Design catalogue NXAIR
NXAIR switchgear,
IEC 62271-200, SION circuit breaker,
<=17,5 kV, <=40 kA, busbar <=4000 A, feeder <=4000 A,
Loss of service continuity category: LSC 2B
Partition class:
PM
Internal arc classification:
IAC A FLR <= 40 kA, 1s

Author / Originator
Herbert Soens

Department
IC LMV MV1 PPM

Telephone

Version

Date

+49 9131 7 33776

01 - 19

17.06.2010
21.06.2011

20

19.07.2011

21

01.08.2011

22

04.08.2011

23

12.09.2011

24

24.10.2011

Draft
Release

Paper Released by:


Name

Function

Department

Thomas Lange

R&D

IC LMV MV1 R&D

Tahsin Karadeniz

R&D

IC LMV MV1 R&D TUR

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

Date

Signature

- 1 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Distribution list:
Name

Function

Department

Date

Signature

IC LMV MV1 S
IC LMV MV1 CoC
IC LMV MV 1 HUB Gebze
IC LMV MV1 R&D SWF
IC LMV MV1 R&D Gebze
IC LMV MV1 POR

Continuous Recording of Changes


In this overview, enter changes as against the released / distributed documents only !!!

Revised chapters /
pages

New issue
00 -19

Object and reason for change /


Reference to change requests
Revisions see version 21.06.2011

20

Optical arc detection system released, IP50/51 for package 2 released, package 2
with absorbers released, Rucksack package 2 released, motor mechanism for all
withdrawable parts, feeder and busbar earthing released (exeption contactor panel),
seismic version released, separate panel for ct in running busbar for <=17.5 kV/40
kA/<=4000 A and <= 17.5 kV / 25/31.5 kA/>=3150 A released, truck type version
released, bar and cable connection to busbar for package 2 released, extend ct
version for package 2 released, redundant forced ventilation for package 2 released,
new earthing crank with free wheel included

21

Panel depth in package 2 feeder current <= 2500 A with extended cts same as
standard cts (1500 mm), small corrections, e.g. page 16 cable information corrected,
page 23 ordering numbers manuals updated, page 33-35 in closed panels IP50/51
added

22

Generally optical arc detection, motor mechanism, truck type version, redundant
forded ventilation remain blocked till last releasing step, truck type version for 3150 A
feeder current blocked, special tool for fixing panels in seismic version in accessories
added, rules for channel system to outside regarding Rucksack corrected

23

Rear side distance >150 mm for switchgear with duct and outlet to rear still open,
motor mechanism of withdrawable part as disconnector and metering cassette to be
blocked (only possible as DTO), auxiliary voltages for motor mechanism added,
confinement of internal arc for 40 kA only up to 100 ms, ventilation slots in bus riser
panel > 2500 A corrected, drilling jig for seismic version added in accessories, for
direct combination busbar current metering panel with contactor panel at least two
contactor panels needed, special absorber location rules regarding contactor panel
added in NX-Tools+, additional ordering code for separate insulation part of 3AE still
open, bar and cable connection to busbar in
2000 A panel of package 2 deleted, switching duty for 40 kA breaker still open,
packing dimensions in chapter 4.26 to be checked

24

Zero sequence transformers adjusted to NX-Tools+ versions, some editorial


corrections

Note for Use:


The individual requirements must be included in the function specification in a table of requirements. During
the reviews to the main milestones it has to be checked and documented whether the requirements were
implemented. To do this, use the requirement tracing matrix.

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 2 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Content
1
1.1
1.2
1.3
1.4
1.5
2
2.1
2.1.1.
2.1.1.1
2.1.1.2
2.1.1.3
2.1.1.4
2.1.1.5
2.1.1.5.1
2.1.1.5.2
2.1.1.6
2.2
2.2.1
2.2.2
2.2.3
3
4

page
Switchgear specification
Technical data
Busbars
Design options
Processing
Rated supply voltages
Panel specification
Components in basic versions
Switching device panel panel
Circuit breaker panel
Contactor panel
Metering panel
Busbar current metering panel
Bus sectionalizer
Bus sectionalizer type 1
Bus sectionalizer type 2
Busbar connecting panel
Configuration of panels
Panel types
Design options
Components
Accessories
Additional tables

IC LMV MV1 PPM, Herbert Soens

4
4
5
5
6
7
8
8
8
8
9
9
9
10
11
11
12
13
13
13
14
20
21

issued: 24.10.2011

- 3 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Switchgear specification

1.1

Technical data
Standard

 IEC 62271-

GOST 1)

200

IEC 62271-

GOST 1)

200

Rated voltage Ur

Rated lightning impulse withstand


voltage Up

60 kV

70 kV

IEC 62271200

12 kV

60 kV

75 kV

17.5

75 kV

95

70 kV

85 kV

85 kV

110

20 kV

32 kV

28 kV

42 kV

38

23 kV

36 kV

32 kV

48 kV

45




3.3 kV

6.0 kV

13.8 kV

3.6 kV

6.6 kV

15 kV

4.8 kV

7.2 kV

16

5.0 kV

10.0 kV

6.0 kV

11.0 kV

6.6 kV
50 Hz

7.2 kV

(phase/phase, phase/earth, open


contact gap)
Rated lightning impulse
withstand voltage Up 2)
(disconnecting distance)
Rated short time power
frequency withstand voltage Ud
(phase/phase, phase/earth, open
contact gap)
Rated short time power
frequency withstand voltage Ud 2)
(disconnecting distance)
Operating voltage UN

7.2 kV

50 Hz

50 Hz

60 Hz

60 Hz

60 Hz

Rated short-time withstand


current Ik

25kA  31.5 kA 

40 kA

25 kA

31.5kA 

25 kA

31.5kA 

Rated peak withstand current Ip


for 50 Hz

63kA  80 kA

100 kA 

63 kA

80kA

100 kA 

63 kA

80kA

100 kA

Rated peak withstand current Ip


for 60 Hz

65kA  82 kA

104 kA 

65kA

82 kA

104 kA 

65kA

82 kA

104 kA

Rated short-circuit duration tk

Rated frequency fr

Ambient temperature 3)

Resistance to internal arc faults 4)

40 kA

1s

3s

30 C

35 C

40 C

45 C

50 C

55 C

IAC A FLR, 1 s (standard version)

IAC A FLR, 1 s (standard version), additionally pressure switches for all three compartments without testing
device

IAC A FLR, 1 s (standard version), additionally pressure switches for all three compartments with testing device

IAC A FLR, 1 s (standard version), additionally optical system for all three compartments (low voltage devices to
be calculated in sedis)

Confinement of internal arc within


compartments (pressure tied
partitions)

Standard, for 40 kA only up to 100 ms (with pressure switches or optical arc detection system)

Pressure relief duct to release


gases outside switchgear room

Optionally with 5)

Degree of protection

IP 3X D

IP 4X

IP 50 6)

IP 51 6)

<= 1000

See level (m)

40 kA

1) Generally insulation levels of GOST standard can be fulfilled, for contactor panel GOST values only for 7.2 kV rated voltage
2) due to partition class PM not applicable
3) switchgear is designed for ambient temperatures between -5 and +55C
4) versions of pressure relief system see table in chapter 1.3, special duct devices see also in chapter 3, accessories
5) have to be ordered depending from room heights, internal arc value etc, see also table in chapter 1.3, see also accessories chapter, 3
6) generally only for non ventilated panels possible, additionally only in combination with channel system to lead the gases outside switchgear room, see also accessories chapter 3

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 4 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

1.2

1.3

Busbars


1250 A, (1 x 100 mm x 10 mm, copper)

3150 A, (3 x 120mm x 10 mm, copper)

2500 A, (2 x 100 mm x 10 mm, copper)

4000 A, (3 x 120 mm x 10 mm, copper)

Busbar insulation

Optionally with

Busbar transverse partition

Optionally with (Standard for 40 kA panels or panels with busbar current >= 3150 A)

Design options
Pressure relief channel system 1)

 Rated IAC
voltage classification
(kV)
 <= 12


IAC A
FLR

Arc
fault
level

Arc fault
duration

Height of switchgear room

(kA)

(s)

(mm)

<= 25

1 or 0.1

31.5

40

1 or 0,1
1 or 0,1


 17.5



IAC A
FLR

<= 25
31.5

40

1 or 0.1
1 or 0,1
1 or 0,1


Busbar system
Design version
Installation

Single

Pressure relief system 2)

>= 2500 / < 2800

duct to outside

>= 2800

absorbers

>= 2500 / < 3000

duct to outside

>= 3000

absorbers

>= 2500 / < 3500

duct to outside

>= 3500

absorbers

>= 2500 / < 3500

duct to outside

>= 3500

absorbers

>= 2500 / < 3500

duct to outside

>= 3500

absorbers

>= 2500 / < 3500

duct to outside

>= 3500

absorbers

Withdrawable part design

Truck type design 3)

Freestanding with cable access from front or rear

Freestanding with cable access from above and rear for 600/800/1000 mm panels up to 17.5 kV/31.5
kA/2500 A or 800/1000 mm panels up to 17.5 kV/40 kA/<=4000 A resp. up to 17.5 kV 25/31.5 kA
3150/4000 A (increasing of depth: 600 mm)


Partitions

Wallstanding with cable access from front


LSC 2B (metal clad) (Standard)
Pressure resistant to neighboring compartments and panels up to 31.5 kA, 1 s resp. 40 kA 0.1s

Shutters

Independently lockable (Standard)




Padlocks facilities 4)
(padlocks itself not included)

With labels busbar and feeder (Standard)


padlocks for both shutters
(standard)

padlock for high voltage


door

padlock for mechanical cover


for ON push button of breaker

padlock for mechanism of


withdrawable part

padlock for mechanism of


feeder earthing switch

padlock for mechanism of


busbar earthing switch

electromagnetic interlocking coil

electromagnetic interlock for


mechanism of withdrawable
part

electromagnetic interlock for


mechanism of feeder
earthing switch

electromagnetic interlock for


mechanism of busbar earthing
switch

Key interlocking system based on


Ronis principle

Key interlocking system 4) for


withdrawable part
with circuit breaker, disconnecting
link, contactor

 Key free in test position

Key interlocking system 4) for


feeder earthing switch in panels
with circuit breaker, disconnecting
link or contactor

 Key free in closed position

Key free in
open position

Key A free in closed position,


Key B free in open position

Key interlocking system 4) for


busbar earthing switch

 Key free in closed position

Key free in
open position

Key A free in closed position,


Key B free in open position

1) special channel devices see under accessories and configuration information in chapter 4 (additional tables)
2) when pressure relief channel to lead gases outside is used absorbers are not needed
3) withdrawable voltage transformers in connection compartment are not possible, truck type version is also not possible for feeder current 3150 A
4) key interlocking system in combination with all padlock variants possible, key interlocking system in combination with electromagnetic interlocking or with motor mechanism of
withdrawable part resp. feeder and busbar earthing not possible

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 5 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Height of low voltage compartment

630 mm (Standard)


Transverse partition in low voltage


compartment

980 mm
Standard

Lightning in low voltage compartment

Optionally with

Language for labels and operating instructions

Optionally english

Optionally german


Pressure resistant floor cover in cable
compartment

Optionally spanish
Standard

Anticondensation heater in switching


device compartment, 100 W

Optionally with

Anticondensation heater in
cable compartment, 100 W

Optionally with

Anticondensation heater in
low voltage compartment, 20 W

Optionally with

Surface treatment enclosure, partitions

Standard:
Steel parts zinc-plated, high voltage and low voltage door at front and end walls powder
coated RAL 7035
Or all sheet metal parts powder coated in RAL 7035 (depending on manufacturing
location)


Optionally powder coating of rear wall in standard colour RAL 7035

Optionally with special colour instead of standard colour for high voltage and low voltage
door at front and end walls

Optionally powder coating of rear wall in special colour

Seismic withstand capability

Optionally with 1)

Separate earthing bar between withdrawable


part and earthing bar in cable compartment

With

Additional earthing wire between high voltage


door and enclosure

Standard

Additional earthing wire between low voltage


door and enclosure

Standard

Surface treatment of primary contacts


Surface treatment of busbar and earthing bar
Surface treatment of components in primary
part

Silver plated (Standard)




Standard


Secondary wiring and channels

1.4

Optionally silver plated


Optionally silicon free
Standard

Optionally halogen free

Optionally silicon free

Panels complete

Panels complete with low voltage compartment as advance delivery

Transport units

Single panels

Packing

Packing for truck on road or rail

Packing for airfreight

Packing for sea freight, transport and storage period up to 6 months

Processing
Scope of order

Acceptance test

Packing for sea freight, transport and storage period up to 12 months

Visual inspection

Complete routine test per panel in acc. to IEC 62271-200

Complete routine test per typical in acc. to IEC 62271-200

Visual inspection and mechanical function test per typical

Without

1) special marking-spreading tool for drive-in anchors to fix panel to bottom and drilling jig needed, see chapter accessories

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 6 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

1.5

Rated supply voltages


Auxiliary voltage

Circuit breaker motor voltage

Operating voltage for closing


solenoid and closing latch of
contactor 3TL6

Operating voltage for releasing


mechanical closing latching 3TL6

DC 24 V

DC 120 V

AC 100 V 1)

DC 30 V

DC 125 V

AC 110 V

1)

DC 32 V

DC 127 V

AC 120 V

1)

DC 48 V

DC 220 V

AC 125 V

1)

DC 60 V

DC 240 V

AC 230 V

1)

DC 110 V

AC 240 V

1)

DC 24 V

DC 120 V

AC 100 V

1)

DC 30 V

DC 125 V

AC 110 V

1)

DC 32 V

DC 127 V

AC 120 V

1)

DC 48 V

DC 220 V

AC 125 V

1)

DC 60 V

DC 240 V

AC 230 V

1)

DC 110 V

AC 240 V

1)

DC 110 V

AC 100 V 1)

DC 125 V

AC 110 V

1)

DC 220 V

AC 115 V

1)

AC 120 V

1)

AC 230 V

1)

AC 240 V




DC 110 V

AC 100 V

DC 125 V

AC 110 V

1)

DC 220 V

AC 115 V

1)

AC 120 V

1)

AC 230 V

1)

AC 240 V

1)

First shunt trip voltage of SION

Second shunt trip voltage of SION

Motor mechanism withdrawable part,


feeder and busbar earthing

Interlocking supply (electromagnetic


interlock of withdrawable part / truck
and earthing switch

Heater supply voltage

1)
1)

DC 24 V

DC 120 V

AC 100 V

1)

DC 30 V

DC 125 V

AC 110 V

1)

DC 32 V

DC 127 V

AC 120 V

1)

DC 48 V

DC 220 V

AC 125 V

1)

DC 60 V

DC 240 V

AC 230 V

DC 110 V

AC 240 V

1)

DC 24 V

DC 120 V

AC 100 V

1)

DC 30 V

DC 125 V

AC 110 V

1)

DC 32 V

DC 127 V

AC 120 V

1)

DC 48 V

DC 220 V

AC 125 V

1)

DC 60 V

DC 240 V

AC 230 V

1)

DC 110 V

AC 240 V

1)

DC 24 V

DC 60 V

DC 110 V







DC 48 V

AC 110 V

AC 230 V

DC 24 V

DC 125 V

DC 48 V

DC 220 V

DC 60 V

DC 240 V

DC 110 V

AC 220 240 V

AC 110 V

1) for 50 and 60 Hz

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 7 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2
2.1

Panel specification
Components

2.1.1

Switching device panel

2.1.1.1

Circuit breaker panel


Panel width (mm)
600 1)

Compartment
busbar

switching
device
connection

Panel width (mm)


800

compartment
busbar

switching
device

connection

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for voltage transformers
optionally with busbar earthing switch hand operated
optionally with top box for make proof earthing switch motor operated
bushing type insulators between breaker and busbar
optionally capacitive voltage indication
withdrawable circuit breaker, hand operated
optionally withdrawable circuit breaker, motor operated
cables
bushing type insulators and optionally block type current transformers
bushing type insulators and optionally extended block type current transformers 2) up
to 17.5 kV / 31.5 kA / 2500 A possible
optionally fixed mounted voltage transformers
optionally make proof earthing switch hand operated
optionally make proof earthing switch motor operated
optionally surge arrestors or limiters
optionally capacitive voltage indication
optionally devices for zero sequence transformers
bare copper
optionally insulated copper
optionally with top box for make proof earthing switch hand operated
optionally with top box for make proof earthing switch motor operated
optionally with top box for voltage transformers
bushing type insulator between breaker and busbar
optionally with top box for bar or cable connection
optionally capacitive voltage indication optionally
withdrawable circuit breaker, hand operated
optionally withdrawable circuit breaker, motor operated
optionally withdrawable disconnetor link, hand operated
closed panel, without slots
cables or optionally bar connection
bushing type insulators and optionally block type current transformers
bushing type insulators and optionally extended block type current transformers up to
17.5 kV / 31.5 kA / 2500 A possible 2) or up to 17.5 kV/40 kA/<=4000 A resp. up to
17.5 kV 25/31.5 kA / 3150/4000 A 3)
optionally fixed mounted voltage transformers
optionally withdrawable voltage transformers in separate compartment with fuses 4)
optionally make proof earthing switch hand operated
optionally make proof earthing switch motor operated
optionally surge arrestors or limiters
optionally capacitive voltage indication optionally
optionally devices for zero sequence transformers










































detailed configuration in NX-Tools+

1) only up to 31.5 kA
2) higher specific core data of ct possible, panel depth 1500 mm instead of 1350 mm
3) higher specific core data of ct possible, panel depth 1500 mm up to feeder current 2500 A resp. 1650 mm for feeder current 3150/4000 A
4) not possible when truck type design is selected

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 8 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.1.1.1

Circuit breaker panel


Panel width (mm)
1000 mm

Design resp. devices

compartment
busbar

bare copper
optionally insulated copper
bushing type insulator between breaker and busbar
optionally capacitive voltage indication optionally
withdrawable circuit breaker, hand operated
optionally withdrawable circuit breaker, motor operated
optionally withdrawable disconnetor link, hand operated
natural ventilated panel
forced ventilated, current relais controlled
forced ventilated, current relais controlled and redundant version
cables or optionally bar connection
bushing type insulators and optionally block type current transformers
bushing type insulators and optionally extended block type current transformers up to
17.5 kV / 31.5 kA / 2500 A possible 1) or up to 17.5 kV/40 kA/<=4000 A resp. up to
17.5 kV 25/31.5 kA / 3150/4000 A 2)
optionally fixed mounted voltage transformers
optionally withdrawable voltage transformers in separate compartment with fuses 3)
optionally make proof earthing switch hand operated
optionally make proof earthing switch motor operated
optionally surge arrestors or limiters
optionally capacitive voltage indication optionally
optionally devices for zero sequence transformers

switching
device

connection






















1) higher specific core data of ct possible, panel depth 1500 mm instead of 1350 mm
2) higher specific core data of ct possible, panel depth 1650 mm instead of 1540 mm for feeder current 3150/4000 A
3) not possible when truck type design is selected and not possible when 3150 A feeder current is selected

