System Investigations
Contents
Introduction to Process....................................................................................2
Specification of Problem...............................................................................3
Proposal for solution.....................................................................................3
System Design Specification.........................................................................4
Instrumentation and Control Devices...........................................................5
Temperature Device...................................................................................5
PH Device...................................................................................................7
Level Transmitter.......................................................................................8
High and Low Level Switches...................................................................10
Flow Meter...............................................................................................11
Process Control Design...............................................................................13
1 | Page
Introduction to Process
I work in a pharmaceutical plant manufacturing Flu Vaccines for distribution
globally. Due to the nature of the business and the live egg waste involved it
must be suitably treated. We have classifications of liquid waste and all
liquid waste falls into these two classifications. Contaminated and noncontaminated waste. Contaminated waste currently is treated through our
waste facility on site and this system is fully automated. Non-contaminated
waste can be distributed through the site main water drain. Recently we
have had various complaints from the local water board in regards to
condition of this waste during routine sampling and they have placed
restrictions on the pH and temperature of outgoing waste. Currently our
system Pipes all non-contaminated waste into local storage tank outside the
plant and when it gets full (typically after a days production) it is discharged
throughout the night.
The main cause of the excursion is deemed to be related to the pH. After
each production day every product contact line must be cleaned and
sanitised. This is first done by caustic in the Clean in place process. The
next stage after the chemical mix removes residue left behind by the process
is to clean steam sanitise the pipework ensuring all pathogens are killed at a
very low level. The pH issues arise from this as all chemical waste must be
disposed of and it is very high strength. Initially the discharge tank would
just dilute due to the excess water waste from post clean flushes, however
since these excursions an automated dilution method is required.
The issue we have now is to implement a system that will govern the
discharge of waste to drain in regards to temperature and pH value and a
suitable control system including automatic valves, PLC control (linked to the
site Siemens PCS7 system) and condition monitoring equipment for
temperature, level pH etc.
2 | Page
Specification of Problem
As discussed earlier the defined issue is with the Environmental monitoring
of the waste water systems to drain. The pH of the waste water can be too
far below pH 7 and is drifting out of our agreed limits. The limits are set by
local regulations and United Utilities and our limits are as follows
Limit Type
pH
Temperature
Flow Rate
Low Limit
6.0
n/a
n/a
High Limit
10.0
43.3C
12l/s
These are the control limits that the instrumentation I will choose will have to
operate within and the control system in place to be robust enough to enable
these tolerances to be controlled within and to block any discharge that it
outside these limits. Also ensuring maintenance of the equipment in line
with our requirements to the Food and Drug Administration (FDA).
The issue in hand has become far more prominent due to the increase in
production waste chemicals from the cleaning. Previously the chemical
would just mix within the tank and dilute after the flush had completed
however this is not currently the case and the pH has been rising and
without manual addition of water to dilute there is no control on this par of
the process.
3 | Page
For the control system to stop discharge we must have interlock systems in
place that will not allow the discharge valve to open until the temperature is
< 43 degrees and the pH >6 and <10. As the whole site uses Siemens step
7 so any solution would have to be created to work with this system. Cards
occupy both digital inputs/outputs and analogue inputs/outputs so either
methods of feedback, inputs and outputs would be adequate.
4 | Page
5 | Page
Fig (1)
In figure 1 I propose we use this housing with a socket weld for enhanced
leak protection, the probe will then sit inside spring loaded onto the metal
edge ensuring good contact and eat transfer (this can be enhanced with
thermal Paste).
The probe is a PT100 and connects directly to the transmitter head mounted
directly to the top. This will then be powered by a 24v supply direct from a
local instrument junction box connected to a 2 wire Siemens analogue input
card.
6 | Page
Working Principal
The working principal of the PT100 Resistance Temperature Device is the use
of a metal coiled wire typically platinum with a predictable resistance value
for the temperature range. The PT100 is most common and its resistance
value is 100 at 0 degrees C. The RTD is useful because it has low drift and
is very accurate; it produces a graph that is almost a straight line, whereas
say a nickel graph will have a curve associated with it.
An RTD is not commonly used above 600 degrees C and in these instances a
thermocouple will be used. This is due to the higher temperature causing
impurities to contaminate the element and cause it to become unusable.
This is purely an application issue and at the design stage it is imperative
that you asses the working range of the probe and determine which type to
select for this application. In general anything below 500 degrees is an RTD
PT100 and above its a range of thermocouple materials that can be selected
depending on the top end on the temperature scale.
