Anda di halaman 1dari 62

ELECTRICAL WORKS FOR

CPCB ZONAL OFFICE AND


LABORATORY AT BANGALORE

Item
No.
1.0

Consultants: SRIMATHA ENTERPRISES

BILL OF QUANTITIES WITH SPECIFICATIONS - ELECTRICALS


Qty.
Unit
Rate
Description
Rs.
415VOLTS MAIN DISTRIBUTION BOARDS
CONSTRUCTION
(i) Sheet steel - 2mm thick for frames and equipment
mounting plates 1.6mm thick for partitions and powder
coated.
(ii) Welded construction with transport sections bolted
together. All such joints to be gasketted
(iii) The cubicles shall be totally dust and vermin proof
conforming to IP-54.
(iv) All doors to be of hinged type except busbar
chamber covers, which shall be of bolted type. The
panels shall be of flush front design, mounted against
the wall and hence shall be designed for maintenance
with front access only.
(v) The construction shall be such as to facilitate easy
extension at both ends.
SMC supports and heat shrinkablePVC sleevesshall be
provided for busbars.
(vi) The design shall be such as to have individual
feeders for MCCBs and switch-disconnector-fuseunits
in separate segregated compartments, with proper
barriers between adjacent feeders, busbar chamber
and cable termination chambers. However a group of
MCB's can be housed in a compartment.
(vii) All MCCB outgoing feeders in compartmentalised
design for housing MCCBs shall have door interlocking
such that the door cannot be opened with the switch in
closed position.
(viii) All feeder terminations shall be properly
terminated to receive aluminium heavy duty power
cables or 1.1KV grade stranded copper cables as the
case may be. Adequate space shall be provided to
facilitate proper and easy terminations. Details of the
same shall clearly be brought out in the layout and
sectional views which the contractor is required to
furnish vide item (xix). The feeder terminations shall be
either from the top or bottom as necessary at site.
(ix) Wherever necessary, if the switch boards are to be
mounted against a wall, the layout of the components
and interconnections shall be designed to facilitate
maintenance from the front.
(x) The design of the switch board shall be such that
clear segregation shall be provided for the various
components, feeders and interconnections - such as
busbars, incoming / outgoing feeders, cable chambers,
etc., The height of the panel shall not exceed 2100mm.
The maximumoperating height of any componentsshall
not exceed 1700mm.
(xi) A minimum clearance of 25mm between phases
and between phases and neutral shall be maintained.

Page 1

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Description

Qty.

Unit

Rate
Rs.

(xii) An Aluminium earth strip/bus of adequate


size/section shall be run throughout the length of the
switch board to which all earth terminals of the various
components shall be connected.
(xiii) Bus bars shall be of Aluminium.
The bus bars shall have uniform cross section
throughout and shall be capable of carrying the rated
current under the increased ambient temp. conditions
within the enclosure and also to suit a fault level of 35
kA for 1 second.
Unless otherwise specified, the neutral shall have a
rating of 50 % of the phase busbars.
The bus bar sizes shall be specified in the drawings to
be submitted by the contractor.
(xiv) The MCCBs shall have the features as specified
in the bill of quantities.
(xv) All MCCBs shall be of current limiting type with
breaking capacity of min. Icu=Ics=35kA
The complete panels shall be capable of withstanding
any mechanical stresses arising out of a fault level of
50kA to cater to any increased fault levelsarising out of
upgradation of existing transformer at a later date.
(xvi) All control wiring shall be carried out with 1.1KV
grade single core PVC cables with stranded copper
conductors of min. 1.5sqmm for potential circuits and
2.5sqmm for current transformer circuits. The wiring
shall be neatly bunched, adequately supported and
properly routed. The wires shall be identified by ferrules
at both ends.
(xvii) Terminal blocks shall be of 500V grade and with
minimum current rating of 10Amps
(xviii) All routine tests as specified in the Indian
Standardsshall be carried out in the presence of CPCB
/ Consultants and test certificates submitted for
approval.
Test certificates shall also be submitted for all major
components of the switch boards like CTs, Relays, etc.,
(xix) Prior to fabrication of the panels, the contractor
shall submit the following drawings for approval :
(a) Single line diagram - power circuit
(b) Control circuit diagrams
(c) Front view showing layout of components
(d) Sectional view
(e) Foundation drawings
(xx) The outgoing cable feeders in distribution boards
shall be either from top or bottom as necessitatedat site
conditions and this shall be properly examined prior to
fabrication of boards.
Tests
All routine tests as per IS shall be conducted on the
panels prior to dispatch/supply in the presence of
CPCB / Consultants representatives.
The tests shall include all operational tests and shall also
cover sequencing and interlocking functions wherever
provided.

Page 2

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Description

Qty.

Unit

Rate
Rs.

On completion of installation, necessary tests shall be


performed at site prior to commissioning.
Documents
The following documents in 5 sets shall be furnished
prior to dispatch / supply : (i) Routine test certificates of complete panel
(ii) Routine test certificates for major components like
circuit breakers, relays, etc.,
(iii) All final drawings as listed in item (xix).
(iv) Operation and Maintenancemanualsfor the panels,
major equipments like breakers, etc.,.
Meters
All meters shall be of digital type and CT secondaries
shall be rated for 1 Amp.
The scope of supply shall cover all installationmaterials
such as base channels on which the panels shall rest,
foundation bolts, nuts, etc., and any other installation
materials as necessary.
The panel shall consist of the following:1.1

SDB-1F-1 at first floor


Incoming feeder shall have 1 No. core balance CT with earth leakage relay in
adjustablesetting of 30-300mA and timer with adjustable
setting.
1set of TPN Aluminium busbars rated min. 400Amps
1 No. 4 pole 250 Amps on load change over switchdisconnector-fuse unit with rotary handle operating
mechanism.
1 No. 4 pole fixed type 250 Amps MCCB with shunt trip
release, neutral link, adjustablethermal and fixed short
circuit releases, rotary handle operating mechanism,
auxiliary and trip contacts.
ON / OFF / Auto trip indicating lamp
R.Y.B. phase indicating lamps.
3Nos. current transformers, ratio 250/1A
1 No. Load manager EM6400, accuracy class-1,
Conzerv make-digital type
1 Set - necessary control fuses.
Note : The cable chamber shall be provided with
suitable termination facilities to receive 2Nos. XLPE
1.1kV grade 95sqmm armoured aluminium conductor
cables.
Outgoing feeders with MCCB's
Outgoing feeders with 3 pole fixed type MCCB's with
neutral link, adjustable thermal and fixed short circuit
releases, rotary handle operating mechanism.
1 No. 32 Amps TP MCCB
4 Nos. 63 Amps TP MCCB's

Page 3

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

No.

