
for cement works networks.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
41
source 2
NC
NC
NO
main MV switchboard
NC
NC
NO
NC
NC
NC
switchboard1
MV
NC
NO
LV
switchboard2
MV
MV
LV
LV
- switchboards 1 and 2 are fed by 2 sources with no coupler, the one backing up the other
- availability is good
- the fact that there is no source coupler for switchboards 1 and 2 renders the network less
flexible to use.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
42
source 1
NC
source 2
NC
NO
NC
NC
NC
NC
NC
main MV switchboard
NC
NO
switchboard1
NC
NC
NO
switchboard2
MV
LV
Switchboards 1 and 2 are fed by 2 sources with coupler. During normal operation, the bus
coupler circuit-breakers are open.
- each bus section can be backed up and fed by one or other of the sources
- this structure should be used when good availability is required and it is often adopted in the
iron and steel and petrochemical industries.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
43
n loop system
This system is suitable for widespread networks with large future extensions.
There are two types depending on whether
operation.
source 2
NC
NC or NO
A
NC
NC NC
NO NC
switchboard 1
MV
LV
main MV switchboard
NC
switchboard 2
MV
LV
switchboard 3
MV
LV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
44
source 2
NC
NC
NC
NC NC
NC NC
switchboard 1
MV
LV
main MV switchboard
NC
switchboard 2
MV
LV
switchboard 3
MV
LV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
45
source 2
NC
NC or NO
NC
main MV switchboard
NC
NC
switchboard 1
MV
LV
switchboard 2
MV
LV
switchboard 3
MV
LV
NO
NC
NO
NO
NC
Figure 1-21: MV parallel feeder network
- this structure is suitable for widespread networks with limited future extensions and which
require good availability.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
46
MV
LV
S1
S2
S3
Switchboards S1, S2 and S3 have only one supply source. The network is said to be of the
arborescent radial type.
If a switchboard supply source is lost, the switchboard is put out of service until the supply is
restored.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
47
source 2
MV
MV
LV
LV
source 3
CB1
CB2
NC
NC
S1
MV
LV
CB3
CB4
NO
NC
S2
Switchboard S1 has a dual power supply with no coupler via 2 MV/LV transformers.
Operation of the S1 power supply :
- both sources feed switchboard S1 in parallel.
- during normal operation only one circuit-breaker is closed (CB1 or CB2).
Switchboard S2 has a dual power supply with no coupler via an MV/LV transformer and
outgoing feeder coming from another LV switchboard.
Operation of the S2 power supply:
- one source feeds switchboard S2 and the second provides a back-up supply.
- during normal operation only one circuit-breaker is closed (CB3 or CB4)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
48
source 1
source 2
MV
MV
LV
LV
CB1
S1
NC
CB2
NC
source 3
NO
MV
CB3
NC
LV
CB4
S2
NC
NC
CB5
NO
CB6
Switchboard S1 has a dual power supply with coupler via 2 MV/LV transformers.
Operation of the S1 power supply: during normal operation, the coupler circuit-breaker CB3 is
open. Each transformer feeds a part of S1. If a supply source is lost, the circuit-breaker CB3 is
closed and a single transformer feeds all of S1.
Switchboard S2 has a dual power supply with coupler via an MV/LV transformer and an
outgoing feeder coming from another LV switchboard.
Operation of the S2 power supply: during normal operation, the circuit-breaker CB6 is open.
Each source feeds part of S2. If a source is lost, the coupler circuit-breaker is closed and a
single source feeds all of S2.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
49
source 2
source 3
MV
MV
LV
LV
NC
NC
NC
NO
S1
Switchboard S1 has a triple power supply with no coupler via 2 MV/LV transformers and an
outgoing feeder coming from another LV switchboard.
During normal operation, the switchboard is fed by 2 transformers in parallel. If one or both of
the transformers fail, switchboard S1 is fed by the outgoing feeder coming from another
switchboard.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
50
source 2
source 3
MV
MV
LV
LV
NC
NC
NC
NC
NO
NO
S1
CB1
CB2
Switchboard S1 has a triple power supply with coupler via 2 MV/LV transformers and an
outgoing feeder coming from another LV switchboard.
During normal operation, the two coupler circuit-breakers are open and switchboard S1 is fed
by 3 supply sources.
If one source fails, the circuit-breaker of the associated source is closed and the incoming
circuit-breaker of the source that has been lost is tripped.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
51
MV
LV
NC
S1
CB1
NC
NO
CB2
S2
mains/standby
priority circuits
During normal operation CB1 is closed and CB2 open. Switchboard S2 is fed by the
transformer. If the main source is lost, the following steps are carried out:
1. The mains/standby changeover switch is operated and CB1 is tripped.
2. Load shedding if necessary of part of the loads on the priority circuit in order to limit the load
impact on the generator.
