_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
APROVAO
______________________
Jlio Csar Ragone Lopes
Diretor Corporativo de Engenharia e Construo DCEC
Grupo Energisa
______________________
Gioreli de Sousa Filho
Vice-Presidente de Distribuio VPD
Grupo Energisa
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
SUMRIO
1.
2.
3.
4.
INTRODUO ........................................................................................................... 1
EXCEES ................................................................................................................ 1
DEFINIES .............................................................................................................. 1
CONDIES GERAIS DE FORNECIMENTO ........................................................... 5
4.1. Tenses de Fornecimento .................................................................................................. 5
4.2. Limites de Fornecimento ................................................................................................... 5
4.3. Tipos de Atendimento ........................................................................................................ 6
4.4. Categorias de Atendimentos (ver tabela n. 13 a 19) ......................................................... 6
4.5. Tipos e Limites de Atendimento ...................................................................................... 10
4.6. Ligaes de Cargas Especiais .......................................................................................... 13
4.7. Fornecimento de Materiais da Entrada de Servio .......................................................... 13
4.8. Execuo da Entrada de Servio ...................................................................................... 14
4.9. Conservao da Entrada de Servio ................................................................................. 14
4.10.
Condies no Permitidas ............................................................................................ 14
4.11.
Documentos Necessrios para Apresentao de Projetos ............................................ 16
4.12.
Ligao de Canteiro de Obra na EPB e EBO ............................................................... 18
5. RAMAL DE LIGAO ............................................................................................. 18
5.1. Condutores ....................................................................................................................... 18
5.2. Critrios Construtivos do Ramal de Ligao ................................................................... 19
5.3. Fixao ............................................................................................................................. 20
6. PONTO DE ENTREGA............................................................................................. 20
7. RAMAL DE ENTRADA EMBUTIDO/SUBTERRNEO ............................................ 21
7.1. Condutores ....................................................................................................................... 21
7.2. Eletroduto......................................................................................................................... 21
7.3. Ramal de Entrada Subterrneo ........................................................................................ 22
8. DISPOSIES DAS ENTRADAS DE SERVIO ..................................................... 24
9. PROTEO DA ENTRADA DE SERVIO .............................................................. 24
10. MEDIO ................................................................................................................. 25
10.1.
Localizao................................................................................................................... 25
10.2.
Instalao ...................................................................................................................... 25
11. ATERRAMENTO ...................................................................................................... 26
12. CAIXAS PARA EQUIPAMENTO DE MEDIO E/OU PROTEO ....................... 27
13. POSTES E PONTALETES ....................................................................................... 28
14. DEMANDA E DIMENSIONAMENTO PARA ENTRADAS TRIFSICAS COM
NEUTRO ......................................................................................................................... 29
15. NOTAS COMPLEMENTARES ................................................................................. 31
16. ANEXO I - TABELAS ............................................................................................... 32
17. ANEXO II - DECLARAO DE COMPROMISSO - RAMAL
SUBTERRNEO ............................................................................................................. 52
18. ANEXO III - DESENHOS .......................................................................................... 53
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
1. INTRODUO
Esta norma fixa os procedimentos a serem seguidos em projetos e execuo das
instalaes de entradas de servio das unidades consumidoras de baixa tenso em toda
a rea de concesso da ENERGISA, quando a carga instalada na unidade consumidora
for igual ou inferior a 75 kW, conforme legislao em vigor.
As recomendaes contidas nesta norma se aplicam s instalaes individuais ou
agrupadas at 3(trs) unidades consumidoras urbanas e rurais, classificadas como
residenciais, comerciais, rurais, poderes pblicos e industriais, a serem ligadas em
redes de distribuio areas de distribuio secundrias, obedecidas as normas da
ABNT (Associao Brasileira de Normas Tcnicas) e as Resolues da ANEEL
(Agncia Nacional de Energia Eltrica).
2. EXCEES
Os casos no previstos nesta norma, ou aqueles que pelas caractersticas exijam
tratamento parte, devero ser previamente encaminhados Concessionria, atravs
de seus escritrios locais, para apreciao conjunta da rea de projetos / rea de
estudos.
3. DEFINIES
3.1. Aterramento
Ligao terra do neutro da rede e o da instalao consumidora.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
-1-
3.6. Condomnio
Chama-se de condomnio loteamento fechado, cujas vias internas de acesso as
unidades no so consideradas pblicas e que as partes comuns so propriedades dos
condminos e por eles administrados.
3.7. Consumidor
Pessoa fsica ou jurdica ou comunho de fato ou de direito, legalmente representada,
que solicitar Concessionria o fornecimento de energia eltrica e assumir a
responsabilidade pelo pagamento das faturas e pelas demais obrigaes fixadas em
normas e regulamentos da ANEEL, assim vinculando-se aos contratos de fornecimento.
3.8. Demanda
a mdia das potncias eltricas, ativas ou reativas, solicitadas ao sistema eltrico,
pela parcela de carga instalada em operao na unidade consumidora, durante um
intervalo de tempo especificado.
3.9. Edificao
toda e qualquer construo, reconhecida pelos poderes pblicos, utilizada por um
ou mais consumidores.
3.16. Medidor
o aparelho instalado pela concessionria, que tem por objetivo medir e registrar o
consumo de energia eltrica ativa e ou reativa.
3.19. Pontalete
Suporte instalado na edificao do consumidor com a finalidade de fixar e elevar o
ramal de ligao.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
-3-
3.22. Potncia
Quantidade de energia eltrica solicitada na unidade de tempo.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
-4-
Tenso(es) de Fornecimento
Empresa
Rede Secundria
Sistema Monofsico
Sistema Trifsico
e/ou Rural
Sergipe
115/230 V
Nova Friburgo
115/230 V
Minas Gerais
115/230 V
Paraba
220 V
Borborema
220 V
Caiu
Nacional
Bragantina
Fora e Luz do
Oeste
Vale
Paranapanema
Celtins
115/230 V e 127/254 V
127/254 V
127/254 V
Comentrios / Excepcionalidades
127/254 V
127/220 V
127/254 V
127/220 V
220/440 V
220/380 V
Cemat
127/254 V
Enersul
127/254 V
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
-5-
Energisa: Sergipe, Nova Friburgo, Minas Gerais, Caiu, Nacional, Bragantina, Fora e
Luz do Oeste, Vale do Paranapanema, Cemat e Enersul.
CATEGORIA
Monofsico
Trifsico
POTENCIA / DEMANDA
M1
M2
M3
B1
B2
B3
T1
T2
T3
T4
T5
T6
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
-6-
NOTAS:
CATEGORIA
Monofsico
Trifsico
POTNCIA / DEMANDA
M1
M2
M3
B1
B2
B3
T1
T2
T3
T4
T5
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
-7-
NOTAS:
CATEGORIA
Monofsico
POTNCIA
M1
M2
M3
B1
B2
B3
B4
B5
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
-8-
NOTA:
CATEGORIA
Monofsico
POTNCIA
M1
M2
M3
M4
M5
CATEGORIA
Monofsico
POTNCIA
M1
M2
NOTA:
CATEGORIA
Monofsico
DEMANDA
M1
M2
M3
M4
NOTA:
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 13 -
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 14 -
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 15 -
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 16 -
NOTAS:
1. A apresentao do projeto dever ser feita em duas vias, das quais uma ser
devolvida, devidamente aprovada ao interessado.
2. Prazo mximo para anlise do projeto eltrico pela Concessionria de 30
dias corridos.
3. O prazo de validade da aprovao do projeto de 24 (vinte e quatro) meses,
a contar da data de aprovao do projeto pela Concessionria. Aps este
prazo, o projeto que no tenha sido executado, dever ser reapresentado
Concessionria tendo sido feitas as adequaes conforme norma vigente,
quando necessrias.
4. No caso de necessidade de alterao do projeto eltrico j analisado pela
Concessionria, obrigatrio encaminhar o novo projeto para anlise pela
Concessionria.
5. A entrada de servio da unidade consumidora s deve ser instalada aps a
aprovao do projeto eltrico, pela concessionria.
