No.
ITS-111122
Date:
2011/11/22
Prepared by: Shogo Yamaguchi
49,896
84 x 108 x 5.5
70%RH at 22 deg C
N/A
8 deg C, 50% RH
0.0033
49,896
1.0
2. Humidity Calculation
Our humidity calculation resulted 178 nozzles at least would be required to get the target humidity
considering the above air conditions.
Target Humidity
70% RH at 22deg C
Desired Humidity [LPH]
497
Absolude humidity [kg/kg (DA)]
Desired Humidity [GPH]
131
Quantity of Nozzles
(Calculation Result)
if only 6,003LPM at 0.3MPa air can be
supplied.
207
Quantity of Nozzles
(Calculation Result)
0.0116
if 5,934LPM at 0.5MPa air can be
supplied.
138
3. Humidification System Layout and Utility
We would like to propose our humidification system using 140 nozzles considering layout balance.
<Required utility> Please check the utility below and the attached system layout.
Quantity of Nozzles
140
Ikeuchi Recommends
Water [LPH]
504
Water pressure
0.1MPa (14psi)
applied to humidifiers
Compressor Air [Normal LPM]
6020
Air pressure
0.5MPa (73psi)
applied to humidifiers
Pitch of Humidifier
See the attached layout
Page 2/3
No.
ITS-111122
Date:
2011/11/22
Prepared by: Shogo Yamaguchi
Required quality specifications for the air and water supply
Pressure:
0.3 - 0.35 MPa (44-51PSI) at a point of use
Temperature: 5 deg C (41 deg F) - Normal temperature
Quality:
Air without moisture, oil mist and dust; Dew point 10 deg C (= 50 degF)
Purifying Devices: Air Dryer, Air Filter, Oil Filter
* Air Filter - Remove foreign particles of over 5 micro meter.
Air
Oil Filter - Remove foreign particles of over 0.03 micro meter.
Air Heater: Place an air heater when the humidifier is operated in low ambient temperature or
when the compressed air temperature becomes lower than 12 degC (=54 degF)
* Apply thermal insulator to air pipe after the point of an air heater.
Water
Pressure:
0.1 - 0.15 MPa (15 - 22PSI) at a point of use
Temperature: Normal temperature
Quality:
No particles
Electric Conductivity
= 0.07 - 10 microsiemens/cm
(Resistance
14 - 0.1 M ohm/cm )
Silica ( SiO2)
= 5ppm or less
Total Hardness + Bicarbonate = 60 ppm or less
Purifying Devices: Y Strainer(0.1mm), Water Filiter (5 micrometer), Water softner
Reverse Osmosis Water Purifier, Ion Exchange Water Purifier
* Water Softener and Reverse Osmosis Water Purifier produce continuous
discharged water during their operation. Provide drainage basin.
Humidifier
Quantity
30
10
Stop Plug
10
Remarks
4 nozzles mounted.
Inelt connections of air and water are 1/4'' NPT female
thread. Refernce drawing and image of intallation are
attached.
2 nozzles mounted.
Inelt connections of air and water are 1/4'' NPT female
thread.
You may need some stop plugs to adjust spray nozzle
numbers or when you maintain nozzles.
Refer to the attached layout and ''Break-down of Dry Fog Humidification System Proposal''.
Option: Quote No.901204
This is the quote of humidifiers only without controller when you prepare humidity controllers, solenoid valve units, humidity sensors by yourself.
3) Supply by customer or third-party contractor
Quantity
Plumbing and Installation
Stainless steel pipes, valves and fittings
Plumbing, Components installation
Power distribution works, Pipe flushing before system start-up
1pkg.
Remarks
General Installation manual
to be provided by IKEUCHI.
Page 3/3
No.
ITS-111122
Date:
2011/11/22
Prepared by: Shogo Yamaguchi
5. Typical System Flow
''E''
''E''
Humidity sensor
Parts
Sensor element
Filter of sensor element
Humidifier
with spray direction
RO Water pipe
Air pipe
18m
9m
Ball valve
Drain discharge
ball valve
Water Regulator