Operating Manual
For

ASHIDA Numerical Self-Powered


Protection Relay
Type: - ADR241S

Mode l: AM-411-08-01-XX-XX-XX-XX.

REV
06

DESCRIPTION

DATE

Operating Manual For Ashida Numerical Self-Powered 10.01.2013


Protection Relay ADR 241S

CHK. BY

APPD. BY

PD

SMK

User Notice
Ashida Electronics (P) Ltd. Reserve all right to make improvements in the
products described in this manual at any time and without notice. All rights are
reserved. No part of this manual may be reproduce, copied, translated or
transmitted in any form or by any means without the prior written permission of
Ashida Electronics (p.) Ltd. Information in this manual is intended to be accurate
and reliable. However Ashida assumes no responsibility for its use; nor for any
infringements of rights of third parties that may result from its use.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 2 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

INDEX
No.
1.0
2.0
3.0
3.1
3.2
3.3
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
11.1
11.2
12.0
13.0
14.0
15.0
16.0
17.0
17.1
17.2
17.3
17.4
17.5
17.6
17.7
17.8
17.9
17.10
17.11
17.12
17.13

Topic
Features
General
Protection Function
Over Current / Earth Fault Protection
3 Phase Over Load Function
Cold Load Pickup
Measurement & Communication Function
Impulse Output for Tripping Coil
Supervision Function
Electrical Noise Immunity
Inrush Blocking
Current Transformer Requirement
Setting Reliability
On Line Testing
On Line Testing using Test Block
Drawing On line Testing using Test Block
Front Panel And Control
Ordering Information
Battery Function
Getting Started
To View Measurement Window
To Adjust General Setting
Password settings
New Password
Set Hours
Set Minutes
Set Seconds
Set Date
Set Month
Set Year
Unit ID
Baud Rate
Set Parity
Trip Test
Frequency Selection

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page No
6
6
7
7
8
9
12
12
12
12
13
13
14
15
15
16
17
19
20
21
23
23
23
24
24
25
25
25
25
26
26
26
26
27
27

Page: 3 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

No.
17.14
17.15
17.16
17.17
17.18
18.0
19.0
19.1
19.2
19.3
19.4
19.5
19.6
19.7
19.8
19.9
19.10
19.11
19.12
19.13
19.14
19.15
19.16
19.17
20.0
21.0
21.1
21.2
21.3
21.4
21.5
21.6
21.7
21.8
21.9
21.10
21.11
21.12
21.13

Topic
External Relay
Trip Block
CT Primary
Inrush Restrain
Save Settings
To View General Settings
To Adjust Protection Settings.
Password Settings
Bank Selection
Ip> (OC)
Ip> TMS (OC)
Ip> Curve Selection
Ip> C6 Time
Ip>> (OC)
Ip>> Delay
IE> (EF)
IE TMS (EF)
IE> Curve Selection
IE> C6 Time
IE>> (EF)
IE>> Delay
3-ph OL
3-ph OL Delay
Save Settings
To View Protection Settings
To Adjust Cold Load Setting
Password
CL Enable
CL Timer
Ip> (OC)
Ip> TMS (OC)
Ip> Curve Selection
Ip> C6 Time
Ip>> (OC)
Ip>> Delay
IE> (EF)
IE TMS (EF)
IE> Curve Selection
IE> C6 Time

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page No
27
28
28
28
29
29
30
30
31
31
32
32
32
33
33
33
34
34
34
34
35
35
35
35
36
37
37
38
38
38
38
39
39
39
40
40
40
41
41

Page: 4 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

No.
21.14
21.15
21.16
22.0
23.0
24.0
25.0
26.0
26.1
26.2
26.3
26.4
26.5
26.6
26.7
27.0
28.0
29.0
29.1
30.0
31.0
32.0
33.0
34.0
35.0
36.0
37.0
38.0

Topic
IE>> (EF)
IE>> Delay
Save Settings
To View Cold Load Settings
To View Faults
To View Error Log
To View Status
Flow Chart
Flow Chart for Measurements
Flow Chart for General Setting
Flow Chart to Protection Settings
Flow Chart to Cold Load Settings
Flow Chart to Faults
Flow Chart to Error Log
Flow Chart to Status
To clear password and fault memory
Sample Test Report
Technical Specification
Conformance to Standard
Typical External Connection
Curve 1
Curve 2
Curve 3
Curve 4
Curve 5
Mechanical Details
Troubleshooting Guideline
Revision Notes

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page No
41
42
42
43
43
46
47
48
48
49
50
51
52
52
53
53
54
56
58
60
61
62
63
64
65
66
67
68

Page: 5 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

1.0 Features: -

Auxiliary Voltage supply is not required. (Relay can also be operated on


Aux. voltage supply, if required).
Low energy pulse output tripping for RMU, Shunt Trip & Series Trip type
Switchgear.
User friendly setting procedure with wide setting range.
4 Element (3 Phase + 1 Earth Fault) Over current IDMT/ Definite time and
Instant Trip.
Inrush current blocking.
Cold Load pickup for prolong inrush current.
Special Overload setting for Phase.
RS232 and RS485 Communication Port for remote SCADA.
On line Test Terminal Block arrangement (By using D15 Type Connector at
the Back side of the Relay).
Programmable (Non Volatile) setting by local keyboard as well as remote
setting by communication port.
LCD Display for settings / parameters.
Display of Fault current as well as Load current.
Latching of last 5 faults with relay time.
Selectable Inverse Time Characteristics (Five selectable curves) : Normal
Inverse1 (C1), Normal Inverse2 (C2), Very Inverse (C3), Extremely Inverse
(C4), Long Time Inverse (C5), Define time (C6).
Separate curve setting for phase and EF.
Internal Battery for maintaining LCD display and communication during fault
condition.
Designed using DSP technology.
Latching of Fault Current and storing in a non-volatile memory with time
stamping.
External status input for Remote Trip & Three Status S1, S2 & S3 for SCADA
purpose.
External latching type potential free contacts.
Back-lit LCD display.

2.0 General: ADR241S is second generation of Numerical Self Power Over current IDMT/DMT
Relay. It consist all the necessary protection and monitoring functions required for
compact RMU. The High speed Digital Signal Controller continuously monitors line
phase current and E/F current. Along with different status input, through CTs, and
optical isolated status connections. The high-speed micro-controller samples

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 6 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

these current signals through A/D converter. The Digital Signal performs powerful
Numerical Algorithms to find out RMS of fundamental & harmonic contents of the
current. All measurement is tuned to fundamental frequency i.e. 50Hz or 60Hz
depending upon setting, thus relay remain stable during distorted waveform by
various industrial load. All these measure values are then used for different
protection function such as IDMT Over current protection, Instantaneous Over
current protection, E/F protection etc. These measured values are also displayed
on large 16 x 2 LCD display for metering purpose. The power supply module is
special electronics circuit which derived relay power from current flowing through
line; no any external power supply is needed. The minimum requirement of current
to build power supply for relay electronics is 20% in any one of the phases or 12%
in any 2 phases or 8% in all three phases. Relay provides pulse output to trip
RMU or compact CB having low energy tripping coil.
A battery for feeding the LCD display and SCADA communication buffers the
relay. After tripping operation relay maintains fault indication on LCD display.
During this time, the relay uses power through internal battery. The relay can
maintain fault indication till the relay is manually reset by using + / key. Failure
of the battery has no effect on the protection function of the relay. The battery has
a service life of more than 5 years.
3.0 Protection Function: 3.1 Over Current / Earth Fault Protection: The relay has inverse time over current / earth fault function as well as
instantaneous protection for both. Following is summary of different protection
functions provided by relay.
ANSI
50
50N
51
51N

IEC
I >>
IE >>
I>T, Ip
IE >t, IEP

Protection Function
Instantaneous Over Current Protection.
Instantaneous Earth Fault Protection.
Time Over Current Protection (Phase).
Time Over Current Protection (Earth).

The relay has 4 sensing elements 3 O/C and 1 E/F. The tripping current can be
set to 20% -240% in steps of 1% for phase and 10% - 100% in steps of 1% for
earth fault by keyboard provided on front panel. These settings are available on
display. The unit has selection of IDMT characteristic of IEC standard Normally

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 7 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Inverse1 (C1), Normally Inverse2 (C2), Very Inverse (C3), Extremely Inverse (C4),
Long Time Inverse (C5) and defines time (C6). The unit also has Time Multiplier
Setting (TMS) from x0.01 to x1.2 in steps of x0.01 (separate for phase and EF) for
IDMT delay multiplication. Separate operating curve can be programmed for
phase and EF. The instantaneous tripping function has range of 50% - 3200% in
steps of 50% for phase and 50% - 1200% in steps of 50% for earth fault. The high
speed CPU continuously monitors all four current inputs and compares with IDMT
as well as instantaneous setting. If anyone current is above instantaneous setting,
the relay provides immediate trip command bypassing IDMT delay.
If input current is less than instantaneous setting but more than IDMT setting, CPU
calculates IDMT delay as per selected IDMT characteristic, multiplies it with TMS
setting and issue trip command if fault is persist even after this time delay.
For EF tripping, there must be current greater than or equal to 20% of the rated
current in any one phase of the relay.
3.2 3 Phase Over Load Function: The relay is having the overload function for the phases. The setting range for the
3 phase overload is 10 200 % in steps of 1% and the time delay is settable form
1s to 30000 secs in steps of 1 sec.
Please note: relay will operates on 10% only when the current flowing through all
the 3 CTs is around 7-8 % of the rated.
Following are some of the cases where we can use the overload function:

When connected distribution transformer is of very low KVA rating:

For example:
Transformer Rating: 100KVA
Transformer Voltage: 11 / 0.440 KV
Rated load at 11KV side: 5A
Connected C.T. Ratio: 40/1 A
As the rated load is very low i.e. 12% of the CT and the setting for IDMT over
current is available from 20%, so we can set the overload setting for 10% and the
time delay at the required value i.e. from 1s to 30000 secs and the IDMT setting at
require value. Hence we can able trip the transformer by using overload function
after desired set time.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 8 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

When connected distribution transformer is of normal KVA rating:

For example:
Transformer Rating: 1000KVA
Transformer Voltage: 11 / 0.440 KV
Rated load at 11KV side: 52A
Connected C.T. Ratio: 80/1 A
In above case the rated load is 65%, so we can set the overload setting at 65%
and the time delay for the overload at require value between 1s to 30000secs. The
IDMT over current setting can be set at 70% and the IDMT delay as per the
requirement.
Thus we can allow the overload of 65% for the allowable time and if the overload
persists after the set overload time the transformer will get tripped with the
overload. The normal IDMT over current & EF protection can be taken care By
Ip>, IE> & the IDMT settings.
3.3 Cold load pick-up Function:
The relay is having special cold load pick-up function to avoid tripping due to
prolong inrush current. The setting range is given same as the normal protection
setting with additional cold load time delay settable from 0.01 to 10.0 secs.
Cold load pick-up function can use to avoid tripping during switching ON C.B. and
position of C.B. can be watched by connecting its auxiliary contact C.B. NO to
dedicated Digital input S1 of Relay.
As per observation normally in distribution system and as per gradation
Instantaneous setting and Ip> TMS required to set very low and due to this relay
can operate during switching on C.B.
In ADR241S Instantaneous elements have inrush blocking function during
switching on condition of CB but relay can operate in IDMT if inrush current flow
for sufficient time to operate relay as per TMS setting.
To avoid such condition Cold Load Pick-up can use in which we can set cold load
setting higher than regular protection setting for selected definite time delay Cold
Load Timer. As Clod Load Timer is finish relay will switch over to normal
Protection Setting.
If we are switching C.B. on fault condition relay will still provide protection as it can

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 9 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

operate when fault current is more than cold load setting and same can be
identified as in fault history CLT trip will appear in SF (status flag).
Following are some examples for getting the idea of cold load pick-up:
Relay ADR241S is connected with RMU on 11KV system with following setting
and Digital input S1 wired up with CB-NO.
Sr.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Protection
Setting

Particular Setting
Cold Load Timer CL Timer
Ip> %
Ip> TMS
Ip> Curve
Ip> C6 Time
Ip>> %
Ip>> Delay
IE> %
IE> TMS
IE> Curve
IE> C6 Time
IE>> %
IE>> Delay
3 Ph OL %
3 Ph OL Delay

NA
100%
0.05
C1(10N=3Sec)
00.1 Sec.
300%
0.05 Sec.
20%
0.05
C1(10N=3Sec)
00.1 Sec
150%
0.05 Sec
90%
600 Sec.

Cold Load
Setting
0.5 Sec.
100%
0.15
C1
00.1
1000%
0.05
20%
0.15
C1(10N=3Sec)
00.1 Sec
400%
0.05 Sec
NA
NA

Case 1: (Current peak is high in amplitude and small in duration) Inrush current
peak is 9 times of the rated CT for the duration of 0.5 s in R, Y & B
With above setting as CB switch ON the S1 digital input will also in ON
condition, cold load setting will comes in picture for selected delay 0.5 Sec.
As our peak current is 9A, the instantaneous element will not operate (as per
the setting it is set at 10A).
As per the over current setting in cold load Ip> = 100% & Ip> TMS = 0.15,
Operating time will be as per the Formula:
T= (0.14*0.15)/ ((9^0.02)-1)
= 0.467 Sec.
As peak current is for 0.5 Sec. and the calculated time in cold load is 0.4675s
relay will operate in Cold Load. In such case we have to increase the TMS
setting in cold load.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 10 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Case 2: (Current peak is high in amplitude and high in duration) Inrush current
peak is 7 times of the rated CT for the duration of 0.6 s in R, Y & B.
As our peak current is 7A, the instantaneous element will not operate (as per
the setting it is set at 10A) in this case also.
As per the over current setting in cold load Ip> = 100% & Ip> TMS = 0.15,
Operating time will be as per the Formula:
T= (0.14*0.15)/ ((7^0.02)-1)
= 0.529 Sec.
As per the above calculation of IDMT delay of the cold load settings the
calculated delay is less than the duration of peak current ,but the set cold load
delay is set at 0.5s (Less than the calculated delay) the relay will not operate
with cold load. After 0.5s it will switch to the Protection Settings. The operating
time as per IDMT for the protection setting will be:
T= (0.14*0.05)/ ((7^0.02)-1)
= 0.176 Sec.
By adding the above calculated delay in the cold load delay the operating time
will be: 0.5s + 0.176s = 0.676s (This is more than the peak duration). But the
Ip>> setting is 300 %( less than the current peak) and the IP>> Delay is 0.05s,
the relay will operate with HF in protection settings within 50 ms time delay (as
the peak duration is more than the calculated time i.e. 0.5s + 0.05s = 0.55s). In
such case we will have to increase the cold load delay.
Case 3: (Current peak is low in amplitude and high in duration) Inrush current
peak is 2.2 times of the rated CT for the duration of 1 s in R, Y & B.
As our peak current is 2.2A, the instantaneous element will not operate (as per
the setting it is set at 10A) in this case also.
As per the over current setting in cold load Ip> = 100% & Ip> TMS = 0.15,
Operating time will be as per the Formula:
T= (0.14*0.15)/ ((2.2^0.02)-1)
= 1.321 Sec.
As per the above calculation of IDMT delay in the cold load settings the
calculated delay is more than the duration of peak current ,but the set cold load
delay is set at 0.5s (less than the calculated delay) the relay will not operate
with cold load. After 0.5s it will switch to the Relay Settings. The operating time

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 11 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

for the protection setting will be:


T= (0.14*0.05)/ ((2.2^0.02)-1)
= 0.440 Sec.
By adding the above calculated delay in the cold load delay the total operating
time will be: 0.5s + 0.440s = 0.940s (This is less than the peak duration). Due to
this the relay will operate with protection setting. In this case we have to increase
the cold load timer or I>p TMS in the protection setting.
4.0 Measurements and Communication Function: In normal condition the relay displays all the current values. Using the front
keyboard the display can be programmed to show settings. If current is in fault
range the relay gives trip command. The type of the fault is displayed on LCD
display. During the fault condition, the relay measures the fault current and stores
it in non-volatile memory. The fault current can be read using keyboard on LCD
display. All settings can be done locally as well as remotely via communication
port and saved in non-volatile memory.
5.0 Impulse Output for Tripping Coil: Low Energy tripping coil of the circuit breaker can be connected to the coil terminal
marked as (COIL + and ) at back terminal. The trip energy (12 - 24 V DC 0.1
W/sec) is provided by a capacitor in the protection relay. Length of the trip impulse
is 40ms and pause between the individual pulses depends on the impedance of
the tripping coil and the current level. Pulsing is continued until the CB operates
and fault current become zero.
6.0 Supervisory Function: The relay continuously keeps track on its internal hardware and the moment it
detects any failure of component, a message is displayed on LCD display. The
type of error can be checked by Error Log menu. This feature is very useful for
giving pre information to avoid mal operation.
7.0 Electrical Noise Immunity: Utility and industrial environments are electrically very noisy. Electronics protection
equipment requires careful design and testing to ensure reliable operation in
switchgear. Ashida has applied its expertise and more than 35 years of experience
in field of electronics design to ensure that the ADR241S operates when required,
without nuisance trips. Thanks to the latest micro-controller technology.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 12 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

8.0 Inrush Blocking:


During switching of load the load take sudden surge of magnetising inrush current.
The ordinary protection may sense this current as fault current and give wrong
tripping. The ADR241S relay has a special feature of inrush current blocking. The
relay detects inrush current then block instantaneous element tripping accordingly.
9.0 Current transformers Requirement: The ADR241S relay is self power numerical relay and derived all power required
for it internal operation as well as for it CB operation is derived from external CT.
The proper operation it necessary to select proper rated CT.
The Impedance to current characteristic of ADR241S is as shown in fig. The graph
is non linear, i.e. at low current Z of CT input is high while at high current it low.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 13 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

From impedance Graph of ADR241S, the maximum Voltage required


across the relay terminal at fault current of 20 times of rated:
The Impedance value at 20 Times is 0.62 Ohm
Thus Voltage required is
V Max. = 0.62 x 20

= 12.4V

VA Min. required for external CT is


VA

V max X Safety Factor


Over Load Factor of CT

Considering Safety Factor 2 for Lead resistance / Connecting Impedance Etc.