6. Ser exigido projeto eltrico para os agrupamentos cujas categorias no
estejam contempladas nas tabelas n. 14 e 16.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 17 -
5. RAMAL DE LIGAO
5.1. Condutores
5.1.1. Os condutores para os ramais de ligao areos sero multiplexados, com
isolamento em XLPE, fases em alumnio CA e neutro nu em alumnio CA at a
bitola de 25mm e CAL para bitolas a partir de 35mm.
5.1.2. Os condutores para os ramais de ligao areos devero atender aos
requisitos da NBR 8182 bem como os padres da Concessionria.
5.1.4. A bitola mnima dos condutores para duas ou trs unidades consumidoras
est dimensionada na tabela n.21.
5.1.5. No sero permitidas emendas nos condutores do ramal de ligao.
5.1.6. O isolamento mnimo dos condutores ser de 0,6 / 1 kV.
5.3. Fixao
5.3.1. Podero ser usados poste auxiliar ou pontalete, dimensionados conforme as
tabelas n. 13 a 19. O poste auxiliar ou pontalete dever ser localizado no limite
da propriedade com a via pblica.
5.3.2. A amarrao dos condutores dever ser executada conforme o desenho 024.
6. PONTO DE ENTREGA
O ponto de entrega de energia eltrica dever situa-se no limite da via pblica com o
imvel em que se localizar a unidade consumidora, ressalvados os seguintes casos:
caso
de
consumidor
rural
atendido
por
transformador
exclusivo
da
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 20 -
7.1.1. Os condutores devero ser de cobre, isolamento do tipo PVC, HEPR, EOR
ou XLPE, todos para classe de tenso em 0,6/1,0kV, prprios para instalao
em eletrodutos, de bitola mnima determinada pelas tabelas n. 13 a 19,
conforme a carga instalada e a demanda, no devendo ser inferior a 6 mm.
7.1.2. Os condutores devero possuir isolamento conforme tabela n. 13 a 19,
inclusive o neutro, que dever ser perfeitamente identificado.
7.1.3. Dever haver continuidade do neutro, sendo nele vedado o uso de chave,
disjuntor ou fusvel ou qualquer outro tipo de seccionamento.
7.1.4. No sero permitidas emendas nos condutores do ramal de entrada.
7.1.5. Os condutores devero ter comprimento suficiente para permitir a conexo
ao ramal de ligao (desenhos 013 a 023) nas condies dos padres
construtivos, bem como aos equipamentos de medio e proteo.
7.1.6. Os condutores do ramal (fases) de entrada devero possuir identificao
no ponto de derivao e no ponto de conexo medio.
7.2. Eletroduto
7.2.1. Para a Energisa Paraba, Borborema e Sergipe, o eletroduto dever ser de
PVC rgido (NBR 6150) ou de ao galvanizado a imerso a quente, tipo
pesado (NBR 5624) para atendimento em Ramal Areo e para ramais
subterrneos derivados do poste da concessionria de dimetro nominal
conforme tabelas n. 13 a 19. Para Energisa Nova Friburgo, Minas Gerais,
Caiu, Nacional, Bragantina, Fora e Luz do Oeste, Vale do Paranapanema
Celtins, Cemat e Enersul, o eletroduto dever ser de PVC rgido (NBR 6150)
ou de ao galvanizado a imerso a quente, tipo pesado (NBR 5624) para
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 21 -
7.3.1. Condutores
a) Os condutores devero ser de cobre, classe 2 de encordoamento e isolamento do
tipo PVC, HEPR, EPR ou XLPE, todos para classe de tenso em 0,6/1,0 kV e de
bitola mnima conforme tabela n. 13 a 19.
b) No sero permitidas emendas nos condutores do ramal subterrneo.
c) Em caso de curvas dos cabos, o raio mnimo adequado dever ser 12 (doze) vezes o
dimetro externo dos cabos, salvo indicao contrria do fabricante.
d) A instalao dos cabos dever ser feita pelo consumidor aps a instalao completa
dos dutos subterrneos.
e) Junto ao poste da Concessionria, dever ser deixada uma sobra de 2,00m de
cabos na caixa de passagem.
7.3.2. Detalhes Construtivos
a) O ramal de entrada subterrneo ser construdo conforme posturas municipais e
com autorizao da Concessionria.
b) A entrada subterrnea dever derivar diretamente da rede de distribuio da
Concessionria.
c) A tubulao do ramal subterrneo no dever cortar terrenos de terceiros, passar
sobre rea construda e/ou cruzar vias de rolamento.
d) A entrada do ramal subterrneo dever ser construda, sempre que possvel, pela
frente a rea da unidade consumidora.
e) Obedecer s padronizaes e recomendaes, conforme desenhos 007 a 010.
f) Os condutores devero ser protegidos por meio de eletroduto de ao galvanizado
por imerso a quente, com conexes conforme NBR 5624 (desenho 007), dimetro
nominal conforme tabelas n. 13 a 19.
g) Devero ser adotadas caixas de passagem de dimenses internas mnimas
conforme desenhos 009 e 010.
h) Para a Energisa Paraba, Borborema e Sergipe a descida do poste dever ser
sempre protegida por eletroduto de ao galvanizado, a fogo do tipo pesado (NBR
5624) ou PVC rgido (NBR 6150), com comprimento de 6,00 metros. Para Energisa
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 23 -
Nova Friburgo, Minas Gerais, Caiu, Nacional, Bragantina, Fora e Luz do Oeste,
Vale do Paranapanema Celtins, Cemat e Enersul a descida do poste dever ser
sempre protegida por eletroduto de ao galvanizado, a fogo do tipo pesado (NBR
5624) com comprimento de 6,00 metros.
i) A extremidade dos eletrodutos dever ser curvada para baixo, atravs de cabeote
para eletroduto, conforme desenho 034.
j) obrigatria a construo de caixa de passagem prximo ao poste, conforme
desenho 007, a qual poder ficar em qualquer posio em relao ao poste, desde
que em cima do passeio a um raio de um metro do poste.
k) permitida a utilizao de uma nica caixa de passagem para mais de um ramal de
ligao subterrneo, sendo que na descida do poste os condutores de cada unidade
consumidora devero ficar em eletrodutos independentes.
l) As edificaes atendidas devero ser identificadas atravs de uma placa metlica de
20cm x 10cm contendo os nmeros das edificaes pintados com tinta de
revestimento anticorrosivo ou pintar o nmero da edificao no eletroduto com tinta
anticorrosiva. Esse procedimento deve ser adotado mesmo que no poste s haja um
consumidor atendido atravs de ramal de ligao subterrneo.
m) de responsabilidade do consumidor a confeco e colocao da placa de
identificao, devendo esta ser instalada imediatamente abaixo do pingadouro, a
aproximadamente 6,0m do solo.
10. MEDIO
10.1. Localizao
10.1.1. A Concessionria reserva-se o direito de, em qualquer caso, indicar o
local mais adequado para instalao da medio, observadas entretanto, as
seguintes disposies.
10.1.2. Dever ficar na propriedade do consumidor, situada no limite do terreno
com a via pblica com o visor voltado p/ mesma, conforme desenhos 005 e
006.
10.1.3. Onde as casas so recuadas em relao via pblica a medio dever
ser feita em mureta ou fixada no muro na divisa do lote com a via pblica,
conforme desenhos 005 e 006.
10.2. Instalao
10.2.1. Os equipamentos de medio sero instalados e ligados pela
Concessionria aps aprovao e vistoria do padro de entrada de energia.
10.2.2. O centro do visor da caixa de medio dever ficar a uma altura de
1.550mm do piso +50 e -100 mm.
10.2.3. Sempre que houver agrupamento de medio, as caixas de medidores
devero ser marcadas pelos consumidores de modo a identific-las com suas
respectivas instalaes.
A marcao dever ser feita na caixa de medio no lado externo da
tampa. As letras, sempre maisculas e os nmeros devero ter 30 5 mm de altura e
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 25 -
devero ser pintadas utilizando moldes e nunca mo livre. As bordas superiores das
letras e nmeros pintados externamente devero ficar a 50 5 mm abaixo do visor
existente na tampa.