2.1.1.2

Contactor panel
Panel width (mm)
435

1)

compartment
busbar

Design resp. devices


bare copper
optionally insulated
bushing type insulators between contactor and busbar
withdrawable contactor with 1 fuse per phase, without fused control transformer, hand
operated
optionally withdrawable contactor with 2 fuses per phase, without fused control
transformer, hand operated
optionally withdrawable contactor with 1 fuse per phase, with fused control
transformer 2), hand operated
optionally withdrawable contactor with 2 fuses per phase, with fused control
transformer 2), hand operated
cables
bushing type insulators and block type current transformers
optionally make proof earthing switch (20 kA peak value) hand operated
optionally surge limiters
optionally capacitive voltage indication optionally
optionally devices for zero sequence transformers

switching
device

connection















1) up tp 40 kA, at least two panels needed if direct connection with busbar current metering panel is planned,
can be used for motor feeder, for transformer incomer earthing switch has to be interlocked electromechanically with secondary breaker of
transformer;
insulation level of GOST standard for 7.2 kV rated voltage as an option possible,
for. 7.2 kV version: 60 kV phase/phase, phase earth, 40 kV open contact gap, 20 kV phase/phase, phase/earth, open contact gap
for 12 kV version: 75 kV phase/phase, phase earth, 60 kV open contact gap, 28 kV phase/phase, phase/earth, open contact gap
2) not possible in 12 kV version,
detailed configuration in NX-Tools+

2.1.1.3

Metering panel (voltage of busbar)


Panel width (mm)
800

compartment
busbar

switching
device
detailed configuration in NX-Tools+

2.1.1.4

Busbar current metering panel


Panel width (mm)
800

1)

compartment
busbar

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for make proof earthing switch hand operated
optionally with top box for make proof earthing switch motor operated
bushing type insulator
optionally with top box for voltage transformers
optionally with top box for bar or cable connection
optionally capacitive voltage indication
withdrawable part with voltage transformers and primary fuses, hand operated











for <= 17.5 kV/40kA/<=4000 A resp. <= 17.5 kV / 25/31.5 kA / 3150/4000 A


Design resp. devices
Bare copper with 3 block type cts
Optionally insulated copper with 3 block type cts




detailed configuration in NX-Tools+


1) when directly added to contactor panel, at least two contactor panels are needed

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 9 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.1.1.5

Bus sectionalizer can be designed as:


Type I consisting of:
circuit breaker
rated
1)
current

circuit breaker

rated
1)
current

rated
1)
current

width of
panel

bus riser panel, optionally


with metering
width of
panel

rated
1)
current

width of
panel

(A)

(mm)

(A)

(mm)

(A)

(mm)

(A)

(mm)

1250

800

1250

800

1250

800

1250

800

800

2000

800

2000

800

2000

2500

1000

2500

1000

2500

1000

2500

3150

1000

3150

1000

3150

1000

3150

1000

4000

1000

4000

1000

4000

1000

4000

1000

2000

2.1.1.5.1

width of
panel

Typ II consisting of:


bus riser panel with
disconnector

1)

1)

Bus sectionalizer type I, 1250 A / 2000 A


Circuit breaker panel, 1250 A / 2000 A
Panel width (mm)
800

Compartment
busbar

switching
device
connection

1)

Compartment
busbar

switching
device
connection

1)

800
800

(mirror-image installation possible)

1)

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for make proof earthing switch hand operated
optionally with top box for make proof earthing switch motor operated
optionally with top box for voltage transformers
bushing type insulators between breaker and busbar
optionally with top box for bar or cable connection
optionally capacitive voltage indication optionally
withdrawable circuit breaker, hand operated
optionally withdrawable circuit breaker, motor operated
bar connection to bus riser panel
bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers
optionally capacitive voltage indication option

Bus riser panel with disconnecting module, 1250 A / 2000 A


Panel width (mm)
800

1)
















1)

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for make proof earthing switch hand operated
optionally with top box for make proof earthing switch motor operated
optionally with top box for voltage transformers
bushing type insulators between breaker and busbar
optionally with top box for bar or cable connection
optionally capacitive voltage indication optionally
withdrawable disconnetor link, hand operated











bar connection to bus circuit breaker panel


bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers
optionally capacitive voltage indication






detailed configuration in NX-Tools+

1) rated current, see also tables in chapter 4.10, 2000 A version only in 40 kA possible

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 10 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.1.1.5.1

Bus sectionalizer type I, 2500 A, 3150 A, 4000 A, (mirror-image installation possible)


Circuit breaker panel, 2500 A, 3150 A, 4000 A
Panel width (mm)
1000

Compartment
busbar

Design resp. devices


bare copper
optionally insulated copper
bushing type insulators between breaker and busbar
optionally capacitive voltage indication optionally
withdrawable circuit breaker, hand operated
optionally withdrawable circuit breaker, motor operated
natural ventilated
forced ventilated, current relais controlled
forced ventilated, current relais controlled and redundant version
bar connection to bus riser panel
bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers
optionally capacitive voltage indication option

switching
device

connection















Bus riser panel with disconnecting module, 2500 A, 3150 A, 4000 A


Panel width (mm)
1000

Compartment
busbar

Design resp. devices


bare copper
optionally insulated copper
bushing type insulators between breaker and busbar
optionally capacitive voltage indication optionally
withdrawable disconnetor link, hand operated
natural ventilated 1)
forced ventilated 1), current relais controlled
forced ventilated 1), current relais controlled and redundant version
bar connection to bus circuit breaker panel
bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers
optionally capacitive voltage indication

switching
device

connection














detailed configuration in NX-Tools+

2.1.1.5.2

Bus sectionalizer type II, 1250 A / 2000 A


Circuit breaker panel, 1250 A / 2000 A
Panel width (mm)
800

Compartment
busbar

2)

(mirror-image installation possible)

2)

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for make proof earthing switch hand operated
optionally with top box for make proof earthing switch motor operated
optionally with top box for voltage transformers
bushing type insulators between breaker and busbar
optionally with top box for bar or cable connection
optionally capacitive voltage indication optionally
withdrawable circuit breaker, hand operated
optionally withdrawable circuit breaker, motor operated
bar connection to bus riser panel
bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers
optionally capacitive voltage indication

switching
device
connection
















2)

Bus riser panel 1250 A / 2000 A , optionally with metering module


Panel width (mm)
800

Compartment
Busbar

switching
device
Connection

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for bar or cable connection
optionally capacitive voltage indication
optionally withdrawable part with voltage transformers and primary fuses, hand
operated
bar connection to circuit breaker panel
bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers










detailed configuration in NX-Tools+

1) 2500 A closed panel, 3150 A natural ventilated panel, 4000 A forced ventilated panel
2) 2000 A only for 40 kA possible

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 11 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.1.1.5.2

Bus sectionalizer type II, 2500 A, 3150 A, 4000 A, (mirror-image installation possible)
Circuit breaker panel, 2500 A, 3150 A, 4000 A
Panel width (mm)
1000

Compartment
busbar

switching
device

connection

Design resp. devices


bare copper
optionally insulated copper
bushing type insulators between breaker and busbar
optionally capacitive voltage indication optionally
withdrawable circuit breaker, hand operated
optionally withdrawable circuit breaker, motor operated
optionally ventilation slots
forced ventilated, current relais controlled
forced ventilated, current relais controlled and redundant version
bar connection to bus riser panel
bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers
optionally capacitive voltage indication















Bus riser panel 2500 A, 3150 A, 4000 A, optionally with metering module
Panel width (mm)
800/1000

Compartment
busbar

switching
device
connection

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for bar or cable connection
optionally capacitive voltage indication
optionally withdrawable part with voltage transformers with primary fuses, hand
operated
optionally ventilation slots for >= 3150 A
bar connection to circuit breaker panel
bushing type insulators and optionally block type current transformers
optionally fixed mounted voltage transformers











detailed configuration in NX-Tools+

2.1.1.6

Busbar connecting panel (only in 800 mm panel width)


Panel width (mm)
800/1000

Compartment
busbar

switching
device
connection

Design resp. devices


bare copper
optionally insulated copper
optionally with top box for make proof earthing switch hand operated
optionally with top box for make proof earthing switch motor operated
optionally with top box for voltage transformers
optionally with top box for bar or cable connection
optionally withdrawable part with voltage transformers and fuses, hand operated









cable connection to bus riser panel


optionally block type current transformers
optionally fixed mounted voltage transformers
optionally capacitive voltage indication






detailed configuration in NX-Tools+

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 12 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2
2.2.1

Configuration of panels
Panel types
basic
version

































































rated
voltage

(kV)
17.5

panel type

Switching
device
panel
with circuit
breaker
or
disconnecting
link

short
circuit
breaking
current

busbar current 1)
(A)

(kA)
25

(A)
1250

rated busbar
current

2500

3150

4000

31.5

1250

2500

3150

4000

40

1250
2500

3150

4000

Contactor
panel 6)

=< 31.5

40

Metering
panel

<= 31.5

<= 40

Busbar
current
metering
panel

<= 31.5
<= 40

1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
3150
4000
3150
4000
1250
2500
3150
4000

feeder current 1)
(A)
rated
current
(A)
630
1000
1250
630
1000
1250
2500
1250
2500
3150
1250
2500
3150
4000
630
1000
1250
630
1000
1250
2500
1250
2500
3150
1250
2500
3150
4000
1250
1250
2000
2500
1250
2000
2500
3150
1250
2000
2500
3150
4000
<= 400
<= 400
<= 400
<= 400
<= 400
<= 400
<= 400
<= 400
-

rated
breaker
current
(A)
800
1250
1250
800
1250
1250
2500
1250
2500
3150
1250
2500
3150
3150
800
1250
1250
800
1250
1250
2500
1250
2500
3150
1250
2500
3150
3150
1250
1250
2500
2500
1250
2500
2500
3150
1250
2500
2500
3150
3150
400
400
400
400
400
400
400
400
-

rated panel
current
(A)
630
1000
1250
630
1000
1250
2500
1250
2500
3150
1250
2500
3150
4000
630
1000
1250
630
1000
1250
2500
1250
2500
3150
1250
2500
3150
4000
1250
1250
2000
2500
1250
2000
2500
3150
1250
2000
2500
3150
4000
400
400
400
400
400
400
400
400
-

width

depth

closed

(mm)
600

(mm)
1350 2)

closed

800
600

natural ventilated
closed
natural ventilated
natural ventilated
closed
natural ventilated
natural ventilated
forced ventilated 5)
closed

800
1000
800
1000
1000
800
1000
1000
1000
600

closed

800
600

panel design

natural ventilated
closed
natural ventilated
natural ventilated
closed
natural ventilated
natural ventilated
forced ventilated 5)
closed

natural ventilated
closed
natural ventilated
natural ventilated
closed
natural ventilated
natural ventilated
forced ventilated 5)
closed
closed
closed
closed
closed
closed
closed
closed
closed

800
1000
800
1000
1000
800
1000
1000
1000
800
800
800
1000
800
800
1000
1000
800
800
1000
1000
1000
435
435
435
435
435
435
435
435
800

1500 3)
1540 4)
1500 3)
1540 4)
1350 2)

1500 3)
1540 4)
1500 3)
1540 4)
1500 3)

1540 4)
1500 3)

1540 4)
1400
1500
1500

1350
1500

closed

800

1500

800

1500

natural ventilated
natural ventilated
closed
closed
natural ventilated
natural ventilated

800

1500

1) permissible current values depending from ambient temperature values, degree of protection etc are included in chapter 4.10
2) 1350 mm when standard block type cts, 1500 mm when extended block type cts are used, when rear side cable connection from above additional 600 mm in depth for duct
3) 1500 mm for standard or extended block type cts, rear side cable connection from above additional 600 mm in depth for duct
4) 1540 mm with standard block type cts, 1650 mm resp. when extended block type cts are used, when rear side cable connection from above additional 600 mm in depth for duct
5) forced ventilation standard, optionally redundant system
6) can be used for motor feeder and transformer feeder (not for transformer incomer), insulation level of GOST standard for 7.2 kV rated voltage as an option possible, for. 7.2 kV
version: 60 kV phase/phase, phase earth, 40 kV open contact gap, 20 kV phase/phase, phase/earth, open contact gap for 12 kV version, 75 kV phase/phase, phase earth, 60 kV open
contact gap, 28 kV phase/phase, phase/earth, open contact gap

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 13 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.1

Panel types
basic
version

rated
voltage

panel type

(kV)

short
circuit
breaking
current

busbar current 1)

feeder current 1)

(A)

(A)

Rated busbar
current

Rated
current

(kA)

(A)

(A)

25

1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
2500
3150
4000
1250
2500

1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000
1250
2500

3150
4000

Rated
breaker
current
(A)

panel design

width

depth

(mm)

(mm)

2x800
2x1000
2x1000
2x1000
2x800
2x1000
2x1000
2x1000
2x800
2x800
2x1000
2x1000
2x1000
2x800
1x1000+
1x800
2x1000

1350

Rated
panel
current

1250
2500
3150
3150
1250
2500
3150
3150
1250
2500
2500
3150
3150
1250
2500

(A)
1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000
1250
2500

closed
natural ventilated
natural ventilated
forced ventilated 2)
closed
natural ventilated
natural ventilated
forced ventilated 2)
closed
closed
natural ventilated
natural ventilated
forced ventilated 2)
closed
natural ventilated

3150

3150

3150

natural ventilated

4000

3150

4000

forced ventilated 2) 2x1000

1250

1250

1250

1250

closed

2x800

1350

2500

2500

2500

2500

natural ventilated

3150

3150

3150

3150

natural ventilated

1x1000+
1x800
2x1000

1540

4000

4000

3150

4000

forced ventilated 2) 2x1000

1250
2500

1250
2000

1250
2500

1250
2000

closed
closed

2x800
2x800

2500

2500

2500

2500

natural ventilated

3150

3150

3150

3150

natural ventilated

1x1000+
1x800
2x1000

4000

4000

3150

4000

forced ventilated 2) 2x1000

1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
2500
3150
4000

1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000

1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000

closed






















Bus
sectionalizer
type I
consisting of:
switching
device panel
and
bus riser
panel with
disconnector
module





40

Bus
25
sectionalizer
type II
consisting of:
switching
device panel
and
31.5
bus riser
panel
optionally with
metering
module











31.5

40

Busbar
connecting
panel

25

31.5

40

1)

permissible current values depending from ambient temperature values, degree of protection etc are included in chapter 4.10

2)

forced ventilation current relais controlled, optionally redundant version possible

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

800
800
1000
1000
800
800
1000
1000
800
800
800
1000
1000

1540
1350
1540
1500

1540
1350

1540

1500

1540
1350
1540
1350
1540
1500

1540

- 14 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.2

Design options


Intermediate panel

Panel arrangement

Left end panel





Right end panel


Door hinges for high voltage and low voltage
door 1)

2.2.3

Components

2.2.3.1

Capacitive voltage indicator


Capacitive voltage indicator

2.2.3.2

Number, type and size of cables

Deep bottom pan


Copper bar connection

Earthing switch 4)
Type of earthing switch
Function of earthing switch

Auxiliary switch
Mechanism
Electromagnetic interlock
Mechanical locking device
Key interlocking

















From bottom, front


From bottom, rear
From above and rear 2)
1 single core cable max. 500 mm per phase
2 single core cable max. 500 mm per phase
3 single core cable max. 500 mm per phase
4 single core cable max. 500 mm per phase
6 single core cable max. 500 mm per phase for panel depth 1540 mm
up to 2 three core cable max. 240 mm 3)
With
With <= 1250 A
With for 2000 A (only for panels 40 kA)
With for 2500 A
With for 3150 A
With for 4000 A







With <= 1250 A


With for 2000 A (only for panels >= 3150 A busbar current
With for 2500 A
With for 3150 A
With for 4000 A















Make proof earthing switch


Feeder earthing
Busbar earthing
<= 25 kA / 3s
31.5 kA / 3s
40 kA / 3s
4 NO + 4 NC
Manual operated
Motor operated 5)
With
Without
Padlock
Key interlocking system for feeder earthing in circuit breaker panel, disconnecting link
panel, contactor panel
 Key free in closed
 Key free in
 Key A free in closed position,
position
open position
Key B free in open position
Key interlocking system for busbar earthing
 Key free in
 Key A free in closed position,
 Key free in closed
position
open position
Key B free in open position

2.2.3.5

at cable side
at busbar side
LRM (low resistant modified)
VOIS
Capdis S1+
Capdis S2+

Panel connection busbar compartment


Copper bar connection

2.2.3.4

right

Panel connection cable compartment


Cable connection

2.2.3.3








left

Bushing-type insulators
installation

Rated short time current / Rated


short circuit duration resp. rated
current








at busbar side (between breaker and busbar) and cables side (between breaker and
cable)
<= 31.5 kA / 3 s, 1000 A
<= 40 kA / 3 s, 1250 A
<= 40 kA / 3 s, 2500 A
<= 40 kA / 3 s, 4000 A
for capacitive voltage indication optionally
Silicon free optionally

1) for contactor panel only left side possible


2) increased panel depth of 600 mm
3) generally only up to 2 three core cables and generally only in combination with deep bottom pan, in 600 mm panel only 3 x 185 mm
4) in contactor panel switching capacity of feeder earthing is limited to 20 kA peak values resp. 8 kA / 1s due to cut off function of fuses, in case of using this contactor panel for other
consumers than motor, this have to be considered (electrical interlocking with upstream breaker to be configurated)
5) not possible for earthing switch in contactor panel

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 15 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.6

Block-type current transformers 4MA72 standard version for current values 2500 A,
in connection compartment,
drawing number 4MA72: <= 1250 A: 110-0135.9; >1250 A / <= 2500 A: 110-0136.9
installation
Number of cores






Rated short time current / Rated


short circuit duration

































Rated primary current


(not reconectable on the secondary
side)

Rated primary current


(reconnectable on the secondary
side)