Installation, testing and commissioning 1

No.

Description

Rate
Rs.

1 No. 200 Amps TP MCCB


Supply

Page 4

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.
1.2

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

No.

Installation, testing and commissioning 1

No.

Description

Rate
Rs.

SDB-2F-1 at second floor


Incoming feeder shall have 1 No. core balance CT with earth leakage relay in
adjustablesetting of 30-300mA and timer with adjustable
setting.
1 set of TPN Aluminium busbars rated minimum
300Amps
1 No. 4 pole fixed type 200 Amps MCCB with shunt trip
release, neutral link, adjustablethermal and fixed short
circuit releases, rotary handle operating mechanism,
auxiliary and trip contacts.
ON / OFF / Auto trip indicating lamp
R.Y.B. phase indicating lamps.
3Nos. current transformers, ratio 200/1A
1 No. Ammeter with selector switch
1 No. Voltmeter with selector switch
1 Set - necessary control fuses.
Note : The cable chamber shall be provided with
suitable termination facilities to receive 1No. XLPE
1.1kV grade 95sqmm armoured aluminium conductor
cables.
Outgoing feeders with MCCB's
Outgoing feeders with 3 pole fixed type MCCB's with
neutral link, adjustable thermal and fixed short circuit
releases, rotary handle operating mechanism.
1 No. 32 Amps TP MCCB
3 Nos. 63 Amps TP MCCB's
3 Nos. 100 Amps TP MCCB's
1 No. 125 Amps TP MCCB
Supply

1.3

SDB-2F-2 at Second floor (for Air-conditioning)


Incoming feeder shall have 1 No. core balance CT with earth leakage relay in
adjustablesetting of 30-300mA and timer with adjustable
setting.
1 set of TPN Aluminium busbars rated minimum
400Amps
1No. 4 pole 250 Amps on load change over switchdisconnector-fuse unit with rotary handle operating
mechanism.
1 No. 4 pole fixed type 250 Amps MCCB with shunt trip
release, neutral link, adjustablethermal and fixed short
circuit releases, rotary handle operating mechanism,
auxiliary and trip contacts.
ON / OFF / Auto trip indicating lamp

Page 5

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

No.

Installation, testing and commissioning 1

No.

Description

Rate
Rs.

R.Y.B. phase indicating lamps.


3Nos. current transformers, ratio 250/1A
1 No. Load manager EM6400, accuracy class-1,
Conzerv make-digital type
1 Set - necessary control fuses.
Note : The cable chamber shall be provided with
suitable termination facilities to receive 2Nos. XLPE
1.1kV grade 95sqmm armoured aluminium conductor
cables.
Outgoing feeders with MCCB's
Outgoing feeders with 3 pole fixed type MCCB's with
neutral link, adjustable thermal and fixed short circuit
releases, rotary handle operating mechanism.
3 Nos. 32 Amps TP MCCB's
2 Nos. 63 Amps TP MCCB's
2 Nos. 125 Amps TP MCCB's
Supply

1.4

SDB-U-1F-1 at 1st floor (for UPS)


This distribution panel shall be in floor / wall mounting
type, non-compartmentalised design and in Rittal or
equivalent enclosure
Incoming feeder shall have 1 set of TPN Aluminium busbars rated minimum
200Amps
1No. 4 pole 63 Amps on load change over switchdisconnector-fuse unit with rotary handle operating
mechanism.
1 No. 4 pole fixed type 63Amps MCCB with shunt trip
release, neutral link, adjustablethermal and fixed short
circuit releases, rotary handle operating mechanism,
auxiliary and trip contacts.
ON / OFF / Auto trip indicating lamp
R.Y.B. phase indicating lamps.
1 Set - necessary control fuses.
Outgoing feeders with MCCB's
Outgoing feeders with 3 pole fixed type MCCB's with
neutral link, adjustable thermal and fixed short circuit
releases, rotary handle operating mechanism.
2 Nos. 32 Amps TP MCCB's
3 Nos. 63 Amps TP MCCB's
Supply

No.

Installation, testing and commissioning 1

No.

Page 6

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Qty.
Description
No.
1.5
SDB-U-2F-1 at 2nd floor (for UPS)
This distribution panel shall be in floor mounting type,
non-compartmentalised design and in Rittal or
equivalent enclosure

Unit

Rate
Rs.

Incoming feeder shall have 1 set of TPN Aluminium busbars rated minimum
200Amps
1 No. 4 pole 125Amps on load change over switchdisconnector-fuse unit with rotary handle operating
mechanism.
1 No. 4 pole fixed type 125Amps MCCB with shunt trip
release, neutral link, adjustablethermal and fixed short
circuit releases, rotary handle operating mechanism,
auxiliary and trip contacts.
ON / OFF / Auto trip indicating lamp
R.Y.B. phase indicating lamps.
1 Set - necessary control fuses.
Outgoing feeders with MCCB's
Outgoing feeders with 3 pole fixed type MCCB's with
neutral link, adjustable thermal and fixed short circuit
releases, rotary handle operating mechanism.
2 Nos. 32 Amps TP MCCB's
4 Nos. 63 Amps TP MCCB's
2 Nos. 100 Amps TP MCCB's
Supply

No.

Installation, testing and commissioning 1

No.