11. ATERRAMENTO
a) Devero ser respeitadas todas as consideraes estabelecidas na NBR5410 da
ABNT.
b) O neutro da entrada de servio dever ser aterrado num ponto nico, e junto com a
caixa quando a mesma for metlica.
c) As partes condutoras, normalmente sem tenso, devero ser permanentemente
ligadas a terra.
d) O condutor de aterramento dever ser protegido mecanicamente at a caixa de
inspeo atravs de eletroduto de PVC rgido independente, e dever ter bitola
mnima conforme tabelas n. 13 a 19.
e) O condutor de aterramento dever ser de cobre.
f) O condutor de aterramento dever ser to curto e retilneo quando possvel, sem
emenda e no ter dispositivo que possa causar sua interrupo.
g) O ponto de conexo do condutor de aterramento a haste dever ser acessvel
inspeo, ser revestido com massa de calafetar, e ser protegido mecanicamente por
meio de uma caixa de cimento, alvenaria, PVC ou similar, com tampa de concreto ou
ferro fundido, conforme desenho 030.
h) O valor da resistncia da terra, em qualquer poca do ano, no dever ultrapassar a
20 Ohms. No caso de no ser atingido esse limite, com o nmero mnimo de haste
empregada conforme tabelas n. 13 a 19, devero ser usadas tantas quantas
necessrias distanciadas entre si de 3000 mm e interligados pelo condutor de
aterramento.
i) Devero ser obedecidos os padres construtivos conforme desenho 035.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 26 -
Caixa para medio direta com medidor de 200A: chapa de ao, pintada
eletrostaticamente, conforme desenhos 034, 035, 037 e 038 (Energisa
Nova Friburgo e Minas Gerais) e desenhos 034, 036, 039 e 040 (Energisa
Borborema, Paraba, Sergipe, Caiu, Nacional, Bragantina, Fora e Luz do
Oeste, Vale do Paranapanema Celtins, Cemat e Enersul).
12.1.2. Identificao
As caixas devero ser marcadas de maneira clara e indelevelmente na parte
frontal da tampa, com as seguintes informaes:
Nome e/ou marca comercial do fabricante.
Ano de fabricao.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 27 -
13.2. Pontalete
a) O pontalete dever ser de tubo de ao galvanizado a quente (tipo pesado-NBR
5624).
b) Os pontaletes devero obedecer aos padres construtivos constantes nesta norma,
conforme desenho 029.
c) O pontalete dever ser dimensionado conforme tabela n. 13 a 19.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 28 -
sendo:
NOTAS:
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 30 -
2.
3.
4.
sejam
especificadas,
projetadas
construdas
conforme
as
prescries da ABNT, atravs da NBR NM-280, NR-10, NBR-5410, NBR5419, NBR 5361, NBR 6150, NBR 10676, NBR 13534, NBR13514,
NBR13570, NBR 15688 e demais Normas aplicveis em vigncia no Brasil.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 31 -
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 32 -
POTNCIA
(VA)
POTENCIA
(W)
DESCRIO
COD.
POTNCIA
(VA)
COD.
DESCRIO
POTENCIA
(W)
AMALGAMADOR
200
217
38
BEBEDOURO
AMPLIFICADOR DE SOM
100
109
39
BETONEIRA
1.000
1.111
BOILLER
1.122
1.122
200
222
APARELHO DE ENDOSCOPIA
45
49
40
APARELHO DE ULTRASONOGRAFIA
600
652
41
184
230
368
460
APARELHO DE OBTURAO
155
168
42
2.000
2.000
43
552
690
1.500
1.500
44
BOMBA D'GUA 1 CV
736
920
920
1.150
800
1000
45
900
1100
46
1.104
1.380
10
1.200
1.412
47
BOMBA D'GUA 2 CV
1.472
1.732
BOMBA D'GUA 3 CV
2.208
2.598
11
1.300
1.500
48
12
1.400
1.647
49
BOMBA DE COMBUSTVEL
736
866
BOMBA SAPO
300
353
13
1.400
1.650
50
14
1.550
1.824
51
CADEIRA DE DENTISTA
184
216
15
1.600
1.882
52
CAFETEIRA ELTRICA
500
500
CAFETEIRA ELTRICA
750
750
350
350
16
1.700
1.900
53
17
1.900
2.100
54
CMARA DE FERMENTAO
18
2.000
2.222
55
CMARA FRIGORFICA
22.080 24.533
CARREGADOR DE BATERIA
660
733
19
2.100
2.333
56
20
2.600
2.860
57
CENTRAL DE AR (1TR)
1.817
2.019
CENTRAL TELEFNICA
30
33
4.500
4.500
21
2.800
3.080
58
22
3.200
3.516
59
CHUVEIRO ELTRICO
23
3.600
4.000
60
6.500
6.500
CILINDRO
2.210
2.456
24
ASPIRADOR DE P COMERCIAL
2.240
2.435
61
25
ASPIRADOR DE P COMERCIAL
1.000
1.087
62
30
33
26
ASPIRADOR DE P RESIDENCIAL
750
815
63
COMPRESSOR
368
409
COMPUTADOR
300
333
27
ASSADEIRA GRANDE
1.000
1.000
64
28
ASSADEIRA PEQUENA
500
500
65
CONJUNTO DE SOM/MICROSYSTEM
100
111
CORTADOR DE GRAMA
1.600
1.778
30
33
29
BALANA ELTRICA
20
20
66
30
1.000
1.111
67
DECK
31
500
556
68
DEPENADOR DE GALINHA
891
990
DESCASCADOR DE BATATAS
1.000
1.111
368
409
33
32
1.304
1.449
69
33
BALCO TRMICO
762
847
70
DESEMPENO
34
1.822
1.822
71
DVD
30
ELEVADOR GRANDE
10.304 11.449
35
BARBEADOR ELTRICO
50
56
72
36
BATEDEIRA DE BOLO
100
111
73
ENCERADEIRA
400
444
338
74
EQUALIZADOR
30
33
37
BATEDEIRA INDUSTRIAL
304
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 33 -
2.208
2.453
118 FREEZER
100
111
76
ESPIGADEIRA
2.208
2.453
90
100
77
ESPREMEDOR DE FRUTAS
50
56
120
133
78
ESTABILIZADOR
920
1.022
150
167
79
ESTEIRA ROLANTE
1.472
1.636
750
833
80
50
56
750
833
81
ESTUFA
1.000
1.000
90
100
82
ESTUFA DENTISTA
1.000
1.000
120
133
83
ETIQUETADORA
70
78
150
167
84
EXAUSTOR GRANDE
400
444
127 FRIGOBAR
80
89
85
EXAUSTOR PEQUENO
200
222
2.000
2.000
86
FACA ELTRICA
140
156
3.000
3.000
87
FATIADOR
736
818
5.000
5.000
88
FAX
50
56
1.000
1.000
89
600
600
350
350
90
400
400
133 GELADEIRA
90
100
90
100
100
111
COD.
COD.
POTNCIA
(VA)
POTNCIA
(VA)
ESMERIL
DESCRIO
POTENCIA
(W)
POTENCIA
(W)
75
DESCRIO
91
100
100
92
FERRO ELTRICO
550
550
93
1.000
1.000
120
133
94
90
90
150
167
95
FOGO ELTRICO
2.000
2.000
150
167
96
FORNO MICROONDAS
1.140
1.239
1.500
1.500
97
2.000
2.000
500
500
98
10.000 10.000
141 GRILL
1.200
1.200
38.000 38.000
142 HIDROMASSAGEM
368
433
24.400 24.400
90
106
800
941
22.000 22.000
145 IOGURTEIRA
30
35
25.000 25.000
40
40
21.600 21.600
60
60
3.000
100
100
99
3.000
52.200 52.200
150
150
16.500 16.500
50
50
3.000
20
22
3.000
28.000 28.000
40
43
28.000 28.000
150
150
35.000 35.000
160
160
36.000 36.000
250
250
8.500
8.500
156 LMPADA PL
10
11
6.000
6.000
157 LMPADA PL
15
17
2.000
2.000
158 LMPADA PL
20
22
116 FORRAGEIRA
736
866
159 LMPADA PL
30
33
117 FOTOCOLORIMENTO
550
550
125
136
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 34 -
POTNCIA
(VA)
POTENCIA
(W)
DESCRIO
COD.