Rated power
Class

Rated secondary current

Additional features





2.2.3.7

one set at cable side, below breaker



1 x 1 core in L2
2 x 2 core in L1/L3

2 x 1 core in L1/L3
2 x 1 core in L1/L3 + 1 x 2 cores in L2

3 x 1 core in L1/L2/L3
2 x 2 core in L1/L3 + 1 x 1 cores in L2

3 x 2 core in L1/L2/L3


16 kA / 1s
40 kA / 1s
31.5 kA / 3s


20 kA / 1s
16 kA / 3s
40 kA / 3s

25 kA / 1s
20 kA / 3s

31.5 kA / 1s
25 kA / 3s


50
200
750


60
250
1000


75
300
1250


100
400
1500


125
500
2000


150
600
2500


2 x 20
2 x 75
2 x 300


2 x 25
2 x 100
2 x 400


2 x 30
2 x 125
2 x 500


2 x 40
2 x 150
2 x 600

2 x 50
2 x 200

2 x 60
2 x 250


2.5 VA
10 VA
20 VA


5 VA
15 VA
30 VA


0.2
FS10
5P
10
5P
30

0.2
SFS10
10P
10

0.5
FS5
5P
15

1
FS5
5P
20


1A
5A/1A
1A/5A/5A


5A
1A/1A/1A
5A/5A/1A


1A/1A
5A/5A/5A
5A/1A/5A


5A/5A
1A/1A/5A
5A/1A/1A

1A/5A
1A/5A/1A
with approval
Current transformers silicon free
Secondary wiring halogen free
Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST
Language of name plate German / English
Primary rated current 1.2 x In

Block-type current transformers 4MA72, size 2, extended version for current values 2500 A,
panel depth 1500 mm, in connection compartment
installation
Number of cores






Rated short time current / Rated


short circuit duration

































Rated primary current


(not reconectable on the secondary
side)

Rated primary current


(reconnectable on the secondary
side)

Rated power
Class

Rated secondary current

Additional features




IC LMV MV1 PPM, Herbert Soens

one set at cable side, below breaker



1 x 1 core in L2
2 x 2 core in L1/L3

2 x 1 core in L1/L3
2 x 1 core in L1/L3 + 1 x 2 cores in L2

3 x 1 core in L1/L2/L3
2 x 2 core in L1/L3 + 1 x 1 cores in L2

3 x 2 core in L1/L2/L3


16 kA / 1s
40 kA / 1s
31.5 kA / 3s


20 kA / 1s
16 kA / 3s
40 kA / 3s

25 kA / 1s
20 kA / 3s

31.5 kA / 1s
25 kA / 3s


50
200
750


60
250
1000


75
300
1250


100
400
1500


125
500
2000


150
600
2500


2 x 20
2 x 75
2 x 300


2 x 25
2 x 100
2 x 400


2 x 30
2 x 125
2 x 500


2 x 40
2 x 150
2 x 600

2 x 50
2 x 200

2 x 60
2 x 250


2.5 VA
10 VA
20 VA


5 VA
15 VA
30 VA


0.2
FS10
5P
10
5P
30

0.2
SFS10
10P
10

0.5
FS5
5P
15

1
FS5
5P
20


1A
5A/1A
1A/5A/5A


5A
1A/1A/1A
5A/5A/1A


1A/1A
5A/5A/5A
5A/1A/5A


5A/5A
1A/1A/5A
5A/1A/1A

1A/5A
1A/5A/1A
with approval
Current transformers silicon free
Secondary wiring halogen free
Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST
Language of name plate German / English
Primary rated current 1.2 x In
issued: 24.10.2011

- 16 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.8

Block-type current transformers CT 12 I only for panels up 17.5 kV, busbar current > = 3150
A, drawing number: 110-0314.9, panel depth 1500 resp. 1540 mm,
in connection compartment or in busbar current metering panel
installation
Number of cores

Rated short time current / Rated


short circuit duration

Rated primary current


(not reconectable on the secondary
side)
Rated power
Class

Rated secondary current

Additional features













one set at cable side, below breaker



1 x 1 core in L2
2 x 1 core in L1/L3 + 1 x 2 cores in L2

2 x 1 core in L1/L3
2 x 2 core in L1/L3 + 1 x 1 cores in L2

3 x 1 core in L1/L2/L3
3 x 2 core in L1/L2/L3
2 x 2 core in L1/L3

16 kA / 1s
16 kA / 3s

20 kA / 1s
20 kA / 3s

25 kA / 1s
25 kA / 3s

31.5 kA / 1s
31.5 kA / 3s

40 kA / 1s
40 kA / 3s

3150 A
4000 A



















2.5 VA
10 VA
20 VA


5 VA
15 VA
30 VA


0.2
FS10
5P
10
5P
30

0.2
SFS10
10P
10

0.5
FS5
5P
15

1
FS5
5P
20


1A
5A/1A
1A/5A/5A


5A
1A/1A/1A
5A/5A/1A


1A/1A
5A/5A/5A
5A/1A/5A


5A/5A
1A/1A/5A
5A/1A/1A

1A/5A
1A/5A/1A
with approval
Current transformers silicon free
Secondary wiring halogen free
Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST
Language of name plate German / English
Primary rated current 1.2 x In





2.2.3.9

Block-type current transformers CT 12 K, extended version only for panels up to 17.5 kV,
busbar current >= 3150 A depth 1650 mm, in connection compartment
installation
Number of cores

Rated short time current / Rated


short circuit duration

Rated primary current


(not reconectable on the secondary
side)
Rated power
Class

Rated secondary current

Additional features
















one set at cable side, below breaker


1 x 1 core in L2
2 x 1 core in L1/L3
3 x 1 core in L1/L2/L3
2 x 2 core in L1/L3
2 x 1 core in L1/L3 + 1 x 2 cores in L2
2 x 2 core in L1/L3 + 1 x 1 cores in L2
3 x 2 core in L1/L2/L3

16 kA / 1s
16 kA / 3s

20 kA / 1s
20 kA / 3s

25 kA / 1s
25 kA / 3s

31.5 kA / 1s
31.5 kA / 3s

40 kA / 1s
40 kA / 3s

3150 A



















2.5 VA
10 VA
20 VA


5 VA
15 VA
30 VA


0.2
FS10
5P
10
5P
30

0.2
SFS10
10P
10

0.5
FS5
5P
15

1
FS5
5P
20


1A
5A/1A
1A/5A/5A


5A
1A/1A/1A
5A/5A/1A


1A/1A
5A/5A/5A
5A/1A/5A


5A/5A
1A/1A/5A
5A/1A/1A

1A/5A
1A/5A/1A
with approval
Current transformers silicon free
Secondary wiring halogen free
Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST
Language of name plate German / English
Primary rated current 1.2 x In





IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

4000 A

- 17 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.10

Block-type current transformers 4MB61 (size 2) for contactor panel


Installation

Rated short time current / Rated


short circuit duration 1)
Rated primary current

Rated power
Class

Rated secondary current






at cable side
3 x 1 core in L1/L2/L3
3 x 2 core in L1/L2/L3
up to 25 kA / 3s




















25 A
75 A
250 A


30 A
100 A
300 A


40 A
125 A
400 A

50 A
150 A

60 A
200 A

5 VA
15 VA

10 VA
30 VA


5 VA 10P 10
30 VA 10P 10
15 VA 1 M5

10 VA 10P 10
5 VA 1 M5

15 VA 10P 10
10 VA 1 M5


1A
1A/1A
1A/5A


5A
5A/5A
5A/1A
with approval
Current transformers silicon free
Secondary wiring halogen free
Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standard
GOST
Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standard GOST
Language of name plate German / English
Primary rated current 1.2 x In





2.2.3.9

Voltage transformers 4MR12 up to 17.5 kV, drawing number for 4MR12 without fuses: 1100137.9

Installation







Earth fault winding

Primary voltage single pole

Rated secondary voltage


Rated secondary voltage earth fault
winding
Rating / Class
Additional features






















3 x 1 pole
3 x 1 pole with earth fault winding
3 x 1 pole with earth fault winding and damping resistor
fix mounted without primary fuses, generally with encapsulated primary connection
on withdrawable part for busbar metering in metering panel 2),
generally with fuses 7.2 kV, 6.3 A
generally with fuses 12 kV, 6.3 A
generally with fuses 17.5 kV, 6.3 A
in separate compartment, withdrawable with fuses at feeder side 3),
generally with fuses 7.2 kV, 6.3 A,
generally with fuses 12 kV, 6.3 A
generally with fuses 17.5 kV, 6.3 A
without
100 / 3 V
110 / 3 V
120 / 3 V


3.3 / 3 kV
6.6 / 3 kV
13.8 / 3 kV


3.6 / 3 kV
7.2 / 3 kV
15 / 3 kV


4.8 / 3 kV
10.0 / 3 kV
17.5 / 3 kV

5.0 / 3 kV
11.0 / 3 kV

6.0 / 3 kV


100 / 3 V
110 / 3 V
120 / 3 V


100 / 3 V
110 / 3 V
120 / 3 V


20 VA / 0.2
50 VA / 0.5
100 VA / 1
Voltage transformer silicon free
Secondary wiring halogen free
Short-duration power-frequency withstand voltage 32 kV 1 min. for 7.2 kV, Standards
GOST
Short-duration power-frequency withstand voltage 42 kV 1 min. for 12 kV, Standards
GOST
Language of name plate German / English
With official certification
With approval
With integral casted primary connection

1) due to current limiting function of fuses not relevant


2) additional ordering code F23
3) only possible in 800 mm panel or in 1000 mm panel 2500 A or 4000 A, additional ordering code F23, truck type design for switching device not possible

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 18 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.10

Surge devices 3EF / 3EK


Type of surge device
Max. operating voltage for limiters

Max. operating voltage for arrestors

Neutral point

2.2.3.11

Limiters 3EF
Arrestors 3EK
3.6 kV
4.8 kV
7.2 kV
12.0 kV
3.6 kV
5.5 kV
7.2 kV
8.25 V
12
15.5
17.5
Compensated or isolated
Solidly earthed
Resistive earthed

Zero sequence transformers 7XR96, UGSS708


Number

Rated secondary current

Core data

2.2.3.12


























1
2
80 mm
120 mm
50 / 1A
60 / 1A
100 / 1 A
1.25 VA, 1 FS10

Specification of withdrawable part 1)


Type of withdrawable part

Mechanism
Auxiliary switch
Mechanical locking devices

for circuit breaker

for disconnecting link

for contactor with 1 fuse per phase, without fused control transformer

for contactor with 2 fuses per phase, without fused control transformer

for contactor with 1 fuse per phase, with fused control transformer 2)

for contactor with 2 fuses per phase, with fused control transformer 2)

Metering with voltage transformers, without fuses

Metering with voltage transformers, with fuses


Manual operated
Motor operated 3)
4NO + 4 NC
With mechanical interlocking of high voltage door
With electromagnetic interlock
With padlock
With key interlocking system, key free in test position









1) withdrawable part on cassette is standard, truck type design as option possible (exception feeder current 3150 A and withdrawable voltage transformers in connection compartment
are excluded)
2) only possible in 7.2 kV version
3) not possible for withdrawable part as disconnector function, metering and for contactor panel

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 19 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.13 Circuit breaker SION (3AE) 12 kV


Ordering number of breaker
Panel data

Breaker data

kV

kA

Busbar Feeder
(A)
(A)

12

25

1250

Width
(mm)

Depth
(mm)
1350 /
1500

630

600

1000

600

1250

800

kV

kA

12

25

800

12

25

1250

12

25 1)

1250

12

25

800

12

25

1250

12

25 1)

1250

12

31.5

2500

12

25 1)

1250

12

31.5

2500

630

600

1000

600

1250

800

2500

1000

1250

800

2500

1000

3150

1000

1540

12

40

3150

1250

800

1500

12

25 1)

1250

2500

1000

12

31.5

2500

3150

1000

12

40

3150

4000

1000

12

40

3150

7
1

2500




3150





4000

630

600

31.5 1250

1000

600

1250

800

2500

1350 /
1500

1500

1540
1350 /
1500

12

31.5

800

12

31.5

1250

12

31.5

1250

12

31.5

800

12

31.5

1250

630

600

1000

600

1250

800

12

31.5

1250

2500

1000

12

31.5

2500

1250

800

2500

1000

3150

1000

1250

800

2500

1000

3150

1000

4000

1000

1250

1250

800

2500

1250

800

2000

3150








4000

40

3150

1350 /
1500

1500

12

31.5

1250

12

31.5

2500

1540

12

40

3150

1500

12

31.5

1250

12

31.5

2500

12

40

3150

12

40

3150

12

40

1250

12

40

1250

800

12

40

2500

2500

1000

12

40

2500

6
2

1540
1500

1250

800

12

40

1250

2000

800

12

40

2500

2500

1000

12

40

2500

3150

1000

1540

12

40

3150

1250

800

1500

12

40

1250

2000

800

12

40

2500

2500

1000

12

40

2500

3150

1000

4000

1000




4000

1500

1540

9.-14.

15 16

12

40

3150

12

40

3150

Standard additional codes for all breakers

Special low voltage connection

Standard additional code for all breakers

Metallic housing of mechnism

Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, with circuit
breakers
breaker tripping signal, 64-pole plug

Additional ordering
code, optionally








Release combinations

Gost-Certification

Secondary wiring halogen free and flame retardent

Silicon free design


1 shunt release
2 shunt releases
1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm
1 shunt release+1 undervoltage release

1) due to temperature rise 31.5 kA breaker is used

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 20 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.13 Circuit breaker SION (3AE) 17.5 kV


Ordering number of breaker
Panel data
kV


kA

17.5 25

Breaker data
Busbar Feeder
(A)
(A)

Depth
(mm)
1350 /
1500

630

600

1000

600

1250

800

1250

Width
(mm)

kV

kA

17,5

25

800

17,5

25

1250

17,5

25 1)

1250

17,5

25

800

17,5

25

1250

17,5

25 1)

1250

17,5

31.5

2500

17,5

25 1)

1250

17,5

31.5

2500

630

600

1000

600

1250

800

2500

1000

1250

800

2500

1000

3150

1000

1540

17,5

40

3150

1250

800

1500

17,5

25 1)

1250

2500

1000

17,5

31.5

2500

3150

1000

17,5

40

3150

4000

1000

17,5

40

3150

7
1

2500




3150





4000

630

600

31.5 1250

1000

600

1250

800

2500

1350 /
1500

1500

1540
1350 /
1500

17,5

31.5

800

17,5

31.5

1250

17,5

31.5

1250

17,5

31.5

800

17,5

31.5

1250

630

600

1000

600

1250

800

17,5

31.5

1250

2500

1000

17.5

31.5

2500

1250

800

2500

1000

3150

1000

1250

800

2500

1000

3150

1000

4000

1000

1250

1250

800

2500

1250

800

2000

1350 /
1500

17,5

31.5

1250

17.5

31.5

2500

1540

17.5

40

3150

1500

17,5

31.5

1250

17.5

31.5

2500

17.5

40

3150

17.5

40

3150

17.5

40

1250

17.5

40

1250

800

17.5

40

2500

2500

1000

17.5

40

2500

1250

800

17.5

40

1250

2000

800

17.5

40

2500

2500

1000

17.5

40

2500

3150

1000

1540

17.5

40

3150

1250

800

1500

17.5

40

1250

2000

800

17.5

40

2500

2500

1000

17.5

40

2500

3150

1000

17.5

40

3150

4000

1000

17.5

40

3150

3150








4000

40

3150




4000

1500

1540
1500

1540

9.-14.

15 16

Standard additional codes for all breakers

Special low voltage connection

Standard additional code for all breakers

Metallic housing of mechnism

MLFB and ordering code for 25/31.5 kA breakers in package 2 frame to


be clarified

Standard version for all 15. position new version: mechanical interlocking, auxiliary switch 12 NO + 12 NC, with circuit
breakers
breaker tripping signal, 64-pole plug

Additional ordering
code, optionally








Release combinations

Gost-Certification

Secondary wiring halogen free and flame retardent

Silicon free design


1 shunt release
2 shunt releases
1 shunt release+1 ct operated release 0,1 Ws / 20 Ohm
1 shunt release+1 undervoltage release

1) due to temperature rise 31.5 kA breaker is used

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 21 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.14 Contactor 3TL 1)


Order nomber














3
3
3

T
T
T

L
L
L

Rated Standard BIL


voltage
kV
kV
phase/phase

6
6
6

2
3
6

3
5
5
1
2

7.2
IEC
60
7.2
GOST
60
12
IEC
75
Auxiliary switch 4NO+3NC
Auxiliary switch 6NO+5NC

PFWV
kV
Open contact
gap
40
40
60

kV
phase/phase
20
32
28

kV
open contact
gap
20
32
28

Without closing latch


With closing latch
AC operating voltage of drive solenoid and closing latch
Fused control transformer secondary voltage 110 V AC 2)
Fused control transformer secondary voltage 230 V AC 2)
1 HVRC fuse per phase, 442 mm length
2 HVRC fuses per phase, 442 mm length

2.2.3.15 Control transformer in contactor panel 2)


Primary voltage (kV)

3.3

3.5

 6
5.5
Secondary voltage (V)

110 V AC
Frequency (Hz)


4.2

4.8

6.3

6.6

6.9

7.2

50

220 V AC

60

2.2.3.16 Fuses motor application of contactor panel


Ur
(kV)

In HV HRC fuse
(A)

Dimension e
(mm)

HV HRC fuse-link
Order no.:

Type

7.2

6,3

192

3000213.6,3

HHD

10

192

3000213.10

HHD

16

192

3000213.16

HHD

20

192

3000213.20

HHD

25

192

3000213.25

HHD

31.5

192

3000213.31.5

HHD

40

192

3000213.40

HHD

50

442

3010853.50

HHM

63

442

3010853.63

HHM

80

442

3010853.80

HHM

100

442

3010853.100

HHM

125

442

3010953.125

HHM

160

442

3010953.160

HHM

200

442

3011054.200

HHM

250

442

3011054.250

HHM

315

442

3011054.315

HHM

6,3 A

292

30 004 13.6.3

HHD

10 A

292

30 004 13.10

HHD

16 A

292

30 004 13.16

HHD

20 A

292

30 004 13.20

HHD

25 A

292

30 004 13.25

HHD

31,5 A

292

30 004 13.31.5

HHD

40 A

292

30 004 13.40

HHD

50 A

442

30 101 53.50

HHM

63 A

442

30 101 53.63

HHM

80 A

442

30 102 53.80

HHM

100 A

442

30 102 53.100

HHM

125 A

442

30 102 53.125

HHM

160

442

30 103 53.160

HHM

12

Required extension tubes for fuses with e < 442 mm



Order no.: SIBA

HV HRC fuse-link with dimension e

3400602

192 mm

3400601

292 mm

1) can be used for motor feeder and transformer feeder (not for transformer incomer),
insulation level of GOST standard for 7.2 kV rated voltage as an option possible,
2) only possible in 7.2 kV version