VA

12.4 x 2

24.8

20
20
= 1.24 VA for CT Class 5P20
= 2.48 VA for CT class 5P10
This is minimum VA required.
Form Definition of the CT
5

Tolerance

10

Over Load

Protection
Class

Factor

The recommended current transformers (CT) are as follows.


Rated Secondary Current

1A

Performance

3.0 VA

Precision

5P10

Service Frequency

50-60 Hz

The actual CT design will be carried out by considering the site condition,
Transformer capacity, required V max. For the relay and fault level. User
should follow necessary design practice.
10.0 Setting Reliability: Any numerical or digital relay in which all settings are programmable via key board
or communication port, use some internal memory to store these settings. Many
relays use internal rechargeable batteries to maintain these settings. In case of

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 14 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

power supply fluctuation, batteries are often unreliable, and settings get corrupted.
In such situation, the relay may mal- operate. Ashida use special non-volatile
memory technology, which do not require any power source to maintain settings of
the relay.
Once the relay is programmed, it maintains the settings for more than 10 years
even in the absence of any power supply. In case if internal fault is detected in this
section during the self diagnosis, then relay gives message.
11.0 On Line Testing: The ADR241S relays are provided with online testing facility. By pressing TEST
key (provided on front panel) the relay immediately provides trip command. This
trip command also gets extended to breaker coil, thus entire trip operation from
relay to circuit breaker can be checked. This trip command is recorded as T flag
on LCD display as shown below.
I>> :

t :0002

I> :

SF : T

If the CB (circuit breaker) operation is un-desirable then, pressing BYPASS key,


the relay trip command can be blocked from extending to CB coil.
(Note: - This Trip Test" function can be enabled through General Settings.)

11.1 On Line Testing by using Test Block.


The Relay is supplied with optional online Testing assignment i.e. Relay is
provided with D15 type connector at the backside of relay for connection of Relay
Testing Unit (TEST BLOCK). By connecting the Test Block via 15-pin cable all the
functions of the relay can be checked in service. While testing, the Trip contact
can be isolated by trip bypass switch on Test Block to avoid any type of tripping
operation. The current injector and the Timer can be connected to relay and entire
verification of the relay can be done.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 15 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

12.0 Front Panel and Control: -

12

6
1
7

2
3
4

5
9

10
11
13

14

No

Legend

Function

1.

ON

LED Power ON indicator. (Required 20% of load


Current).

2.

PKP

LED Relay PICKUP Indicator.

3.

FAULT

LED - FAULT Flag Indicator (HR) Type. Output


element status indicator of Annunciation or Tele
signaling

4.

TRIP

LED Relay TRIP indicator (SR) Type. Output


element status indicator of Trip coil or Spare coil.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 17 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

5.

/
6.

/
RESET
+ /

7.

- /

8.

BAT. ON

9.

TEST

The light symbol is for Back-lit ON indication / [ ] is


for 'MODE'. i.e. To select setting parameter in Main
Menu and to SAVE settings.
Feather Touch Key RESET is for reseting the Flag
and to RESET the Annunciation / Tele signalling
element.
[ + ] to INCREMENT the values & [ ] to
SCROLL the Main Menu.
Feather Touch Key [ - ] is to 'DECREMENT' the values
& [] to View current Settings (in case of General &
Protection Setting window) or recorded data (in case of
faults & measurement window.)
Feather Touch Key to switch ON the Battery.
Feather Touch Key for online TESTING.

10.

BYPASS

11.

HW RESET

Feather Touch Key for HARDWARE RESET of the


relay.

Feather Touch Key for BYPASSING TRIP command.

12.

LCD Display

To observe setting and parameters of the relay .

13.

Battery

14.

RS 232
Connector

Capacity 4.5Volt (1.5V x 3) AAA Lithium,


Non-rechargeable battery.
D type - 9 pin male Connector RS 232 Communication
Port / Programming Port.

Feather Touch Keys


The function of relay is controlled by the Feather Touch Keys TEST, BYPASS, HW
RESET,, RESET + / , - / , and BAT. ON (which are provided on the front
Plate).
(Note: - At the time of setting if changes are not carried within 100s then the display
will reset itself and return to the main menu and the settings get lost.)

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 18 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

13.0 Ordering Information:


The relay is available with nos. of different option. The option is specified by model
no. It is user responsibility to specify correct model no. while ordering.
While Ordering Specify the following Information for ADR241S
Relay
D e f i n i t i o n

o f

M o d e l

N o

o f

Ad i t ya

S e r i e s

o f

R e l a ys

AM XXX XX XX XX XX XX - XX

XX = Communication
Protocol
Not Applicable
00
ASCADA
01
IEC - 103
02

XX = PT.
Not Applicable
00

XX = Auxiliary Supply.
18 52 VAC/DC
26
77 250 VAC/DC
27
XX = Cabinet Size
CSG 122 ( Vertical
08
Bracket/Clamp Mounting )

XX = CT.
1 Amp.
01
5 Amps.
02

Note:
Communication
Protocol is applicable
only for ADR241S.

XX = Cabinet Type
Non Draw out
01

XXX = Sub Type


411

Relay For RMU


Trip Setting OC: 20 -240 % & EF: 10 100 %, OC HF: 50 3200 % in
steps of 50% & EF HF: 50 1200 % in steps of 50%, OC & EF TMS:
X0.1 X1.2. Selectable Frequency 50 or 60 Hz.
Contacts: 2 C/O Latching Type
Status: 3 Status Input
With Test block facility

Ordering information:
ADR241S

AM

XXX

XX

XX

XX

XX

XX

XX

Available Models:
ADR241S-AM-411-08-01-26-01-00-02.
ADR241S-AM-411-08-01-27-01-00-02.
ADR241S-AM-411-08-01-26-01-00-02.
ADR241S-AM-411-08-01-27-01-00-02.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 19 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

14.0 Battery Function: Battery Specification: Capacity 4.5Volt (1.5 x 3) AAA Lithium non-rechargeable
battery, Make Panasonic, Energizer, or equivalent.
The ADR241S relay is Self Power relay, it takes power from CT Current for its
operation, after the tripping operation and when no current is available to view the
Fault Current in the different Phases of the relay, Relay takes power from Battery.
When there is no CT Current press BAT ON Key to view Fault current. When
BAT ON Key is pressed relay will remain ON for 1 Minute and after 1 Minute
relay becomes OFF to save the battery life, but if before completion of 1 Minute
any of the key (Excluding the HW Reset and the Bypass key) is being pressed it
will retriggered for 1 Minute time slab again. When the CT current is at 20% the
relay gets activated. Battery is located in the battery box on the Front Plate and
can be easily replaced by opening the cover.
Conditions of the relay getting switchover momentarily on battery are as
follows.
1.

If the relay is in ON Condition and current drops below 10%.

2.

When the current exceeds to settings i.e. pkp condition but not tripped and
drops below 10%.

Condition of relay getting switchover on battery for 10 Seconds is as


follows.
1.

When relay gets tripped and current becomes Zero.

Note: 1.

The relay uses battery only for indication purpose. Battery is not required for
protection purpose.

2.

AAA Lithium (1.5V x 3) non-rechargeable batteries are placed in Battery


Socket as shown below.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 20 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

15.0 Getting started: After getting Power ON (20% current in any one of the phases or balance load of
7-8 % in all phases) or pressing Bat. ON key the relay display following
message.
Ashida Digital
OC/EF Relay
ADR 241S IEC
ID =0001 V3.08_1
What is displayed is as follows: Relay Name Ashida Digital OC/EF Relay.
Relay Type ADR 241S with IEC103 Protocol
Unit ID for RS 485 communication and software Version V 3.01
If Trip Block setting is set YES through General setting after displaying software
version, window will display as follows
Trip Block = Yes
If Trip Block setting is set NO through General setting after hardware resetting
window will display as follows
Ashida Digital
OC/EF Relay
ADR 241S IEC
ID =0001 V3.08_1
R =0000 Y = 0000
B =0000 N = 0000
Relay Display Online Primary Current of R, Y, B & N.
The relay is having the protection as well as metering function. After Power ON
the relay will start showing actual current flowing through CTs.
ASHIDA believe in continuous improvement of our products, also implementing
the valuable suggestions and feedback from actual user. Whenever we do any

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 21 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

relay firmware modification it is recorded as version change. The relay has the
facility to upgrade firmware at site.
(Note: - To view display in the dark or in low light conditions relay is filled
with back-lit. The back-lit will become ON whenever MODE KEY () is
pressed. Back-lit will remain ON of 30s).
Now, when the - /Key is pressed the secondary current will be displayed as
shown below,
r =00.00 y = 00.00
b =00.00 n = 00.00
Now, when the - /Key is pressed the first setting parameter in the Main Menu
will be displayed as shown below,
Measurement
Now, each time the + / Key is pressed the setting parameters in the Main Menu
will be displayed one by one respectively in the following order.
General
Settings
Protection
Settings
Cold Load
Settings
Faults

Error Logs

Status

Measurement

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 22 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Measurement, General Settings, Protection Settings, Cold Load Settings, Faults,


Error Logs & Status are the different parameters available in the Main Menu.
16.0 To View the Measurement Window: By using the + / Key select to display Measurement in the Main Menu.
Measurement

Now when the - / Key is pressed then following window is displayed.