POTNCIA
(VA)
POTENCIA
(W)
COD.
DESCRIO
250
272
204 MOINHO
606
673
70
76
205 MONITOR
154
171
100
109
206 MOTOR
750
833
150
163
552
613
250
272
180
200
400
435
1.200
1.333
30.276 35.619
80
89
168 LIQUIDIFICADOR
200
222
100
111
1.000
1.111
220
244
1.000
1.111
213 PLAINA
746
829
850
944
214 POLIDORA
50
56
281
281
215 PONTIADEIRA
1.417
1.574
373
373
184
204
100
111
281
312
911
1.012
218 PRENSA
1.104
1.227
850
944
219 PROCESSADOR/CENTRFUGA
460
511
140
140
220 PROJETOR
215
239
792
880
221 PURIFICADOR DE AR
25
28
1.700
1.889
30
33
1.200
1.333
40
44
1.000
1.111
300
333
373
414
1.087
1.208
6.400
6.400
12.144 13.493
1.000
1.111
467
15
17
110
122
396
440
228 REBOBINADOR
2.000
2.222
519
1.400
1.556
230 REFLETOR
500
556
6.133
150
150
324
360
100
111
1.104
1.227
12.000 12.000
1.417
1.574
4.500
4.500
192 MASSAGEADOR
220
244
1.500
1.500
193 MASSEIRA
2.208
2.453
1.000
1.000
194 MERGULHO
583
648
5.000
5.000
350
389
1.100
1.100
1.000
1.111
2.429
2.429
197 MICROONDAS
1.200
1.333
20
22
40
44
1.000
1.111
199 MINILAB
3.000
3.333
600
667
200 MIX
80
89
240
267
201 MODELADORA
490
544
244 SORVETEIRA
20
22
370
411
245 STERILAIR
396
440
320
356
40
44
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 35 -
POTNCIA
(VA)
POTENCIA
(W)
COD.
DESCRIO
247 TECLADO
50
56
10
11
50
56
100
111
150
167
90
100
30
33
2.000
2.222
255 TORNO
1.817
2.019
256 TORQUIA
7.266
8.073
257 TORRADEIRA
800
889
700
778
259 TRAADEIRA
3.680
4.089
1.214
1.349
200
222
262 TV AM/FM
50
56
263 VAPORIZADOR
300
333
250
278
120
133
80
89
267 VIBRADOR
1.000
1.111
30
33
20
22
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 36 -
FATOR DE DEMANDA
(%)
RESIDNCIAS
0<P1kW
1<P2kW
2<P3kW
3<P4kW
4<P5kW
5<P6kW
6<P7kW
7<P8kW
8<P9kW
9<P10kW
10<P75kW
86
75
66
59
52
45
40
35
31
27
24
86
RESTAURANTES E SIMILARES
LOJAS E SIMILARES
86
IGREJAS E SIMILARES
86
HOSPITAIS E SIMILARES
HOTEIS E SIMILARES
GARAGEM, REAS DE
SERVIO E SIMILARES
ESCRITRIOS
ESCOLAS E SIMILARES
40
50
50
40
30
86
CLUBES E SEMELHANTES
86
70
86
50
86
BARBEARIAS, SALES DE
BELEZA E SIMILARES
86
BANCOS E CANTEIROS DE
OBRAS
86
86
QUARTIS E SEMELHANTES
100
40
Notas:
1 Instalaes em que a carga ser utilizada de maneira simultnea devero ser consideradas com o fator de
demanda de 100%.
2 No esto sendo considerados nesta tabela cargas do tipo letreiro e iluminao de vitrines.
3 - Clculo da demanda Industrial Ver item 14.2
4 - No clculo da demanda residencial o valor percentual de cada faixa acumulativo, ou seja, a soma dos
valores de cada faixa.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 37 -
1
2
3
4
5
6
7
8
9
10
11
12
100
75
70
66
62
59
56
53
51
49
47
45
13
14
15
16
17
18
19
20
21
22
23
24
Acima de 24
FATOR DE
DEMANDA
(%)
N. DE
APARELHOS
FATOR DE
DEMANDA
(%)
N. DE
APARELHOS
43
41
40
39
38
37
36
35
34
33
32
31
30
FATOR DE DEMANDA
(%)
100
70
60
50
45
FATOR DE
DEMANDA (%)
100
60
48
40
37
35
33
N. DE
APARELHOS
8
9
10 a 11
12 a 15
16 a 20
21 a 25
Acima de 25
FATOR DE
DEMANDA (%)
32
31
30
28
27
26
25
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 38 -
8500
10000
12000
CAPACIDADE
1775
(kcal/h)
2125
2500
3000
3500
4500
5250
7500
TENSO (V)
127
220
127
CORRENTE
(A)
8,66
5,00
12,20 6,82
POTNCIA
(VA)
POTNCIA
(W)
220
127
220
127
220
220
220
220
220
12,99
7,50
14,96
8,64
9,55
13,00
14,00
18,18
1500 1650
1650 1900
1900 2100
2860
3080
4000
900
1300 1400
1400 1700
1700 1900
2600
2800
3600
900
1300
APARELHOS
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 39 -
DE
AR-
APARELHOS
N. DE APARELHOS
1 a 10
100
11 a 20
90
21 a 30
82
31 a 40
80
41 a 50
77
Acima de 50
75
DE
AR-
Potncia
kVA
Cos
Eixo CV
Absorvida da
Rede kW
kVA
1/4
0,391
0,62
0,63
1/3
0,522
0,74
0,71
1/2
0,657
0,91
0,72
Corrente
(A) - 220 V -
Corrente (A)
- 380 V -
0,47
2,82
0,47
3,34
0,56
4,15
1 Motor (I)
2 Motores (I)
3 a 5 Motores
(II)
Mais de 5
Motores (IV)
1,64
0,62
0,50
0,43
0,37
1,93
0,74
0,59
0,51
0,44
2,40
0,91
0,73
0,64
0,55
3/4
0,890
1,24
0,72
0,62
5,62
3,25
1,24
0,99
0,87
0,74
1,00
1,099
1,48
0,74
0,67
6,75
3,91
1,48
1,19
1,04
0,89
1,50
1,577
1,92
0,82
0,70
8,74
5,06
1,92
1,54
1,35
1,15
2,00
2,073
2,44
0,85
0,71
11,09
6,42
2,44
1,95
1,71
1,46
3,00
3,067
3,19
0,96
0,72
14,52
8,41
3,19
2,56
2,24
1,92
4,00
3,978
4,14
0,96
0,74
18,84
10,91
4,14
3,32
2,90
2,49
5,00
4,907
5,22
0,94
0,75
23,73
13,74
5,22
4,18
3,65
3,13
7,50
7,459
7,94
0,94
0,74
36,07
20,88
7,94
6,35
5,55
4,76
10,00
9,436
10,04
0,94
0,78
45,63
26,42
10,04
8,03
7,03
6,02
12,50
12,105
13,02
0,93
0,76
59,17
34,25
13,02
10,41
9,11
7,81
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 40 -
Potncia
kVA
Cos f
Corrente
(A) - 220 V -
Corrente
(A) - 380 V -
Eixo CV
Absorvida da
Rede kW
kVA
1 Motor (I)
2 Motores (I)
3a5
Motores (II)
Mais de 5