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 22 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

2.2.3.17 Fuses for withdrawable voltage transformers resp. control transformer of contactor panel




3.

application
Metering panel for busbar metering
Withdrawable voltage transformers at feeder
side
Control transformer in contactor panel 1)

Rated current
6.3 A
6.3 A

fuses 6.3 A include inside voltage transformer housing


fuses 6.3 A include inside voltage transformer housing

3.15 A

Type Bussmann, 3.15 A

Accessories

MLFB No.:

1 2 3 4 5 6 7
- 8 9 10 11 12 - 13 14
Standard accessory set consisting of:
8 B X 2 0 4 2
- 2 T
1 hand crank for charging spring of circuit breaker, 1 Push rod for actuating the
ON/OFF push buttons, 1 Hand lever for moving withdrawable part, 1 Hand lever
for earthing switch, 1 socket spanner for high voltage and low voltage door, 1
operating manual
1 hand crank for charging spring of circuit breaker
8 B X 2 0 4 2
- 2 U
1 Push rod for actuating the ON/OFF push buttons
8 B X 2 0 7 2
1 Hand lever for moving withdrawable part
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
1 Hand lever for earthing switch
8 B X 2 0 4 3
- 1 H
1 Adapter for earthing without withdrawable part
8 B X 2 0 4 3
- 1 G
1 Hand lever for withdrawable voltage transformers
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
1 socket spanner for high voltage door
8 B X 1 6 0 0
1 socket spanner for low voltage door
8 B X 1 6 0 1
1 marking spreading tool for drive-in anchor to fix panel to bottom for seismic
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
version
1 drilling jig for seismic version
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
Endwalls 1Set=2peaces
8 B X 2 0 4 4
- 2 F
Service truck, simplified version, 435 mm panel
8 B X 2 0 4 2
- 2 X A
2)
Service truck , simplified version, 600 mm panel, platform
8 B X 2 0 4 3
- 1 A
Service truck 2), simplified version, 800 / 1000 mm panel, platform
8 B X 2 0 4 3
- 1 B
Service truck device for withdrawable voltage transformers at cable side
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
Hand lever for shutter mechanism (set)
8 B X 2 0 4 2
- 2 F A
Voltage indication device for LRM-System
8 D X 1 6 2 0
Phase comparison measuring instrument for capacitive voltage indication system 8 D X 1 6 0 7
Type EPV-HR (Pfisterer incl. 2 HR-LRM Adapter and transport bag
KP Glow lamp voltage tester with operation rod 12 kV
8 B X 1 6 1 5
KP Glow lamp voltage tester with operation rod 17,5 / 24 kV
8 B X 1 6 1 7
Testing equipment for pressure switch
8 A X 1 0 5 0
Portable earthing device up to 25 kA / 1 s, <= 1000 A
8 B X 2 0 4 3
- 1 E
Portable earthing device up to 25 kA / 1 s, = 1250 A
8 B X 2 0 4 5
Tube of Vaseline (250 g) for connecting coppers
8 B X 2 0 4 1
Can of Longtherm 2 Grease (1 kg) for isolating and mating contacts
8 B X 1 0 2 2
Lubrications for 3AE 180 g of Klber-Isoflex Topas
L32
3 A X 1 1 3 3
- 3 H
1 kg of Klber-Isoflex Topas
L32
3 A X 1 1 3 3
- 3 E
1 kg of Molykote-Fett
3 A X 1 1 3 3
- 2 L
Wall panel for accessories
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
Sealing compound for IP4X (Sikaflex)
8 B X 2 0 4 2
- 2 L
Coupling cable connector 64 pin for connection withdrawable part for function
8 B X 2 0 5 0
- 0 A
tests
Fixing material
8 B X 2 0 6 0
Touch-up paint (1 Kg) for paint damages, colour RAL 7035
8 B X 2 0 0 8
- 0 A
Touch-up pen for minor paint damages, colour RAL 7035
8 B X 2 0 0 7
- 0 A
Spare assembly parts for wiring on site
8 D X 1 6 2 1
to Phoenix Standard terminals, consisting of Type UPCV3K, 12 Bus wiring
terminals, 4 plugs PCC4/6-ST-MTN 1.5-2.5, Type VBST4-FS: 12 Terminals, 4
Modul plugs with sockets, 50 contact sockets (single pins), 50 insulating
coverings
Installation manual German
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
Operation manual German
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
Installation manual English
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
Operation manual English
8 B X 3 3 0 0
- 0 L A 0 0 - 0 A
3)
Additional adapter channels to lead internal arc fault gases outside of switchgear room (quantity of channel parts depends from dimensions of
switchgear room and required channel for both sides lateral or one side lateral or rear side, see also chapter 4.21
pressure relief channel, length 1 m,
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
pressure relief channel for IP4X, length 0,26 m,
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
pressure relief channel, 45 angle up/down
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
pressure relief channel, 45 angle right/left
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
pressure relief channel, length 0.5 m
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
pressure relief channel, flexible length 0.595 to 0,76 m in 20 mm steps
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
pressure relief channel, wall outlet box, length 0.37 m with flap for wall of
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
switchgear room
fixing ledges, (2 pieces)
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A
fixing angles, (2 pieces)
8 B X 3 4 0 0
- 0 A A 0 0 - 0 A

15 16

C 1
C 2

C 0

A
B
A
B

0
0
1
1

A
B
A
A
A
A
A

0
0
1
2
3
4
5

A
A

6
7

1) only possible up to 7.2 kV;


2) not needed, when truck type version is selected
3) to be used when channel system is required from technical data or in combination with IP50/IP51 up to 17.5 kV / <= 31.5 kA, see chapter 1.3,

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 23 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.

Additional tables

4.1

Technical standards
IEC 62271-1

Common clauses for high-voltage switchgear and controlgear standards

VDE 0671 1

Gemeinsame Bestimmungen fr Hochspannungsschaltgerte


IEC 60071 - 1

Insulation co-ordination for equipment in three-phase systems above 1 kV

VDE 0111 - 1

Isolationskoordination fr Betriebsmittel in Drehstromnetzen ber 1 kV


IEC 62271-200

A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up VDE 0670 6
to and including 52 kV
Metallgekapselte Wechselstrom-Schaltanlagen fr Nennspannungen ber 1 kV bis
52 kV

IEC 62271-100

High-voltage alternating current circuit-breakers

VDE 0671-100

Hochspannungs-Wechselstrom-Leistungsschalter
IEC 62271-102

Alternating current disconnectors (isolators) and earthing switches

VDE 0671-102

Wechselstromtrennschalter und Erdungsschalter


IEC 60470

Contactors

VDE 0670-501

Schtze
IEC 62265-1

High voltage alternating current switches

VDE 0671-301

Hochspannungs-Wechselstrom-Lastschalter
IEC 62271-105

High-voltage alternating current switch-fuse combinations

VDE 0671-105

Hochspannungs-Lastschalter-Sicherungskombinationen
IEC 60529

Degree of protection provided by enclosures (IP-code)

VDE 0470 - 1

Schutzarten durch Gehuse (IP-Code)


IEC 61243-5

Working under voltage - Voltage detectors

VDE 0682 - 415

Part 5: Voltage detection systems


Arbeiten unter Spannung - Spannungsprfer Teil 5: Spannungsprfsysteme
IEC 60282 1

Current limiting fuses

VDE 0670 4

Strombegrenzende Sicherungen
IEC 60044 -1

Current transformers

VDE 0414 1

Stromwandler
IEC 60044 -2

Voltage transformers

VDE 0414 2

Spannungswandler
IEC 60721-3-3

Classification of environmental conditions

DIN EN 60721-3-3

Klassifizierung von Umweltbedingungen

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 24 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.2

Technical data

4.2.1

insulation values
Rated voltage

kV

7,2

12

Rated frequency

Hz

50/60

50/60

17.5

Rated short-duration power frequency withstand voltage


Phase/phase, phase/earth, open contact gap 1)

kV

20
32

IEC
GOST 2)

28
42

IEC
GOST 2)

38

IEC

Rated short-duration power frequency withstand voltage


Disconnecting distance 3)

kV

23
36

IEC
GOST 2)

32
48

IEC
GOST 2)

45

IEC

Rated lightning impulse withstand voltage


Phase/phase, phase/earth, open contact gap 1)

kV

60

IEC, GOST 2)

75

IEC, GOST 2) 95

IEC

Rated lightning impulse withstand voltage

kV

70

IEC, GOST 2)

85

IEC, GOST 2) 110

IEC

50/60

Disconnecting distance 3)

4.2.2

short circuit values, dimensions


rated
panel type
voltage

short
circuit
breaking
current

(kV)
(kA)
<=17.5 Switching
25
device
panel
with circuit
breaker
or
disconnecting
link

busbar current 4) feeder current 4)


(A)
(A)
rated busbar
current
(A)
1250

2500

3150

4000

31.5

1250

2500

3150

4000

40

1250
2500

3150

4000

rated
rated
current breaker
current
(A)
(A)
630
800
1000
1250
1250
1250
630
800
1000
1250
1250
1250
2500
2500
1250
1250
2500
2500
3150
3150
1250
1250
2500
2500
3150
3150
4000
3150
630
800
1000
1250
1250
1250
630
800
1000
1250
1250
1250
2500
2500
1250
1250
2500
2500
3150
3150
1250
1250
2500
2500
3150
3150
4000
3150
1250
1250
1250
1250
2000
2500
2500
2500
1250
1250
2000
2500
2500
2500
3150
3150
1250
1250
2000
2500
2500
2500
3150
3150
4000
3150

rated
panel
current
(A)
630
1000
1250
630
1000
1250
2500
1250
2500
3150
1250
2500
3150
4000
630
1000
1250
630
1000
1250
2500
1250
2500
3150
1250
2500
3150
4000
1250
1250
2000
2500
1250
2000
2500
3150
1250
2000
2500
3150
4000

width

depth

Height 5)

closed

(mm)
600

(mm)
1350 6)

2300

closed

800
600

panel design

natural ventilated
natural ventilated
forced ventilated
closed

800
1000
800
1000
1000
800
1000
1000
1000
600

closed

800
600

natural ventilated
natural ventilated
natural ventilated

natural ventilated
natural ventilated
natural ventilated
natural ventilated
natural ventilated
forced ventilated
closed

natural ventilated
closed
natural ventilated
natural ventilated
closed
natural ventilated
natural ventilated
forced ventilated

800
1000
800
1000
1000
800
1000
1000
1000
800
800
800
1000
800
800
1000
1000
800
800
1000
1000
1000

1500 7)
1540 8)
1500 7)
1540 8)
1350 6)

1500 7)
1540 8)
1500 7)
1540 8)
1500 7)

1540 8)
1500 7)

1540 8)

1) for 7.2 kV contactor panel version: 60 kV phase/phase, phase earth, 40 kV open contact gap, 20 kV phase/phase, phase/earth, open contact gap for 12 kV version, 75 kV phase/phase,
phase earth, 60 kV open contact gap, 28 kV phase/phase, phase/earth, open contact gap
2) GOST = Russian standard
3) due to partition class PM not applicable
4) permissible current values depending from ambient temperature, frequency etc. see tables in chapter 4.10
5) standard height 2300 mm, 2350 mm with extended low voltage box or busbar voltage transformers resp. busbar earthing switch, 2450 mm for panels with forced ventilation (4000 A ),
2500 mm for panels with absorbers <= 17.5 kV / <= 31.5 kA
6) 1350 mm when standard block type cts, 1500 mm when extended block type cts are used, when rear side cable connection from above additional 600 mm in depth for duct
7) 1500 mm with standard block type cts, when rear side cable connection from above additional 600 mm in depth for duct
8) 1540 mm with standard block type cts, 1650 mm when extended block type cts are used, when rear side cable connection from above additional 600 mm in depth for duct

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 25 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.2.3

short circuit values, dimensions


short
circuit
breaking
current

busbar current 1) feeder current 1)


(A)
(A)

(kV)

(kA)

(A)

<=17.5 Contactor
panel 3)

=< 31.5

1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
3150
4000
3150
4000
1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
2500
3150
4000
1250
2500
3150

panel type
rated
voltage

40

Metering
panel

<= 31.5

<= 40

Busbar
current
metering
panel

Bus
sectionalizer
type I
consisting of:
switching
device panel
and
bus riser
panel with
disconnector
module

<= 31.5
<= 40

25

31.5

40

Bus
25
sectionalizer
type II
consisting of:
switching
device panel 31.5
and
bus riser
panel
optionally with
metering
40
module

Busbar
connecting
panel

25

31.5

40

rated busbar
current

rated
rated
current breaker
current
(A)
(A)
<= 400 400
<= 400 400
<= 400 400
<= 400 400
<= 400 400
<= 400 400
<= 400 400
<= 400 400
-

rated
panel
current
(A)
400
400
400
400
400
400
400
400
-

width

depth

height 2)

(mm)

(mm)

(mm)

435
435
435
435
435
435
435
435
800

1400

2300

panel design

closed
closed
closed
closed
closed
closed
closed
closed
closed

1500
1500

1350
1500

closed

800

1500

800

1500

800

1500

1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000
1250
2500
3150

1250
2500
3150
3150
1250
2500
3150
3150
1250
2500
2500
3150
3150
1250
2500
3150

1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000
1250
2500
3150

natural ventilated
natural ventilated
closed
closed
natural ventilated
natural ventilated
closed
natural ventilated
natural ventilated
forced ventilated
closed
natural ventilated
natural ventilated
forced ventilated
closed
closed
natural ventilated
natural ventilated
forced ventilated
closed
natural ventilated
natural ventilated

2x800
2x1000
2x1000
2x1000
2x800
2x1000
2x1000
2x1000
2x800
2x800
2x1000
2x1000
2x1000
2x800
1x1000+1x800
2x1000

1350

4000

4000

3150

4000

forced ventilated

2x1000

1250

1250

1250

1250

closed

2x800

2500

2500

2500

2500

natural ventilated

1x1000+1x800

3150

3150

3150

3150

natural ventilated

2x1000

4000

4000

3150

4000

forced ventilated

2x1000

1250
2500

1250
2000

1250
2500

1250
2000

closed
closed

2x800
2x800

2500

2500

2500

2500

natural ventilated

1x1000+1x800

3150

3150

3150

3150

natural ventilated

2x1000

4000

4000

3150

4000

forced ventilated

2x1000

1250
2500
3150
4000
1250
2500
3150
4000
1250
2500
2500
3150
4000

1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000

1250
2500
3150
4000
1250
2500
3150
4000
1250
2000
2500
3150
4000

closed

800
800
1000
1000
800
800
1000
1000
800
800
800
1000
1000

1540
1350
1540
1500

1540
1350
1540
1350
1540
1500

1540
1350
1540
1350
1540
1500

1540

1) permissible current values depending from ambient temperature, frequency etc. see tables in chapter 4.10
2) standard height 2300 mm, 2350 mm with extended low voltage box or busbar voltage transformers resp. busbar earthing switch, 2450 mm for panels with forced ventilation
(4000 A ), 2500 mm for panels with absorbers <= 17.5 kV / <= 31.5 kA
3) for 7.2 kV contactor panel version: 60 kV phase/phase, phase earth, 40 kV open contact gap, 20 kV phase/phase, phase/earth, open contact gap for 12 kV version, 75 kV phase/phase,
phase earth, 60 kV open contact gap, 28 kV phase/phase, phase/earth, open contact gap
generally contactor panels can be used for motor feeder and transformer feeder (not for transformer incomer)

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 26 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.2.4

dimensions of switchgear room


Height

Distances

aisles

4.3

with pressure release channel to


lead gases outside 1)

<= 17.5 kV / <= 40 kA 1s or 0.1 s

mm

>= 2500

without pressure release channel


to lead gases outside (with
absorbers)

<= 12 kV / <= 25 kA 1s or 0.1 s

mm

>= 2800

<= 12 kV / 31.5 kA 1s or 0.1 s

mm

>= 3000

<= 12 kV / 40 kA 1s or 0.1 s

mm

>= 3500

<= 17.5 kV / <= 31.5 kA 1s or 0.1 s

mm

>= 3500

<= 17.5 kV / 40 kA 1s or 0.1 s

mm

>= 3500

behind switchgear to wall, cable connection from front (minimum)

mm

>= 150

behind switchgear to wall, cable connection from rear (minimum)

mm

> = 500

beside switchgear to wall, (minimum)

mm

> = 150 at one side of switchgear row, >= 100


for contactor panel,
when pressure release duct is used at least at
one opposite side of switchgear row >= 500
mm

for operating in front of switchgear

mm

>= 1250

for panel replacement

mm

>= 1750

Loss of service continuity class


For feeders with withdrawable parts

4.4

LSC 2B (metal clad design)

Partition class
For feeders with withdrawable parts

4.5

PM (metal clad design)

Internal arc fault classification


Standard design

IAC = internal arc classification


A = 300 mm distance of indicators,
F/L/R accessibility from F = front, L = lateral and R = rear,
40 kA = short circuit current of switchgear,
1 s = duration of tested arc fault current
(versions of pressure relief system see table in chapter 1.3, special duct devices see also in chapter
3, accessories)

Optional design

Additionally with pressure switch system without testing device, duration 0.1 s
Additionally with pressure switch system with testing device, duration 0.1 s
Additionally with optical system, duration 0.1 s

Additionally to Standard IEC 62271-200

4.6

Degree of protection
enclosure

Standard IP 3X D

partitions

4.7

Confinement of internal arc within a compartment (pressure tight partitions up to 17.5 kV/31.5
kA/2500A)

optional

IP 4X

optional

IP 50, (only for non ventilated panels, and in combination with additional pressure relief channel to
lead the gases outside the switchgear room)

optional

IP 51, (only for non ventilated panels, and in combination with additional pressure relief channel to
lead the gases outside the switchgear room)

Standard IP 2X

Creepage distances, clearances in air


contactor panel

circuit breaker panel and others typicals

435 mm panel

600 mm panel, <= 630 A

600 mm panel, 1000 A

800 mm panel, 1250 A

800 and 1000 mm


panel, >= 2500 A, <=
4000 A

phase to phase

>= 55 mm

on request

on request

>= 110 mm

>= 90 mm

phase to earth

>= 55 mm

on request

on request

>=80 mm

>= 80 mm

creepage distance

on request

on request

on request

>= 220 mm

>= 220 mm

A main benefit of type tested switchgear in accordance to IEC 62271-200 is saving space in order to minimize volume of switchgear room. NXAIR
switchgear are type tested and fulfill the following requirements with required values as shown in table 4.1, such as:
rated short-duration power frequency withstand voltage, Phase/phase, phase/earth, open contact gap,
rated short-duration power frequency withstand voltage, Disconnecting distance
rated lightning impulse withstand voltage, Phase/phase, phase/earth, open contact gap
rated lightning impulse withstand voltage, Disconnecting distance
Due to this special dimensions between phases and to earth are no criteria for quality of isolation capacity. Important criteria are only fulfilling the
required test values.