Total of Item 1.0


2.0

WALL MOUNTING TYPE MCB


BOARDS

DISTRIBUTION

Supply, installation, testing and commissioning of the


following TPN MCB Distribution Boards, of following
types, Legrand make or equivalent-catalogue numbers
as specified below For four, six, eight, twelveand sixteenways with acrylic
door IP43 protection cat. No. 607725 to 607729

Cable / conduit entry shall be either from top or bottom


and suitable termination facilities shall be provided.
Suitable mounting brackets as required considering
their locations shall be provided.
MCCB's where provided shall be rated for min. 35kA
rupturing capacity.
All RCBO's and MCB's shall be rated for min. 10kA
rupturing capacity.

Page 7

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

No.

Installation, testing and commissioning 2

No.

Description

Rate
Rs.

RCBO's shall be have a sensitivity of 100mA


All unutilised outlets of DB's shall be covered with
blanking plates
Wherever possible and practical, distribution boards
shall be concealed mounted.
2.1

Lighting Distribution Boards (LDB's)


The details of the lighting distribution boards are as
under LDB-1F-1, LDB-2F-1 (6way) each with
Incomer 32Amps 4pole RCBO and outgoings 18Nos.
SP 10Amps MCB's
Supply

2.2

Power Distribution Boards (PDB's)-raw power

a)

PDB-1F-1, (6way)
Incomer 63Amps RCBO and outgoings 9Nos. SP
20Amps and 3Nos. TP 20Amps MCB's
Supply

b)

c)

d)

e)

No.

Installation, testing and commissioning 1

No.

PDB-1F-2, (4way)
Incomer 63Amps RCBO and outgoings 9Nos. SP
20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-2F-1
Incomer 100Amps MCCB with integral earth leakage
protection and outgoings 12Nos. SP 20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-2F-2
Incomer 100Amps MCCB with integral earth leakage
protection and outgoings 9Nos. SP 32Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-2F-3
Incomer 100Amps MCCB with integral earth leakage
protection and outgoings 12Nos. SP 20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

Page 8

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Qty.
Description
No.
f)
PDB-2F-4, (4way)
Incomer 63Amps RCBO and outgoings 9Nos. SP
20Amps MCB's
Supply
1
Installation, testing and commissioning 1
g)

2.3
a)

b)

c)

d)

e)

f)

PDB-2F-5, (4way)
Incomer 63Amps RCBO and outgoings 9Nos. SP
20Amps MCB's
Supply

Unit

No.
No.

No.

Installation, testing and commissioning 1

No.

UPS Power Distribution Boards (PDB-U)


PDB-U-1F-1, (4way)
Incomer 63Amps RCBO and outgoings 12Nos. SP
20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-U-1F-2, (4way)
Incomer 63Amps RCBO and outgoings 12Nos. SP
20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-U-1F-3, (4way)
Incomer 32Amps RCBO and outgoings 12Nos. SP
20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-U-2F-1, (4way)
Incomer 63Amps RCBO and outgoings 12Nos. SP
20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-U-2F-2, (4way)
Incomer 63Amps RCBO and outgoings 9Nos. SP
20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

PDB-U-2F-3
Incomer 100Amps MCCB with integral earth leakage
protection and outgoings 18Nos. SP 20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

Page 9

Rate
Rs.

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
No.
g)

h)

Qty.

Unit

No.

Installation, testing and commissioning 1

No.

Description
PDB-U-2F-4, (4way)
Incomer 63Amps RCBO and outgoings 9Nos. SP
20Amps MCB's
Supply

PDB-U-2F-5
Incomer 100Amps MCCB with integral earth leakage
protection and outgoings 18Nos. SP 20Amps MCB's
Supply

No.

Installation, testing and commissioning 1

No.

Rate
Rs.

Total of Item No 2.0


3.0

1.1 KV grade XLPE insulated armoured heavy duty


Aluminium conductor cables
1.1 KV grade XLPE insulated heavy duty armoured typ
power cables with Aluminiumconductors complete with
all hardware such as clamps, saddles etc., or for
clamping along cable trays or along walls etc., as the
case may be.
Rates to be quoted shall exclude preparation of cable
trenches - cable trays as such wherever applicable.
Where cables are to be laid individually on
walls/columns/slabsand not on the cable trays specified
in the miscellaneous items, rates quoted shall include
necessary mounting supports and saddles as required.

3.1

3 1/2 x 185 sq mm

supply
Laying

3.2

3 1/2 x 95 sq mm

supply
Laying

3.3

3 1/2 x 70 sq mm

supply
Laying

3.4

3 1/2 x 25 sq mm

supply
Laying

R.O

R.M

R.O

R.M

330

R.M

330

R.M

100

R.M

100

R.M

R.O

R.M

R.O

R.M

Total of item 3.0

Page 10

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Description

Qty.

Unit

4.0

Cable end terminations for 1.1 KV grade XLPE


insulated armoured heavy duty Aluminium
conductor cables
Supplying and making cable end terminations for
following 1.1KV grade XLPE insulated armoured heavy
duty Aluminium conductor cables complete with double
compression type brass cable glands, crimping type
Aluminium lugs, necessary insulation tape, etc.,
complete in all respects.

4.1

3 1/2 x 185 sqmm

R.O

No.

4.2

3 1/2 x 95 sqmm

10

No.

4.3

3 1/2 x 70 sqmm

No.

4.4

3 1/2 x 25 sqmm

R.O

No.

Rate
Rs.

Total of item 4.0


5.0

INTERCONNECTING CABLING & WIRING FROM


DB's, PDB's AND UPSDB's TO SINGLE PHASE
POWER SOCKETS / OUTLETS ON PER METRE
BASIS
Exclusive phase for fluctuating/heating load and
separate phase for sensitive instrument shall be
connected. 3 phase input/outputUPS shall be provided.
Cables from Panels to PDB's, DB's etc., shall be run
externally on overhead cable trays at beam level - as
per execution drawings to be furnished later.
In case of wiring from DB's, where a number of sockets
are located near to each other, cable management
systems (separate item of BOQ) has been foreseen as
also indicated in the layout drawings.
Wherever the outletsare located in isolationand are not
part of the channel systems, wiring from PDB's to
sockets / power outlets shall be run in MS conduits to
the appropriate locations. The scope would then cover
groove cutting of wallsand rough plaster cover-up of the
same.
Wherever the cables are to be dropped vertically, the
same shall be laid either in cable managementsystem
channels itself or in MS conduits as applicable for the
isolated cases mentioned earlier.
Cables shall generally be of 1.1 KV grade three core for
single phase and four core for three phase circuits,
PVC insulated sheathed,FRLS flexibletype with copper
conductors.