R =0000 Y = 0000
B =0000 N = 0000
The display shows the primary current of R, Y, B & N flowing through the CTs.
(Note: The relay displays primary current values by considering the set primary
current in general settings.)
Now when the - / Key is pressed then following window is displayed,
r =00.00 y = 00.00
b =00.00 n = 00.00
The display shows the secondary current of R, Y, B & N flowing through the CTs.
Then, the - / Key is pressed again, the relay will return to Main Menu to show,
Measurement

Now, by using the + / Key, select General Settings window in the Main Menu.
17.0 Adjusting the General Settings: General
Settings
Now, when the Key is pressed the following message is displayed.
17.1 Password Settings: Password = 0001
Use Inr / Dec

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 23 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

The + / Key is used to increment and the - / Key is used to decrement the
values. By using these Keys set the Password to match the previously set
password, by default this password is '0'. Hence to go ahead user must
select 0 Password initially using - / Key.
If 0 password is not selected and Key is pressed again, the user cannot
access the other settings parameters and the following error message will be
shown on the display
PassWord Fail

The relay returns to the selected parameter in the main menu i.e. General setting
window.
General
Setting
Now when the Key is pressed the following message is displayed again.
PassWord = 001
Use Inr / Dec
Now select default password i.e. 0 or correct password by pressing - / Key.
Then press Key and the following window is displayed.
17.2 New Password: PassWord = 000
New PassWord
By using the + / Key or the - / Key New Password can be set, now when the
Key is pressed again the following window will be displayed.
17.3 Set Hours: SET Hrs = 016
Range 0 - 23
By using the + / Key or the - / Key the desired Hour can be set. The range will

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 24 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

be from 0 hour to 23 hours.


Then when the Key is pressed again the following message will be displayed.
17.4 Set Minutes: SET Mins = 010
Range 0 - 59
By using the + / Key or the - / Key the desired Minutes can be set. The range
will be from 0 minute to 59 minutes.
Then when the Key is pressed again the following message will be displayed.
17.5 Set Seconds: SET Sec = 012
Range 0 59
By using the + / Key or the - / Key the desired Seconds can be set. The
range will be from 0 second to 59 seconds.
Then when the Key is pressed again, the following message will be displayed.
17.6 Set Date: SET Date = 028
Range 1 31
By using the + / Key or the - / Key the desired Date can be set. The range will
be from 1 to 31.
Then when the Key is pressed again the following message will be displayed.
17.7 Set Month: SET Month = 001
Range 1 12
By using the + / Key or the - / Key the desired Month can be set. The range
will be from 1 to 12.
Then when the Key is pressed again the following message will be displayed.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 25 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

17.8 Set Year: SET Year = 008


Range 00 99
By using the + / Key or the - / Key the desired Year can be set. The range will
be from 00 to 99.
Then when the Key is pressed again, the following message will be displayed.
17.9 Unit ID: -

Unit Id = 0001
Range 1 - 255
By using the + / Key or the - / Key the desired Unit address can be selected.
The unit addresses will vary from 001 to 255, out of which 254 devices can be
connected to single computer and the id 255 is reserved for special command.
These settings are required to communicate with the SCADA System. Then
when the Key is pressed again the following window will be displayed.
17.10 Baud Rate
Baud Rate = 09600
Range 1200-9600
By using the + / Key or the - / Key the desired Baud Rate can be selected.
The settings are from 1200 to 19200. (i.e. 1200, 2400, 4800 and 9600)
Press the Key the following window will be displayed.
17.11 Set Parity
Set Parity= None
None/E ven/Odd
By using the + / Key or the - / Key the desired Set Parity can be selected, that
is None/Even/Odd. These settings are required to communicate with the
SCADA System.
Press the Key the following window will be displayed.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 26 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

17.12 Trip Test: Trip Test = 0002


01 = Yes 02 = No
By using the + / Key or the - / Key the desired Trip Test can be set, that is 01
or 02. In which case 1 corresponds to Yes i.e. Trip Test is enabled and 2
corresponds to No i.e. Trip Test is blocked Now, when the Key is pressed
again the following message will be displayed.
17.13 Frequency Selection: Frequency = 0001
50Hz = 1 , 60Hz = 2
By using the + / Key or the - / Key the desired frequency can be changed that
is 1 or 2. In which case 1 corresponds to 50Hz and 2 corresponds to 60Hz, and
now when the Key is pressed again the following message will be displayed.
17.14 External Relay: Ext. Relay = 0001
ON = 1, OFF = 2
By using the + / Key or the - / Key the External Relay can be set that is 1 or
2. By selecting 1 relay is enable (ON), and selecting 2 relay is disable (OFF),
when the Key is pressed again the following message will be displayed.
External relay logic:
The relay is provided with 2 C/O potential free contacts, which can be used for
tele-signaling or annunciation purpose. These contacts are operating at the time of
tripping and of latching type i.e. will get reset only when the LED RESET gets
pressed after supply gets resumed. The logic of relay operation is as shown
below.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 27 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

17.15 Trip Block: Trip Block = 0002


01 : Yes 02 :No
By using the + / Key or the - / Key the Trip Block can be set that is 1 or 2. By
selecting 1 relay tripping will be blocked, and by selecting 2 relay tripping will
not be blocked (i.e. Relay will trip), when the Key is pressed again the
following message will be displayed.
17.16 CT Primary: CT Primary = 0010
Range 10 - 1000
By using the + / Key or the - / Key the CT Primary can be set, the setting
range is from 10 to 1000 in steps of 1.
Please note: After 500 the measurement of relay will be change to kilo-amp.
Press the Key the following window will be displayed.
17.17 Inrush Res: Inrush Res = 0001
01: En 02 :Dis
By using the + / Key or the - / Key the Inrush Restrain function can be set
that is 1 or 2. By selecting 1 inrush restrain is enabled, and by selecting 2 the

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 28 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

inrush restrain is disabled.


Press the Key the following window will be displayed.
17.18 Save Settings: Save Settings?
Mode For Save
The relay will now ask if you would like to save the changes made to the various
setting parameters by you.
(Note: In this relay all the settings are done in foreground and the relay works in
background i.e. the relay will take the new settings only after completion of all
settings and the confirmation by the user, then the relay will use these settings for
actual operation.) When the Key is pressed again then the relay will Save the
new settings made and returns to the General setting's window as shown below.
General
Settings
18.0 To View General Settings: By using the + / Key select to display General Settings in the Main Menu.
General
Settings
Press the - /Key the following window is displayed.
Time : 14:19:36
Date :24/05/11
Press the - /Key the following window is displayed.
Unit Id = 0001
Baud Rate = 9600
Press the - /Key the following window is displayed.
Set Parity = None
Trip Test = Yes

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 29 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Press the - /Key the following window is displayed.


Frequency = 0050Hz
Ext Relay En = ON
Press the - /Key the following window is displayed.
Trip Block = No

Press the - /Key the following window is displayed.


CT Primary = 0010
Inrush Res = En
Now, by using the + / Key select to display Protection Settings in the
Main Menu.
19.0 To Adjust Protection Settings: Protection Settings

Now, when the Key is pressed the following message is displayed.


19.1 Password Setting: PassWord = 0001
Use Inr/Dec
By using the + / Key or the - / Key set the Password to match the previously
set password, by default this password is '0'. Hence to go ahead user must
decrement this pass using - / Key. Now When the Key is pressed again and
if the set password is not matching to the previously set password, the following
message will be displayed.
PassWord Fail

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 30 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Now, it returns to the Main Menu parameter and displays the 'Bank Setting'
window as follows,
Protection Settings

Now, when the Key is pressed again, the following message will be displayed.
PassWord = 0001
Use Inr/Dec
By using the + / Key or the - / Key set the Password to match the previously
set or default password and press Key. If the Password matches the following
window is shown.
19.2 Bank Selection: Bank = 001
Bank 1 To 1
By using the + / Key or the - / Key the Bank can be selected to do necessary
changes to the settings.
The Key is pressed the following message will be displayed.
19.3 Ip> (OC)Trip Setting (IEC notation I>): Ip> = 020
Range 20240%
By using the + / Key or the - / Key the desired Ip> OC can be set. The setting
range is from 20% (min) to 240% (max) in steps of 1%. If any of the Keys is
remained pressed for more than 1 sec. the selected value will start incrementing
or decrementing with high speed. If +/ or -/ key is pressed then display value
will scroll between min. & max. in forward or reverse direction respectively.
For example if required value to be set is 100% then press + / Key till you get
reading 95, then releases the + / Key and increment one by one till 100%. Or
vice versa if - /key is used.
This setting is common to all three phases. Then when the Key is pressed

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 31 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

again the following message will be displayed.