3. Start-up of the generator.
4. CB2 is closed when the frequency and voltage of the generator are within the required
ranges.
5. Reloading of loads which may have been shed during step 2.
Once the main source has been restored, the mains/standby changeover device switches the
S2 supply to the mains and the generator is stopped.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
52
source 2
MV
MV
TR1
TR2
LV
CB4
NC
NC
LV
CB5
G
S2
G
S3
NO
CB1
NC
CB2 mains / standby
NO
CB3
S1
priority circuits
Figure 1-28: 2 transformers and 2 generators
During normal operation, the coupler circuit-breaker CB1 is open and the mains/standby
changeover device is in position CB2 closed and CB3 open. Switchboard S1 is fed by
transformer TR2.
If source 2 is lost or there is a breakdown on TR2, the S1 (and part of S2) standby supply is
given priority by transformer TR1, after reclosing of the coupler circuit-breaker CB1.
The generators are only started-up after the loss of the 2 main supply sources or the S2
busbar.
The steps for saving the priority circuit supply are carried out in the same way as in
example 1.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
53
NO
(4) static contactor
NC
network 2
supply network
incoming
feeders
network 1
(8) switch
NC
~
_
(7) switch
(1) rectifieror
charger
circuit-breaker
NC
~
(9) switch
NC (3) inverter
load
(2) battery
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
54
Device name
Ref. n
Function
Rectifier-charger
(1)
Storage battery
(2)
Inverter
(3)
Static contactor
(4)
Manual by-pass
(5)
Manual switches
Battery circuitbreakers
Tableau 1-1: function of different devices making up an uninterruptible power supply system
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
55
The inverter's frequency and phase are synchronised with network 2. Thus, the static contactor
can instantaneously switch the power supply to network 2 (in less than 1 ms).
The connection of a UPS system to a second independent network is recommended since it
increases the reliability of the system. It is nevertheless possible to have only one common
incoming feeder.
The choice of an uninterruptible power supply structure depends on the quality of networks 1
and 2, the use and the availability required. The manufacturer must provide the designer with
sufficient elements for him to choose the most suitable structure. The following examples show
the most common structures.
n example 1: LV switchboard backed up by an inverter, with a generator to eliminate the
problem of the limited autonomy of the battery (usually about 15 mn) (see fig. 1-30)
MV
G
LV
NC
NO
NC
NC
filter
The filter allows harmonic currents travelling up the supply network to be reduced.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
56
MV
G
LV
NC
NO
NC
NC
network 2
network 1
non priority circuits
filter
filter
P
2
~
_
P
2
~
_
priority
circuits
This configuration only allows an overall power capacity above that of a single rectifier/inverter
unit.
The power P to be supplied is also divided between the 2 inverters.
A fault in one of the units leads to the load being switched to network 2 without interruption,
except if the network is beyond its tolerance level.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
57
MV
G
LV
NC
NO
NC
NC
filter
filter
filter
P
2
~
_
P
2
~
_
P
2
~
_
priority
circuits
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
58
MV
G
LV
NC
NO
NC
NC
~
_
network 2
network 1
~
_
1
2
~
_
priority
circuits
~
priority
circuits
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction , either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
60
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
61
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
62
- the low voltage network is the arborescent radial type. The secondary switchboard and
terminal boxes are fed by a single source.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
63
MV consumer substation
MV
incoming feeders from utility
LV
LV meter
main LV switchboard
UPS
priority switchboard
secondary LV
switchboard
terminal box
terminal box
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
64
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
65
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
66
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
67
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
68
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
69
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
70
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
71
main MV switchboard : U = 20 kV
MV
MV
MV
MV
VT
main MV switchboard : U = 6 kV
incoming feeders
from utility
MV
MV
LV
LV
MV
MLVS A
MV
LV
secondary MV 1
switchboard
MV
MV
secondary MV 3
switchboard
secondary MV 2
switchboard
M
LV
LV
G
LV
LV
4 generators
MV
MV
M
LV
MV
MLVS B
earthing
transformer
MV
LV
MLVS 2
MLVS 1
M
LV
MLSV 3
UPS
UPS
motor
control
centre 1
motor
control
centre 2
M
motor
control
centre 3
M
LV
secondary MV 5
switchboard
MV
LV
MV
LV
secondary MV 6
switchboard
MV
MV
LV
LV
MV
LV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
72
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE
73
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
T&D
6 883 427/AE