PH Device
pH used to be a particularly difficult process measurement to take, it
required multiple probes into one line and was very prone to misreadings
and failures. Newer methods have come into the forefront now and
reliability and calibration methods have really improved. Currently on our
site we use a single probe method that proves with regular calibration to be
reliable. The probe is connected into a local display and transmitter box that
is modular. You can buy different modules for whatever application you
require. Relays can be activated to trigger alarm points back to the control
7 | Page
system or to local valves to enable one small sub system to complete some
steps of control.
Measuring principal
The pH analysis equipment used in this equipment uses the potentiometric
measurement principle. The type of probe used is called a glass electrode,
it has a buffer solution internally and a pH sensitive glass membrane. A gel
layer develops on the inside of the membrane which is in contact with the
buffer. Positive hydrogen ions either diffuse out or into the gel layer
8 | Page
Level Transmitter
The level transmitter will be used to give constant reading of levels in the
tank and will be graphed to show dropping level along with all other system
parameters to ensure when dumping water it is at the correct temperature
and pH.
9 | Page
The Micropilot is a downward facing level measurement device that uses the
time of flight method of measurement. Time of flight uses a known distance
to empty value that is measured beforehand and uses radar impulses to
reflect off the measured level and to be received by the measuring device.
This time taken given the measured to empty distance gives a distance to
level which can then be worked out to a live level as measured on the field
as shown in figure 3 below.
Fig 3
High and Low Level Switches
This part of my design is all about safety of both equipment and people.
These switches offer another level of protection other than the radar level.
The radar level will be used for control however the switches are used purely
for safety.
10 | P a g e
Fig 4
Measurement Principle
The level switch operated by using a tuning fork vibrating at their resonant
frequency when the liquid touches the tip of the probe the frequency
changes and this will then activate a limit and cause the switch to operate.
This also provides a self-monitoring function, as corrosion builds up or fouling
the frequency will also change generating an error and the probe will need to
be replaced.
11 | P a g e
Flow Meter
The flow meter will be in line with discharge pipe to control the flow rate to
keep it within specification of discharge amount per day. This flowmeter will
enable the control system to throttle a control valve to keep the flow rate to
the set point and our discharge within agreed limits.
Measuring Principle
The electromagnetic flowmeter measuring principle is based on theory of
voltage induction, the process medium is the moving conductor and the
voltage induced through a magnetic field caused by this conductor is
proportional to the flow velocity of the liquid. Figure 5 shows a graphical
representation of this process with a full explanation and formulae
Fig 5
12 | P a g e
Control Valve
The process flow will be governed by a control valve made by GEMU valves.
Its electronically positioned with feedback for current position. They are
very accurate for rate control and provide very fine tuning for this type of
application. The operate by controlling a diaphragm to modulate the valve,
the input for this would come from the control system via an output signal of
4-20 mA 4 being closed and 20 fully open. This would effectively ensure no
high flowrates on the outlet.
13 | P a g e
This section we will cover the design of the system and layout drawing. The
design has been chosen to meet a specification that will solve the initial
problem. We do not want water to be discharged to drain until it is within
specification set by the local water board.
The specification I devised is as follows each step will be broken down to see
if the chosen solution would be effective.
4. Level switched for protection of pump and secondary high high level
valve shut off.
Two level switches have been placed onto drawing that would dictate
interlock conditions for inlet and outlet valves and pump for protection of
overspill and pump.
level switch (LS330002), this will protect the pump from running dry. The
same is true for high level (LS330003) if the transmitter for level is defective
the there is some safety systems in place where the valve will fill only up to
the high level point and interlock conditions would be initiated and the valve
locked out.
Agitation will only be operational when low level is not initiated and level is
measured above 30%.
This system will fulfill the design and the problem and enable us to operate
safely and within our agreed discharge parameters. Figure 6 shows a mock
up drawing showing locations of instrumentation and a graphical display
using on site PCS7 Graphics (readings would be underneath Tag Names).
Fig 6
16 | P a g e
Bibliography
Promag Flowmeter Manual TI01159DEN_0114.pdf
http://www.omega.com/prodinfo/magmeter.html Omega Measuring principle
electromagnetic
http://www.endress.com/ PH Analysis Sensor
Temperature sensor TI13 manual TI00110ren_1312.pdf
Level Switch Manual ftl50.pdf
Beamex Ultimate Calibration on site book