Page 11

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

R.O

R.M

R.O

R.M

100

R.M

100

R.M

360

R.M

360

R.M

2760

R.M

Laying 2760

R.M

Description

Rate
Rs.

Cables for single phase circuits including the earth core


shall be connected at both ends by suitablecable lugs &
prices quoted shall be inclusive of these terminations.

Cable termination prices for three phase circuits shall


be quoted separately against the respective items
5.1

M.S. CONDUITS

a)

20 mm dia

supply
Laying

b)

25 mm dia

supply
Laying

5.2

Three core cables (for single phase ckts)

a)

3 x 2.5sqmm copper

supply
Laying

b)

c)

3 x 4sqmm copper

supply

3 x 6sqmm copper

supply
Laying

5.3

Four core cables (for three phase ckts)

a)

4 x 4sqmm copper cables

supply
Laying

4 x 4sqmm cable terminations

supply
Installation

b)

4 x 6sqmm copper

supply
Laying

4 x 6sqmm cable terminations

supply
Installation

c)

4 x 10sqmm copper

supply
Laying

4 x 10sqmm cable terminations

supply

Page 12

600

R.M

600

R.M

20

R.M

20

R.M

No.

No.

80

R.M

80

R.M

No.

No.

130

R.M

130

R.M

10

No.

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Description
Installation

d)

4 x 16sqmm copper

supply
Laying

4 x 16sqmm cable terminations

supply
Installation

e)

4 x 25sqmm copper

supply
Laying

4 x 25sqmm cable terminations

supply
Installation

f)

4 x 35sqmm copper

supply
Laying

4 x 35sqmm cable terminations

supply
Installation

Qty.

Unit

10

No.

300

R.M

300

R.M

26

No.

26

No.

30

R.M

30

R.M

No.

No.

15

R.M

15

R.M

No.

No.

Rate
Rs.

Total of item 5.0


6.0

CIRCUIT WIRING
The scope of this item covers the circuit wiring from
lighting distribution boards (mentioned in item 2.0
above) to the first switch points only, wherever wiring is
reckoned on point wiring basis. Subsequent looping
from the first switch point onwards if any, wouldneither
be permitted under this item nor any additional costs
allowed under any separate item
The circuit wiring shall be of concealed conduit system
when laid in walls and exposed type in conduits /
casings where concealed system is not possible - wirin
to be with PVC insulated stranded flexible copper
conductor FRLS cables of 1.1kV grade. PVC conduits
shall be 25mm dia FRLS type complete with all
accessories, such as bends, junction boxes, etc.,
Scope shall include groove cutting of walls and making
good the same with rough plaster
Engineer-in-charge's decision regarding interpretation
of this circuit wiring & allowing the same under this
heading shall be final.
The Single line diagram indicates the various circuits
that are to be taken from the respective LDB's at first
and second floors - which could be marginallychanged
to suit site conditions.

Page 13

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Description
No.
6.1
FRLS PVC CONDUITS - 2mm thick
a)

20 mm dia

Qty.

Unit

R.O

R.M

R.O

R.M

750

R.M

Laying

750

R.M

supply

360

R.M

Laying

360

R.M

supply
Laying

b)

6.2

25 mm dia

supply

Rate
Rs.

COPPER CABLES
3 core 2.5 sqmm copper

Total of item 6.0


7.0

WIRING TO LUMINAIRES / CEILING FANS /


EXHAUST FANS AND 6/16AMPS SOCKETS ON
POINT BASIS
The quantities indicated below are tentative and
likely to vary during execution. The quantities as
shown in the drawings would prevail and be taken
up for execution

7.1

In areas where false ceiling is provided and the existing


lighting arrangement does not fit into the lab layouts,
wiring to luminaires and fans needs to be carried out
afresh with control locations to suit the lab layouts. New
recessed type luminaires are covered in a separate
item.
The Contractor can utilise the existing conduits
wherever possible after drawing out the existing wires /
cables.
The scope of this item covers wiring from switch points
to Luminaires in concealed conduit system - when laid
in wallsor exposedsurface run when laid in ceiling slab
or run over false ceiling - wiring to be with PVC
insulatedFRLS stranded copper cables of 1.1KV grade
1.5sqmm for phase & neutral and 1.5sqmm for earth
drawn in 25mm / 20mm dia. FRLS PVC conduit pipes
2mm thick complete with all accessories, such as
bends, junction boxes, switch boxes, switch plates and
switches, etc.
Scope shall include groove cutting of walls and making
good the same with rough plaster
An earth cable shall be run through all the conduits
Wherever possible and practical, the existing conduits
can be utilised by drawing out the existing wires which
has to be handed over to CPCB.

Page 14

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Description

Qty.

Unit

Rate
Rs.

The scope shall include disconnection and removal of


such existinglight fittings which have become redundant
consequent to this new lighting layout and handing over
the same to CPCB.
Switch boxes and switches / sockets shall be of
moulded plastic, modular type
The rooms which are to be wired afresh as per this item
are been given below

Page 15

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

supply

77

No.

Installation

77

No.

supply

No.

Installation

No.

R.O

No.

Installation R.O

No.

Description

Rate
Rs.

At first floorConference room, Library, Accounts head, Admin.


Head, Admin. Section, R1, R2, R3, R4, Seating, Zonal
Officer's cabin, Reception and Visitors lobby, Cabins,
Secretariat, Passage (partly), Room-3, Electrical room,
Toilet attached to Zonal Officer and Pantry

At Second floorSamplereceipt, SSA / JSA seating, Lab incharge, GAS


Chromatography,Passage (partly), Solid sample prep.,
AHU room, Elect. Room, DM plant, AOX, BTX
Analysers, ION Chromatography, AAS, TCLP

7.1.1

Light points

a)

Single light controlled from 1switch - 1way

b)

Two lights controlled from 1 switch - 1 way

c)

Single light controlled from 2 switches - 2 way


supply

7.1.2
a)

Fan points & single phase A/C outlets


Ceiling fan points
supply

b)

R.O

No.

