Anda di halaman 1dari 25

5/13/2013

Educational Package Ventilation

Lecture 4: Displacement ventilation

ES

-E

IEE/09/631/SI2.558225
28.10.2011

Summary

Displacement Ventilation Introduction


Displacement Ventilation Characteristics

ID

Displacement Ventilation vs. Mixing Ventilation


Ventilation Effectiveness
Design Considerations
Thermal Comfort
Humidity Control
Acoustics
Designing with AHUs and RTUs
Diffuser Type, Layout and Location

DV Supply Air Methods


Case Study

Introduction

Airflow in ventilated spaces generally can be classified by two different types:


mixing (or dilution) ventilation
displacement ventilation.

Mixing ventilation systems generally supply air in a manner such


that the entire room volume is fully mixed.

Displacement Ventilation

5/13/2013

Displacement ventilation systems introduce air into the space at


low velocities which causes minimal induction and mixing.
3

Introduction

Displacement ventilation takes advantage of the


difference in air temperature and density between an
upper contaminated zone and a lower clean zone.
Cool air is supplied at low velocity into the lower
zone.
Convection from heat sources creates vertical air motion
into the upper zone where high level return outlets
extract the air

ID

Displacement Ventilation

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Fig.3
4
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Introduction

While each system has its comparative


benefits and drawbacks, displacement
ventilation is slowly gaining in popularity
due to its less energy intensive nature.

Fig.4

-E

Displacement Ventilation

5/13/2013

Displacement Ventilation

ES

Source: Abbas, T. (1999) Displacement ventilation and static cooling devices (COP 17/99)

Flexibility
as loads change within the space, a displacement system will be able to
compensate. For example, if the space was designed to have a fairly even load
distribution and now has the loads concentrated to one side, the system is able
to compensate as the buoyant forces drive supply system and will draw the air
towards the loads.
IAQ
because fresh supply air is pooling at the floor level, personal thermal plumes
draw fresh air up the body. All of the warm and polluted air is extracted at the
high return. When properly designed, there should always be a greater amount
of fresh air in the breathing zone when compared to a conventional dilution
system.
Energy Savings
the lower pressure drop associated with displacement ventilation outlets, may
allow a reduction in fan energy with the selection of a smaller fan components.
economizer operating hours can be increased to take advantage of free cooling
because supply air temperatures are higher than with overhead air distribution
systems.
chiller efficiency may be increased when the system is not dehumidifying, as
there is a lower supply air temperature and higher return air temperature.

ID

Introduction

6
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Introduction
Application

Restrictions/additional comments

Industrial

Offices

Should not be used where pollutants are heavier


than air unless they are directly removed by local
extraction.

Production/assembly
halls, stores,
factories.

Likely to need additional cooling devices.


Works best when
ceiling heights are greater than 2.5m
casual loads are moderate
occupants are mainly sedentary
buildings are airtight

Open plan or
cellular.

Can achieve very low noise levels compared to


mixing systems.
Underseat air supplies should be used with
particular attention to local draught conditions.

Theatres, cinemas,
auditoria, sports
halls, fitness rooms
and restaurants.

Should not be used where pollutants are heavier


than air unless they are directly removed by local
extraction.

All types.

Laboratories
General Public
Areas

Recreation

Examples

Significant solar gain must be precluded.

Conference rooms,
airport concourses,
atria, shops.

-E

Displacement Ventilation

5/13/2013

ES

Source: Abbas, T. (1999) Displacement ventilation and static cooling devices (COP 17/99)

Thermal Plume

ID

Displacement Ventilation

DV Characteristics

Heat sources
such as people,
computers, lights,
etc. create a
rising convection
flow known as a
thermal plum

Stratification Height

The downward
moving
airflow resulting
from cool surface

The upward moving


airflow contained
in thermal plumes that
form above heat
sources

Stratification
Height

The supply airflow


into the room from a
low side-wall diffuser

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE


Source: Hazim B. Awbi, Ventilation of Buildings, Second Edition, 2003

An important objective in
designing and operating a
displacement
ventilation
system is to maintain Yst
near to the breathing zone

(1,7m standing work position and


1,1 m seated work position)

5/13/2013

Airflow Penetration

Room Airflow Pattern

Quite different than in a


mixing system.
The convection flows are
created by heat sources
within the room cause
the formation of horizontal
air layers.

