Power Cube:
S. No

ALM

ALM1

ALM2

3
4

ALM3
ALM4

ALM5

ALM6

DO_2

Card

UPEU EXT1
TO
CPMU

UPEU EXT0
TO
CPMU

UPEU EXT0
TO
HPMU DO2
8
DI_5
BATT ROOM
TO
HPMU DO5
9
EXT0(UEI
UEIU EXT0
U)
TO
Civil ALM
BOX(8,9)
DO2: (White Blue/Blue) is From BBU

ALM Name

ALM Color Code

AC OFF ALM

White
Orang/Orange
White
Green/Green
White Blue/Blue
White
Brown/Brown
White
Orange/Orange
White
Green/Green
White Blue/Blue

DC LOW ALM
RECT FAULT AL
SMOKE ALM
DOOR ALM
HIGH TEMP ALM
GEN FAULT ALM

ALM
CODE
65101
65108
65125
65103
65104
65105
65109

BATT DOOR ALM

White
Orange/Orange

65104

TOWER LIGHT
ALM

White
Orange/Orange

65107

(UPEU - EXT- ALM-0) to HPMU (D0-2)

DO5: Battery Door Alarm (White Orange/White) is connected here.


UEIU EXT1 White blue/Blue is connected in battery room for Battery AC.
UEIU EXT0 White Orange/Orange is connected for Tower light

Mini Shelter:
S.

ALM

By Asad Iqbal Jamal

Card

ALM Name

ALM Color Code

ALM

By Engnr.Asad Iqbal Jamal


No
1

Location
ALM1

ALM2

ALM3

ALM4

ALM5

UPEU
EXT1

MAJ PWR
FAILURE
DC LOW ALM
RECT FAULT
ALM
EMPTY
CONNECTED
SMOKE ALM

UPEU EXT0
6

ALM6

7
8

ALM7
ALM8

EXT0(UEIU
)

HIGH TEMP
ALM
DOOR ALM
AC OFF
UEIU

TOWER LIGHT

White
Orang/Orange
White
Green/Green
White Blue/Blue
White
Brown/Brown
White
Orang/Orange
White
Green/Green
White Blue/Blue
White
Brown/Brown
White
Orang/Orange

Code
65110
65108
65125

65103
65105
65104
65101
65107

Power Cube:
Power Cube Alarm Configuration:
There are two parts two alarm configuration (1) HPMU (2) CMPU.
HPMU Port Configuration:
Here we can configure only two alarms 1.Genset Fault, 2. Battery Door.
Battery Door is already configured no need to configure while Genset Fault
can be configured on HPMU DO2 as,
Step 1 >Go to>Setting
Step 2 >Go to>Put Password as (0)
Step 3 >Go to>Alarm Setting
Step 4 >Go to>Dry Node
Step 5 >Go to>Adio Backup DO2 (Make DO2 SDG Fail)
So Now DO2 is configured for Genset Fault ALM.
CPMU Port Configuration:
AC OFF, DC LOW, HIGH TEMP, RECTIFIRE FAULT, SMOKE can be configured on
CPMU as,
By Asad Iqbal Jamal

By Engnr.Asad Iqbal Jamal

Step 1 >Go to>Setting


Step 2 >Go to>Alarm Setting
Step 3 >Go to>Relay Relate
Step 4 >Go to>Alarm (Configured each Alarm on desired port.

Power Cube Alarm Generation or Checking.


1. AC OFF:
Turn off the AC breaker AC Alarm will be appeared. If check the cable
connection in the battery door upper most corner right side. For
clearing this alarm turn on the AC braker.
2. DC LOW:
This is the most difficult alarm to generate. It can be generated in
many ways but on simple way is given as,
Step 1 >Go to HPMU> Setting
Step 2 >Go to>Put Password as (0)
Step 3 >Go to>Critical Point
Step 4 >Go to>Battery Under Volta:( Make it Maximum or 51.5V)
Step 5 >Go to CPMU>Setting
Step 6 >Go to>Battery Setting
Step 7 >Go to>Charge
Step 8 >Go to>Boost (Make It maximum or 57.5)
Step 9 >Go to>Click on Back Button and Press DC Setting
Step 10 >Go to>Under Volt (Make it Maximum or 51.5)
You will found DC low Alarm. It can remove by putting the original values
back in the HPMU and CPMU.
Reminder: This Alarm can be Generated Only and Only when voltage is
greater than 53.3V and keep the Genset off for generation.

By Asad Iqbal Jamal

By Engnr.Asad Iqbal Jamal

3. RECTIFIRE FAULT:
Take a cable tie and stop the fan in any rectifier module for 2minutes, a
beef sound will produce and alarm will appear. For clearing remove the
cable tie after a minute beef will stop and alarm will be clear.
4. SMOKE ALARM:
Produce the Smoke near to the smoke sensor. Smoke alarm will appear.
For clearing this alarm remove the green connector back to smoke
sensor and then insert back.
5. DOOR ALARM:
Open the Door alarm will appear and closed the door alarm will
disappear.
6. HIGH TEMP:
Step 1>Go to> Setting
Step 2>Go to>Ambient Temp Setting (Make it 25 or less alarm will
appear. To clear it back make the value again the original.

7. Genset Fault:
Stop the Generator and put the AC main braker turn off. It will appear
and do its vice versa to clear this alarm.
8. Genset Running:
Make only this alarm polarity high in the power cube, then start the
Genset alarm will appear and stop alarm will disappear.
9. Tower Light Alarm:
Turn off the tower light power alarm will appear, if not then climb up
the tower and hide the light sensor from light, wait for few minutes
while keeping the Tower Light power off. Alarm will appear and do vice
versa to clear the alarm.