Motores (IV)
1/6
0,250
0,37
0,67
0,49
0,98
0,335
0,48
0,69
0,55
1,27
0,57
0,37
0,30
0,26
0,22
0,74
0,48
0,39
0,34
0,29
1/3
0,409
0,55
0,74
0,60
0,566
0,72
0,79
0,65
1,45
0,84
0,55
0,44
0,39
0,33
1,88
1,09
0,72
0,57
0,50
0,824
1,08
0,76
0,43
0,67
2,84
1,65
1,08
0,87
0,76
0,65
1,0
1,132
1,38
1,5
1,577
2,02
0,82
0,65
3,62
2,10
1,38
1,10
0,97
0,83
0,78
0,70
5,31
3,07
2,02
1,62
1,42
2,0
1,937
1,21
2,39
0,81
0,76
6,28
3,63
2,39
1,91
1,67
1,43
3,0
4,0
2,905
3,63
0,80
0,76
9,53
5,52
3,63
2,91
2,54
2,18
3,823
4,97
0,77
0,77
13,03
7,54
4,97
3,97
3,48
2,98
5,0
4,779
5,62
0,85
0,77
14,76
8,54
5,62
4,50
3,94
3,37
6,0
5,452
6,49
0,84
0,81
17,03
9,86
6,49
5,19
4,54
3,89
7,5
6,900
8,12
0,85
0,80
21,30
12,33
8,12
6,49
5,68
4,87
10,0
9,684
10,76
0,90
0,76
28,24
16,35
10,76
8,61
7,53
6,46
12,5
11,795
12,04
0,98
0,78
31,59
18,29
12,04
9,63
8,42
7,22
15,0
13,630
14,98
0,91
0,81
39,31
22,76
14,98
11,98
10,48
8,99
20,0
18,400
20,67
0,89
0,80
54,26
31,41
20,67
16,54
14,47
12,40
25,0
22,439
24,66
0,91
0,82
64,71
37,46
24,66
19,73
17,26
14,79
30,0
26,927
29,59
0,91
0,82
77,65
44,96
29,59
23,67
20,71
17,75
Solda a arco e
aparelhos de
galvanizao
Solda a resistncia
Aparelho de raios X
POTNCIA DO
APARELHO
FATOR DE
DEMANDA
1 maior
100
2 maior
3 maior
Soma dos demais
70
40
30
Maior
100
60
Maior
100
70
Nota: As mquinas de solda do tipo motor gerador devero ser consideradas como motores.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 41 -
De Rotor em Curto-Circuito
(Assncrono ou Sncrono)
POTNCIA DO MOTOR
MTODO DE PARTIDA
P < 5 CV
Direto
5 CV P 15 CV
Chave Estrela-Tringulo
Compensador de partida, Soft-Start ou
Inversor de Frequncia
(exceto chave estrela-tringulo)
Reostato
15 CV < P 30 CV
De Rotor Bobinado (ou anis) P 30 CV
NOTAS:
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 42 -
FIXAO EMBUTIDO NA
PAREDE (mm)
POSTE DT
PONTALETE
POSTE TUBO DE AO
GALVANIZADO (mm)
POSTE
ELETRODUTO DE AO
GALVANIZADO (mm)
ATERRAMENTO (COBRE)
RAMAL DE ENTRADA
EMBUTIDO E
SUBTERRNEO (COBRE
EPR/XLPE 90C)
RAMAL DE ENTRADA
EMBUTIDO E
SUBTERRNEO (COBRE
PVC 70C)
RAMAL DE LIGAO
CONCNTRICO (ALUMINIO)
RAMAL DE LIGAO
MULTIPLEX (ALUMNIO)
POTNCIA/DEMANDA
N. DE FASES
N. DE FIOS
CATEGORIA
CONDUTORES (mm )
DISJUNTOR TERMOMAGNTICO
(Limite Maximo (A))
Energisa: Sergipe, Nova Friburgo, Minas Gerais, Caiu, Nacional, Bragantina, Fora e Luz do
Oeste, Vale do Paranapanema e Enersul.
M1
0 < P 3,80
1x1x10+10
2x10
6(6)
6(6)
1H 16X2400
30/32
25
20
5/7m
150
80X 5/7m
40
40
M2
1x1x10+10
2x10
10(10)
10(10)
10
1H 16X2400
50
25
20
5/7m
150
80X 5/7m
40
40
M3
1x1x16+16
16(16)
16(16)
16
1H 16X2400
70
25
25
5/7m
150
80X 5/7m
40
40
B1
0 < P 10,1
2x1x10+10
2#10(10)
2#6(6)
1H 16X2400
40
32
25
5/7m
150
80X 5/7m
50
50
B2
2x1x16+16
2#16(16)
2#10(10)
10
1H 16X2400
50
32
25
5/7m
150
80X 5/7m
50
50
B3
2x1x25+25
2#25(25)
2#16(16)
16
1H 16X2400
70
32
32
5/7m
150
80X 5/7m
50
50
T1
0 < D 15,2
3x1x10+10
3#10(10)
3#6(6)
*H 16X2400
40
32
32
5/7m
150
80X 5/7m
50
50
T2
3x1x16+16
3#10(10)
3#10(10)
10
*H 16X2400
50
32
32
5/7m
150
80X 5/7m
50
50
T3
3x1x25+25
3#25(25)
3#16(16)
16
*H 16X2400
80
40
40
5/7m
150
100X 5/7m
50
50
T4
3x1x35+35
3#35(35)
3#25(25)
16
*H 16X2400
100
50
50
5/7m
300
100X 5/7m
50
50
T5
3x1x70+70
3#70(35)
3#70(35)
35
*H 16X2400
150
75
80
5/7m
600
T6
57,1 < D 75
3x1x120+70
N.A.
3#95(50)
50
*H 16X2400
200
85
90
5/7m
600
N.A - No se Aplica
03 - Nova Friburgo, Minas Gerais, Caiu, Nacional, Bragantina, Fora e Luz do Oeste, Vale do
Paranapanema e Enersul.
Notas:
D = Demanda provvel em kVA ;
Condutores e eletrodutos esto dimensionados com valores mnimos;
Para as categorias T5 e T6 dever ser instalado a caixa padro para medio direta para medidor de 200A;
A coluna ramal de Ligao se refere a condutores multiplexados de alumnio XLPE, fases CA, Neutro nu CAL;
A coluna Proteo est dimensionada para o limite superior de cada faixa. A proteo a ser utilizada ser calculada em
funo da demanda de projeto;
Os condutores para os ramais de entrada, monofsicos, bifsicos e trifsicos devero possuir isolamento do tipo HEPR,
XLPE ou EPR para 0,6/1kV ou PVC para 0,6/1kV;
Os condutores para os ramais subterrneo, devero possuir isolamento do tipo HEPR, XLPE ou EPR para 0,6/1kV ou
PVC para 0,6/1kV;
O ramal de sada dever possuir no mnimo a mesma seo do ramal de entrada;
A categoria B1 ficar para consumidores com carga maior que 8,8 kVA e para o atendimento de instalaes com
equipamentos que requeiram nmeros de fases e/ou tenso prpria destas categorias;
A categoria T1 ficar para o atendimento de instalaes com equipamentos que requeiram nmeros de fases e/ou
tenso prpria destas categorias;
Nos agrupamentos at 03 consumidores o projetista dever efetuar a soma das demandas.