Obstruction

Irregular Room Geometry

Fig.5.a

`
`

The warmest air layers are


near the ceiling
The coolest air layers are
near the floo

When designing the system to deal with


the cooling demand of the space, the
penetration depth of a displacement
diffuser can be 26 30 feet from the
face of the diffuser. For rooms
exceeding 30 feet in length or width,
diffusers on several walls would normally
be required.

Displacement Ventilation

DV Characteristics

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

ID

Displacement Ventilation

DV Characteristics

Fig.5b

Typical temperature profile for a


room with displacement ventilation.

The stratification is
affected by several
factors:
supply air volume
room cooling load
location and type of heat
source
space height.
The greater the volume of
air supplied into a room,
the lower the temperature
difference between floor
and ceiling

10
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

5/13/2013

Isothermal Air Supply


Fig.6 a,b,c

Heating Air Supply

Cool Air Supply

In order to avoid draft it is essential for the


displacement diffuser to uniformly deliver

the supply air across the entire diffuser face


at low velocity. This requires an internal

Displacement Ventilation

DV Characteristics

equalization baffle in combination with a


low free area face.

11

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

ID

Displacement Ventilation

DV Characteristics

When heat sources are


located in the upper
part of the room
the greatest
stratification occurs
near the ceiling

If heat sources are


located in the lower part
of the room, the
temperature gradient is
greater in the lower part
of the room and lessens
in the upper part.
12

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

5/13/2013

Displacement ventilation with wall-mounted diffuser

Wall mounted low velocity


diffuser and smoke visualization
of the stratified
flow from the diffuser

Room with
DV and wall
mounted
diffuser

Displacement Ventilation

DV Characteristics

Fig. 7 a,b

13

ES

-E

Source: Hazim B. Awbi, Ventilation Systems Design and performance, 2008

Design chart for an air


distribution system with wall
mounted diffusers
for displacement ventilation

Displacement ventilation with floor-mounted diffusers

ID

Displacement Ventilation

DV Characteristics
Flow in a room with
displacement ventilation
and a floor mounted
diffuser

High momentum displacement ventilation

Fig.7 c,d

Impinging jet
ventilation
system

14
Source: Hazim B. Awbi, Ventilation Systems Design and performance, 2008

5/13/2013

High momentum displacement ventilation


Impinging jet ventilation
MAIN ADVANTAGES over a standard displacement system are:
the air can be supplied over a much wider temperature range than can be
tolerated in a displacement system. Tests have shown that a supply
temperature down to 15 C can be tolerated as the jet quickly entrains room air
at higher temperature as it leaves the diffuser;

the ability to use the impinging jet system for heating by supplying air at
higher temperature than room air, which is not possible in a standard DS;

the impinging jet spreads quickly as it descends on the floor creating a thin

layer that can travel a long distance on the floor even with the presence of

heat sources. In a standard displacement system, the supply air does not

Displacement Ventilation

DV Characteristics

normally travel long distances as it is quickly consumed by heat sources in its


path.

15

ES

-E

Source: Hazim B. Awbi, Ventilation Systems Design and performance, 2008

High momentum displacement ventilation


Confluent jets ventilation

Flow pattern

ID

Displacement Ventilation

DV Characteristics

Typical
confluent jets
installations

Fig.7 e, f

Source: Hazim B. Awbi, Ventilation Systems Design and performance, 2008

16

5/13/2013

Performance
Cooling Capacity

Displacement ventilation system


(DVS)

20 35 W/m2

DVS with induction of room air into


supply and lower primary
temperature

35 60 W/m2

DVS with chilled ceiling panels

70 100 W/m2

Allows additional cooling of 200


250 W/m length of beam

DVS with passive chilled beams

System Configuration

17

-E

Displacement Ventilation

DV Characteristics

DV vs MV

Contaminant
distribution in a
space is influenced by
several factors such as
supply air method
contaminant source
type
location within the
space
heat sources
space height.