1) generally needed for 40 kA internal arc current value

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 27 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.8

Type tests in accordance to IEC 62271-1 resp. IEC 62271-200


Following type tests will be carried out mandatory:
chapter

Type test

6.2

Test to verify the insulation level of main circuits and low voltage circuits
test values:
Rated lightning impulse withstand voltage depending form rated voltage of switchgear, see also 4.2.1
rated short duration power frequency withstand voltage depending from rated voltage, see also 4.2.1

6.4, 6.5

Tests to prove temperature rise of any part of equipment and measurement of the resistance of circuits
test values:
rated current of busbar and feeder, maximum temperature rise values for main parts depending from material of contacts and
materials based on 40C ambient temperature:
silver coated contacts: temperature rise 65C K
bolted connections bare copper: temperature rise 50C K
bolted connections silver-coated copper: temperature rise 75C K
materials used as insulation: temperature rise 50C K
accessible parts of enclosure: temperature rise 40C K

6.6

Tests to prove capability of the main circuits and earthing circuits


test values:
short time withstand current for 1 or 3 s, see also 4.2.1, multiplied with 2.5 = peak withstand current for 50 Hz applications
short time withstand current for 1 or 3 s, see also 4.2.1, multiplied with 2.6 = peak withstand current for 60 Hz applications

6.101

Tests to prove the making and breaking capacity of the included devices
test values:
short circuit breaking current, see also 4.2.1, multiplied with 2.5 = short circuit making current for 50 Hz applications
short circuit breaking current, see also 4.2.1, multiplied with 2.6 = peak circuit making current for 60 Hz applications

6.102

Tests to prove satisfactory operation of the included switching devices and removable parts
test values:
1000 mechanical cycle for withdrawable part and earthing switch

6.7

Test to verify the protection of persons against access to hazardous parts and the protection of the equipment against solid foreign
objects
test values: IP2X, IP3X D, IP 4X; IP50, IP51 depending from version

Following type tests will be carried out generally ( in standard required mandatory, where applicable):

4.9

6.106

Test to verify internal arc classification


test values: IAC A FLR Isc 1s or 0.1 s, see also 4.5

6.9

Test to verify electromagnetic compatibility (EMC)

Routine tests in accordance to IEC 62271-1 resp. IEC 62271-200


Following routine tests will be carried out:
7.1

Dielectric test with power frequency voltage of main circuits


test values:
rated short duration power frequency withstand voltage depending from rated voltage, see also 4.2.1

7.2

Dielectric test of auxiliary circuits


test values: 1 kV, 1 s

7.5

Design and visual checks

7.102

Mechanical operation tests

7.104

Test of auxiliary devices, verification of the correct wiring

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 28 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.10

NXAIR, <= 12 kV, 50 Hz, 25/31.5 kA, <= 2500 A, permissible current values

Rated
voltage

freShort
busbar width panel version
qucircuit insulaency current tion

(kV)

(Hz)

(kA)

<= 12

50

<= 25

degree panel
of protection

panel cb

(A)

(A)

30

35

40

45

50

IP3X D/ closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

1000 1250 1105 1065 1000 985

945

900

1250 1355 1310 1250 1210 1160 1105

(mm)
without 600

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A /C)
(A / C)
(A /C)

busbar

(A /C)

55

(A)

30

630

1250 1355 1310 1250 1210 1160 1105

35

40

45

50

55

2500 2685 2595 2500 2400 2300 2195


2500 2685 2595 2500 2400 2300 2195

800

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent

1250 1250 1355 1310 1250 1210 1160 1105 1250 1355 1310 1250 1210 1160 1105
2500 2685 2595 2500 2400 2300 2195

2400 2500 2610 2520 2430 2335 2235 2130 2500 2685 2595 2500 2400 2300 2195
2500 2500 2685 2595 2500 2400 2300 2195 2500 2685 2595 2500 2400 2300 2195

IP4X

nat. vent

2400 2500 2490 2410 2320 2230 2135 2035 2500 2685 2595 2500 2400 2300 2195
2500 2500 2550 2465 2375 2280 2185 2085 2500 2685 2595 2500 2400 2300 2195

31.5

without 600

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1355 1310 1250 1210 1160 1105

1000 1250 1105 1065 1000 1000 1000 990

1250 1355 1310 1250 1210 1160 1105

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1355 1310 1250 1210 1160 1105 1250 1355 1310 1250 1215 1160 1110

2500 2685 2595 2500 2400 2300 2195


2500 2685 2595 2500 2400 2300 2195

800

2500 2685 2590 2500 2400 2295 2190

1000 IP3X D nat. vent. 2400 2500 2610 2520 2430 2335 2235 2130 2500 2685 2595 2500 2400 2300 2195
2500 2500 2685 2595 2500 2400 2300 2195 2500 2685 2595 2500 2400 2300 2195
IP4X

nat. vent. 2400 2500 2490 2410 2320 2230 2135 2035 2500 2685 2595 2500 2400 2300 2195
2500 2500 2550 2465 2375 2280 2185 2085 2500 2685 2595 2500 2400 2300 2195

<= 25

with

600

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1345 1300 1250 1205 1150 1100

1000 1250 1095 1060 1000 980

940

895

1250 1345 1300 1250 1205 1150 1100

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1345 1300 1250 1205 1150 1100 1250 1345 1300 1250 1205 1150 1100

2500 2630 2540 2450 2355 2255 2150


2500 2630 2540 2450 2355 2255 2150

800

2500 2630 2540 2450 2355 2255 2150

1000 IP3X D nat. vent. 2400 2500 2565 2475 2385 2295 2195 2095 2500 2630 2540 2450 2355 2255 2150
2500 2500 2630 2540 2450 2355 2255 2150 2500 2630 2540 2450 2355 2255 2150
IP4X

nat. vent. 2400 2500 2435 2350 2265 2180 2085 1990 2500 2630 2540 2450 2355 2255 2150
2500 2500 2500 2410 2330 2240 2140 2040 2500 2630 2540 2450 2355 2255 2150

31.5

with

600

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1345 1300 1250 1205 1150 1100

1000 1250 1095 1060 1000 1000 1000 980

1250 1345 1300 1250 1205 1150 1100

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1345 1300 1250 1205 1150 1100 1250 1345 1300 1250 1205 1150 1100

2500 2630 2540 2450 2355 2255 2150


2500 2630 2540 2450 2355 2255 2150

800

2500 2630 2540 2450 2355 2255 2150

1000 IP3X D nat. vent. 2400 2500 2565 2475 2385 2295 2195 2095 2500 2630 2540 2450 2355 2255 2150
2500 2500 2630 2540 2450 2355 2255 2150 2500 2630 2540 2450 2355 2255 2150
IP4X

nat. vent. 2400 2500 2435 2350 2265 2180 2085 1990 2500 2630 2540 2450 2355 2255 2150
2500 2500 2500 2410 2330 2240 2140 2040 2500 2630 2540 2450 2355 2255 2150

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 29 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.10

NXAIR, <= 12 kV, 60 Hz, 25 / 31.5 kA, <= 2500 A, permissible current values

Rated
voltage

freShort
busbar width panel version
qucircuit insulaency current tion

(kV)

(Hz)

(kA)

<= 12

60

<= 25

degree panel
of pro- version
tection

panel cb

(A)

(A)

30

35

40

45

50

IP3X D/ closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

1000 1250 1080 1045 1000 965

925

880

1250 1325 1280 1210 1180 1135 1080

(mm)
without 600

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A /C)
(A / C)
(A /C)

busbar

(A /C)

55

(A)

30

630

1250 1325 1280 1210 1180 1135 1080

35

40

45

50

55

2500 2615 2525 2435 2335 2240 2135

2500 2615 2525 2435 2335 2240 2135


800

IP3X D/ closed
IP4X,
IP50,
IP51

1250 1250 1325 1280 1210 1180 1135 1080 1250 1325 1280 1210 1180 1135 1080
2500 2615 2525 2435 2335 2240 2135

1000 IP3X D natural


2400 2500 2545 2460 2370 2275 2180 2080 2500 2615 2525 2435 2335 2240 2135
ventilated 2500 2500 2615 2525 2435 2335 2240 2135 2500 2615 2525 2435 2335 2240 2135
IP4X
31.5

without 600

natural
2400 2500 2420 2340 2250 2160 2070 1975 2500 2615 2525 2435 2335 2240 2135
ventilated 2500 2500 2485 2400 2315 2220 2130 2030 2500 2615 2525 2435 2335 2240 2135

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1325 1280 1210 1180 1135 1080

1000 1250 1105 1065 1000 1000 1000 970

1250 1325 1280 1210 1180 1135 1080

2500 2615 2525 2435 2335 2240 2135


2500 2615 2525 2435 2335 2240 2135

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1325 1280 1210 1180 1135 1080 1250 1325 1280 1210 1180 1135 1080
2500 2615 2525 2435 2335 2240 2135

1000 IP3X D natural


2400 2500 2545 2460 2370 2275 2180 2080 2500 2615 2525 2435 2335 2240 2135
ventilated 2500 2500 2615 2525 2435 2335 2240 2135 2500 2615 2525 2435 2335 2240 2135
IP4X
<= 25

with

600

natural
2400 2500 2420 2340 2250 2160 2070 1975 2500 2615 2525 2435 2335 2240 2135
ventilated 2500 2500 2485 2400 2315 2220 2130 2030 2500 2615 2525 2435 2335 2240 2135

IP3X D / closed
IP4X,
IP50,
IP51
closed

630

800

675

655

630

630

630

630

1250 1305 1260 1215 1165 1115 1065

1000 1250 1075 1035 1000 960

920

875

1250 1305 1260 1215 1165 1115 1065

2500 2560 2470 2385 2290 2190 2090


2500 2560 2470 2385 2290 2190 2090

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1315 1270 1210 1180 1125 1075 1250 1305 1260 1215 1165 1115 1065
2500 2560 2470 2385 2290 2190 2090

1000 IP3X D natural


2400 2500 2495 2410 2320 2230 2135 2035 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2560 2470 2385 2290 2190 2090 2500 2560 2470 2385 2290 2190 2090
IP4X
31.5

with

600

natural
2400 2500 2370 2290 2205 2120 2030 1935 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2430 2345 2265 2175 2080 1985 2500 2560 2470 2385 2290 2190 2090

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1305 1260 1215 1165 1115 1065

1000 1250 1075 1035 1000 1000 1000 960

1250 1305 1260 1215 1165 1115 1065

2500 2560 2470 2385 2290 2190 2090


2500 2560 2470 2385 2290 2190 2090

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1315 1270 1210 1175 1125 1075 1250 1305 1260 1215 1165 1115 1065
2500 2560 2470 2385 2290 2190 2090

1000 IP3X D natural


2400 2500 2495 2410 2320 2230 2135 2035 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2560 2470 2385 2290 2190 2090 2500 2560 2470 2385 2290 2190 2090
IP4X

IC LMV MV1 PPM, Herbert Soens

natural
2400 2500 2370 2290 2205 2120 2030 1935 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2430 2345 2265 2175 2080 1985 2500 2560 2470 2385 2290 2190 2090

issued: 24.10.2011

- 30 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.10

NXAIR, 17.5 kV, 50 Hz, 25 / 31.5 kA, <= 2500 A, permissible current values

Rated
voltage

freShort
busbar width panel version
qucircuit insulaency current tion

(kV)

(Hz)

(kA)

<= 17.5

50

<= 25

degree panel
of pro- version
tection

panel cb

(A)

(A)

30

35

40

45

50

IP3X D/ closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

1000 1250 1105 1065 1000 985

945

900

1250 1355 1310 1250 1210 1160 1105

(mm)
without 600

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A /C)
(A / C)
(A /C)

busbar

(A /C)

55

(A)

30

630

1250 1355 1310 1250 1210 1160 1105

35

40

45

50

55

2500 2630 2540 2450 2355 2255 2150


2500 2630 2540 2450 2355 2255 2150

800

IP3X D/ closed
IP4X,
IP50,
IP51

1250 1250 1355 1310 1250 1210 1160 1105 1250 1355 1310 1250 1210 1160 1105
2500 2630 2540 2450 2355 2255 2150

1000 IP3X D natural


2400 2500 2565 2475 2385 2295 2195 2095 2500 2630 2540 2450 2355 2255 2150
ventilated 2500 2500 2630 2540 2450 2355 2255 2150 2500 2630 2540 2450 2355 2255 2150
IP4X
31.5

without 600

2400 2500 2435 2350 2265 2180 2085 1990 2500 2630 2540 2450 2355 2255 2150
natural
ventilated 2500 2500 2500 2410 2330 2240 2140 2040 2500 2630 2540 2450 2355 2255 2150

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

655

630

630

630

630

630

1250 1355 1310 1250 1210 1160 1105

1000 1250 1105 1065 1000 1000 1000 990

1250 1355 1310 1250 1210 1160 1105

2500 2630 2540 2450 2355 2255 2150


2500 2630 2540 2450 2355 2255 2150

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1355 1310 1250 1210 1160 1105 1250 1355 1310 1250 1210 1160 1105
2500 2630 2540 2450 2355 2255 2150

1000 IP3X D natural


2400 2500 2565 2475 2385 2295 2195 2095 2500 2630 2540 2450 2355 2255 2150
ventilated 2500 2500 2630 2540 2450 2355 2255 2150 2500 2630 2540 2450 2355 2255 2150
IP4X
<= 25

with

600

natural
2400 2500 2435 2350 2265 2180 2085 1990 2500 2630 2540 2450 2355 2255 2150
ventilated 2500 2500 2500 2410 2330 2240 2140 2040 2500 2630 2540 2450 2355 2255 2150

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1345 1300 1250 1205 1150 1100

1000 1250 1095 1060 1000 980

940

895

1250 1345 1300 1250 1205 1150 1100

2500 2630 2540 2450 2355 2255 2150


2500 2630 2540 2450 2355 2255 2150

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1345 1300 1250 1205 1150 1100 1250 1345 1300 1250 1205 1150 1100
2500 2630 2540 2450 2355 2255 2150

1000 IP3X D natural


2400 2500 2565 2475 2385 2295 2195 2095 2500 2630 2540 2450 2355 2255 2150
ventilated 2500 2500 2630 2540 2450 2355 2255 2150 2500 2630 2540 2450 2355 2255 2150
IP4X
31.5

with

600

natural
2400 2500 2435 2350 2265 2180 2085 1990 2500 2630 2540 2450 2355 2255 2150
ventilated 2500 2500 2500 2410 2330 2240 2140 2040 2500 2630 2540 2450 2355 2255 2150

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1345 1300 1250 1205 1150 1100

1000 1250 1095 1060 1000 1000 1000 980

1250 1345 1300 1250 1205 1150 1100

2500 2630 2540 2450 2355 2255 2150


2500 2630 2540 2450 2355 2255 2150

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1345 1300 1250 1205 1150 1100 1250 1345 1300 1250 1205 1150 1100
2500 2630 2540 2450 2355 2255 2150

1000 IP3X D natural


2400 2500 2565 2475 2385 2295 2195 2095 2500 2630 2540 2450 2355 2255 2150
ventilated 2500 2500 2630 2540 2450 2355 2255 2150 2500 2630 2540 2450 2355 2255 2150
IP4X

IC LMV MV1 PPM, Herbert Soens

natural
2400 2500 2435 2350 2265 2180 2085 1990 2500 2630 2540 2450 2355 2255 2150
ventilated 2500 2500 2500 2410 2330 2240 2140 2040 2500 2630 2540 2450 2355 2255 2150

issued: 24.10.2011

- 31 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.10

NXAIR, 17.5 kV, 60 Hz, 25 / 31.5 kA, <= 2500 A, permissible current values

Rated
voltage

freShort
busbar width panel version
qucircuit insulaency current tion

(kV)

(Hz)

(kA)

<= 17.5

60

<= 25

degree panel
of pro- version
tection

panel cb

(A)

(A)

30

35

40

45

50

IP3X D/ closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

1000 1250 1080 1045 1000 965

925

880

1250 1325 1280 1210 1180 1135 1080

(mm)
without 600

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A /C)
(A / C)
(A /C)

busbar

(A /C)

55

(A)

30

630

1250 1325 1280 1210 1180 1135 1080

35

40

45

50

55

2500 2560 2470 2385 2290 2190 2090

2500 2560 2470 2385 2290 2190 2090


800

IP3X D/ closed
IP4X,
IP50,
IP51

1250 1250 1325 1280 1210 1180 1135 1080 1250 1325 1280 1210 1180 1135 1080
2500 2560 2470 2385 2290 2190 2090

1000 IP3X D natural


2400 2500 2495 2410 2320 2230 2135 2035 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2560 2470 2385 2290 2190 2090 2500 2560 2470 2385 2290 2190 2090
IP4X
31.5

without 600

natural
2400 2500 2370 2290 2205 2120 2030 1935 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2430 2345 2265 2175 2080 1985 2500 2560 2470 2385 2290 2190 2090

IP3X D / closed
IP4X,
IP50,
IP51
closed

630

800

675

655

630

630

630

630

1250 1325 1280 1210 1180 1135 1080

1000 1250 1075 1035 1000 1000 1000 960

1250 1325 1280 1210 1180 1135 1080

2500 2560 2470 2385 2290 2190 2090


2500 2560 2470 2385 2290 2190 2090

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1315 1270 1210 1175 1125 1075 1250 1325 1280 1210 1180 1135 1080
2500 2560 2470 2385 2290 2190 2090

1000 IP3X D natural


2400 2500 2495 2410 2320 2230 2135 2035 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2560 2470 2385 2290 2190 2090 2500 2560 2470 2385 2290 2190 2090
IP4X
<= 25

with

600

natural
2400 2500 2370 2290 2205 2120 2030 1935 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2430 2345 2265 2175 2080 1985 2500 2560 2470 2385 2290 2190 2090

