Characteristics of run sections
Symbol

Unit

General characteristics

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Compliance with standards

IEC/EN 60439-2

Protection degree

IP

55
Any installation (indoors only) is possible for the busbar truncking: edgewise,
flat or vertical. See test condition, page 153.

Shock resistance

IK

Nominal rated current at an ambient temperature of


3&

Inc

08

Rated insulation voltage

Ui

Rated operating voltage

Ue

Operating frequency

Hz

G 50/60 (for 60 to 400 Hz AC or for DC, consult us)

Allowable rated short-time withstand current (t = 1 s)

Icw

kA

50

50

65

110

113

Allowable rated peak current

Ipk

kA

110

110

143

242

248

Maximum thermal stress I2t (t = 1s)

I2t

A2s 106

2500

2500

4225

4900

m /m

0.041

0.029

0.024

m /m

0.049

0.035

0.029

1000

1350

1600

2000

2500

3200

4000

5000

86

90

95

189

198

209

6400

7396

8100

9025

0.018

0.014

0.012

0.009

0.007

0.022

0.018

0.015

0.012

0.009

1000
1000

Short-circuit current withstand


Standard version 3L + PE

Conductor characteristics
Phase conductors
$YHUDJHUHVLVWDQFHDWDQDPELHQWWHPSHUDWXUHRI& R20
R1
Average resistance at Inc and at 3&
Average reactance at Inc and at 3&DQGDW+]

X1

m /m

0.022

0.016

0.015

0.013

0.011

0.008

0.007

0.007

Average impedance at Inc and at 3&DQGDW+]

Z1

m /m

0.054

0.039

0.033

0.026

0.021

0.017

0.014

0.012

$YHUDJHUHVLVWDQFHDWDQDPELHQWWHPSHUDWXUHRI&

m /m

0.203

0.178

0.164

0.143

0.126

0.113

0.093

0.080

Casing
(Equivalent copper cross-section)

PP

120

130

140

155

165

180

190

200

PE = casing

Fault loop characteristics


Fault loop
Ph/PE
characteristics DW&

Impedance
method

Average resistance

R0 ph/PE

m /m

0.688

0.566

0.509

0.435

0.378

0.335

0.279

0.238

Average reactance

X0 ph/PE

m /m

0.666

0.489

0.410

0.315

0.247

0.196

0.147

0.113

Average impedance

Z0 ph/PE

m /m

0.958

0.748

0.654

0.537

0.452

0.388

0.315

0.263

Ph/Ph Rb0 ph/ph

m /m

0.078

0.056

0.047

0.036

0.029

0.025

0.019

0.015

Ph/PE Rb0 ph/PE

m /m

0.439

0.351

0.298

0.239

0.199

0.170

0.135

0.110

At Inc and Average resistance


at 3&

Ph/Ph Rb1 ph/ph

m /m

0.094

0.068

0.057

0.044

0.036

0.032

0.024

0.019

Ph/PE Rb1 ph/PE

m /m

0.527

0.428

0.364

0.292

0.247

0.214

0.173

0.141

At Inc and Average reactance


at 3&
and at
50 Hz

Ph/Ph Xb ph/ph

m /m

0.040

0.029

0.024

0.019

0.015

0.013

0.010

0.008

Ph/PE Xb ph/PE

m /m

0.426

0.329

0.275

0.212

0.170

0.141

0.106

0.084

$W&

Average resistance

Other characteristics
Voltage drop
Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
For a cosine

of

V/100 m/A

0.0043

0.0031

0.0026

0.0019

0.0015

0.0013

0.0010

0.0008

0.9

V/100 m/A

0.0047

0.0034

0.0029

0.0022

0.0018

0.0015

0.0012

0.0010

0.8

V/100 m/A

0.0046

0.0033

0.0028

0.0022

0.0018

0.0015

0.0012

0.0010

0.7

V/100 m/A

0.0044

0.0031

0.0027

0.0021

0.0018

0.0014

0.0012

0.0010

kg/m

19

25

29

36

44

51

66

82

kWh / m

2.1

2.9

3.2

3.9

5.7

6.2

8.9

11.2

0.4

0.5

0.75

0.9

1.3

1.6

2.1

3.0

Average weight
3L + PE

Fire load value

Radiated magnetic field


Radiated magnetic field strength 1 metre from the
trunking

134

version: 1.1

K9CE39000.indd

'EREPMW/8'024)

Characteristics of run sections


Symbol

Unit

General characteristics

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Compliance with standards

IEC/EN 60439-2

Protection degree

IP

55
Any installation (indoors only) is possible for the busbar truncking: edgewise,
flat or vertical. See test condition, page 153.