ID

Displacement Ventilation

ES

Source: Abbas, T. (1999) Displacement ventilation and static cooling devices (COP 17/99)

Fig. 8 a,b

With mixing ventilation, contaminants


are diluted with supply air and are
distributed evenly throughout the
space

Displacement ventilation improves


occupant air quality by reducing
the contaminants in the lower
portion of the room. The general
upward motion of air causes
contaminants to concentrate within
the upper zone
18

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

DV vs MV
Mixing ventilation is preferable in the following cases:
Where the main pollutants are colder/denser than the
ambient air (e.g. dust)
Where overheating is the main problem and not air quality
Where ceiling height is below 2.3m
Where the air flow is often disturbed by movement in the
room

Displacement ventilation has the following advantages:


Less cooling needed for a given temperature in an occupied
zone
Longer periods with free cooling
Better air quality in the occupied zone (though there can be
more airborne respirable dust in the breathing zone)

Displacement Ventilation

5/13/2013

19

DV vs MV

The main weak points of displacement ventilation are:


Risk of cold sensation or draught near the floor
Wall mounted diffusers take up a lot of space and must not
be blocked
Wall mounted diffusers do not permit a lot of flexibility
when it comes to future changes in the layout of the building

ID

Displacement Ventilation

ES

-E

Source: Schild, G. P. (2004) Displacement Ventilation, AIVC, Ventilation Information Paper VIP 05

Appropriate ventilation systems for


different flow rates and heat loads
The
T
lines
are
temperature
difference between room and supply air
when ventilation alone is used for cooling

Fig.9

Source: Schild, G. P. (2004) Displacement Ventilation, AIVC, Ventilation Information Paper VIP 05

20

10

DV vs MV

Comparison between different air distribution systems

Fig.10 a, b, c, d, e

Five different
air distribution
systems

Displacement Ventilation

5/13/2013

Ventilation Effectiveness

ID

Displacement Ventilation

ES

-E

Source: Hazim B. Awbi, Ventilation Systems Design and performance, 2008

Nominal time constant

Pollutant concentration in the exhaust

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE


Source: Chapter 25 of 1997 ASHRAE Fundamentals Handbook

Room mean age of air

Pollutant mean concentration in the room

22

11

Ventilation Effectiveness

Pollutant mean concentration at


breathing level

Displacement Ventilation

5/13/2013

23

Displacement Ventilation

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Ventilation Effectiveness

Supply diffuser

ID

The type of supply diffuser used will have a direct impact in the
ventilation effectiveness.

The overall ventilation effectiveness of overhead diffuser systems may


vary due to diffuser type (0.7 < < 1.0 with average = 0.9) and mode of
operation
Well-designed displacement ventilation air distribution systems have a
ventilation effectiveness that are at least = 1.2 and have the potential
for greater ventilation effectiveness when used in combination with
dedicated outdoor air systems and radiant heating/cooling systems.

Ventilation Effectiveness for Different Types of


Air Distribution Systems [Source: Krantz]
24
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

12

5/13/2013

Displacement Ventilation

Design Considerations
Thermal Comfort
Controlling stratification in
the occupied zone is
critical to maintaining
occupant comfort. ASHRAE
Standard 55 requires the
temperature difference
between the head and foot
level of a standing person
not to exceed 5F.

ASHRAE Thermal Comfort Range


Source: ASHRAE Standard 55-2004

ASHRAEStandard55definesthermal
comfortasaconditionofthemindwhich
expressessatisfactionwiththethermal
environment.Thisdefinitionisbasedon
thefactthateachpersondefineswhatis
thermallycomfortablebasedupontheir
ownphysiologicalandpsychological
states.

ES

-E

25
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE
Source: Architectural Energy CorporationDisplacement Ventilation Design Guide: K-12 Schools, Final Report, 2006

Controlling humidity

Humidity Control

is the most common question when discussing the concepts of


underfloor air distribution, or displacement air distribution.
means different things to different people as their personal
perspectives are different, e.g.:

ID

Displacement Ventilation

Design Considerations

In the office environment, humidity control means limiting the upper


humidity level to the guidelines of ASRHAE Standard 55 in
order to provide good thermal comfort.
Museums often need humidity levels to be maintained in a narrow
range to slow or prevent decay in artwork and historical displays.