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1305 1260 1215 1165 1115 1065

1000 1250 1075 1035 1000 960

920

875

1250 1305 1260 1215 1165 1115 1065

2500 2560 2470 2385 2290 2190 2090


2500 2560 2470 2385 2290 2190 2090

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1315 1270 1210 1175 1125 1075 1250 1305 1260 1215 1165 1115 1065
2500 2560 2470 2385 2290 2190 2090

1000 IP3X D natural


2400 2500 2495 2410 2320 2230 2135 2035 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2560 2470 2385 2290 2190 2090 2500 2560 2470 2385 2290 2190 2090
IP4X
31.5

with

600

natural
2400 2500 2370 2290 2205 2120 2030 1935 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2430 2345 2265 2175 2080 1985 2500 2560 2470 2385 2290 2190 2090

IP3X D / closed
IP4X,
IP50,
closed
IP51

630

800

675

655

630

630

630

630

1250 1305 1260 1215 1165 1115 1065

1000 1250 1075 1035 1000 1000 1000 960

1250 1305 1260 1215 1165 1115 1065

2500 2560 2470 2385 2290 2190 2090


2500 2560 2470 2385 2290 2190 2090

800

IP3X D / closed
IP4X,
IP50,
IP51

1250 1250 1315 1270 1210 1175 1125 1075 1250 1305 1260 1215 1165 1115 1065
2500 2560 2470 2385 2290 2190 2090

1000 IP3X D natural


2400 2500 2495 2410 2320 2230 2135 2035 2500 2560 2470 2385 2290 2190 2090
ventilated 2500 2500 2560 2470 2385 2290 2190 2090 2500 2560 2470 2385 2290 2190 2090
IP4X

IC LMV MV1 PPM, Herbert Soens

2400 2500 2370 2290 2205 2120 2030 1935 2500 2560 2470 2385 2290 2190 2090
natural
ventilated 2500 2500 2430 2345 2265 2175 2080 1985 2500 2560 2470 2385 2290 2190 2090

issued: 24.10.2011

- 32 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.11 NXAIR, <= 12 kV, 50 Hz, 40 kA, <= 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated freShort
busbar width panel version
voltage qucircuit insulaency current tion
degree panel
of pro- version
tection
(kV)

(Hz)

(kA)

<= 12

50

25

(mm)
with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A / C)
(A /C)
panel cb

(A /C)

(A)

30

(A)

35

40

45

50

55

busbar

(A /C)

(A)

30

35

40

45

50

55

1250 1250 1345 1300 1250 1205 1150 1100 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

2400 2500 2610 2520 2430 2335 2235 2130 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2685 2595 2500 2400 2300 2195 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3295 3185 3070 2950 2825 2690 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

1000 IP4X

forc. vent.1)

4000 3150 4000 4000 4000 3945 3775 3600 4000 4665 4525 4380 4235 4080 3920

nat. vent.

2400 2500 2490 2410 2320 2230 2135 2035 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2550 2465 2375 2280 2185 2085 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3130 3025 2915 2805 2680 2555 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

forc. vent.1)
31.5

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

4000 3150 4000 4000 3900 3750 3590 3420 4000 4665 4525 4380 4235 4080 3920
1250 1250 1345 1300 1250 1205 1150 1100 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

2400 2500 2610 2520 2430 2335 2235 2130 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2685 2595 2500 2400 2300 2195 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3305 3190 3075 2955 2830 2695 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

1000 IP4X

forc. vent.1)

4000 3150 4000 4000 4000 3915 3750 3575 4000 4665 4525 4380 4235 4080 3920

nat. vent.

2400 2500 2490 2410 2320 2230 2135 2035 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2550 2465 2375 2280 2185 2085 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3130 3025 2915 2805 2680 2555 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

forc. vent.1)
40

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

4000 3150 4000 4000 3900 3750 3590 3420 4000 4665 4525 4380 4235 4080 3920
1250 1250 1430 1385 1320 1255 1180 1105 1250 1350 1310 1270 1225 1180 1135
2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2000 2500 1885 1805 1720 1635 1540 1440 2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

1000 IP3X D nat. vent.

2500 2500 2720 2630 2535 2405 2270 2120 2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3295 3185 3070 2950 2825 2690 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

IP4X

forc. vent.1)

4000 4000 4000 4000 4000 3945 3775 3600 4000 4665 4525 4380 4235 4080 3920

natural
ventilated

2500 2500 2580 2500 2405 2280 2155 2010 2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3130 3025 2915 2805 2680 2555 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

forc. vent.1)

4000 3150 4000 4000 3900 3750 3590 3420 4000 4665 4525 4380 4235 4080 3920

1) standard version current relais controlled, optionally current relais controlled and redundant version

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 33 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.11 NXAIR, <= 12 kV, 60 Hz, 40 kA, <= 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated freShort
busbar width panel version
voltage qucircuit insulaency current tion
degree panel
of pro- version
tection
(kV)

(Hz)

(kA)

<=12

60

25

(mm)
with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A / C)
(A /C)
panel cb

(A /C)

(A)

30

(A)

35

40

45

50

55

busbar

(A /C)

(A)

30

35

40

45

50

55

1250 1250 1315 1270 1210 1180 1125 1075 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

2400 2500 2545 2460 2370 2275 2180 2080 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2615 2525 2435 2335 2240 2135 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3230 3125 3005 2890 2765 2640 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

forced vent.1 4000 3150 4000 4000 4000 3850 3685 3510 4000 4520 4385 4245 4100 3950 3795
1000 IP4X

nat. vent.

2400 2500 2420 2340 2250 2160 2070 1975 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2485 2400 2315 2220 2130 2030 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3070 2965 2855 2745 2630 2505 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

forced vent.1 4000 3150 4000 3945 3805 3655 3500 3335 4000 4520 4385 4245 4100 3950 3795
31.5

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

1250 1250 1315 1270 1210 1175 1125 1075 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

2400 2500 2545 2460 2370 2275 2180 2080 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2615 2525 2435 2335 2240 2135 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3230 3125 3005 2890 2765 2640 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

1000 IP4X

forc. vent.1)

4000 3150 4000 4000 4000 3850 3685 3510 4000 4520 4385 4245 4100 3950 3795

nat. vent.

2400 2500 2420 2340 2250 2160 2070 1975 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2485 2400 2315 2220 2130 2030 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3070 2965 2855 2745 2630 2505 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

forc. vent.1)
40

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

4000 3150 4000 3945 3805 3655 3500 3335 4000 4520 4385 4245 4100 3950 3795
1250 1250 1410 1365 1305 1240 1170 1195 1250 1350 1310 1270 1225 1180 1135
2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2000 2500 1805 1730 1650 1565 1475 1380 2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

1000 IP3X D nat. vent.

2500 2500 2645 2560 2455 2325 2195 2050 2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3230 3125 3005 2890 2765 2640 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

IP4X

forc. vent.1)

4000 4000 4000 4000 4000 3850 3685 3510 4000 4520 4385 4245 4100 3950 3795

natural
ventilated

2500 2500 2510 2430 2330 2205 2085 1945 2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3070 2965 2855 2745 2630 2505 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

forc. vent.1)

4000 3150 4000 3945 3805 3655 3500 3335 4000 4520 4385 4245 4100 3950 3795

1) standard version current relais controlled, optionally current relais controlled and redundant version

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 34 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.11 NXAIR, 17.5 kV, 50 Hz, 40 kA, <= 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated freShort
busbar width panel version
voltage qucircuit insulaency current tion
degree panel
of pro- version
tection
(kV)

(Hz)

(kA)

17.5

50

25

(mm)
with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A / C)
(A /C)
panel cb

(A /C)

(A)

30

(A)

35

40

45

50

55

busbar

(A /C)

(A)

30

35

40

45

50

55

1250 1250 1345 1300 1250 1205 1150 1100 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

2400 2500 2565 2475 2385 2295 2195 2095 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2630 2540 2450 2355 2255 2150 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3235 3125 3010 2895 2770 2640 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

1000 IP4X

forc. vent.1)

4000 3150 4000 4000 4000 3870 3705 3530 4000 4665 4525 4380 4235 4080 3920

nat. vent.

2400 2500 2435 2350 2265 2180 2085 1990 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2500 2410 2330 2240 2140 2040 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3070 2965 2855 2750 2630 2505 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

forc. vent.1)
31.5

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

4000 3150 4000 4000 3820 3675 3515 3330 4000 4665 4525 4380 4235 4080 3920
1250 1250 1345 1300 1250 1205 1150 1100 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

2400 2500 2565 2475 2385 2295 2195 2095 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2630 2540 2450 2355 2255 2150 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3235 3125 3010 2895 2770 2640 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

1000 IP4X

forc. vent.1)

4000 3150 4000 4000 4000 3870 3705 3530 4000 4665 4525 4380 4235 4080 3920

nat. vent.

2400 2500 2435 2350 2265 2180 2085 1990 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2500 2500 2500 2410 2330 2240 2140 2040 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3070 2965 2855 2750 2630 2505 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

forc. vent.1)
40

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

4000 3150 4000 4000 3820 3675 3515 3330 4000 4665 4525 4380 4235 4080 3920
1250 1250 1430 1385 1320 1255 1180 1105 1250 1350 1310 1270 1225 1180 1135
2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
2000 2500 1885 1805 1720 1635 1540 1440 2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

1000 IP3X D nat. vent.

2500 2500 2720 2630 2535 2405 2270 2120 2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3235 3125 3010 2895 2770 2640 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

IP4X

forc. vent.1)

4000 4000 4000 4000 4000 3870 3705 3530 4000 4665 4525 4380 4235 4080 3920

natural
ventilated

2500 2500 2580 2500 2405 2280 2155 2010 2500 2965 2875 2785 2690 2590 2490
3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920
3150 3150 3070 2965 2855 2750 2630 2505 3150 4665 4525 4380 4235 4080 3920
4000 4665 4525 4380 4235 4080 3920

forc. vent.1)

4000 3150 4000 4000 3820 3675 3515 3330 4000 4665 4525 4380 4235 4080 3920

1) standard version current relais controlled, optionally current relais controlled and redundant version

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 35 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.11 NXAIR, 17.5 kV, 60 Hz, 40 kA, <= 4000 A or 25/31,5 kA with 3150/4000 A busbar, permissible current
values
Rated freShort
busbar width panel version
voltage qucircuit insulaency current tion
degree panel
of pro- version
tection
(kV)

(Hz)

(kA)

17.5

60

25

(mm)
with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

Rated current feeder resp bus sectionalizer / Ambient Rated current busbar / Ambient temperature
temperature
(A / C)
(A /C)
panel cb

(A /C)

(A)

30

(A)

35

40

45

50

55

busbar

(A /C)

(A)

30

35

40

45

50

55

1250 1250 1315 1270 1210 1180 1125 1075 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

2400 2500 2495 2410 2320 2230 2135 2035 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2560 2470 2385 2290 2190 2090 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3170 3065 2950 2835 2715 2590 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

1000 IP4X

forc. vent.1)

4000 3150 4000 4000 3930 3775 3615 3445 4000 4520 4385 4245 4100 3950 3795

nat. vent.

2400 2500 2370 2290 2205 2120 2030 1935 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2430 2345 2265 2175 2080 1985 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3010 2910 2800 2690 2575 2460 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

forc. vent.1)
31.5

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

1000 IP3X D nat. vent.

4000 3150 4000 3870 3730 3585 3430 3270 4000 4520 4385 4245 4100 3950 3795
1250 1250 1315 1270 1210 1175 1125 1075 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

2400 2500 2495 2410 2320 2230 2135 2035 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2560 2470 2385 2290 2190 2090 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3170 3065 2950 2835 2715 2590 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

1000 IP4X

forc. vent.1)

4000 3150 4000 4000 3930 3775 3615 3445 4000 4520 4385 4245 4100 3950 3795

nat. vent.

2400 2500 2370 2290 2205 2120 2030 1935 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2500 2500 2430 2345 2265 2175 2080 1985 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3010 2910 2800 2690 2575 2460 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

forc. vent.1)
40

with /
800
without

IP3X D/ closed
IP4X,
IP50,
IP51

4000 3150 4000 3870 3730 3585 3430 3270 4000 4520 4385 4245 4100 3950 3795
1250 1250 1410 1365 1305 1240 1170 1195 1250 1350 1310 1270 1225 1180 1135
2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
2000 2500 1805 1730 1650 1565 1475 1380 2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

1000 IP3X D nat. vent.

2500 2500 2645 2560 2455 2325 2195 2050 2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3170 3065 2950 2835 2715 2590 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

IP4X

forc. vent.1)

4000 4000 4000 4000 3930 3775 3615 3445 4000 4520 4385 4245 4100 3950 3795

natural
ventilated

2500 2500 2510 2430 2330 2205 2085 1945 2500 2865 2780 2690 2600 2505 2410
3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795
3150 3150 3010 2910 2800 2690 2575 2460 3150 4520 4385 4245 4100 3950 3795
4000 4520 4385 4245 4100 3950 3795

forc. vent.1)

4000 3150 4000 3870 3730 3585 3430 3270 4000 4520 4385 4245 4100 3950 3795

1) standard version current relais controlled, optionally current relais controlled and redundant version

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 36 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.12

Permissible combination of components in connection compartment of switching device panel


resp. busbar connecting panel, detailed configuration NX-Tools+
Rate Short
Rated width Cable
d vol- circuit feeder
access
tage withcurrent
from:
stand
current
(kV)

(kA)

(A)

ventilation

current earthing voltage


trans- switch transformers
formers

front / rear without 3


3
Circuit breaker or disconnector panel
<=
<= 31.5 630
600 front / rear without 3
17.5
3
3
<= 31.5 1000
600 front / rear without 3
3
3
3
< = 40 1250
800 front / rear without 3
3
3
3
3
3
3
3
3
3
3
3
6)
2000
800 front / rear without 3
3
3
3
3
3
3
3
2500
1000 front / rear natural 3
3
3
3
3
3
3
3
3150
1000 front / rear natural 3
3
3
3
4000
1000 front / rear forced 8) 3
3
3
3
3
3
3
3

4)
5)
6)
7)
8)

Surge Surge Connection in cable


limiter 1) arrestor compartment

withdrawable

fixed
mounted

(mm)

Contactor panel
12
<= 31,5 <= 400 435

1)
2)
3)

voltage
transformers

From bottom,
front or rear

From top,
rear 2)

Number of
cables 3) per
phase / bar

Number of
cables 3) per
phase / bar

1
1

<= 2
<= 1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3
3
3
3
3
3
3
3
3
3

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

3
3
3
3
3
3
-

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

<= 2
<= 2
<= 2
<= 2
<= 2
<= 3
<= 2
<= 4
Bar
<= 4 4)
Bar
<= 4 5)
Bar
<= 4
Bar
<= 4 4)
Bar
<= 4 6)
Bar
<= 4
Bar
<= 4
Bar
<= 4
Bar
<= 4
Bar
<= 4
Bar
<= 4
Bar
<= 4
Bar
<= 4
Bar
<= 6
Bar
<= 6
Bar
<= 6
Bar
<= 6
Bar
<= 6
Bar
<= 6
Bar

<= 3
<= 3
<= 3
<= 3
<= 3
<= 3
<= 3
<= 4

3
3
3
3
3
3
3 7)
3
3
3
3
3
3
3
-

<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 4
<= 6
<= 6
<= 6
<= 6
<= 6
<= 6

limiters are only used for up to 12 kV


rear side cable box up to <= 17.5 kV / <= 31.5 kA / <= 2500 A, additional depth for rear side cable box: + 600 mm
screw size in connecting copper: M12, hole in connecting copper: 13 mm diameter up to 300 mm
screw size in connecting copper: M16, hole in connecting copper: 17 mm diameter up to 500 mm
only <= 2 cables in version for 12 kV, up to 31.5 kA with panel depth 1350 mm
only <= 2 cables up to 17.5 kV up to 31.5 kA with panel depth 1350 mm
2000 A only for 40 kA panels
only possible in panel depth >= 1500 mm
standard version current relais controlled, optionally current relais controlled and redundant version

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 37 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.13 Permissible combination of components in busbar compartment of switching device panel,


detailed configuration NX-Tools+
Rated Short circuit
voltage with-stand
current

Rated
feeder
current

Width

(kV)

(kA)

ventilation

Bushing type
insulators

Voltage
transformers in
top box

Earthing switch in top


box

Bar or cable connection


to busbar

(A)

(mm)

Contactor panel
12
31.5

400

435

All other panel types


<= 17.5 <= 40

630

600

without

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
-

3
3
3
3
-

1
-

1000

600

without

1250

800

without

2000 1)

800

without

2500

1000

natural

3150

1000

natural

4000

1000

Forced 3)

1
1
1
-

1
1
-

1) only possible in 800 and 1000 panels, set of cts in installed in additional channel over two panels
2) 2000 A only for 40 kA
3) standard version current relais controlled, optionally current relais controlled and redundant version

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 38 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.14

Technical data of circuit breaker


Rated voltage

kV

12

17.5

Rated frequency

Hz

50 / 60

50 / 60

Rated short-duration power frequency


withstand voltage

kV

28, IEC
42, GOST

38, IEC

kV

75, IEC, GOST

95, IEC

kA

25

Rated duration of short circuit

1, 3

Rated peak withstand current

kA

Rated short circuit breaking current

Phase/phase, phase/earth, open contact gap


Rated lightning impulse withstand voltage
Phase/phase, phase/earth, open contact gap
Rated short-time withstand current of main
circuits