Installation R.O

No.

Single phase exhaust fan and A/C outlet points Mosaic


frames, with 16 Amps, 3pin modular construction socket
to be provided near exhaust fans / A/C outlets and
scope also includes wiring from switch to socket for all
points and wiring from socket to exhaustfans in flexible
pipe.
Switch in white colour with indicator to be independently
mounted (not on channel)
supply

24

No.

Installation

24

No.

Page 16

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Qty.
Description
No.
c) Single phase A/C outlet point Mosaic frames with
16Amps, 3pin modular construction socket to be
provided near A/C outlets and scope shall include
switch in white colour to be mounted on existing cable
channel with all fixing accessories, wiring from switch to
A/C socket outlet in concealed 2mm thick PVC conduit
or externally in casing.
supply 16
Installation
d)

e)

f)

7.2

Unit

Rate
Rs.

No.

16

No.

Single phase A/C outlet point Mosaic frames with


16Amps, 3pin modular construction socket to be
provided near A/C outlets and scope shall include
switch in black colour to be mounted independentlywith
all fixing accessories, wiring from switch to A/C socket
outletin concealed 2mm thick PVC conduit or externally
in casing.
supply

No.

Installation

No.

Call bell point - wiring with 1.5 sqmm flexible Copper


conductor cable including musical ding dong bell
supply

No.

Installation

No.

Point wiring for spot lights with each switch controlling


two to five numbers spot lights, all located nearby to
provide illumination for display boards.
supply R.O

No.

Installation R.O

No.

For Areas with minor relocation work


In certain areas, it is proposed to utilise the existing
lighting system with minor changes to suit the lab
requirements.
The scope of work involvedfor each of such rooms has
been listed separately in Annexure-I
Tenderers are requested to quote separately for each o
the rooms as under-

7.2.1

At first floor -

a)

For passage lights controlled from L1

lot

b)

For passage lights controlled from L2

lot

c)

For air laboratory

lot

d)

For instrumentation room

lot

e)

For conditioning room

lot

Page 17

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.
f)
7.2.3

Consultants: SRIMATHA ENTERPRISES

Description
For tool room

Qty.

Unit

lot

At second floor-

a)

For passage lights controlled from L1, l2 & L4

lot

b)

For passage lights controlled from L3

lot

c)

Instrumentation lab

lot

d)

Cold room

lot

e)

TKN Digestion

lot

f)

For Bio-Assay lab

lot

g)

For micro biology lab

lot

h)

For water lab

lot

i)

For waste water lab and hot room

lot

7.3

Rate
Rs.

Retaining existing lighting system


In certain areas, the existing lighting system including
the control position, luminaires, etc., can be retained as
it is.
However,during dismantlingwork, and actual execution
process, it is likely that minor shift in control locations
may be required practically at site to suit the interior
layouts including door positioning.
The scope of work here cannot be foreseen at this
stage but however would be very limited to include
extension in wiring and relocation from the present one.
The prices quoted in this item will be allowed for
consideration and payment only if any work is carried
out.
The concerned rooms are as under -

7.3.1

at first floor - Toilets

lot

7.3.2

At second floor - Toilets

lot

Total of item 7.0


8.0

LUMINAIRES

8.1

Commercial mirror optic surface / recessed mounting


type compact fluorescent luminaires with paralite louvre
system, housing made out of CRCA MS sheet, epoxy
powder coated complete with High-purity aluminium
reflector, push fit lamp holder, electronic ballasts,
starter, power factor improvement capacitor, prewired
and earthing terminals.

Page 18

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
No.

Description

a)

Luminaires to be provided with 2 x 36 watts compact fluorescent lamps. Type : from


latest model of standard make

b)

c)

8.2

8.3

8.4

Qty.

Unit

Supply

13

No.

Installation

13

No.

Supply

91

No.

Installation

91

No.

2x18 watts compact fluorescent lamps housed in


luminaire
Type : from latest model of standard make
Supply

19

No.

Installation

19

No.

Rate
Rs.

2x26 watts compact fluorescent lamps housed in


luminaire. Type : from latest model of standard make

Wall bracket mounted incandescent fitting with 60 watts


lamp
Supply R.O

No.

Installation R.O

No.

Spot lights with 50Watts halogen lamp to be fixed to wa


display boards, etc.,
Supply R.O

No.

Installation R.O

No.

LIGHTING TRACKS WITH SPOT LIGHTS


Luminac track lighting system complete with all
accessories like busbars, couplings, bends, holder
units, low voltage transformers, halogen lamps,
connecting wires, etc.,

a)

Electronic transformer
Supply

b)

R.O

No.

Installation R.O

No.

6 metres system tube


Supply

Page 19

R.O

length

Installation R.O

length

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Qty.
Description
No.
c) Spot light luminaires suitable for 12 Volts 50watts
halogen lamps including lamps
Type : LHS 412 B Fluo-lite make or equivalent
Supply R.O

Unit

Installation R.O

No.

Rate
Rs.

No.