Building Shells Are Sources of Humidity


All buildings leak air through the building shell. This leakage is a
direct transfer of moisture into or out of the interior zones and
needs to be accounted for in the building moisture loads.

26
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

13

5/13/2013

Pretreat Ventilation Air

In a humid climate, the biggest source of moisture is typically the ventilation


air from the outside => Pretreated the air for humidity control will control
the entire building humidity load without any additional moisture removal
1st approach for humidity control

SideStreamBypassHumidityControl

Humidity Control
Design suggestions

2nd approach for humidity control

SeriesFanTerminal

Displacement Ventilation

Design Considerations

27

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Displacement Ventilation

Design Considerations

Humidity Control
Design suggestions

Direct Expansion Roof Top Units

ID

DX packaged roof top units may be used to


condition raised floor cavities and displacement
ventilation. However, care must be exercised to
select the proper sized equipment and controls to
maintain moisture removal.

Control Tip

When a DX system is oversized, the compressors will remove


the cooling load with very little cycle time;
in this case, the compressors shut down and the moisture on
the coil will re-evaporate and be added to the air;
additionally, the ventilation air is still required and will also
transport moisture into the zone;
the net effect is a humid occupied zone.
28

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

14

5/13/2013

Humidity Control
Design suggestions

Dedicated Dehumidification and


Energy Recovery
Dehumidification

ASHRAE has several recommendations for dehumidification of a building:


Dry the ventilation air first as the bulk of the moisture load in buildings is
due to the ventilation air.
Lower the design dew point and raise the interior set point dry bulb
temperature. When the occupants of a building are in a dry climate, RH < 45%,
they will have the same perceived comfort level at 78F as they would at 74F
and 50% RH. Interestingly, most people find the dryer and warmer combination
more comfortable.
Downsize the cooling equipment and use a dehumidifier. If the cooling system
is not required to remove latent loads, it can typically have a smaller cooling
capacity. This will raise the overall efficiency of the HVAC system and allow
for more localized cooling in high sensible loadings such as call centers. This is
a great approach for the use of fan air columns in a raised floor application.
Remember to analyze the dehumidification cycle at the peak moisture removal
load as well as the peak temperature point.

Displacement Ventilation

Design Considerations

29

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Acoustics

There are typically at least 5 primary


sources of sound generation in a
displacement ventilation application:

ID

Displacement Ventilation

Design Considerations

Fanpoweredterminals

3
4
5

The 1st most


commonly
considered
sound

Controlvalves
Diffusers
Airhandlingequipment

The 2nd most


commonly
considered
sound

Structuralbornesound.
30

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

15

5/13/2013

Design Considerations

Displacement Ventilation

Acoustics

The NC values for the diffusers are calculated using


ASHRAE Standard 70.
Largely due to their low pressure drop, displacement
diffusers do not typically have NC values above NC 30.

Sample Performance Data for a DF3


displacement outlet (example of diffuser noise)

31

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Displacement Ventilation

Design Considerations
Acoustics-Diffusers

ASHRAE Standard 70: All diffusers are discharging air into a typical
space that will experience a sound absorption of 10dB in all bands.
The tabulated NC values may be corrected for the type of space in
your design by using this formula:

ID

The design goal

Nb of outlets in the space

Catalog NC = Room NC 10 + SEF 10*log 10 N

Space Effect Factor [ASHRAE Fundamentals]

Example:
`

`
`
`
`

Private Office space (Design NC = 30).


10 ft x 10 ft with 2.5 CFM/SF (295 CFM)
The SEF = 5.
Number of supply diffusers is 1 (250 CFM)
and the number of return diffusers is 1.
Catalog NC = 30 10 + 5 10*log 10 (1+1)
Catalog NC = 22
DF1 Diffuser (48x24x13) at 295 CFM
generate an NC values < 15 NC.
The return grill would be selected to have
an NC values of 19 or less as well.