19.4 Ip TMS (OC) (Time Multiplier Setting): Ip> TMS = x1.00
Range x0.01- 1.20
By using the + / Key or the - / Key the desired Ip TMS OC can be set. The
range will be from x0.01 x1.20 and can be adjusted in steps of x0.01. This
setting is common to all three phases. Then when the Key is pressed again
the following window will be displayed.
19.5 I p > Curve Selection: Ip> Curve = 001
Range C1 C6
By using the + / Key or the - / Key the desired IDMT curve for Phase can be
selected. Six different types of curves are provided C1 to C6. When the given
value is 001 curve 1 is selected and when the given value 002 curve 2 is selected.
In similar manner any desired curve can be selected giving value from 001 to 006
i.e. C1 to C6.
Curve
C1
C2
C3
C4
C5
C6

Description
Normal Inverse 1 (10N = 3.0 sec)
Normal Inverse 2 (10N = 1.3 sec)
Very Inverse (10N = 1.5 sec)
Extremely Inverse (10N = 0.8 sec)
Long Time Inverse (10N = 13.3 sec)
Definite Time (00.1 To 99.9 sec)

Then when the Key is pressed again the following message will be
displayed.
19.6 I p > C 6 Time Selection ( Definite Time): Ip> C6 Time = 00.1
Range 00.1 - 99.9 S
By using the + / Key or the - / Key the desired Definite Time Delay can be

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 32 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

selected. Range for definite time is from 00.1 to 99.9 sec in steps of 0.1 secs.
This setting is effective only when C6 curve is selected for phase. Selection of
curve C6 will bypass IDMT TMS time delay for phase. Then when the Key is
pressed again the following window will be displayed.
19.7 Ip>> (OC) (High Fault IEC notation I >>): Ip>> = 01.5
Multiply by 100
This is instantaneous setting for phase. The moment input current crosses this
value; relay gives instant trip command (provided HF operating delay is set at
instant i.e. I p > > D e l a y = 0.05) bypassing IDMT delay timing. By using the + /
Key or the - / Key the desired Ip >> OC can be set. The HF value can be
adjusted between 00.0 to 32.0 times of the CT secondary and can be adjusted in
steps of 0.5. To get setting in terms of % multiply it by 100. The 00.0 HF value
corresponds to bypass, i.e. adjusting it to 00.0 will bypass the instantaneous
element.
Then when the Key is pressed again the following message will be displayed.
19.8 Ip>> Delay: Ip>> Delay = 0.05
Range 0.05-1.00 S
By using the + / Key or the - / Key the desired HF Operating Delay for Phase
can be selected. Range for Phase HF operating time is from inst (0.05) to 1.00 sec
in steps of 0.05 sec.
Then when the Key is pressed again the following window will be displayed.
19.9 IE> EF Trip setting (IEC notation IE>t): IE> = 010
Range 10100%
By using the + / Key or the - / Key the desired I E > T r i p can be set. The EF
trip value can be adjusted in between 10% (min) to 100% (max) of the CT
secondary and can be adjusted in steps of 1%. Then when the Key is pressed

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 33 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

again the following message will be displayed.


19.10 IE TMS (IE Time Multiplier Setting):IE> TMS = x1.15
Range x0.01- 1.20
By using the + / Key or the - / Key the desired IE TMS can be set. The
minimum value of TMS is x 0.1 and maximum value is x 1.20 and can be adjusted
in steps of x0.05.
Now, when the Key is pressed again the following message will be displayed.
19.11 I E > Curve Selection: IE> Curve = 002
Range C1 C6
By using the + / Key or the - / Key the desired IDMT curve for EF can be
selected.
Then when the Key is pressed again the following window will be displayed.

19.12 IE> C6 Time Selection (Definite Time): IE> C6 Time = 00.1


Range 00.1 - 99.9 S
By using the + / Key or the - / Key the desired Definite Time Delay can be
selected. Range for definite time is from 00.1 to 99.9 sec in steps of 0.1 secs.
This setting is effective only when C6 curve is selected for EF. Selection of curve
C6 will bypass IDMT TMS time delay for EF.
Now, when the Key is pressed again the following message will be displayed.
19.13 I E > > ( IE High Fault IEC notation IE >>): IE>> = 01.0
Multiply by 100
By using the + / Key or the - / Key the desired I E > > HF can be set. The HF

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 34 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

value can be adjusted in between 00.0 to 12.0 times of the CT secondary and can
be adjusted in steps of 0.5. To get setting in turns of %, multiply it by 100. The
00.0 HF value is corresponding to bypass. Setting the HF value to 00.0 will
bypass the instantaneous element. Then when the Key is pressed again
the following window will be displayed.
19.14 IE>> Delay: IE>> Delay = 0.05
Range 0.05-1.00 S
By using the + / Key or the - / Key the desired " HF Operating Delay" for EF
can be selected. Range for Earth HF operating time is from inst (0.05) to 1.00 sec
in steps of 0.05 sec.
Then when the Key is pressed again the following message will be displayed.
19.15 3-ph OL : 3-ph OL = 010
Range 10200%
By using the + / Key or the - / Key the desired 3 - p h O v e r L o a d can be
set. The setting range is between 10% (min) to 200% (max) and can be adjusted
in steps of 1%.
Press the Key the following window will be displayed.
19.16 OL Delay : OL Delay = 00020
Range 1 30000S
By using the + / Key or the - / Key the desired 3 - p h o v e r l o a d D e l can
be set. The setting range is from 1 to 30000sec in steps of 1 sec.
Press the Key the following window will be displayed.
19.17 Save Settings: Save Settings?
Mode For Save

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 35 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

The relay will now ask if you would like to save the changes made to the various
setting parameters by you.
(Note: In this relay all the settings are done in foreground and the relay works in
background i.e. the relay will take the new settings only after completion of all the
settings and the confirmation by the user, then the relay will use these setting for
actual operation.)
When the Key is pressed again then the relay will save the new settings made
and the following message will be displayed and returns to the Bank Setting
window as shown below.
20.0 To View Protection Settings: By using the + / Key select to display Protection Setting in the Main Menu.
Protection
Settings
Press the - / Key the following window will be displayed.
Ip> 100%

t>0.10

Ip>>3200% T:0.05
Press the - / Key the following window will be displayed.
Ip>= Normal Inv.1

Press the - / Key the following window will be displayed.


IE>020% t>1.00
IE>>0050% T: 0.05
Press the - / Key the following window will be displayed.
IE>= Normal Inv.1

Press the - / Key the following window will be displayed.


3-ph OL>012%
OL Del> 00010s

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 36 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Press the - / Key the relay with no other settings to be displayed will return to
Main Menu to show
Protection
Settings

21.0 To Adjust Cold Load Settings: By using the + / Key select to display Cold Load Setting in the Main Menu.
Cold Load
Settings
Now, when the Key is pressed the following message is displayed.
21.1 Password Setting: PassWord = 0001
Use Inr/Dec
The + / Key is used to increment and the - / Key is used to decrement the
values. By using these Keys set the Password to match the previously set
password, by default this password is '0'.
When the Key is pressed again and if the set password is not matching to the
previously set password, the following message will be displayed.
PassWord Fail

Now, it returns to the Main Menu parameter and displays the 'Protection Setting'
window as follows,
Cold Load
Settings
Press the Key the following message is displayed
PassWord = 0000
Use Inr/Dec

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 37 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Now select default password i.e. 0 by pressing - / Key. [OR the previously set
password]
Press the Key the following window will be displayed
21.2 CL (Cold Load) Enable : CL Enable = 001
01: En 02 :Dis
By using the + / Key or the - / Key the Cold Load can be set that is 1 or 2.
By selecting 1 Cold Load is enabled, and by selecting 2 the Cold Load is
disabled.
Press the Key the following window will be displayed.
21.3 CL Timer: CL Timer = 02.00
Range 0 - 10.00S
By using the + / Key or the - / Key the desired Cold Load Timer can be
selected. The setting range is from 0 to 10.00 sec in steps of 0.01 sec.
Press the Key the following window will be displayed.
21.4 Ip> (OC)Trip Setting (IEC notation I>): Ip> = 020
Range 20 240%
By using the + / Key or the - / Key the desired Ip> OC can be set. The setting
range is from 10% (min) to 240% (max) in steps of 1%.
Press the Key the following window will be displayed.
21.5 Ip> TMS (OC) (Time Multiplier Setting): Ip> TMS = x1.00
Range x0.01- 1.20
By using the + / Key or the - / Key the desired Ip TMS OC can be set. The
range will be from x0.01 x1.20 and can be adjusted in steps of x0.01.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 38 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Press the Key the following window will be displayed.


21.6 Ip> Curve Selection: Ip> Curve = 001
Range C1 C6
By using the + / Key or the - / Key the desired IDMT curve can be selected.
Six different types of curves are provided C1 to C6. When the given value is 001
curve 1 is selected and when the given value 002 curve 2 is selected. In similar
manner any desired curve can be selected giving value from 001 to 006 i.e. C1 to
C6.
Curve
C1
C2
C3
C4
C5
C6

Description
Normal Inverse 1 (10N = 3.0 sec)
Normal Inverse 2 (10N = 1.3 sec)
Very Inverse (10N = 1.5 sec)
Extremely Inverse (10N = 0.8 sec)
Long Time Inverse (10N = 13.3 sec)
Definite Time (00.1 To 99.9 sec)

Press the Key the following window will be displayed.