Total of item 8.0


9.0

CABLE MANAGEMENTSYSTEM (CMS), SWITCHES


AND SOCKETS

9.1
a)

DLP plastic trunking


Legrand make cable management system type DLP wi
plastic trunking of size 150x50mm, double covers
2x65mm, surface mounting type, complete with all
accessories including internal angles, external angles,
flat angles, junctions, clips, earth links, cover joint, base
joint, T-joint, extension couplers, end caps, etc.,
The central line of the channel would be taken for
measurement purposes.
Supply

b)

330

R.M

Installation 330

R.M

Internal partition (Clip-on) for the above channel in item


a) to be used for running data and telephone wiring
Supply

c)

330

R.M

Installation 330

R.M

Legrand make cable management system type DLP wi


plastic trunking of size 80x50mm, single cover 65mm,
surface mounting type, complete with all accessories
including internal angles, external angles, flat angles,
junctions, clips, earth links, cover joint, base joint, Tjoint, extension couplers, end caps, etc.,
The central line of the channel would be taken for
measurement purposes.
Supply

Page 20

100

R.M

Installation 100

R.M

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

a)

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

R.O

R.M

Installation R.O

R.M

Description
ALTERNATE TO ABOVE
DLP Aluminium trunking
Legrand make cable management system type DLP wi
Aluminium trunking of size 150x50mm, double covers
2x65mm, surface mounting type, complete with all
accessories including internal angles, external angles,
flat angles, junctions, clips, earth links, cover joint, base
joint, T-joint, extension couplers, end caps, etc.,
The central line of the channel would be taken for
measurement purposes.
Supply

b)

Internal partition (clip-on) for the above channel in item


a) to be used for running data and telephone wiring
Supply

9.2

a)

b)

9.3

Rate
Rs.

R.O

R.M

Installation R.O

R.M

Single phase switch socket for raw power


The switch socket outlets shall be of Mosaic range type Legrand make or equivalent complete with all
accessories like fixing frames suitable for mounting on
the DLP trunkings mentioned in 9.1 above.
One way 1pole switch rated 16Amps - white colour
Supply

70

No.

Installation

70

No.

Supply

70

No.

Installation

70

No.

158

No.

Installation 158

No.

6/16A 3pin shuttered socket - white colour

Single phase socket outlets for UPS power


The socket outlets shall be of Mosaic range - type
Legrand make or equivalent complete with all
accessories like fixing frames suitable for mounting on
the DLP trunkings mentioned in 9.1 above.
16Amps switch with 3 pin 6/16Amps socket in black
colour
Supply

Page 21

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Qty.
Description
No.
9.4
Computer outlets
The socket outlets, shall be of Mosaic range - type
Legrand make or equivalent complete with all
accessories like fixing frames suitable for mounting on
the DLP trunkings mentioned in 9.1 above with
necessary blanking plates.
Each computer outlet shall comprise of -

Unit

a) 1 No. 16Amps switch along with 3Nos. 6Amps 2/3pin


sockets in black colour
b) 1No. RJ 11 telephone socket
c) 1No. additional module to house a data outlet to be
provided by the networking agency at a later date.
Supply

31

No.

Installation

31

No.

16Ampsplug and socket with 4pole 20AmpsMCB - Cat.


No. 607871 of Legrand make or equivalentbut with plug
& socket rating 16Amps
Supply

No.

Installation

No.

R.O

No.

Installation R.O

No.

Rate
Rs.

Note: 1) Prior clearance shall be taken before procurement supplies & lengths as required at site only shall be
supplied and installed.
2) The lengths indicated are tentative.Based on actual
positioning of sockets at site, lengths and accessories
as required shall be measured at site. Payments shall
be made only for such lengths installed based on the
unit rate per metre and quantities of sockets, switches,
etc.,
Total of item 9.0
10.0

3 PHASE POWER - PLUG SOCKETS


3 phase, 5 Pin plug and socket outlet with P17 Tempra
plug and sockets Legrand make or equivalent, housed
in enclosures, complete with 4pole MCBs (D-curve),
plug, socket with flap suitable for surface / concealed
mounting

10.1

10.2

32Amps plug & socket with 4 pole 32Amps MCB - Cat.


No. 607871 of Legrand make or equivalent
Supply

Total of item 10.0

Page 22

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Description

Qty.

Unit

11.0

6/16 AMPS SINGLE PHASE DOMESTIC TYPE


MODULAR SWITCH SOCKETS TO BE MOUNTED
INDEPENDENTLY (NOT ON CHANNELS)
The switches, socket outlets, etc., shall be of Mosaic
range - types Legrand make or equivalentcompletewith
all accessories like fixing frames suitable for
independent mounting, surface / concealed including
suitable mounting boxes.

11.1

Single phase switch and socket for raw power


One way SP switch rated 16Amps with 6/16A, 3pin
shuttered socket - white colour
Supply

No.

Installation

No.

Single phase switch and socket for UPS power


One way SP switch rated 16Amps with 6/16A, 3pin
shuttered socket - black colour
Supply

10

No.

Installation

10

No.

Computer outlets
Each computer outlet housed in 1No. 8module and 1No.
2module mounting boxes with necessary blanking plates
shall comprise of a) 1 No. 16 Amps switch along with 3 Nos. 6Amps 2/3pin
sockets in black colour
b) 1No. RJ 11 telephone socket
c) 1No. additional module to house a data outlet to be
provided by the networking agency at a later date.
Supply 10

No.

11.2

11.3

Installation

10

Rate
Rs.

No.

Total of item 11.0


12.0

UPS SYSTEM
UPS system - Power-one make or equivalentwith IGBT
based online, 400/415volts,3phase input and selectable
output of 380-400-415volts, 3phase with neutral,
complete with SMF batteries to provide 30minutes
backup.
Scope to be completewith battery stand and connecting
battery leads.
Input voltage range +/-20%
Input frequency range 45-65Hz
Input PF >0.99
UPS shall be provided with bypass facility
Over load capability 110% for 5Hrs, 125% for 10Min
and 150% for 1minute.
Crest factor 3:1

Page 23

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.
12.1

12.2

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

Supply

No.

Installation

No.

Supply

No.

Installation

No.

R.O

R.M

R.O

R.M

R.O

R.M

R.O

R.M

R.O

R.M

R.O

R.M

300

R.M

300

R.M

R.O

R.M

R.O

R.M

Description

Rate
Rs.