Para agrupamentos at 02 consumidores monofsicos ou bifsicos a entrada de dever ser bifsica, caso contrrio
trifsica;
No caso de agrupamento, as cargas instaladas (consumidor monofsico e bifsico) devero ser somadas as demandas
(consumidor trifsico) e aps, associar a faixa adequada.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 43 -
ATERRAMENTOAOCOBRE
5/7m
50
50
32
5/7m
50
50
2 x B1
40
2x1x10+10
2#6(6)
2#6(6)
3H 16X2400
32
32
5/7m
50
50
2 x B2
50
2x1x16+16
2#10(10)
2#10(10)
10
3H 16X2400
40
40
5/7m
50
50
M1 + B1
30/32
40
3x1x10+10
6(6) + 2#6(6)
6(6) + 2#6(6)
10
3H 16X2400
32
32
5/7m
50
50
M2 + B2
50
50
3x1x16+16
10(10) + 2#10(10)
10(10) + 2#10(10)
10
3H 16X2400
32
32
5/7m
50
50
2 x T1
30/40
3x1x10+10
3#6(6)
3#6(6)
10
3H 16X2400
40
40
5/7m
50
50
2 x T2
50
3x1x16+16
3#10(10)
3#10(10)
10
3H 16X2400
50
50
5/7m
50
50
M1 + T1
30/32
30/40
3x1x10+10
6(6) + 3#6(6)
6(6) + 3#6(6)
3H 16X2400
40
40
5/7m
50
50
M2 + T2
50
50
3x1x16+16
10(10) + 3#10(10)
10(10) + 3#10(10)
10
3H 16X2400
50
50
5/7m
50
50
B1 + T1
40
30/40
3x1x10+10
2#6(6) + 3#6(6)
2#6(6) + 3#6(6)
B2 + T2
50
50
3 x M1
30/32
3 x M2
50
3 x B1
40
3 x B2
50
3 x T1
2xM1 + B1
30/32
40
3x1x10+10
6(6) + 2#6(6)
6(6) + 2#6(6)
10
3H 16X2400
40
40
5/7m
50
50
2xM2 + B2
50
50
3x1x16+16
10(10) + 2#10(10)
10(10) + 2#10(10)
10
3H 16X2400
40
40
5/7m
50
50
2xM1 + T1
30/32
30/40
3x1x10+10
6(6) + 3#6(6)
6(6) + 3#6(6)
10
3H 16X2400
40
40
5/7m
50
50
2xM2 + T1
50
30/40
3x1x16+16
10(10) + 3#6(6)
10(10) + 3#6(6)
10
3H 16X2400
50
50
5/7m
50
50
2xB1 + T1
40
30/40
3x1x10+10
2#6(6) + 3#6(6)
2#6(6) + 3#6(6)
3H 16X2400
50
50
5/7m
50
50
2xB2 + T1
50
30/40
3x1x16+16
2#10(10) + 3#6(6)
2#10(10) + 3#6(6)
10
3H 16X2400
50
50
5/7m
50
50
M2 + 2xT1
50
30/40
3x1x16+16
10(10) + 3#6(6)
10(10) + 3#6(6)
10
3H 16X2400
50
50
5/7m
50
50
B2 + 2xT1
50
30/40
3x1x16+16
2#10(10) + 3#6(6)
2#10(10) + 3#6(6)
10
3H 16X2400
50
50
5/7m
50
50
PAREDE (mm)
FIXAOEMBUTIDONA
FIXAOCOM
PARAFUSO(mm)
PONTALETE
GALVANIZADO(mm)
POSTE TUBODE AO
POSTE DT
POSTE
GALVANIZADO(mm)
EMBUTIDOE
RAMAL DE ENTRADA
PVC 70C)
EMBUTIDOE
SUBTERRNEO(COBRE
RAMAL DE ENTRADA
RAMAL DE LIGAO
MULTIPLEX (ALUMNIO)
(A)
TERMOMAGNTICO
TERMOMAGNTICO
TERMOMAGNTICO
RGIDO(mm)
32
32
ELETRODUTODE AO
32
3H 16X2400
ELETRODUTODE PVC
3H 16X2400
10
HASTE PARA
10(10)
ATERRAMENTO(COBRE)
6(6)
10(10)
EPR/XLPE 90C)
6(6)
2x1x16+16
CONDUTORES (mm2)
SUBTERRNEO(COBRE
2x1x10+10
TRIFSICO(Limite Maximo
-
(A)
50
DISJUNTOR
30/32
BIFSICO(Limite Maximo
Maximo (A)
DISJUNTOR
MEDIES BIFSICAS
MEDIES TRIFSICAS
2 x M2
MONOFSICO(Limite
MEDIES MONOFSICAS
2 x M1
DISJUNTOR
CATEGORIAS
PARA 03 MEDIES
PARA 02 MEDIES
AGRUPAMENTO
Energisa: Sergipe, Nova Friburgo, Minas Gerais, Caiu, Nacional, Bragantina, Fora e Luz do
Oeste, Vale do Paranapanema e Enersul.
3H 16X2400
40
40
5/7m
50
50
3H 16X2400
40
40
5/7m
50
50
3x1x10+10
6(6)
6(6)
3H 16X2400
32
32
5/7m
50
50
3x1x16+16
10(10)
10(10)
10
3H 16X2400
40
40
5/7m
50
50
3x1x10+10
2#6(6)
2#6(6)
3H 16X2400
40
40
5/7m
50
50
3x1x16+16
2#10(10)
2#10(10)
10
3H 16X2400
50
50
5/7m
50
50
30/40
3x1x16+16
3#6(6)
3#6(6)
3H 16X2400
65
65
5/7m
50
50
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 44 -
30/32
25
20
5/7m
150
80X 5/7m
40
40
M2
1x1x10+10
2x10
10(10)
10(10)
10
1H 16X2400
50
25
20
5/7m
150
80X 5/7m
40
40
M3
1x1x16+16
16(16)
16(16)
10
1H 16X2400
70
25
25
5/7m
150
80X 5/7m
40
40
B1
0 < P 17,6
2x1x10+10
2#10(10)
2#6(6)
1H 16X2400
40
32
25
5/7m
150
80X 5/7m
50
50
B2
2x1x16+16
2#10(10)
2#10(10)
10
1H 16X2400
50
32
25
5/7m
150
80X 5/7m
50
50
B3
2x1x25+25
2#16(16)
2#16(16)
16
1H 16X2400
70
40
40
5/7m
150
80X 5/7m
50
50
T1
0 < D 26,3
3x1x10+10
3#10(10)
3#6(6)
*H 16X2400
40
32
32
5/7m
150
80X 5/7m
50
50
T2
3x1x16+16
3#10(10)
3#10(10)
10
*H 16X2400
50
32
32
5/7m
150
80X 5/7m
50
50
T3
3x1x25+25
3#25(25)
3#16(16)
10
*H 16X2400
70
40
40
5/7m
150
100X 5/7m
50
50
T4
3x1x35+35
3#35(35)
3#25(25)
16
*H 16X2400
100
50
50
5/7m
300
100X 5/7m
50
50
T5
65,8 < D 75
3x1x70+70
3#70(35)
3#50(35)
25
*H 16X2400
125
65
75
5/7m
600
FIXAO EMBUTIDO NA
PAREDE (mm)
POSTE DT
PONTALETE
POSTE TUBO DE AO
GALVANIZADO (mm)
POSTE
ELETRODUTO DE AO
GALVANIZADO (mm)
ATERRAMENTO (COBRE)
RAMAL DE ENTRADA
EMBUTIDO E SUBTERRNEO
(COBRE EPR/XLPE 90C)
6
RAMAL DE ENTRADA
EMBUTIDO E SUBTERRNEO
(COBRE PVC 70C)
6(6)
RAMAL DE LIGAO
CONCNTRICO (ALUMINIO)
6(6)
RAMAL DE LIGAO
MULTIPLEX (ALUMNIO)
2x10
POTNCIA/DEMANDA
1x1x10+10
N. DE FASES
0 < P 6,0
N. DE FIOS
CATEGORIA
POTNCIA /DEMANDA
M1
CONDUTORES (mm2)
Notas:
D = Demanda provvel em kVA ;
Condutores e eletrodutos esto dimensionados com valores mnimos;
Para as categorias T5 dever ser instalada a caixa padro para medio direta para medidor de 200A;
A coluna ramal de Ligao se refere a condutores multiplexados de alumnio XLPE, fases CA, Neutro nu CAL;
A coluna Proteo est dimensionada para o limite superior de cada faixa. A proteo a ser utilizada ser calculada em funo da
demanda de projeto;
Os condutores para os ramais de entrada, monofsicos, bifsicos e trifsicos devero possuir isolamento do tipo HEPR, XLPE ou EPR
para 0,6/1kV ou PVC para 0,6/1kV;
Os condutores para os ramais subterrneo, devero possuir isolamento do tipo HEPR, XLPE ou EPR para 0,6/1kV ou PVC para
0,6/1kV;
O ramal de sada dever possuir no mnimo a mesma seo do ramal de entrada;
A categoria B1 ficar para consumidores com carga instalada maior que 17,6 kVA e para uso restrito ao atendimento de casos
especiais, tais como os de instalaes com equipamentos que requeiram nmeros de fases e/ou tenso prpria destas categorias;
A categoria T1 ficar para consumidores com carga instalada maior que 22,00 kVA ou para o atendimento de instalaes com
equipamentos que requeiram nmeros de fases e/ou tenso prpria destas categorias;
Nos agrupamentos at 03 consumidores o projetista dever efetuar a soma das demandas individuais;
Para agrupamentos at 2 consumidores monofsicos ou bifsicos a entrada de dever ser bifsica, caso contrrio trifsica;
As Categorias B1 e B2 so aplicadas apenas na Energisa Sergipe, Celtins e Cemat, e B3 apenas para Energisa Celtins e Cemat.