21.7 Ip> C6 Time Selection ( Definite Time): Ip> C6 Time = 00.1
Range 00.1 99.9 S
By using the + / Key or the - / Key the desired Definite Time Delay can be
selected. Range for definite time is from 00.1 to 99.9 sec in steps of 0.1 secs.
This setting is effective only when C6 curve is selected for phase. Selection of
curve C6 will bypass IDMT TMS time delay for phase.
Press the Key the following window will be displayed.
21.8 Ip>> (OC) (High Fault IEC notation I >>): Ip>> = 01.5
Multiply by 100
This is instantaneous setting for phase. The moment input current crosses this

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 39 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

value; relay gives instant trip command (provided HF operating delay is set at
instant i.e. I p > > D e l a y = 0.05) bypassing IDMT delay timing.
By using the + / Key or the - / Key the desired Ip >> OC can be set. The HF
value can be adjusted between 00.0 to 32.0 times of the CT secondary and can be
adjusted in steps of 0.5. To get setting in terms of % multiply it by 100. The 00.0
HF value corresponds to bypass, i.e. adjusting it to 00.0 will bypass the
instantaneous element.
Press the Key the following window will be displayed.
21.9 Ip>> Delay: Ip>> Delay = 0.05
Range 0.05-1.00 S
By using the + / Key or the - / Key the desired HF Operating Delay for Phase
can be selected. Range for Phase HF operating time is from inst (0.05) to 1.00 sec
in steps of 0.05 sec.
Press the Key the following window will be displayed.
21.10 IE> EF Trip setting (IEC notation IE>t): IE> = 010
Range 10100%
By using the + / Key or the - / Key the desired I E > T r i p can be set. The EF
trip value can be adjusted in between 10% (min) to 100% (max) of the CT
secondary and can be adjusted in steps of 1%.
Press the Key the following window will be displayed.
21.11 IE TMS (IE Time Multiplier Setting):IE TMS = x1.15
Range x0.01- 1.20
By using the + / Key or the - / Key the desired IE TMS can be set. The
minimum value of TMS is x 0.01 and maximum value is x 1.20 and can be
adjusted in steps of x0.01.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 40 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Press the Key the following window will be displayed.


21.12 IE> Curve Selection: IE> Curve = 002
Range C1 C6
By using the + / Key or the - / Key the desired IDMT curve for Phase can be
selected. Six different types of curves are provided C1 to C6. When the given
value is 001 curve 1 is selected and when the given value 002 curve 2 is selected.
In similar manner any desired curve can be selected giving value from 001 to 006
i.e. C1 to C6.
Curve
C1
C2
C3
C4
C5
C6

Description
Normal Inverse 1 (10N = 3.0 sec)
Normal Inverse 2 (10N = 1.3 sec)
Very Inverse (10N = 1.5 sec)
Extremely Inverse (10N = 0.8 sec)
Long Time Inverse (10N = 13.3 sec)
Definite Time (00.1 To 99.9 sec)

Press the Key the following window will be displayed.


21.13 IE> C6 Time Selection (Definite Time): IE> C6 Time = 00.1
Range 00.1 99.9 S
By using the + / Key or the - / Key the desired Definite Time Delay can be
selected. Range for definite time is from 00.1 to 99.9 sec in steps of 0.1 secs.
This setting is effective only when C6 curve is selected for EF. Selection of curve
C6 will bypass IDMT TMS time delay for EF.
Press the Key the following window will be displayed.
21.14 IE>> (IE High Fault IEC notation IE >>): IE>> = 01.0
Multiply by 100
By using the + / Key or the - / Key the desired I E > > HF can be set. The

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 41 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

HF value can be adjusted in between 00.0 to 12.0 times of the CT secondary and
can be adjusted in steps of 0.5.
To get setting in turns of %, multiply it by 100. The 00.0 HF value is
corresponding to bypass. Setting the HF value to 00.0 will bypass the
instantaneous element.
Press the Key the following window will be displayed.
21.15 IE>> Delay: IE>> Delay = 0.05
Range 0.05-1.00 S
By using the + / Key or the - / Key the desired HF Operating Delay for EF
can be set. The setting range for Earth HF operating time is from inst (0.05) to
1.00 sec in steps of 0.05 sec.
Press the Key the following window will be displayed.

21.16 Save Settings: Save Settings?


Mode For Save
The relay will now ask if you would like to save the changes made to the various
setting parameters by you.
(Note: In this relay all the settings are done in foreground and the relay works in
background i.e. the relay will take the new settings only after completion of all the
settings and the confirmation by the user, then the relay will use these setting for
actual operation.)
Press the Key relay will save the new settings made and the following
message will be displayed.
Cold Load
Settings

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 42 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

22.0 To View Cold Load Setting: By using the + / Key select to display Cold Load Setting in the Main Menu.
Cold Load
Settings
Press the - / Key the following window will be displayed.
Cold Load = Dis
CL Timer = 00.01S
Press the - / Key the following window will be displayed.
Ip>101% t>0.15
Ip>>0080% T: 0.05
Press the - / Key the following window will be displayed.
Ip>= Normal Inv.1

Press the - / Key the following window will be displayed.


IE>020% t>0.10
IE>>0400% T: 0.05
Press the - / Key the following window will be displayed.
IE>= Normal Inv.1

Press the - / Key the relay with no other settings to be displayed will return to
Main Menu to show
Cold Load
Settings
23.0 To View FAULTS: By using the + / Key select to display Faults in the Main Menu.
Faults

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 43 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Now when the - /Key is pressed then following window will be displayed.
Fault 1

Now when the + / Key is pressed then following window will be displayed.
Fault 2

Similarly by pressing + / we can select Fault 3, fault4 and fault5.


After selecting the requite fault to view press - /following data will displayed.
I>> :
I>

OL:
:

SF : T

Explanation:I > > i n d i c a t e s Type of HF Fault (e.g. RE for phase to Earth fault, RY for
phase to phase fault).
O L : indicates the faults due to over Load
I > Indicates TYPE of IDMT fault (e.g. RE for phase to Earth fault, RY for phase
to phase fault).
SF indicates Status Flag. When there is non- fault trip such as trip due to TEST
push button or Remote trip etc. it is displayed at SF
Following are the status fault and there meanings:T : Trip due to TEST push button.
R : Trip due to Remote Trip.
CLT: Tripped with cold load setting.
But if in General settings, Trip block is set YES it will display B at SF to indicate
that tripping is blocked as follows
SF : B ( For IDMT or HF Fault Trip).
SF : TB (Trip due to Test push button)
SF : RB ( Trip due to Remote Trip)
SF : CLT ( Trip due to Cold Load)
(Note:- Fault 1 is always treated as most recent occurred fault and the data stored
in these fault windows keep on shifting sequentially i.e. when any new fault
occurs, the data related to the fault gets stored in Fault 1 and earlier stored data in

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 44 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Fault 1 gets shifted to Fault 2 and so on till Fault 5 and previously stored data in
Fault 5 gets lost.)
When the - /Key is pressed then following data is displayed.
Trip Counter
t : 0001
This indicates the no of tripping occurred till the fault. The counter will get Reset
when the password and memory get cleared (refer 27.0 for details).
When the - /Key is pressed then following data is displayed.
Fr = 00.00

y = 00.00

b = 00.00

n = 00.00

Explanation:
The R Phase Current measured at the time of the fault.
The Y Phase Current measured at the time of the fault.
The B Phase Current measured at the time of the fault.
The N Phase (Earth) Current measured at the time of the fault.
Note: All the currents shown in this window are secondary current
When the - /Key is pressed again then the following data will be displayed,
Trip Timing
001.70 Sec
Explanation:The Trip Timing is measured from relay pick up condition to relay tripping.
Note: this time is measure by internal software calculations i.e. from PKP value of
the relay till getting trip command. The actual time will be having some additional
hardware delay. Due this there will be some error of 10% in this measured
value.
When the - / Key is pressed then following data is displayed,
13/03/09
10:15:10.123
Note: The windows after the above windows is for internal use at the time of Fault
analysis
Explanation:The Date / Time of the fault.
Then when the - / Key is pressed again, the relay with no other data to be

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 45 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

displayed will return to Main Menu to show,


Faults

To Display of (FAULT 2), (FAULT 3), (FAULT 4), and (FAULT 5) follow step as
given above.
24.0 To View Error Log: By using the + / Key select to display Error Log window in the Main Menu.
Error Log

Now, when the - / Key is pressed then following message is displayed.


Error Code = 000
0000 0088
The relay continuously keeps track on its internal hardware and the moment it
detects any failure of component, a message is displayed on LCD display. The
type of error can be checked by Error Log menu. This feature is very useful for
giving pre information to avoid mal operation.
Following are some of Error codes: Error Code
001

Description
RAM Error

002

RTC Error

003

RAM + RTC Error

004

ADC Error

005

RAM + ADC Error

006

RTC + ADC Error

008

Setting Error

009

Setting + RAM Error

010

Setting + RTC Error

011

Setting + RAM + RTC Error

012

Setting + RAM + RTC + ADC Error

016

RTC Time corrupted Error

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 46 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Note:
1.
2.

In case of ADC error (004) relay will not work at all and will directly
show ADC Error on display, It also lock the function of the relay.
In case of RTC time corrupted error (016), the RTC (Date & Time)
needs to reset from General Setting Menu.

(Note: - The second line of the above shown window gives 0000 0088 which is
used while firmware up-gradation hence its of no use for the user.)
Then when the - / Key is pressed again, the relay with no other settings to be
displayed will return to Main Menu to show
Error Log

25.0 To View Status


By using the + / Key select to display Status window in the Main Menu.
Status

Now when the - /Key is pressed then following message is displayed.