Rated output 30KVA - 24KW

Rated output 60KVA - 48KW

Total of item 12.0


13.0

CONDUITS & WIRING


INTERCOM SYSTEM

13.1

CONDUITS

FOR

TELEPHONE

MS conduits concealed type laid in wall/ceiling or run


over false ceiling complete with all accessories such as
junction boxes, bends, draw boxes, inspection bends,
tee, etc., as required.
a)

20 mm dia

supply
Laying

b)

25 mm dia

supply
Laying

13.2

Telephone cables with 0.5 sqmm annealed copper


conductor, jelly filled as follows.

a)

1 pair

supply
Laying

b)

2 pair

supply
Laying

c)

5 pair

supply
Laying
Total of item 13.0

15.0

EARTHING :

15.1

Body earthing of 415 Volts main distribution board, DB,


LDB's, PDB's, Isolators and all electrical equipmentsto
the earth ring, formation of a main earthing ring and
interconnections between earth electrodes.

Page 24

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

200

R.M

200

R.M

400

R.M

400

R.M

100

R.M

Laying

100

R.M

Earthing of UPS ground with 1.1 KV grade


1Rx1Cx25sqmmflexible copper cable including cable
terminations at both ends,
Supply

120

R.M

Laying

120

R.M

Earthing of LDB's to the nearest earthing ring by single


core 4sqmm flexible copper cables
Supply

20

R.M

Laying

20

R.M

Earthing of PDB's (with incomers rated 63Amps) to the


nearest earthing ring by single core 6sqmm flexible
copper cables
Supply

60

R.M

Laying

60

R.M

Earthing of PDB's (with incomers rated 100Amps) to the


nearest earthing ring by single core 16sqmm flexible
copper cables
Supply

30

R.M

Laying

30

R.M

Description

Rate
Rs.

The rates to be quoted shall include all necessary


clamps, saddles, hardware's, fixing arrangements,etc.,
as required.
The quantities involved are as under a)

50 x 6 mm GI

Supply
Laying

b)

25 x 6 mm GI

Supply
Laying

c)

15.2

15.3

15.4

15.5

No.8 SWG GI

Supply

15.6

Single core flexible copper conductor cables for


earthing

a)

1R x 1.5sqmm copper for interlinking earth terminals of


single phase socket outlets in channels covered by
separate circuits
supply

50

R.M

Laying

50

R.M

Page 25

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Qty.
Description
No.
b)
1R x 2.5sqmm copper for earthing of three phase
outlets to the relevant distribution boards
supply 50
Laying
15.7

Unit

Rate
Rs.

R.M

50

R.M

GI plate type earth electrode as per IS:3043 standards


complete with excavation, civil works, funnel, cast iron
cover, earth pit marker, etc.,
Supply

No.

Laying

No.

Danger Boards of appropriate voltage grade danger


signals, size and style as required by the electrical
Inspectorate.
supply

No.

Installation

No.

Note: Earth cable for lab 16Amps / 32Amps sockets, lighting


luminaires, etc., covered in respective items of wiring.

Total of item 15.0


16.0

SAFETY EQUIPMENT:
The quantities indicated below are tentative, for
guidance only and only such quantities as actually
necessary and insisted upon by Electrical Inspectorate
shall be supplied, the unit rate as quoted below shall be
applied for the actual rate as quoted below shall be
applied for the actual quantities supplied.

16.1

16.2

Fire fighting buckets with stand and sand

No.

16.3

Rubber mats 6.15 mm thick, 900 mm wide in standard


lengths of 1800 mm suitable for voltage levels of 415
volts in front of LT switch board, SDB's.

10

No.

16.4

First Aid Box

No.

16.5

Shock treatmentchart fixed in teak wood frame covered


with glass and suitable for hanging on wall

No.

16.6

Hand gloves suitable for working potential upto 415V.

No.

16.7

Dry chemical powder type fire extinguisher 5Kgs


capacity cartridge type fitted with gun metal, operational
assembly card, CO2 gas cartridge, high pressure
discharge hose and Aluminiumsqueeze, grip nozzle as
per IS:2171.

No.

Total of item 16.0

Page 26

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

No.

No.

No.

No.

No.

No.

No.

Installation

No.

1 No. DP 32Amps 10KA MCB housed in plastic


enclosure Legrand make catalogue No. 01356 to be
used in certain locations to serve as power outlets for
single phase loads in range of 3 to 5 KW - locations as
directed by CPCB. Necessary wiring has already been
considered separately.
supply

No.

Installation

No.

50

R.M

50

R.M

R.M

R.M

Description

17.0

MISCELLANEOUS :

17.1

Switch-Disconnector Unit

Rate
Rs.

TPN 32Amps/ 63Amps/ 125AmpsSwitch-disconnector


fuse unit (SDFU) wall mounting type housed in a
14SWG CRCA sheet steel enclosure complete with
knockouts for entry/exit of cables, hinged door
interlocked with SDU handle, removablegland plateson
top and bottom,2Nos. earthing terminals. The enclosure
shall be painted with epoxy powder coating.

a)

32 AMPS

supply
Installation

b)

32 AMPS (weather proof)

supply
Installation

c)

63 AMPS

supply
Installation

d)

17.2

17.3

125 AMPS (weather proof )

supply

GI open rung type cable tray arrangement run


horizontally, supported from ceiling by ISMC channel
welded to inserts in ceiling or run vertically along wallsProfab make or equivalent
Scope shall include necessary anchoring arrangement
in ceiling/wall at 1.5Mtrs intervals

a)

1 tier 450 mm width

supply
Erection

b)

1 tier 300 mm width

supply
Erection

Page 27

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Item
Description
No.
c)
1 tier 150 mm width
supply

Qty.

Unit

40

R.M

40

R.M

400

R.M

Installation 400

R.M

Erection
17.4

Cablofil' wire mesh cable tray system - Legrand make,


hot dip galvanised steel wires, complete with couplers,
mountings and all accessories as required to achieve
the running routes indicated in the drawings.

a)

150mm width, 54mm height


stainless steel (304L)

b)

c)

- supply

Hot dip galvanised steel separators to suit above


Supply

50

R.M

Installation

50

R.M

Bi-metallic clamps attached to the cable tray for


earthing to the nearest earth ring
BLF 8/16 for 16sqmm wire
Supply

50

No.

Installation

50

No.

R.O

R.M

Installation R.O

R.M

Rate
Rs.