32
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

16

5/13/2013

Displacement Ventilation

Design Considerations
Designing with Air Handling Units

AHUs in a displacement ventilation systems must


be
able
to supply an off-coil supply air
temperature of ~65F [18C] in order to limit
discomfort.

When climate permits, the use of an economizer is


recommended.

Where dehumidification is required, side steam bypass or heat recovery wheels can be used.

Variable speed drives on a VAV system will help to


save energy under partial load conditions and will
help to promote stratification in the space.

Demand control ventilation can be incorporated


into the displacement system to help reduce the
energy demand of the system in low load cases
and still provide the proper space ventilation.

Fig.11

Fig.12
33

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Loading Within the Space

Overhead Air Distribution

ID

Displacement Ventilation

Design Considerations

A
traditional
mixing
system
conditions the whole space to be
an even temperature. The system
then has be designed to cool
the entire volume of the space
Fig.14

Fig.13

With displacement
ventilation only the occupied
zone needs to be conditioned
to meet comfort conditions.
Occupied Zone

34

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

17

5/13/2013

Displacement Ventilation

Design Considerations

Loading Within the Space

Solar, Conduction, and Overhead Lighting

B- Shades at windows will


reduce the amount of energy
transferred to the space as the
shades will absorb and reflect
the energy. Some of the energy
will become a convective energy
gain outside of the occupied zone

A- Solar energy gain in the


space is both radiant and
convective, the amount heating
however, depends on the
design of the window
treatment. Without treatment,
the majority of this load falls on
the floor.

Fig.15 a,b

External/Lighting Loads

35

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Displacement Ventilation

Design Considerations

Loading Within the Space

Solar, Conduction, and Overhead Lighting

ID

External/Lighting Loads

C- In the case of conduction and


lighting loads, only a portion of the
load remains in the occupied zone.
Wall conduction, for example, shown
in the figure, will contribute a
predicable amount of the heat to
the occupied zone

Fig.16 a,b

D- Only the radiant component


of overhead lighting loads are
considered because the
convective loads from the
lighting remains above the
occupied zone by convecting
directly to the upper zone

36

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

18

5/13/2013

Loading Within the Space

People and Equipment Loads

People and equipment transfer heat to their


surroundings by four heat transport methods:
Conduction
Convection
Radiation
Evaporation

Sensible heat gain


to the space

Latent heat gain

ASHRAE 2005 Fundamentals


Chapter 30, Nonresidential
Cooling, and Heating Load
Calculations, give general heat
load generated by people and
equipment in various states of
activities for both sensible and
latent components.

Thermal Plume

Displacement Ventilation

Design Considerations

Fig.17

37

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Sensible Heat

Loading Within the Space

The sensible heat gain to the occupied zone is only a portion of the total
sensible load emitted from the occupants. When using displacement
ventilation for cooling, only this portion is considered when sizing the air
volume and supply air temperature.

ID

Displacement Ventilation

Design Considerations

The rate at which occupant heat is generated


is dependent on several factors:

Fig.18

Clothing levels
Metabolic rate
Environmental conditions
Activity level, etc.

Latent Heat

All of the latent load generated by people and equipment need to be


accounted for in the air volume calculation.
Evaporation from occupants, humid air generated by certain equipment, and
warm moist air exhaled by occupants all contribute to the space latent load.

Control of the latent portion of the heat generated in the space is


critical to controlling the relative humidity of the space.

38
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

19

5/13/2013

Design Considerations

Displacement Ventilation

Diffuser Type

One-Way Diffuser
Fig.19 a,b,c,d

Three-Way Diffuser

Wall Mounted

Recessed Diffuser

39

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Diffuser Type

Displacement
Linear Enclosure

ID

Displacement Ventilation

Design Considerations

Fig.20 a,b,c,d

Corner Diffuser

Circular Diffuser
Semi Circular
Diffuser
40
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

20

5/13/2013

Design Considerations

Displacement Ventilation

Diffuser Type

IndustrialDiffuser
Fig.21 a,b,c

LinearFloorGrille

RoundFloorGrille

41

Design Considerations
Diffuser Layout and Location

Some general recommendations for supply diffusers:

Rectangular or semi-circular units are often located on walls


opposite to the exterior windows and walls.