Shock resistance

IK

Nominal rated current at an ambient temperature of


3&

Inc

08

Rated insulation voltage

Ui

Rated operating voltage

Ue

Operating frequency

Hz

G 50/60 (for 60 to 400 Hz AC or for DC, consult us)

Allowable rated short-time withstand current (t = 1 s)

Icw

kA

50

50

65

70

80

Allowable rated peak current


Maximum thermal stress I2t (t = 1s)

Ipk
I2t

kA
A2s 106

110
2500

110
2500

143
4225

154
4900

176
6400

R20
R1
X1
Z1

m
m
m
m

/m
/m
/m
/m

0.041
0.049
0.022
0.054

0.029
0.035
0.016
0.039

0.024
0.029
0.015
0.033

0.018
0.022
0.013
0.026

m /m
PP

0.203
120

0.178
130

0.164
140

R0 ph/N
X0 ph/N
Z0 ph/N
R0 ph/PE
X0 ph/PE
Z0 ph/PE

m
m
m
m
m
m

/m
/m
/m
/m
/m
/m

0.192
0.124
0.229
0.688
0.666
0.958

0.138
0.089
0.164
0.566
0.489
0.748

Ph/Ph
Ph/N
Ph/PE
Ph/Ph

Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph

m
m
m
m

/m
/m
/m
/m

0.078
0.080
0.439
0.094

Ph/N

Rb1 ph/N

m /m

Ph/PE
Ph/Ph
Ph/N
Ph/PE

Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE

m
m
m
m

1000

1350

1600

2000

2500

3200

4000

5000

86

90

95

189
7396

198
8100

209
9025

0.014
0.018
0.011
0.021

0.012
0.015
0.008
0.017

0.009
0.012
0.007
0.014

0.007
0.009
0.007
0.012

0.143
155

0.126
165

0.113
180

0.093
190

0.080
200

0.116
0.075
0.138
0.509
0.410
0.654

0.089
0.058
0.106
0.435
0.315
0.537

0.071
0.044
0.084
0.378
0.247
0.452

0.062
0.040
0.074
0.335
0.196
0.388

0.046
0.030
0.055
0.279
0.147
0.315

0.037
0.024
0.044
0.238
0.113
0.263

0.056
0.057
0.351
0.068

0.047
0.048
0.298
0.057

0.036
0.037
0.239
0.044

0.029
0.029
0.199
0.036

0.025
0.026
0.170
0.032

0.019
0.019
0.135
0.024

0.015
0.015
0.110
0.019

0.096

0.070

0.059

0.045

0.036

0.032

0.024

0.020

0.527
0.040
0.065
0.426

0.428
0.029
0.047
0.329

0.364
0.024
0.040
0.275

0.292
0.019
0.030
0.212

0.247
0.015
0.024
0.170

0.214
0.013
0.021
0.141

0.173
0.010
0.016
0.106

0.141
0.008
0.013
0.084

1000
1000

Short-circuit current withstand


Standard version 3L + N + PE

Conductor characteristics
Phase conductors
$YHUDJHUHVLVWDQFHDWDQDPELHQWWHPSHUDWXUHRI&
Average resistance at Inc and at 3&
Average reactance at Inc and at 3&DQGDW+]
Average impedance at Inc and at 3&DQGDW+]

PE = casing
$YHUDJHUHVLVWDQFHDWDQDPELHQWWHPSHUDWXUHRI&
Casing
Equivalent copper cross-section

Fault loop characteristics


Fault loop
Ph/N
Average resistance
characteristics DW& Average reactance
Average impedance
Ph/PE
Average resistance
DW& Average reactance
Average impedance
Impedance
method