No caso de agrupamento, as cargas (consumidor monofsico e bifsico) devero ser somadas as demandas (consumidor trifsico) e
aps, associar a faixa adequada;
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 45 -
MEDIES TRIFSICAS
DISJUNTOR TERMOMAGNTICO
MONOFSICO (Limite Maximo
(A))
ATERRAMENTO (COBRE)
ELETRODUTO DE AO
GALVANIZADO (mm)
POSTE TUBO DE AO
GALVANIZADO (mm)
FIXAO EMBUTIDO NA
PAREDE (mm)
2 x M1
30/32
2x1x10+10
6(6)
6(6)
3H 16X2400
32
32
5/7m
150
80X 5/7m
50
50
2 x M2
50
2x1x16+16
10(10)
10(10)
10
3H 16X2400
32
32
5/7m
150
80X 5/7m
50
50
M1 + T1
30/32
30/40
3x1x10+10
6(6) + 3#6(6)
6(6) + 3#6(6)
3H 16X2400
40
40
5/7m
150
80X 5/7m
50
50
M2 + T2
50
50
3x1x16+16
10(10) + 3#10(10)
10(10) + 3#10(10)
10
3H 16X2400
50
50
5/7m
150
80X 5/7m
50
50
2 x T1
30/40
3x1x10+10
3#6(6)
3#6(6)
10
3H 16X2400
40
40
5/7m
150
80X 5/7m
50
50
2 x T2
50
3x1x16+16
3#10(10)
3#10(10)
10
3H 16X2400
50
50
5/7m
150
80X 5/7m
50
50
3 x M1
30/32
3x1x10+10
6(6)
6(6)
3H 16X2400
32
32
5/7m
150
80X 5/7m
50
50
3 x M2
50
3x1x16+16
10(10)
10(10)
10
3H 16X2400
40
40
5/7m
150
80X 5/7m
50
50
2xM1 + T1
30/32
30/40
3x1x10+10
6(6) + 3#6(6)
6(6) + 3#6(6)
10
3H 16X2400
40
40
5/7m
150
80X 5/7m
50
50
2xM2 + T1
50
30/40
3x1x16+16
10(10) + 3#6(6)
10(10) + 3#6(6)
10
3H 16X2400
50
50
5/7m
150
80X 5/7m
50
50
M2 + 2xT1
50
30/40
3x1x16+16
10(10) + 3#6(6)
10(10) + 3#6(6)
10
3H 16X2400
50
50
5/7m
150
80X 5/7m
50
50
3 x T1
30/40
3x1x16+16
3#6(6)
3#6(6)
3H 16X2400
65
65
5/7m
150
80X 5/7m
50
50
POSTE
POSTE DT
RAMAL DE ENTRADA
EMBUTIDO E SUBTERRNEO
(COBRE PVC 70C)
RAMAL DE LIGAO
MULTIPLEX (ALUMNIO)
CONDUTORES (mm 2)
RAMAL DE ENTRADA
EMBUTIDO E SUBTERRNEO
(COBRE EPR/XLPE 90C)
MEDIES MONOFSICAS
DISJUNTOR TERMOMAGNTICO
TRIFSICO (Limite Maximo (A))
CATEGORIAS
PARA 03 MEDIES
PARA 02 MEDIES
AGRUPAMENTO
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 46 -
PONTALETE
DISJUNTOR TERMOMAGNTICO
(Limite Maximo (A))
ELETRODUTO DE AO GALVANIZADO
(mm)
6(6)
1H 16X2400
30/35
25
20
5/7m
150
80 X
5/7m
40
40
M2
1X1X10+10
2x10
10(10)
10(10)
10
1H 16X2400
50
25
20
5/7m
150
80 X
5/7m
40
40
40
40
FIXAO EMBUTIDO NA
PAREDE (mm)
POSTE TUBO DE AO
GALVANIZADO (mm)
PONTALETE
POSTE DT
ATERRAMENTO (COBRE)
6(6)
2x10
1X1X10+10
RAMAL DE LIGAO
CONCNTRICO (ALUMINIO)
0 < P 3,45
POTNCIA/DEMANDA
N. DE FASES
M1
N. DE FIOS
POSTE
CATEGORIA
POTNCIA /DEMANDA
CONDUTORES (mm2)
M3
1X1X16+16
16(16)
16(16)
16
1H 16X2400
70
25
25
5/7m
150
80 X
5/7m
B1
0 < P 6,9
2X1X10+10
2#6(6)
2#6(6)
1H 16X2400
30
25
25
5/7m
150
80 X
5/7m
50
50
150
80 X
5/7m
50
50
50
50
B2
2X1X10+10
2#10(10)
2#10(10)
10
1H 16X2400
40
32
25
5/7m
B3
2X1X16+16
2#10(10)
2#10(10)
10
1H 16X2400
50
32
25
5/7m
150
80 X
5/7m
B4
11,5 < P 15
2X1X25+25
2#16(16)
2#16(16)
16
1H 16X2400
70
32
32
5/7m
150
80 X
5/7m
50
50
150
80 X
5/7m
50
50
B5
15 < P 23
2X1X35+35
2#35(35)
2#35(35)
16
1H 16X2400
125
32
32
5/7m
Notas:
Condutores e eletrodutos esto dimensionados com valores mnimos;
A coluna ramal de Ligao se refere a condutores multiplexados de alumnio XLPE, fases CA, Neutro nu CAL;
A coluna Proteo est dimensionada para o limite superior de cada faixa. A proteo a ser utilizada ser calculada em
funo da demanda de projeto;
Os condutores para os ramais de entrada, monofsicos e bifsicos devero possuir isolamento do tipo HEPR, XLPE ou
EPR para 0,6/1kV ou PVC para 0,6/1kV;
Os condutores para os ramais subterrneo, devero possuir isolamento do tipo HEPR, XLPE ou EPR para 0,6/1kV; ou
PVC para 0,6/1kV;
O ramal de sada dever possuir no mnimo a mesma seo do ramal de entrada;
As categorias B1 e B2 ficaro para consumidores com carga instalada maior que 8,05 kVA e para uso restrito ao
atendimento de casos especiais, tais como os de instalaes com equipamentos que requeiram nmeros de fases e/ou
tenso prpria destas categorias;
Os agrupamentos com 2 ou 3 caixas devero possuir entrada de servio bifsica;
No caso de agrupamento, as cargas instaladas (consumidor monofsico e bifsico) devero ser somadas as demandas
e aps, associar a faixa adequada;
A categoria B5 dever apenas ser utilizada na Energisa Minas Gerais.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 47 -
DISJUNTOR TERMOMAGNTICO
(Limite Maximo (A))
PONTALETE
1H 16X2400
30/32
25
20
5/7m
150
50
50
50
M2
1X1X10+10
2x10
10(10)
10(10)
10
1H 16X2400
40
25
20
5/7m
150
50
50
50
M3
1X1X16+16
10(10)
10(10)
10
1H 16X2401
50
25
25
5/7m
150
50
50
50
M4
11,5 < P 15
1X1X25+25
16(16)
16(16)
16
1H 16X2400
70
32
32
5/7m
150
50
50
50
M5
15 < P 23
1X1X70+70
35(35)
35(35)
16
1H 16X2400
125
32
32
5/7m
150
50
50
50
POSTE DT
RAMAL DE ENTRADA
EMBUTIDO E
SUBTERRNEO (COBRE
EPR/XLPE 90C)
FIXAO EMBUTIDO NA
PAREDE (mm)
6(6)
POSTE TUBO DE AO
GALVANIZADO (mm)
6(6)
ELETRODUTO DE AO
GALVANIZADO (mm)
2x10
ATERRAMENTO (COBRE)
1X1X10+10
RAMAL DE LIGAO
MULTIPLEX (ALUMNIO)
0 < P 6,9
POTNCIA/DEMANDA
N. DE FASES
N. DE FIOS
M1
CATEGORIA
RAMAL DE ENTRADA
EMBUTIDO E
SUBTERRNEO (COBRE
PVC 70C)
POSTE
RAMAL DE LIGAO
CONCNTRICO (ALUMINIO)
POTNCIA /DEMANDA
CONDUTORES (mm )
Notas:
Condutores e eletrodutos esto dimensionados com valores mnimos;
A coluna ramal de Ligao se refere a condutores multiplexados de alumnio XLPE, fases CA, Neutro nu CAL;
A coluna Proteo est dimensionada para o limite superior de cada faixa. A proteo a ser utilizada ser calculada em
funo da demanda de projeto;
Os condutores para os ramais de entrada, monofsicos e bifsicos devero possuir isolamento do tipo HEPR, XLPE ou
EPR para 0,6/1kV ou PVC para 0,6/1kV;