31.5

40

25

31.5

40

63 / 65

80 / 82

100 / 104

63 / 65

80 / 82

100 / 104

kA

25

31.5

40

25

31.5

40

Rated short circuit making current

kA

63 / 65

80 / 82

100 / 104

63 / 65

80 / 82

100 / 104

Rated normal current

800
1250

800
1250
2500

1250
2500
3150

800
1250

800
1250
2500

1250
2500
3150

1, 3

Asymmetrical breaking current

kA

28

35.4

44.9

28

35.4

44.9

DC component at rated short circuit breaking


current

36

36

36

36

36

36

Rate-of-rise (RRRV)

kV /
s

0.34

0.34

0.34

0.42

0.42

0.42

Voltage (TRV) peak value

kV

20.6

20.6

20.6

30

30

30

Switching duty

0 0.3 s CO 15 s. CO up to 31.5 kA
0 3 min. CO 3 min. CO for 40 kA

Closing time

ms

< 75

Opening time 1 st shunt release

ms

< 65 ms

Opening time 2 nd, 3 rd shunt release

ms

< 50 ms

Arcing time

ms

< 15 ms

Breaking time 1 st shunt release

ms

< 80 ms

Breaking time 2 nd, 3 rd shunt release

ms

< 65 ms

Dead time

ms

300 ms

Close-/ Open time 1 st shunt release

ms

< 75 ms

Close-/ Open time 2 nd, 3 rd shunt release

ms

< 60 ms

Pulse time for breaker tripping signal for 1 st shunt release

ms

> 15

Pulse time for breaker tripping signal for 2 nd and 3 rd shunt release

ms

> 10

Spring-charging time for electrical operation

10

Synchronous operation error between the poles


Release

Order no
of release

ms

Power consumption

Tripping ranges

at DC
operation

at AC

Tripping voltage DC

appr. W

appr. VA

50/60 Hz operation

2
Tripping
pulse

Tripping voltage /
current
(50/60 Hz AC)

Closing solenoid

3AY1510

140

140

85 to 110 % U

85 to 110 % U

1 st shunt release

3AY1510

140

140

70 to 110 % U

85 to 110 % U

3AX1101

70

50

70 to 110 % U

85 to 110 % U

Undervoltage release

3AY1103

20

20

35 to 0 % U

35 to 0 % U

Ct operated release

3AX1104

(without energy store)


2 nd shunt release
(with energy store)

(tripping pulse>= 0.1


Ws
Power consumption of motor DC

350 W

Power consumption of motor AC


Switch classification 1)
contacts of auxiliary switch of
breaker

400 VA
electrically

mechanically

Capacitive switching capability

E2

M2

C2

12 NC+12NO

Free contacts for external use

1) detailed information see also 4.15 next page

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 39 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.15

Technical data of contactor


Rated voltage

Rated frequency

kV

7.2

Ordering
nomber

3TL62

12
3TL63

3TL66

Hz

50/60

phase/phase,
phase/earth

kV

20

32

28

open contact
gap

kV

20

20

28

Phase/phase,
phase/earth

kV

60

60

75

open contact
gap

kV

40

40

60

Rated short-time withstand current

kA / s

8/1

8/1

8/1

Rated continuous normal current according to 60470

450

400

400

Rated making capacity

4500

4000

4000

Rated breaking capacity

3600

3200

3200

Limit switching capacity

5000

4500

4500

Rated breaking current for capacitor switching

250

250

250

Rated making current for capacitor switching

kA

10

10

10

Mechanical endurance of contactor

cycles

1,000,000

1,000,000

1,000,000

Electrical endurance of vacuum interrupter of contactor while


breaking the continuous current

cycles

1,000,000

500,000

500,000

Switching rate without mechanical closing latching

cycles /
h

1200

600

600

Power consumption of drive solenoid, making capacity

650

650

650

Power consumption of drive solenoid, holding power referred to


230 V AC

90

90

90

Rated short-duration power frequency


withstand voltage

Rated lightning impulse withstand voltage

Voltage range of drive solenoid, operating voltage

0,8 1.1 Ua

0,8 1.1 Ua

0,8 1.1 Ua

Minimum closing command for drive solenoid

ms

100

100

100

Closing time (interval of time between closing command and the


instant when the contacts touch for the first time)

ms

100 ms at 0.85 Ua
80 ms at 1.00 Ua
60 ms at 1.1 Ua

100 ms at 0.85 Ua
80 ms at 1.00 Ua
60 ms at 1.1 Ua

100 ms at 0.85 Ua
80 ms at 1.00 Ua
60 ms at 1.1 Ua

30 ms at 0.85 Ua
50 ms at 1.00 Ua
50 ms at 1.1 Ua

30 ms at 0.85 Ua
50 ms at 1.00 Ua
50 ms at 1.1 Ua

30 ms at 0.85 Ua
50 ms at 1.00 Ua
50 ms at 1.1 Ua

Opening time (interval of time between opening command and


the instant when the contacts start to separate)
Mechanical closing latch, operating cycles

cycles

100,000

100,000

100,000

Mechanical closing latch, switching rate

Cyles / h

60

60

60

Mechanical closing latch, power consumption of the latch release


solenoid

900

900

900

Mechanical closing latch, voltage range of the latch release


solenoid

0.85 1.1 Ua

0.85 1.1 Ua

0.85 1.1 Ua

Mechanical closing latch, opening pulse

0.2 max. 1

0.2 max. 1

0.2 max. 1

Mechanical closing latch, opening time

ms

< 45

< 45

< 45

Contacts of auxiliary switch of contactor

4NO/3NC or
6NO/5NC

4NO/3NC or
6NO/5NC

4NO/3NC or
6NO/5NC

Free contacts for external use

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 40 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.16

Technical data of fuses for motor application of contactor panel


Current carrying capacity of fuses in contactor panel
Un

Ith

kV

kA

Hz

7.2

<= 40

50

Type

Number per
phase

In HV HRC fuse

Current carrying capacity in A


at ambient temperature in C

(A)

25C

30C

35C

40C

3011054.250

250

344

333

322

310

298

285

272

3011054.200

200

284

275

266

256

246

235

225

3010953.160

160

250

242

233

225

216

207

197

3011054.315

315

264

256

247

238

229

219

209

3011054.250

250

224

217

210

202

194

186

177

3011054.200

200

184

178

172

166

159

153

146

3010953.160

160

161

156

150

145

139

133

127

3010953.125

125

124

120

116

112

108

103

98

3010853.100

100

100

97

93

90

86

83

79

3010853.80

80

80

79

76

74

71

68

65

3010853.63

63

63

63

63

63

63

63

63

3010853.50

50

50

50

50

50

50

50

50

45C

50C

55C

For rated fuse currents < 50 A, no current reduction must be considered due to the
ambient temperature
60

3011054.250

250

339

328

317

305

293

281

268

3011054.200

200

280

271

262

252

242

232

221

3010953.160

160

246

238

230

222

213

204

194

3011054.315

315

260

252

243

234

225

216

206

3011054.250

250

221

214

206

199

191

183

175

3011054.200

200

181

176

170

164

157

150

143

3010953.160

160

158

153

148

143

137

131

125

3010953.125

125

122

119

114

110

106

101

97

3010853.100

100

98

95

92

89

85

82

78

3010853.80

80

79

78

75

73

70

67

64

3010853.63

63

63

63

63

63

63

63

63

3010853.50

50

50

50

50

50

50

50

50

For rated fuse currents < 50 A, no current reduction must be considered due to the
ambient temperature
12

<= 40

50

30 103 53.160

160

212

205

198

191

184

176

30 103 53.160

160

136

132

128

123

118

113

168
108

30 102 53.125

125

105

102

99

95

91

87

83

30 102 53.100

100

84

82

79

76

73

70

67

30 102 53.80

80

69

67

64

62

60

57

54

30 101 53.63

63

59

57

55

53

51

49

46

30 101 53.50

50

47

45

44

42

40

39

37

For rated fuse currents < 50 A, no current reduction must be considered due to the
ambient temperature
60

30 103 53.160

160

205

199

192

185

178

170

30 103 53.160

160

132

128

124

119

115

110

162
105

30 102 53.125

125

102

99

96

92

88

85

81

30 102 53.100

100

82

79

76

74

71

68

65

30 102 53.80

80

67

65

62

60

58

55

53

30 101 53.63

63

57

55

53

51

49

47

45

30 101 53.50

50

45

44

42

40

39

37

36

For rated fuse currents < 50 A, no current reduction must be considered due to the
ambient temperature

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 41 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Type designitions for all possible rated fuse currents for motor application, fuse length e, order nomber
Ur

In HV HRC fuse

Dimension e

(kV)

(A)

(mm)

Order no.:

Type

7.2

6,3

192

3000213.6,3

HHD

10

192

3000213.10

HHD

16

192

3000213.16

HHD

20

192

3000213.20

HHD

25

192

3000213.25

HHD

31.5

192

3000213.31.5

HHD

40

192

3000213.40

HHD

50

442

3010853.50

HHM

63

442

3010853.63

HHM

80

442

3010853.80

HHM

100

442

3010853.100

HHM

125

442

3010953.125

HHM

160

442

3010953.160

HHM

200

442

3011054.200

HHM

250

442

3011054.250

HHM

315

442

3011054.315

HHM

12

HV HRC fuse-link

6,3

292

30 004 13.6.3

HHD

10

292

30 004 13.10

HHD

16

292

30 004 13.16

HHD

20

292

30 004 13.20

HHD

25

292

30 004 13.25

HHD

31.5

292

30 004 13.31.5

HHD

40

292

30 004 13.40

HHD

50

442

30 101 53.50

HHM

63

442

30 101 53.63

HHM

80

442

30 102 53.80

HHM

100

442

30 102 53.100

HHM

125

442

30 102 53.125

HHM

160

442

30 103 53.160

HHM

Required extension tubes for fuses with e < 442 mm


Order no.: SIBA

HV HRC fuse-link with dimension e

3400602

192 mm

3400601

292 mm

Table for selection fuses depending from starting conditions of motor


Starting
time of
motor

Number
of starts
per hour

Maximum permissible motor starting current in A at rated current and number of HV HRC fuse-links per phase in A

1x50

1x63

1x100

1x125

1x160

1x200

1x250

2x160

2x200

2x250

5s

131

165

310

418

566

765

1283

1132

1530

2566

118

148

278

375

509

687

1153

1018

1374

2306

107

134

252

340

461

622

1044

922

1244

2088

15 s

30 s

60 s

16

95

120

225

304

413

557

935

826

1114

1870

32

87

109

205

276

374

505

848

748

1010

1696

112

139

254

344

459

641

1007

918

1282

2014

101

125

228

309

412

575

905

824

1150

1810

91

113

207

280

374

521

819

748

1048

1638

16

82

102

185

251

335

467

734

670

934

1468

32

74

92

168

228

303

423

666

606

846

1332

99

126

229

303

406

552

865

812

1104

1730

89

113

206

272

365

496

777

730

992

1554
1408

81

102

186

247

330

449

704

660

898

16

72

92

167

221

296

403

630

592

806

1260

32

65

83

151

200

268

365

572

536

730

1144

91

114

204

273

357

501

777

714

1102

1554

82

103

183

246

321

450

698

642

900

1369

74

93

166

222

291

407

632

582

814

1264

16

66

83

149

199

260

365

566

520

730

1132

472

662

1028

32
60
76
135
181
236
331
514
Detailed information regarding fuses also in intranet:
https://intranet.wss02.ptd.siemens.de/content/00001122/AIS_Common/HH-SiSchuetz_Kennlinien.pdf

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 42 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Design example for selection of fuses and current transformer depending from motor data
Motor data, example
Motor data, example
Ub = 6 kV
Ik = 25 kA
In = P / Ubx3x cos x = 900 kW / 6 kVx3x0.85x0.85 = 120 A
P = 900 kW
cos = 0.85
Ia = 6 x In = 720 A
= 0.85
Ia = 6 x In
The rated operating current of the HV HRC fuse should be read from the above shown table
max. 2 starts per hour
using the data given: 250 A
max. starting time 5s
Definitions
Selection of current transformers
Ia = starting current of motor
Idyn = max. peak current of current transformer
ID = cut-off current of fuse
Ik = short circuit current (r.m.s. value)
In = rated current of motor
Ith = short time withstand current
P = rated motor power
cos = Power factor of motor
= motor efficiency

The cut-off current of a fuse with 250 A rated current is for Ik = 25 kA short circuit value: 25
kA (depending from characteristic of fuse for these values, see also above mentioned link to
intranet)
Thermal stressing of current transformer by the short time current rating Ith is negligible as a
result of current limiting by the HV HRC fuses. The current transformer must be capable of
withstanding mechanical stress due only to the cut-off current ID. In this connection the cut-off
current ID is equivalent to the peak current of current transformer Idyn.
Idyn >= ID
Ith = Idyn / 2.5 = 25 kA / 2.5 = 10 kA

The current transformer must be designed for an Ith of >= 10 kA


selection guide according contactor or circuit breaker for motor switching applications
Selection of switching device for motors is influenced by following key factors:

rated voltage of network and motor


frequency of network
rated power of motor
rated current of motor
required switching cycles based on application of motor in production process
power factor cos of motor
motor efficiency factor
starting current of motor
number of starts per hour
starting time of motor
max. number and rated current of fuses which can be installed in panel when contactor is used,
ambient temperature of switchgear room
for contactors lower rated lightning impulse withstand voltages across the open contact gap as circuit breakers are required based on
different standards
(at 7.2 kV: 40 kV instead of 60 kV, at 12 kV: 60 kV instead of 75 kV)

Additionally to above mentioned key factors protection and primary cable philosophy have to be considered. Protection philosophy is influenced by
significance and importance of motor in process while using differential protection relays in combination with circuit breakers or over current
protection in combination with fuses and contactors.
Due to current limiting function of fuses in combination with contactors cross section of primary cables can be optimized.
Based on above mentioned key factors following advice for selecting contactor with fuses can be given:
Max. fuses which can be installed in contactor panels:
NXAIR switchgear:

7.2 kV:

single fuse per phase 1 x 315 A,

parallel fuses per phase 2 x 250 A

12 kV:

single fuse per phase 1 x 160 A,

parallel fuses per phase 2 x 160 A

NXAIR P switchgear: 7.2 kV:

single fuse per phase 1 x 315 A,

parallel fuses per phase 2 x 250 A

Depending from max. permissible current values of complete contactor panel including fuses with above mentioned ratings in NXAIR and NXAIR P
switchgear,
based on 35 C ambient temperature of switchgear ro om,
rated voltage of motor for 7.2 kV application: 6.6 kV
rated voltage of motor for 12 kV application: 11 kV
power factor cos = 0,9
motor efficiency = 0,9
following average power values of motors can be switched with fused contactor units:
7.2 kV:

3000 kW

12 kV:

3000 kW

For higher power values of motors circuit breakers should be checked.


Detailed calculation based on precise figures and specific conditions on site can vary above mentioned result.

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 43 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.17

Technical data of withdrawable part for circuit breaker, disconnector link, measuring device
Mechanism 1)

interlockings

Switch classification 2)

hand operated

Standard

motor operated optionally

for withdrawable part with


circuit breaker

Mechanical to circuit
breaker position

Standard

padlockable

option

key interlocking device

option

mechanically
M0

contacts of auxiliary switch of


withdrawable part

4 NC+4 NO

free contacts for external


use

Power consumption motor mechanism

auxiliary voltage DC

35 W

auxiliary voltage AC

35 VA

Time for moving withdrawable part from test to service position or vice versa

4.18

appr. 25 s

Technical data of earthing switches


Rated voltages

kV

12

17,5

Rated frequency

Hz

50 / 60

50 / 60

Rated short-duration power frequency withstand voltage

kV

Phase/phase, phase/earth
Rated lightning impulse withstand voltage

kV

28

IEC

42

GOST

75

IEC, GOST

38, IEC
95, IEC

Phase/phase, phase/earth
Rated short-time withstand current 3)

kA

Rated short time duration 3)

Rated peak withstand current 3)

kA

<= 100 at 50 Hz, 104 at 60 Hz

Rated short.circuit making current 3)

kA

<= 100 at 50 Hz, 104 at 60 Hz

Mechanism

Hand operated

Standard

Motor operated optionally

In contactor panel not possible

<= 40

<= 40

3
<= 100 at 50 Hz, 104 at 60 Hz
<= 100 at 50 Hz, 104 at 60 Hz

Interlockings
Cable earthing
Busbar earthing

Standard

Mechanical and electrically

option

padlockable

Standard

electrically

option

Power consumption of motor mechanism

35 W

Switch classification 2)

mechanically

contacts of auxiliary switch of


withdrawable part

4.19

Mechanical to withdrawable part

electrically
E1

M0

4 NC+4 NO

free contacts for external use

Switching classifications of breaker, withdrawable part, earthing switch


Circuit breaker
Electrically

mechanically

Capacitive switching
capability

Withdrawable part

Earthing switch

mechanically

electrically

E2

M2

C2

M0

E1

M0

56xIp, 130x10% Isc


130x30% Isc, 8x60% Isc
6x100% isc

10.000 cycles

very low probability


of restrikes

1.000 cycles

2xIma

1.000 cycles

Ima=making
current (peak
value)

Ip= peak current


Isc=short circuit breaking current

4.20

mechanically

Position indication of electrical devices


Circuit breaker

Mechanical indication through high voltage door, included in


single line

Withdrawable part

Mechanical indication ON / OFF, included in single line

Earthing switch feeder

Mechanical indication ON / OFF, included in single line

Earthing switch busbar

Mechanical indication ON / OFF

Switch fixed mounted

not released for sales

Contactor

electrically

1) cassette design is standard, truck type design as option possible (then withdrawable voltage transformers in connection compartment are excluded)
2) see also chapter 4.18
3) in contactor panel limited due to cut off function of fuses

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 44 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.21

Power consumptions of electrical devices


device

Power consumption

Circuit breaker

Motor for spring charging, DC

contactor

Withdrawable part

Earthing switch busbar or feeder

4.22

350 W,

Motor for spring charging, AC

400 VA

Running time of motor

10 s

Drive solenoid, making capacity

650 W

Drive solenoid, holding power

90 W

Mechanical closing latch, power


consumption of the latch release solenoid

900 W

Motor mechanism DC

35 W

Motor mechanism AC

35 VA

Running time of motor

Appr. 25 s

Motor mechanism DC

35 W

Motor mechanism AC

35 VA

Running time of motor

appr. 25 s

Electrical interlocking magnets

Only active in releasing function

10 W, suitable for continous energisation

heaters

Circuit breaker compartment

100 W

Cable compartment

100 W

Low voltage compartment

20 W

Configuration information pressure release channel system


Application of pressure release channel system to lead gases due to internal arc outside switchgear room
Rated voltage