$W&

Average resistance

At Inc and Average resistance


at 3&

At Inc and Average reactance


at 3&
and at
50 Hz

/m
/m
/m
/m

Other characteristics
Voltage drop

For a cosine

of

Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
1
V/100 m/A 0.0043 0.0031 0.0026 0.0019 0.0015 0.0013 0.0010 0.0008
0.9
V/100 m/A 0.0047 0.0034 0.0029 0.0022 0.0018 0.0015 0.0012 0.0010
0.8
V/100 m/A 0.0046 0.0033 0.0028 0.0022 0.0018 0.0015 0.0012 0.0010
0.7
V/100 m/A 0.0044 0.0031 0.0027 0.0021 0.0018 0.0014 0.0012 0.0010

Average weight
3L + N + PE

kg/m

25

33

39

49

60

71

92

114

kWh / m

2.5

3.6

4.1

5.9

7.3

8.0

11.5

14.4

0.4

0.5

0.75

0.9

1.3

1.6

2.1

3.0

Fire load value

Radiated magnetic field


Radiated magnetic field strength 1 metre from the
trunking

K9CE39000.indd

version: 1.1

135

Characteristics

(IWMKRKYMHI

'EREPMW/8'024)6
Canalis KTC
Characteristics of run sections
Symbol

Unit

General characteristics
Compliance with standards
Protection degree

Shock resistance
Nominal rated current at an ambient temperature of
3&
Rated insulation voltage
Rated operating voltage
Operating frequency

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50
IEC/EN 60439-2
55
Any installation (indoors only) is possible for the busbar truncking: edgewise,
flat or vertical. See test condition, page 153.
08
1000
1350
1600
2000
2500
3200
4000
5000

IP

IK
Inc

Ui
Ue
f

V
V
Hz

G 50/60 (for 60 to 400 Hz AC or for DC, consult us)

Allowable rated short-time withstand current (t = 1 s)

Icw

kA

50

50

65

70

80

86

90

95

Allowable rated peak current


Maximum thermal stress I2t (t = 1s)

Ipk
I2t

kA
A2s 106

110
2500

110
2500

143
4225

154
4900

176
6400

189
7396

198
8100

209
9025

Icw
Ipk
I2t

kA
kA
A2s 106

65
143
4225

65
143
4225

85
187
7225

110
242
12100

113
248
12769

113
248
12769

120
264
14400

120
264
14400

R20
R1
X1
Z1

m
m
m
m

/m
/m
/m
/m

0.041
0.049
0.022
0.054

0.029
0.035
0.016
0.039

0.024
0.029
0.015
0.033

0.018
0.022
0.013
0.026

0.014
0.018
0.011
0.021

0.012
0.015
0.008
0.017

0.009
0.012
0.007
0.014

0.007
0.009
0.007
0.012

m /m
PP

0.050
210

0.039
300

0.034
360

0.026
480

0.022
600

0.019
720

0.014
960

0.012
1200

R0 ph/N
X0 ph/N
Z0 ph/N
R0 ph/PE
X0 ph/PE
Z0 ph/PE

m
m
m
m
m
m

/m
/m
/m
/m
/m
/m

0.189
0.087
0.208
0.206
0.067
0.217

0.134
0.061
0.148
0.157
0.051
0.164

0.113
0.054
0.125
0.135
0.043
0.142

0.085
0.042
0.095
0.106
0.034
0.111

0.069
0.041
0.080
0.087
0.028
0.091

0.057
0.029
0.064
0.074
0.024
0.078

0.043
0.022
0.049
0.057
0.019
0.060

0.035
0.018
0.039
0.047
0.015
0.049

Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph
Rb1 ph/N
Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE

m
m
m
m
m
m
m
m
m

/m
/m
/m
/m
/m
/m
/m
/m
/m

0.083
0.087
0.105
0.099
0.104
0.126
0.028
0.043
0.050

0.058
0.059
0.077
0.071
0.072
0.094
0.020
0.032
0.040

0.048
0.019
0.065
0.059
0.060
0.080
0.017
0.028
0.035

0.036
0.239
0.050
0.044
0.045
0.061
0.013
0.021
0.039

0.029
0.199
0.041
0.036
0.036
0.051
0.011
0.017
0.023

0.024
0.170
0.034
0.030
0.031
0.043
0.009
0.015
0.020

0.018
0.135
0.026
0.023
0.023
0.033
0.004
0.011
0.016

0.014
0.110
0.021
0.019
0.019
0.027
0.006
0.009
0.013

1000
1000

Short-circuit current withstand


Standard version 3L + N + PER

Reinforced version 3L + N + PER (optional)