S1 = ON

S2 =OFF

S3 = OFF
The three statuses S1, S2 an S3 can be enabled or disabled through SCADA. For
e.g. Status S1 is Enable if shown as S1 = ON and Status S2 is disable if shown as
S2 = OFF.
Now when the - /Key is pressed then again the relay with no other settings to
be displayed will return to Main Menu to show.
Status

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 47 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

26.0 Flow Charts:26.1 Flow Chart for measurement Menu: -

Measurement

-/

-/

R =00.00
B=00.00

Y=00.00
N=00.00

-/

r =00.00
b=00.00

y=00.00
n=00.00

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 48 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

26.2 Flow Chart for General Settings Menu: -

General
Settings

-/

Password = 0000
New Password

Password = 0001
Use Inr/Dec

-/

Time : 14.24.30
Date : 25/09/11

SET Mins = 050


Range 0 - 59

SET Hrs = 012


Range 0 - 23

-/

Unit ID = 0001
Baud Rate = 9600

SET Date = 025


Range 1 - 31

SET Sec = 010


Range 0 - 59

-/

Set parity = None


Trip Test = Yes

SET Year = 011


Range 00 - 99

SET Month = 005


Range 1 - 12

-/

Frequency = 0050Hz
Ext Relay En = ON

Baud Rate = 9600


Range 1200 - 9600

Unit Id = 0001
Range 1 - 255

-/

Trip Test = 0001


01 : Yes 02 : No

Set Parity = None


None/Even/Odd

-/

Ext Relay = 0001


ON = 1, OFF = 2

Frequency = 0001
50Hz=1,60Hz=2

CT Primary = 0010
Range 10 - 1000

Trip Block = 0002


01 = Yes 02 = No

Save Settings?
Mode For Save

Inrush Res = 0001


01: En 02: Dis

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Trip Block = No

CT Primary = 0100

Inrush Res = En

Page: 49 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

26.3 Flow Chart for Protection Settings Menu:-

Bank = 001
Bank 1 To 1

Protection
Settings

-/

Password = 0001
Use Inr/Dec

-/

Ip> = 100
Range 20 240 %

-/

Ip> C6 Time = 00.5


Range 00.1 -99.9s

Ip> Curve = 001


Range C1 C6

-/

Ip>> Delay=0.05
Range 0.05 1.00s

Ip>> = 10.0
Multiply by 100

-/

IE> = 020
Range 10 100%

-/

Ip> TMS = x0.10


Range x0.01 1.20

IE > TMS
= x0.10
Range x0.01 1.20

IE> C6 Time = 00.5


Range 00.1 -99.9s

IE> Curve = 001


Range C1 C6

IE>> Delay=0.05
Range 0.05 1.00s

IE>> = 10.0
Multiply by 100

OL Delay = 30000
Range 1 -30000s

3-Ph OL = 050
Range 10 -200%

Save Settings?
Mode For Save

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Ip> 100% t>0.10


Ip>>1000% T: 0.05

Ip> Normal Inv .1

IE> 040% t>0.10


IE>>1000% T: 0.05

IE> Normal Inv .1

3ph OL>050%
OL Del >30000s

Page: 50 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

26.4 Flow Chart for Cold Load Settings Menu:-

Cold Load
Settings

-/

CL Enable = 001
01:En 02:Dis

Password = 0001
Use Inr/Dec

-/

Cold Load=En
CL Timer = 01.50S

Ip> = 100
Range 20 240 %

CL Timer = 01.50
Range 0 10.00S

-/

Ip> 100% t>0.10


Ip>>1000% T: 0.05

Ip> Curve = 001


Range C1 C6

Ip> TMS = x0.10


Range x0.01 1.20

-/

Ip>> = 10.0
Multiply by 100

Ip> C6 Time = 00.5


Range 00.1 -99.9s

-/

IE> = 020
Range 10 100%

Ip>> Delay=0.05
Range 0.05 1.00s

-/

IE> Curve = 001


Range C1 C6

IE > TMS
= x0.10
Range x0.01 1.20

IE>> = 10.0
Multiply by 100

IE> C6 Time = 00.5


Range 00.1 -99.9s

Save Settings?
Mode For Save

IE>> Delay=0.05
Range 0.05 1.00s

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Ip> Normal Inv .1

IE> 040% t>0.10


IE>>1000% T: 0.05

IE> Normal Inv .1

Page: 51 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

26.5 Flow Chart for Faults:Faults

-/

Fault 1

+/

Fault 2

+/

+/

Fault 4

+/

Fault 3

Fault 5

NOTE : Use -/key to select the fault to be view from Fault 1 to Fault5

Faults

-/

-/

Fault 1

-/

-/

Fr=00.00 y=00.00
B=00.00 n=00.00

-/

I>>:
I> :

OL:
SF: T

Trip Timing
00000 sec

-/

Trip Counter
t:0001

-/

15/09/11
17:45:11.440

NOTE: Following windows are for the fault analysis at factory


-/

r1 = + 00.00
i1 = + 00.00

-/

r2 = + 00.00
i2 = + 00.00

-/

-/

r4 = + 00.00
i4 = + 00.00

-/

r = 00.00
y =00.00

-/

0001
0001

r3 = + 00.00
i3 = + 00.00

b = 00.00
e =00.00

0001
0001

NOTE: Similarly the Fault 2 to Fault 5 can be viewed


26.6 Flow Chart for Error Log:Error Log

-/

-/

Error Code : 0000


0000 0088

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 52 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

26.7 Flow Chart for Status:Status

-/

-/

S1= OFF
S3=ON

S2=OFF

27.0 To clear Password and Fault Memory : To clear password and fault memory, press Key & HW RESET Key, and Bat
ON key simultaneously & release HW RESET Key only, keeping Key and
Bat ON key pressed. Then the default value for password i.e 000 gets loaded
and data stored in all five (5) Fault windows is cleared.
The following windows are displayed consecutively.
PassWord & Fault
Memory Cleared
Ashida Digital
OC/EF Relay
ADR 241S IEC
ID =0001 V3.08_1
R =0000 Y = 0000
B =0000 N = 0000
Note :
In case authorised person forgets the set password then by clearing password as
said above default password i.e. 000 is set. By entering 000 password new
password can be set through General Settings.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 53 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

28.0 Sample Test Report


C1: Reading By Curve 10N = 3 Sec.

C2: Reading By Curve 10N = 1.3 Sec.

C3: Reading By Curve 10N = 1.5 Sec. C4: Reading By Curve 10N = 0.8 Sec.
C5: Reading By Curve 10N = 13.3 Sec.
CURVE : C1
Set
Current

CURVE : C2
Actual Max.
Time Sec.

Tolerance in
Sec.

Set
Current

Actual Max.
Time Sec.

Tolerance in
Sec.

2N

10.128

8.86 to 11.39

2N

4.389

3.84 to 4.93

5N

4.322

3.99 to 4.64

5N

1.873

1.73 to 2.01

10N

3.000

2.85 to 3.15

10N

1.300

1.23 to 1.36

20N

2.290

2.17 to 2.40

20N

0.992

0.94 to 1.04

Actual Max.
Time Sec.

Tolerance in
Sec.

CURVE : C3
Set
Current

CURVE : C4
Actual Max.
Time Sec.

2N
5N
10N
20N

Tolerance in
Sec.

13.500
3.375
1.500
0.711

Set
Current

11.81 to 15.18
3.12 to 3.62
1.42 to 1.57
0.67 to 0.74

2N
5N
10N
20N

26.667
3.333
0.808
0.201

23.33 to 30.00
3.08 to 3.58
0.76 to 0.84
0.19 to 0.21

CURVE : C5
Set
Current

Actual Max.
Time Sec.

Tolerance in Sec.

2N

120.000

105 .00 to 135.00

5N

30.000

27.75 to 32.25

10N

13.333

12.66 to 13.99

20N

6.316

6.00 to 6.63

Note: TMS is considered: x1.0 for all above curve tables.


TIME ACCURACY CLASS 5 AS PER IS 3231
Current Multiplying Factor
2N
5N
10N
Multiplying Factor
Percentage
1.

2.

20N

2.5

1.5

12.5%

7.5%

5%

5%

Pickup Test for Phase & EF (Tolerance 1N 1.1N)


Keep Phase & EF TMS at x0.1
Set %
R (Amp.)
Y (Amp.)
B (Amp.)

Set %

20

10

240

100

EF (Amp.)

Testing for Phase & EF TMS (Tolerance 12.5%)


Phase

EF

Trip setting = 100% , Current 2N

Trip Setting = 100%, Current 2N

Curve = C1
TMS Setting

0.50

1.00

Curve = C2
1.20

0.50

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

1.00

1.20

Page: 54 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

Actual

5.064

10.128

12.153

2.194

4.389

5.266

4.43 to
5.69

8.86 to
11.39

10.63 to
13.67

1.91 to
2.46

3.84 to
4.93

4.60 to
5.92

Observed
Tolerance in
Sec.
3.

Operating Time Test for Phase & EF


Keep TMS Set at x1.0 position
Tolerance

Set

In Sec.

4.

Curve

EF Trip

Current

Phase Trip 50%

40%

8.86 to 11.39

2N

3.84 to 4.93

2N

3.12 to 3.62

5N

3.08 to 3.58

5N

12.66 to 13.99

10N

0.475 to 0.525
For set Time 0.5Sec

1.2N

HF Testing for Phase & EF (Tolerance 1N 1.1N)


Keep Trip setting maximum & TMS set Maximum
HF

R (Amp.)