IAC-classification

Arc fault current Arc fault duration

<= 12 kV

IAC A FLR

<= 25 kA
31.5 kA
40 kA

17.5 kV

IAC A FLR

<= 25 kA
31.5 kA
40 kA

1 s or 0.1 s
1 s or 0.1 s
1 s or 0.1 s
1 s or 0.1 s
1 s or 0.1 s
1 s or 0.1 s

Height of switchgear
room

Pressure relief system

>= 2500 / < 2800 mm

duct to outside

> 2800 mm

absorbers

>= 2500 / < 3000

duct to outside

>= 3000 mm

absorbers

>= 2500 / < 3500 mm

duct to outside

>= 3500

absorbers

>= 2500 / < 3500 mm

duct to outside

> 3500 mm

absorbers

>= 2500 / < 3500

duct to outside

>= 3500 mm

absorbers

>= 2500 mm / < 3500

duct to outside

>= 3500 mm

absorbers

All parts of channel system are included in accessories of NXAIR, chapter 3, and can be configurated with NX-Tools+ and will be delivered together
with switchgear.
Channel parts consists of zinc coated steel, thickness 2 mm, screws M8, following parts can be plugged and screwed together, cross section 530
mm x 245 mm:
Adapter device at standard pressure relief channel to left, will be configurated with NX-Tools+
Adapter device at standard pressure relief channel to right, will be configurated with NX-Tools+
Adapter device at standard pressure relief channel to rear, will be configurated with NX-Tools+
Channel, length 1000 mm, ordering number 8BX3400-0AA00-0AA0
Angle channel 45 up / down, ordering number 8BX3400- 0AA00-0AA1
Angle channel 45 right / left, ordering number 8BX34 00-0AA00-0AA2
Channel, length 500 mm, ordering number 8BX3400-0AA00-0AA3
Channel length extendable from 595 mm to 760 mm in 20 mm steps, ordering number 8BX3400-0AA00-0AA4
Channel, length 370 mm for wall outgoing, powder coated RAL 7035, ordering number 8BX3400-0AA00-0AA5
Fixing ledges, ordering number per set 8BX3400-0AA00-0AA6
Fixing angles, ordering number per set 8BX3400-0AA00-0AA7
Additional fixing parts have to be organized on site.
Generally all type tests in accordance to IEC 62271-200 will be made on representative functional units. As mentioned in this IEC it is not practicable
to make for all arrangements of switchgear special type tests. Because of the variety of types, ratings and possible combinations of components it is
possible in accordance to standard that the performance of any particular arrangement may be substantiated by test data or simulation calculations
of comparable arrangements. Due to this and the fact that each switchgear room never will have exactly same dimensions, installed equipment etc.,
the functionality of this channel system has been evaluated by type tests in combination with simulation calculations.
Following rules for planning have to be considered, see also below shown pictures:
Channel should be realized to lateral side or rear side
Lateral direction of channel system:
end panel (all available typicals) which should be used for adaption of channel does not have busbar voltage transformer resp. busbar earthing
switch, ventilated panel is possible
Rear side direction of channel system:
panel which should be used for adaption of channel does not have busbar voltage transformer resp. busbar earthing switch or ventilation resp. rear
side cable box for primary cables coming from above, adaption to one single contactor panel is not possible, but in the middle of two contactor
panels.
At least one panel of each busbar section (when bus sectionalizer is included) must have one connected channel system to lateral or rearside
Length of switchgear and number of busbar device have no impact on configuration of channel system
IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 45 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Height of switchgear room have to be >= 2500 mm


Principle version of pressure release channels, detailed drawing see intranet

distance at rear side between switchgear and wall > = 150


mm for cable connection from front resp. >= 500 mm for
cable connection from rear

switchgear front view,


channel lateral

switchgear front view,


channel rearside

switchgear top view,


channel lateral

switchgear top view,


channel rear side

distance lateral > 150 mm resp. >=100 mm for contactor


panel at one side of switchgear rrow resp. 500 mm at
opposite side of switchgear row

Pressure release channel to left or right side,


cross section of channel itself 537 mm x 248.5 mm, location see above drawing

Front view of switchgear, channel to lateral

side view of switchgear, channel to lateral

Pressure release channel to rear side, cross section of channel itself 537 mm x
248.5 mm

2248.5

2000

2000

2248.5

537

600
800
1000

Side view of switchgear, channel to rear

IC LMV MV1 PPM, Herbert Soens

Rear side of switchgear with channel to rear,


e.g. three panels

issued: 24.10.2011

- 46 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

Channel device

Ordering nomber

Channel type

8BX3400-0AA00-0AA0

Channel length 1000 mm

8BX3400-0AA00-0AB0

Channel length 260 mm, IP4X

8BX3400-0AA00-0AA1

Angle 45 rotatable upwards or


downwards

8BX3400-0AA00-0AA2

Angle 45 rotatable right or left

8BX3400-0AA00-0AA3

Channel length 500 mm

8BX3400-0AA00-0AA4

Channel extendable 595 mm to


760 mm in 20 mm steps

8BX3400-0AA00-0AA5

Wall outlet box,


length 370 mm

8BX3400-0AA00-0AA6

Fixing ledges,
consisting of two parts

8BX3400-0AA00-0AA7

Fixing angles,
Consisting of two parts

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 47 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.23

Climate and ambient influences


In accordance to IEC 62271-200 , IEC 62271-1
Ambient temperature does not exceed

40 C

Average value, measured over 24 h does not exceed

35C

Minimum ambient temperature

-5C

Ambient air

Not significantly polluted by dust, corrosive and/or flammable


gases, vapours or salt

Average value of relative humidity, measured over 24 h

<= 95%

Average value of relative humidity, measured over 1 month

<= 90%

Other special required ambient conditions in accordance to IEC 60721, 3-3


Conditions in switchgear room1)

Additional measure to standard design of switchgear 1)

Climate in
Ambient
switchgear temperoom, Class rature
of climate

Relative
humidity

Condensation

3K3

+5C +40C

5 95%

-25 +55C

10
100%

3K6

3K8H

-25 +55C

10
100%

Special ambient heater


conditions

Degree of Bolted
protection joints
with
special
grease

All metal partitions


inside panel
painted in
standard colour all
galvanized parts
treated specially 3)

Movable
contacts of
Additional 2)
main circuits measures for
nickel-plated circuit breaker
and current
transformers
resp. bushings

--

--

--

--

--

yes

--

--

yes

Design as above, but also


with:

yes

--

--

Sulphur dioxide
(SO2)
>= 2 ppm

IP3X D

yes

yes

--

yes

Hydrogin
sulphide (H2S)
>= 1 ppm

IP3X D

yes

yes

yes

yes

Hydrocloric acid (HCl)


>= 3 ppm

IP3X D

yes

yes

--

yes

Ammonia (NH3)
>= 15 ppm

IP3X D

yes

yes

--

yes

Nitric oxide (NO2) >= 2 ppm

IP3X D

yes

yes

--

yes

Chloride deposit (Cl_)


>= 2 mg/dm

IP3X D

yes

yes

--

yes

IP3X D

IP4X

occasionally, -

yes

IP3X D

1 per month for 2h


dust

yes

IP4X

yes

IP50 4)

vermin proof

yes

IP50

4)

frequently,

yes

IP3X D

1 per day,
for 2h

yes

IP4X

dust

yes

IP50 4)

vermin proof

yes

IP50 4)

Dripping water
due to
condensation

yes

IP3X D

Dripping water
due to IEC
60529

yes

IP51 4)

Damp tropical areas

Areas subject to chemical pollution

1) transport and commissioning not included


2) temperatures < - 5C requires special measures f or switching devices
3) DTO-design with special request
4) only possible for panels with rated current <= 1250 A

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 48 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.24

Protection of voltage transformers with fuses, technical argumentation


Voltage transformer faults are after cable termination faults one of the most frequent sources of failure and cause of arcing faults of
switchboard. For this reason, appropriate protection measure need to be taken into account. In order to avoid overloading at the secondary
winding the standard IEC 61936-1 requires protection on the secondary side.
IEC 61936-1, 6.2.4.2.The secondary side of voltage transformers shall be protected against the effects of short-circuits, and it is
recommended that protective devices (i.e. their tripping) be monitored.
The secondary cables of voltage transformers (like any other auxiliary and control wires) must be laid so that they are protected against
electrical and mechanical interference (see IEC/EN 62271-1, 5.4.4.5.1). Protection with fuses on the primary side of voltage transformers in
not required in standards, nevertheless in some customer specification included.
Following technical reasons show that fuses on primary side of voltage transformers will not protect voltage transformers itself:
Failure:
short circuit at secondary terminals of voltage transformers or secondary equipment:
Rated current on primary side at rated power:
I1 = max. 100 mA at <= 12 kV; I1 = 50 mA at <= 24 kV
highest current on primary side at secondary terminal short circuit: I1 = max. 1 A
lowest rated current of fuses:
IrHRC = 6 A
lowest breaking current of fuses:
Imin HRC 25 A
fuses of primary side will not trip, due to:
I1 << Imin HRC
Failure:
short circuit within voltage transformer itself:
leads rapidly to thermal overload of voltage transformers, this leads to explosion of voltage transformer, this leads to arc fault outside voltage
transformer with current value depending form earthing of neutral point with ionising of air in the same compartment, depending from value of
this arc fault current and ionising rate of air fuse will trip and minimize damages of compartment or upstream circuit breaker have to trip this
internal arc, destruction of voltage transformers will not be avoided
Failure:
short circuit on primary side of voltage transformers:
leads to arc fault outside voltage transformers with same effect as described one topic before
Conclusion:
HRC fuses on primary side of voltage transformers will not avoid destruction of voltage transformers. Secondary circuit fuses are sensible and
are recommended by VDE: Attention must be given to careful selection and installation so that their additional contact and internal resistance
do not lead to false measurement due to voltage drop. Resistance and limiting reactors fitted to a da-dn winding (former e-n winding) to damp
ferroresonances shall not be fitted with fuses, detailed information also:
https://intranet.wss02.ptd.siemens.de/content/M-Products/nxair/ProductDocumentation/fused%20voltage%20transformers_e.pdf

4.25

Application of surge arrestors resp. surge limiters


Surge arrestors limit overvoltages by diverting thermal overvoltages which can be caused as external overvoltages by lightning strikes in
overhead lines or as internal overvoltages in the form of switching overvoltages or earth fault. They are normally installed in cable
compartment, please check table of max. possible installation combinations in cable compartment.
Surge limiters are used to protect high voltage motors which are switched by vacuum circuit breakers or vacuum contactors with starting
current up to 600 A. For higher starting current these surge limiters are not neccessary. They are normally installed in cable compartment,
please check table of max. possible installation combinations in cable compartment.

4.26

Packing dimensions and transport weights of packing (tare weight) 1)


Domestic transport, transport within Europe

Seaworthy packaging

<= 17.5 kV, 31.5 kA, <= 2500


A

<= 17.5 kV, 40 kA, <= 4000 A

<= 17.5 kV, 31.5 kA, <= 2500


A

<= 17.5 kV, 40 kA, <= 4000 A

width (mm)

435

600

435

600

1000

435

600

435

600

rated current
(A)

<=400

1000 1250 >1250

<=400

1000 1250

>1250

<=400

1000 1250 >1250

<=400

1000 1250 >1250

Depth 2)
(mm)

1572

1572 1572 1572

1772

1772 1772

1772

1572

1572 1572 1572

1772

1772 1772 1772

width (mm)

722

722

722

722

1122

822

822

822

822

height (mm)

2510

2510 2510 2510

2510

2510 2510

2510

2531

2531 2531 2531

2531

2531 2531 2531

weight (kg)

40

40

45

45

55

145

145

155

155

switchgear
type

1)

2)

800

922
45

1000

1122
50

800

922
50

800

1000

1022 1222
160

175

800

1000

1022 1222
170

185

figures include standard panels or panels with extended low voltage box or busbar devices,
for separate delivered pressure relief ducts one separate packing unit per 6 panels have to be calculated,
absorbers are also delivered separately
for panels in extended version 1500 mm instead of 1350 mm ???? mm resp. 1600 mm instead of 1500 mm ???? mm to be added,
for rear side cable connection box ???? mm ot be added

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 49 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.27

Weights of panels (appr., net weight)


<= 17.5 kV / <= 2500 A busbar

4.28

<= 17.5 kV / > 2500 A busbar

contactor panel, 435 mm width

~ 685 kg

~ 770 kg

Breaker panel, 600 mm width, 1000 A

~ 750 kg

Breaker or disconnecting panel, 800 mm width, 1250 A

~ 800 kg

~ 1130 kg

Breaker or disconnecting panel, 1000 mm width, <= 2500 A

~ 1100 kg

~ 1380kg

Breaker or disconnecting panel, 1000 mm width, 3150 A

~ 1630 kg

Breaker or disconnecting panel, 1000 mm width, 4000 A

~ 1650 kg

Bus riser panel of bus sectionalizer, 800 mm width

~ 800 kg

~ 1260 kg

Bus riser panel of bus sectionalizer, 1000 mm width, 2500 A

~ 1100 kg

~ 1320 kg

Bus riser panel of bus sectionalizer, 1000 mm width, 3150 A

~ 1570 kg

Bus riser panel of bus sectionalizer, 1000 mm width, 4000 A

~ 1590 kg

Metering panel, 800 mm width

~ 700 kg

~ 840 kg

Busbar connecting panel, 800/1000 width

~ 1000 kg

~ 1180 kg

Transport and storage information


Temperature limits for transportation and storage

- 25 C - +70 C for primary part


Electronic components in secondary part to be checked
separately

Storage location (check also


detailed information in installation
maunual)

4.29

Packaging for domestic transport,


transport within Europe

In original unpacked packing, in closed rooms,

Seaworthy packaging
(6 months)

If possible in closed room,


Outdoor storage in original packaging for 12 month period

Painting, surface treatment


Front and endwalls
of switchgear and
optionally rear side
wall

Standard

Powder coated RAL 7035

other steal parts

Standard

Zinc plated

Standard: DIN EN 10327, DIN EN ISO 2081, Zn8/C


Thickness: appr: 20 m resp. 275 g/m zinc plated

complete
switchgear

optionally

Powder coated RAL 7035

as discription above

Surface coating setup: powder coating baking 180C 200C


Thickness: appr.: 75 to 125 m

Parts of mechanism

Chromium coated

Parts of mechanism

Primary contacts

movable contacts:
silver plated 20 + 6 m

Standard: DIN EN ISO 2819,

fixed contacts:
silver plated 25 + 6 m

4.30

4.31

4.32

Preliminary treatment of steel:


Alkaline-acid spray degreasing and alkaline phosphatization, Gardobond A
4932, forming a layer of 0.2 to 0.5 g/m

Tested with temperature shock 250C / 30 min.


Fixed contacts if necessary: 3 +/- 2 m

Cross section of earthing bar


Rated voltage (kV)

Rated short-time withstand current (kA)

7.2 / 12 / 17.5

<= 25 kA

Cross section (mm)


50 x 5

31.5 kA

50 x 8

40 kA

50 x 10

Thickness of used steel sheets


Frame

2 mm

High voltage door

2.5 mm

Low voltage door

2 mm

Pressure release flaps

1 mm

Partitions between compartments

2 mm

Partition wall between panels

2 x 2 mm

Ground plate

2 mm

Rear side cover plates

2 mm / 2.5 mm at 40kA

End walls

2 mm

Interlocks
device
Withdrawable part

Interlocked with:

method

Position of switching device on


withdrawable part

Standard: mechanically

Feeder earthing switch

Standard: mechanically

Circuit breaker

Position of withdrawable part

Standard: mechanically

Withdrawable part with disconnector link

Option: padlocked, Option: electrically

Feeder earthing switch

Position of withdrawable part

Standard: mechanically

Busbar earthing switch

Standard: padlocked, Option: electrically

High voltage door

Position of withdrawable part

Option: mechanically

Rear side cover of cable compartment when


cable connection from rear

Feeder earthing switch

Standard: with screws


Option: padlocked
Option: interlocked with earthing switch

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 50 / 51 -

nur fr internen Gebrauch, by Siemens AG, IC LMV MV1

4.33

Used materials (average values)


Material / panel width

435 mm

600 mm

800 mm

1000 mm

steel

~ 500 kg

~ 600 kg

~ 700 kg

~ 800 kg

copper

~ 80 kg

~ 160 kg

~ 100 kg

~ 140 kg

Insulation material for current transformers, cast resin

~ 60 kg

~ 75 kg

~ 75 kg

~ 75 kg

Insulation material for bushing type insulators, cast resin

~ 40 kg

~ 50 kg

~ 50 kg

~ 50 kg

Aluminium

~ 5 kg

~ 15 kg

~ 15 kg

~ 20 kg

Optional insulation of busbar,

~ 5 kg

~ 8 kg

~ 8 kg

~ 10 kg

optionally insulation of busbar joints,


material: polyurethane, sealing compound PV5

~5 kg

~8 kg

~8 kg

~10 kg

optionally busbar transverse partition,


material plate:Durostone, UPM S14 (grey)

~3 kg

~3 kg

~3 kg

~3 kg

material: fibre-glass reinforced insulation tubes

4.34

material bushings: cast resin

~ 3 kg

~ 3 kg

~3 kg

~3 kg

Insulation of control wiring Standard, H07V

~10 kg

~10 kg

~10 kg

~10 kg

Insulation of control wiring optional, HX4GAF, halogen free

~10 kg

~10 kg

~10 kg

~10 kg

Low voltage devices

~20 kg

~20 kg

~20 kg

~20 kg

435 mm

600 mm

800 mm

1000 mm

Fire loads
panel width

~ 1600 MJ

4.35

~ 1800 MJ

~ 2000 MJ

~ 2500 MJ

Dynamic loads
Circuit breaker panel

Impact load due to switching devices are negligible

Contactor panel

4.36

Fixing hardware
device

4.37

4.38

scew

Fixing moment

Main busbar

M12

Earthing bar

M12

70
70

Termination of cables

M12 or M16

70 /170

Between frames

M8

30

Between panel and foundation rails

M10 / M12

105 / 260

Heat losses
Panel <= 630 A

~<= 200 W

Panel 1000 A

~500 W

Panel 1250 A

~750 W

Panel 2000 A

~850 W

Panel 2500 A

~2000 W

Panel 3150 A

~2650 W

Panel 4000 A

~4300 W

maintenance
visual inspection

Every year or at the operator`s discretion, see also operation instructions

maintenance

Every ten years or depending on operational facts, or at operator`s discreption, see also operation instructions

Greases to be used

Longtherm 2 for fixed contacts of main circuits in bushings and fixed contacts of earthing switch, see also operation
instructions
Isoflex Topas L32 for moving rails of withdrawable part, see also operation instructions

4.39

Spare parts
List for 1 year operation

Depends on client requirements, parts from accessories, spare parts for breaker catalogue HG
11.02, page 37 can be offered

List for 5 year operation

Depends on client requirements, parts from accessories, spare parts for breaker catalogue HG
11.02, page 37 can be offered

IC LMV MV1 PPM, Herbert Soens

issued: 24.10.2011

- 51 / 51 -