Allowable rated short-time withstand current (t = 1 s)
Allowable rated peak current
Maximum thermal stress

Conductor characteristics
Phase conductors
$YHUDJHUHVLVWDQFHDWDQDPELHQWWHPSHUDWXUHRI&
Average resistance at Inc and at 3&
Average reactance at Inc and at 3&DQGDW+]
Average impedance at Inc and at 3&DQGDW+]

PE = internal copper protective conductor


$YHUDJHUHVLVWDQFHDWDQDPELHQWWHPSHUDWXUHRI&
Copper cross-section

Fault loop characteristics


Fault loop
Ph/N
characteristics at 3&
Ph/PE
at 3&

Impedance
method

Average resistance
Average reactance
Average impedance
Average resistance
Average reactance
Average impedance

$W&

Average resistance Ph/Ph


Ph/N
Ph/PER
At Inc and Average resistance Ph/Ph
at 3&
Ph/N
Ph/PE
At Inc and Average reactance Ph/Ph
at 3&
Ph/N
and at
Ph/PE
50 Hz

Other characteristics
Voltage drop

For a cosine

of

Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
1
V/100 m/A 0.0043 0.0031 0.0026 0.0019 0.0015 0.0013 0.0010 0.0008
0.9
V/100 m/A 0.0047 0.0034 0.0029 0.0022 0.0018 0.0015 0.0012 0.0010
0.8
V/100 m/A 0.0046 0.0033 0.0028 0.0022 0.0018 0.0015 0.0012 0.0010
0.7
V/100 m/A 0.0044 0.0031 0.0027 0.0021 0.0018 0.0014 0.0012 0.0010

Average weight
3L + N + PER

kg/m

25

33

39

49

60

71

92

114

kWh / m

2.5

3.6

4.1

5.9

7.3

8.0

11.5

14.4

0.4

0.5

0.75

0.9

1.3

1.6

2.1

3.0

Fire load value


Radiated magnetic field
Radiated magnetic field strength 1 metre from the
trunking

136

version: 1.1

K9CE39000.indd

3XLIVGLEVEGXIVMWXMGW

Characteristics of run sections


Symbol

Unit

Other characteristics

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

&KRLFHRISURGXFWVZKHQKDUPRQLFVDUHSUHVHQW VHHKDUPRQLFFXUUHQWVIRUPRUHGHWDLOV 
Rated current according to THD3 (3rd order
distortion)

THD < 15 %

1000

1350

1600

2000

2500

3200

4000

5000

15 % < THD < 33 %

1000

1350

1600

2000

2500

3200

4000

THD > 33 %

1000

1350

1600

2000

2500

3200

Allowable current as a function of ambient temperature


&DQDOLVEXVEDUWUXQNLQJLVVL]HGWRRSHUDWHDWDQDPELHQWDLUGRHVQRWH[FHHG&DQGLWVDYHUDJHRYHUDSHULRGRIKGRHVQRWH[FHHG
+3&DERYHWKLVYDOXHWKHEXVEDUWUXQNLQJPXVWEHGHUDWHG
Where k1 = ambient temperature derating coefficient.
Ambiant temperature 24 hours average
&

35

40

45

50

Busbar trunking installed indoors

k1

k1=1

k1=0.95

k1=0.90

k1=0.84

Busbar trunking installed outside under an


aluminium roof

k1

Busbar trunking installed in a fire duct

k1

See "Busbar trunking installed outside under an aluminium roof"


on page 139.
Please, see your sales office.

Through-wall fire barrier


Tests performed in accordance with the requirements of NF EN 1363-1 and those specific to EN 1366-3.
Performance criteria
Fire integrity

Thermal
insulation

Without external fire barrier

120 mn

30 mn

With external fire barrier

120 mn

120 mn

Tap-off unit characteristics


General characteristics

Symbol

Protection degree

IP

Shock resistance

IK

Rated insulation voltage

Ui

Rated operating voltage

Ue

Operating frequency

Hz

K9CE39000.indd

Unit
55
08
400 or 500 depending on protection device
50/60

version: 1.1