Gener atorul 2
Vs: 15000 V
GE N
GE N
Intrer upator ul 1
Intrer upator ul 2
Separatorul 14
Separatorul 5
Separatorul 1
Separatorul 2
Separatorul 3
Separatorul 4
Bara 1
Vs: 15 kV
15 kV
Separatorul 12
Intr er upatorul 4
Intr er upator 3
Bara 2/1
Vs: 15 kV
15 kV
Separatorul 11
Separatorul 10
Separatorul 13
Separatorul 9
Bara 2/2
Vs: 15 kV
15 kV
Separatorul 7
Separatorul 6
Separatorul 8
Intr er upator 6
Intr erupator 5
Trafo 2
Trafo 1
Consumatorul 1
Vs: 15 kV
14.96 kV
Consumatorul 2
Vs: 15 kV
14.98 kV
:
:
:
:
:
System Information
==================
Base Power
Frequency
MaxIterations
Error Tolerance
# of Active Buses
# of Swing Buses
# of Generators
# of Lines/Breakers
# of Transformers
# of Loads
# of Shunts
=
=
=
=
=
=
=
=
=
=
=
100000.00 (kVA)
50 (Hz)
1000
10.000 (kVA), 0.0100 (%)
23
0
2
16
2
2
0
=
=
=
upto
upto
1
1
No
Abbreviations
=============
2-W xfmr = 2-winding transformer
FeederM
= Feeder in Magnetic
= 3-winding transformer
= Autotransformer
occ/yr
IEAR
= Curtailment or curtailed
SeriesC
Conduit
3-W xfmr
Autoxfmr
Assessment Rate
curt
Transformer
f./y
= Series Capacitor
Pmax
Qmax
Qmin
(MW)
(MVAR)
(MVAR)
Failure
Repair
Priority
Rate
Time
1 to 99
Reliability
(f./y)
(hours)
(Yes/No)
------------------------ -------- -------- -------- --------- ------- --------------Generatorul 1
200.000
0.500
-0.500 0.001050
952.0
1
Yes
Generatorul 2
200.000
0.500
-0.500 0.001050
952.0
1
Yes
Type
Carrying Failure
Capacity Rate
(MVA)
(f./y)
------------------------ -------- -------- --------Intrerupator 3
Breaker
15.588 0.010700
Intrerupator 5
Breaker
15.588 0.010700
Intrerupator 6
Breaker
15.588 0.010700
Intrerupatorul 1
Breaker
15.588 0.010700
Intrerupatorul 2
Breaker
15.588 0.010700
Intrerupatorul 4
Breaker
15.588 0.010700
Separatorul 1
Switch
25.981 0.000000
Separatorul 10
Switch
25.981 0.000000
Separatorul 11
Switch
25.981 0.000000
Separatorul 13
Switch
25.981 0.000000
Separatorul 14
Switch
25.981 0.000000
Separatorul 3
Switch
25.981 0.000000
Separatorul 5
Switch
25.981 0.000000
Separatorul 6
Switch
25.981 0.000000
Separatorul 7
Switch
25.981 0.000000
Separatorul 9
Switch
25.981 0.000000
Trafo 1
2-W xfmr
1.050 0.001620
Trafo 2
2-W xfmr
1.050 0.001620
Repair
Time
(hours)
------93.6
93.6
93.6
93.6
93.6
93.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
616.0
616.0
Consider
Reliability
(Yes/No)
-------Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Type
-----P_Load
P_Load
Required
Availability (%)
---------------100.00000
100.00000
Calculated
Pass/Fail
Availability (%)
---------------- --------99.96592
Fail
99.96592
Fail
=
=
0.022995 (MW/MW-yr)
0.250000 (MW/curt.)
2.985665 (MWh/MW-yr)
0.000341
179.139893 (Sys-Min)
System availability
99.965919 (%)
=
=
=
=
=
0.00 (Mvar/yr)
0.00 (Mvar/viol)
=
=
0.00 (k$/yr)
0.00 (k$/curt.)
0.000682
0.000170 (MW/occ)
0.045136 (MWh/occ)