Os condutores para os ramais subterrneo, devero possuir isolamento do tipo HEPR, XLPE ou EPR para 0,6/1kV; ou
PVC para 0,6/1kV;
O ramal de sada dever possuir no mnimo a mesma seo do ramal de entrada;
No caso de agrupamento, as cargas instaladas (consumidor monofsico e bifsico) devero ser somadas as demandas
e aps, associar a faixa adequada;
A categoria M5 dever apenas ser utilizada na Energisa Nova Friburgo.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 48 -
DISJUNTOR TERMOMAGNTICO
(Limite Maximo (A))
PONTALETE
50
25
20
7m
150
50
50
50
M2
12<P15,0
2X1X16+16
25(16)
25(16)
16
01H 16x2400
70
32
32
7m
150
50
50
50
POSTE DT
FIXAO EMBUTIDO NA
PAREDE (mm)
01H 16X2400
10
POSTE TUBO DE AO
GALVANIZADO (mm)
10(10)
ELETRODUTO DE AO
GALVANIZADO (mm)
10(10)
ATERRAMENTO (COBRE)
RAMAL DE ENTRADA
EMBUTIDO E
SUBTERRNEO (COBRE
EPR/XLPE 90C)
2X1X10+10
RAMAL DE LIGAO
MULTIPLEX (ALUMNIO)
0 < P 12,0
POTNCIA/DEMANDA
N. DE FASES
N. DE FIOS
M1
CATEGORIA
RAMAL DE ENTRADA
EMBUTIDO E
SUBTERRNEO (COBRE
PVC 70C)
POSTE
RAMAL DE LIGAO
CONCNTRICO (ALUMINIO)
POTNCIA /DEMANDA
CONDUTORES (mm )
Energisa: Caiu, Nacional, Bragantina, Fora e Luz do Oeste, Vale do Paranapanema, Cemat e
Enersul.
Notas:
Condutores e eletrodutos esto dimensionados com valores mnimos;
A coluna ramal de Ligao se refere a condutores multiplexados de alumnio XLPE, fases CA, Neutro nu CAL;
A coluna Proteo est dimensionada para o limite superior de cada faixa. A proteo a ser utilizada ser calculada em
funo da demanda de projeto;
Os condutores para os ramais de entrada, monofsicos e bifsicos devero possuir isolamento do tipo HEPR, XLPE ou
EPR para 0,6/1kV ou PVC para 0,6/1kV;
Os condutores para os ramais subterrneo, devero possuir isolamento do tipo HEPR, XLPE ou EPR para 0,6/1kV; ou
PVC para 0,6/1kV;
O ramal de sada dever possuir no mnimo a mesma seo do ramal de entrada;
Potencia /Demanda superior a 4kW utilizar transformador monofsico particular de 5, 10 e 15kW.
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 49 -
4- COMPRIMENTO
MULTIPLICADOR POR
PARA OBTER
MULTIPLICADOR POR
PARA OBTER
HP
0,7457
kW
Pol
0,0254
kW
1,341
HP
39,37
Pol
CV
0,7355
kW
0,3048
kW
1,36
CV
3,281
HP
1,014
CV
milha
1,609
km
CV
0,986
HP
km
0,621
milha
HP
42,44
Btu/min
mm
0,03937
Pol
-4
Btu
2,928x10
kWh
kW/h
3,415
BTU
2- VOLUME
5- PESO
MULTIPLICADOR POR
PARA OBTER
Litro
dm
Litro
16,387
cm
dm
Pol3
cm
0,061
MULTIPLICADOR POR
PARA OBTER
libra
0,4536
kg
kg
2,204
libra
kg/m
0,672
libra/p
libra/p
1,488
kg/m
Pol
3
0,0283
35,31
Galo Americano
3,785
Litro
Litro
0,2642
Galo Americano
6- OUTRAS UNIDADES
MULTIPLICADOR POR
2
kg/cm
14,22
libra/pol
W/1000 P
3,281
W/km
W/km
0,3048
W/1000 P
0,03613
libra/Pol
libra/Pol
27,68
g/cm
watt-hora
3600
joule
joule
0,0028
watt-hora
Caloria-grama
4,186
joule
joule
0,2389
Caloria-grama
km/h
0,277
m/s
m/s
3,6
km/h
kg/cm
MULTIPLICADOR POR
Circular mil
mm
Pol
m
2
2
P
m
PARA OBTER
2
0,00051
mm
1973,5
Circular mil
0,00065
1550
Pol
0,09209
10,764
2
2
2
2
0,0707
libra/pol
3- REA
PARA OBTER
g/cm
3
3
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 50 -
127
115
1x1x10+10
54
12.420,00
11.880,00
6.858,00
6.210,00
1x1x16+16
72
16.560,00
15.840,00
9.144,00
8.280,00
1x1x25+25
98
22.540,00
21.560,00
12.446,00
11.270,00
2x1x10+10
43
18.920,00
9.890,00
10.922,00
2x1x16+16
57
25.080,00
13.110,00
14.478,00
2x1x25+25
79
34.760,00
18.170,00
20.066,00
2x1x70+70
154
67.760,00
35.420,00
39.116,00
3x1x10+10
43
18.920,00
16.385,00
3x1x16+16
57
37.516,22
21.719,92
3x1x25+25
79
51.996,17
30.103,04
3x1x35+35
97
63.843,39
36.961,96
3x1x70+70
154
101.359,61
58.681,88
3x1x120+70
224
147.432,16
85.355,46
3x1x185+120
370
243.526,34
140.988,94
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 51 -
17. ANEXO
II
SUBTERRNEO
DECLARAO
DE
COMPROMISSO
RAMAL
ENERGISA
Eu,...........................................................................................................................................................,
Portador do RG.................................................................e do CPF ........................................,
proprietrio do imvel situado ...............................................................................................de
n.....................(vila, casa n.................), de CDC n........................ , venho com a presente solicitar a
conexo do ramal subterrneo com a rede da concessionria para o supracitado imvel.
Outrossim, concordo em que todas as despesas necessrias para instalao do ramal subterrneo,
devam ocorrer por minha conta. Caso necessrio, comprometo-me a providenciar a remoo ou
substituio do ramal subterrneo no mximo em 10 (dez) dias contados a partir da data em que
essa Concessionria notificar-me a respeito. Ao assumir o presente compromisso, declaro-me
tambm ciente de que findo o prazo aludido, na falta das providencias que me couberem, essa
Concessionria poder efetuar o desligamento da instalao em apreo independente de outro aviso
sem que, do desligamento em tais circunstncias, me decorra direito de reclamao por qualquer
ttulo.
OS n............................................
..................................................................
(Assinatura)
..................................................................
(Testemunha)
..................................................................
(Testemunha)
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 52 -
_____________________________________________________________________________________
NDU-001
VERSO 4.0
SETEMBRO/2014
- 53 -