Alternatively
Perforated cable trays, powder coated Profab make,
complete with all installation material, bends, couplers,
complete with covers
(i) 1 tier 150mm width x 50mm height x 2mm thick
Supply

Tray covers for the above


Supply

17.5

R.O

R.M

Installation R.O

R.M

Dismantling,disconnection and removalof all redundant


equipments with utmost care to retrieve as many
equipments - components as possible and handing
over of the same to CPCB consequent to the new
distribution systems to suit the CPCB lab requirements.
Amongst such equipments are the LDB's, raw power
distribution boards, UPS power distribution boards,
cables from and to the distribution boards.

17.6

Removal of all existing wires / cables in unutilised


conduits for lighting and power sockets and handing
over of the same to CPCB.
This item of work shall be carried out only after
obtaining clearance from CPCB.

Page 28

lot

lot

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE
Item
No.
17.7

17.8

Consultants: SRIMATHA ENTERPRISES

Qty.

Unit

1set of summation CT's to provide the combined output


signals to the tri-vector meter.
1No. Tri-vector meter ER-300P L&T make of equivalent
with accuracy class 0.5
Suitable length of busbars for mounting the CT's and
termination facilities for entry and exit of the two feeder
cables shall be provided
Supply

No.

Installation

No.

50

R.M

Description
Metering arrangement in 14 gauge sheet steel
enclosure suitable for floor / pedestal mounting.
Two numbers Incoming supplies, each with 2runs of 3
1/2 x 95sqmm XLPE armoured aluminium conductor
cables shall be jointly metered as follows 3Nos current transformers ratio 250/5Amps output
15VA, accuracy class-1 for each of the two incomers.

Excavation, supply of bricks, sand to form a cable


trench for laying 11KV and 1.1 KV grade cables
complete with back filling, consolidation and with cable
route markers.
500mm widthx750mm depth for 1.1kV cable

17.9

Rate
Rs.

Miscellaneous works as necessary which the tenderer


feels is not covered in the above scope but is necessar
in order to achieve the desired scheme.
If so, details to be furnished by tenderer
lumpsum
Total of item 17.0

Page 29

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 30

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 31

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 32

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 33

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 34

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 35

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 36

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 37

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 38

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 39

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 40

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 41

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 42

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 43

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 44

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 45

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 46

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 47

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 48

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 49

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 50

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 51

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 52

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 53

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 54

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 55

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 56

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 57

BOQ

ELECTRICAL WORKS FOR


CPCB ZONAL OFFICE AND
LABORATORY AT BANGALORE

Consultants: SRIMATHA ENTERPRISES

Amount
Rs.

Page 58

BOQ

ABSTRACT
Item No.

Description

1.0

415 Volts Main distribution boards

2.0

Wall mounting type MCB distribution boards

3.0

1.1 KV grade XLPE insulated armoured Aluminium conductor cable

4.0

Cable end terminations for 1.1 KV grade PVC insulated armoured heavy duty
Aluminium conductor cables

5.0

Interconnecting cabling & wiring from DB's, PDB's and UPSDB's to single
phase power sockets / outlets on per metre basis

6.0

Circuit wiring

7.0

Wiring to luminaires / ceiling fans / Exhaust fans and 6/16 Amps switch
sockets on point basis

8.0

Luminaires

9.0

Cable management system (CMS), switches and socket

10.0

Three phase power - plug sockets

11.0

6/16 Amps single phase domestic type modular switch sockets to be mounted
independently (not on channels

12.0

UPS system

13.0

Conduits & sockets for telephone / intercom system

15.0

Earthing

16.0

Safety equipment

17.0

Miscellaneous
Total of items 1.0 to 17.0

Page 59

ABSTRACT
Amount Rs.

Page 60

ANNEXURE-I
SCOPE OF WORK TO BE CARRIED OUT AGAINST ITEM 7.2 FOR AREAS WITH MINOR RELOCATION

a)

At first floor For passage lights controlled from L1

b)

For passage lights controlled from L2

retain existing light positions, wiring and control


switch - new luminaire, recessed type to match the
other passage luminaires

c)

For air laboratory

retain existing lights, fans, wiring - shift existing


control location marginally only if required at site
using existing control switches

d)

For instrumentation room

retain existing lights, fans, wiring - shift existing


control location marginally only if required at site
using existing control switches

e)

For conditioning room

retain existing lights, fans, wiring - shift existing


control location outside to passage using existing
control switches

f)

For tool room

retain existing lights, fans, wiring - shift existing


control location marginally only if required at site
using existing control switches

a)

b)

retain existing light positions and wiring - shift


existing control location marginally only if required
at site using existing control switches - new
luminaires to match the other passage luminaires

At second floorFor passage lights controlled from L1, l2 & retain existing wiring, control location - luminaires
L4
need to be changed to recessed type CFL
luminaire - scope here to include extension in
wiring in flexible to drop down to the recessed
luminaire - luminaire itself is covered in a separate
item.
For passage lights controlled from L3

retain existing wiring, control location and


luminaires - shift existing control location
marginally only if required at site using existing
control switches

Page 61

c)

Instrumentation lab

retain existing lights, fans, wiring - shift existing


control location using existing control switches with
necessary extension in wiring with PVC casing

d)

Cold room

retain existing lights, fans, wiring - shift existing


control location using existing control switches with
necessary extension in wiring with PVC casing

e)

TKN Digestion

retain existing lights, fans, wiring - shift existing


control location using existing control switches with
necessary extension in wiring with PVC casing

f)

For Bio-Assay lab

retain existing lights, fans, wiring - shift existing


control location using existing control switches with
necessary extension in wiring with PVC casing

g)

For micro biology lab

retain existing lights, fans, wiring - shift existing


control location using existing control switches with
necessary extension in wiring with PVC casing

h)

For water lab

retain existing lights, fans, wiring - shift existing


control location using existing control switches with
necessary extension in wiring with PVC casing

i)

For waste water lab and hot room

retain existing lights, fans, wiring - shift existing


control location marginally only if required at site
using existing control switches - contractor present
during demolition as stipulated in the tender shall
check whether the short length of wall housing the
control switches could be retained for this purpose.

Page 62

Anda mungkin juga menyukai