ID

Displacement Ventilation

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

For large rooms wider than 9 m, consider


mounting the diffuser on two opposite walls.

Long Rooms

Wide Rooms

Fig.22 a,b,c

For rooms longer than 5 m, consider several


diffusers along the wall.

Large Open Rooms

For large open spaces, round or rectangular


diffusers can be placed in the mid of the
space.

42

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

21

Design Considerations
Diffuser Layout and Location
Some general recommendations for supply diffusers:

Place diffusers no closer than 2 feet from occupants as shown in


the figure:

Fig.23

Displacement Ventilation

5/13/2013

Avoid placing large obstacles near the diffuser face.

Place more diffusers in areas which have a higher cooling load.


43

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Displacement Ventilation

DV Supply Air Methods

Ducted Connection

ID

The most common method to supply


air to a displacement diffuser is via
a ducted connection. Diffusers can
be connected from the top, bottom,
and sides depending on the function
and design of the diffuser.
Balancing dampers required for
diffusers should be mounted at
least 3 duct diameters away from
the inlet connection on the diffuser,
in a ducted configuration

Fig.24

44
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

22

5/13/2013

Pressurized Plenum

Fig.25

When utilizing a pressurized plenum with a


displacement diffuser, ensure that the plenum is
properly sealed .
Advantages of using a pressurized plenum are reduced
ductwork easier balancing and quicker installation.

Displacement Ventilation

DV Supply Air Methods

45

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Small Office Example

Small office in renovated office building.

North facing room


Wide =3 m
Long =3,65 m
Height = 2,7 m
2 occupants
Occupation:

ID

Displacement Ventilation

Case Study

Fig.26a

from 8:00 to 12:00 and from 13:00 to 17:00

Computer with LCD monitor


T8 florescent lighting
Control temperature of 22C

46
Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

23

5/13/2013

Boardroom Example
Private boardroom in a new office building
In the center of the building
Wide = 7,3 m
Long = 4,3 m
Height = 3 m
8 occupants
Computer with LCD monitor
T8 florescent lighting
Control temperature of 22F Fig.26b
Large white board at the west end of the room
Cabinets along the south and east end of the
room

Displacement Ventilation

Case Study

47

ES

-E

Source: E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

References

Abbas, T. (1999) Displacement ventilation and static cooling devices (COP 17/99).

Bracknell: BSRIA

ID

Schild, G. P. (2004) Displacement Ventilation, AIVC, Ventilation Information Paper

VIP 05

E.H. PRICE (2007) Displacement Ventilation DESIGN GUIDE

Chapter 25 of 1997 ASHRAE Fundamentals Handbook


Architectural Energy CorporationDisplacement Ventilation Design Guide: K-12

Schools, Final Report, 2006


Hazim B. Awbi, Ventilation Systems Design and performance, 2008
Hazim B. Awbi, Ventilation of Buildings, Second Edition, 2003

48

24

5/13/2013

Levels for the Figures


Level 1, bring best quality to the material: Get permission to the use the original picture.
Level 2, medium quality: Redraw the illustration
Level 3, poor quality: replace the illustration with a link or a reference to where to find the illustration.

Level (1 3)

Fig 2

Fig 3

Fig.4

Fig.5a,b

Fig.6
a,b,c
Fig.7
a,b,c,d,e,f
Fig.8a,b

Fig.9

Fig.10
a,b,c,d,e
Fig.11

1
1
1

Fig 14

Fig 15a,b

Fig 17

Fig 18

Fig.19
a,b,c,d
Fig.20
a,b,c,d
Fig.21
a,b,c
Fig.22
a,b,c
Fig.23

2
2
2
2

Fig.24

Fig.25

Fig.26
a,b

49

ID

ES

-E

Fig.12
Fig 13

Level (1 3)

Figure
Numbe
rbb
Fig 16

Figure
Number
Fig 1

25

Anda mungkin juga menyukai