Y (Amp.)

B (Amp.)

EF (Amp.)

200%
500%
5.

HF Time Delay Testing for Phase and EF


(Adjust current 1.2N to trip Relay with HF)
HF Time Delay Settings

6.

Phase

0.5

Tolerance +/- 5% (0.475 to 0.525 Sec.)

1.0

Tolerance +/- 5% (0.95 to 1.05 Sec.)

EF

Pickup test for 3 Phase OVERLOAD setting 10% (by injecting current in all three
phases) found _____.

7.

OVERLOAD Time Delay Testing for Phase. (Adjust current 1.2N to trip Relay with
OVERLOAD)
OVERLOAD Time Delay Settings

1.0

5.0

(0.95 to 1.05 Sec.)

(4.75 to 5.25 Sec.)

Observed Delay
Tolerance +/- 5%
8.

Cold Load Trip test :


Keep the Protection setting at the higher range and give voltage to status S1 i.e. CB NO.
Keep CL Timer at 10.0 Secs. and set the cold load setting as follow:
Settings in Cold load
Ip> = 100 %, Ip> TMS = x0.1, Ip
Curve = 1, Ip>> = Bypass &
IE> = 100 %,IE> TMS = x1.0, IE
Curve = 1, IE>> = Bypass

Set Current at
R Phase

Observed
Delay (Secs.)

2N

Tolerance
(Secs.)
0.886 1.139

Note: Please check that relay should operates with cold load i.e. CL in the fault window.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 55 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

29.0 Technical Specification: General specifications


Sr.
No.

Specification

Particulars

I.

Current Input

: Suitable for CT secondary 1 Amp. or 5 Amp to be


specify while ordering

II.

VA burden on CTs

: Refer the current transformer requirement chapter of


this leaflet.

III.

Minimum current require to : In 1 20%, 2 12% and 3 8%.


energize the relay

IV.

Aux. Supply

: 18-52 V AC/DC or 77-250V AC/DC (230VAC) optional

V.

VA burden on Aux.

: Less than 10 Watts

VI.

Pick up

: Within 1.1 times of set value

VII.

Reset Value

: 95% to 90% of pick up.

VIII.

Operating Time

: 5 selectable IDMT curve C1, to C5. Or define time C6


: Instantaneous Time < 50ms on 2 times current of
setting, In supply ON condition.

IX.

Output Contact

: 2 Change over latching type

X.

Contact Rating

:Alarm Duty

XI.

Opto-isolated input

: 3Nos. Rated for 230Vac (1 No. is dedicated for CB NO)

XII.

Impulse output for the


tripping coil

: 12 V - 24 VDC (Energy < 0.1 W/sec). Suitable for


sensitive RMU tripping coil

XIII.

Operating temperature
range

: -10 C to +65 C

XIV.

Relative Humidity

: Humidity (RH) 95% maximum

XV.

Storage temperature
range

: -20 C to +80 C.

General Settings
XVI.

: Set Hours

0 23

: Set Min

0 59

: Set sec

0 59

: Set Date

1 31

: Set Month

1 12

: Set Year

0 99

: Unit ID

1 250 in step of 1

: Baud Rate

1200 9600

: Set Parity

None / Even / Odd

: Trip Ckt Test

YES / NO

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 56 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

: Frequency

50 / 60 Hz

: Ext. Relay

ON / OFF

: Trip Block

YES / NO

: CT Primary

10 1000 in step of 1

: Inresh Restrain

YES / NO

Protection Section
XVII.

: Bank

: Ip> Settings

20% 240% in steps of 1%.

: Ip> Time
Multiplier (TMS)

x0.01 x1.20 in steps of 0.01

: Ip> Curve
(Operating Time)

C1 C6 ( IDMT curve C1 C5 or
Define Time C6 )

: Ip> C6 Delay

0 99.9 Sec in steps of 0.1Sec.

: Ip>> Settings

50% 3200% in steps of 50%.

: Ip>> Delay

0.05 1.00 Sec in steps of 0.05


Sec.

: IE> Settings

10% 100% insteps of 1%

: IE> Time
Multiplier (TMS)

x0.01 x1.20 in step of 0.01

: IE> Curve
(Operating Time)

C1 C6 (IDMT curve C1 C5 or
Define Time C6)

: IE> C6 Delay

0 99.9 Sec in steps of 0.1Sec.

: IE>> Settings

50% 1200% in steps of 50%.

: IE>> Delay

0.05 1.00 Sec in steps of 0.05


Sec.

: 3 Ph Overload

10 200% in steps of 1%

: Overload Delay

1 30000 s in steps of 1s

: Cold Load

En/Dis

Cold Load
XVIII.

Cold Load

: Cold Load Timer

0.01 10 sec

: Ip> Settings

20% 240% in steps of 1%.

: Ip> Time
Multiplier (TMS)

x0.01 x1.20 in steps of 0.01

: Ip> Curve
(Operating Time)

C1 C6 ( IDMT curve C1 C5 or
Define Time C6 )

: Ip> C6 Delay

0 99.9 Sec in steps of 0.1Sec.

: Ip>> Settings

50% 3200% in steps of 50%.

: Ip>> Delay

0.05 1.00 Sec in steps of 0.05


Sec.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 57 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

: IE> Settings

10% 100% insteps of 1%

: IE> Time
Multiplier (TMS)

x0.01 x1.20 in step of 0.01

: IE> Curve
(Operating Time)

C1 C6 ( IDMT curve C1 C5 or
Define Time C6 )

: IE> C6 Delay

0 99.9 Sec in steps of 0.1Sec.

: IE>> Settings

50% 1200% in steps of 50%.

: IE>> Delay

0.05 1.00 Sec in steps of 0.05


Sec.

Operational Indicators (Flags)


XIX.

ON

: Red LED indicates that the actual current is more than


the minimum required current.

PKP

: Red LED indicates OC/EF relay Pickup.

TRIP

: Red LED Indicates that Trip pulse is being executed.

FAULT

: Red LED Indicates that Fault occurred HR type

XX.

Thermal Withstand
Capacity

: X20 times the normal current for 3sec.

XXI.

Battery

: Capacity 4.5Volt (1.5 x 3) AAA non-rechargeable Battery:

XXII.

Drawing References

: For Cabinet Type

- CSG -122 (MAC01401_C)

: For Electrical
Connection

- APR08402

: X2.5 Continuous
Recommended Lithium Energizer or equivalent.

29.1 Conformance to Standards: Sr. No.


I.

Specification

Particulars

High Voltage Test

: IEC 60255-5.
: At 2.5kV 50Hz between all terminal connected together
and Earth for 1 minutes

II.

Impulse Voltage Test

: IEC60255-5.
: Test voltage: 5KV (peak) 1.2 / 50us,
: Energy : 0.5 J,
: Polarity : + ve and Ve
: Nos. of impulses : 3 positive and 3 negative impulse
: Duration between Impulses : 5 sec.

III.

High Frequency test

: IEC 60255-22-1,
: Frequency : 1MHz Damped Oscillatory
: Longitudinal : 5 KV (peak)
: Duration: sec duration 2 sec.
Between input current Terminal

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 58 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

IV.

Electro static
Discharge

: IEC 60255-22-2 Class III and IEC 61000-4-2 class III.


: Contact discharge : 6kV,
: Air discharge: 8KV
: Polarity: both +ve and Ve polarities.

V.

Fast transient
interference/bursts

: IEC 60255-22-4 and IEC 61000-4-4, class III


: Amplitude 2Kv, pulse shape 5/50ns.
: Burst duration = 15ms.
: Repetition rate 300ms;
: Both polarities; Ri = 50; duration 1 min.

VI.

Vibration Test

: IEC 60255-21-1 class 1


: Frequency Range = 10Hz 150Hz ,
: Acceleration. = 1gn (9.8 m/s2)
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.

VII.

Shock Test

: IEC 60255-21-2 class 1


: Acceleration. = 15gn (15 x 9.8 m/s2)
: Half sine pulse width 11ms
Number of shocks per axis 3 per direction.

VIII.

Serge Immunity Test

: IEC 60255-22-5 / BS EN 61000-4-5 : 1995


: Differential Mode = 2kV
: Common Mode = 4kV
: 1.2/50uS , 5 surges of each polarity

IX.

Conducted Emission
Test

: BS EN 55011 : 1998

X.

Radiated Emission
Test

: BS EN 55011 : 1998

XI.

Power Frequency
Magnetic Test

: BS EN 61000-4-8 : 1994.

Conducted Disturbance
induced by Radio
Frequency field

: IEC 60255-22-6 / BS EN 61000-4-6: 1996.

Radiated
Electromagnetic Field
Disturbance Test

: IEC 60255-22-3 / BS EN 61000-4-3 : 1995

XII.

XIII.

: Frequency 0.15MHz 30MHz


: Frequency 30MHz 1GHz
: Freq. 50 Hz, Field 100 A/m for 1 min. 1000 A/m for 3 sec.,
: Freq. 150kHz 80MHz, Amplitude 10 V, Modulation 80%
AM @ 1KHz
: Freq. 80 MHz 1000 MHz, Amplitude 10 V / m,
Modulation 80% AM @ 1KHz

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 59 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

37.0

Troubleshooting Guide line:-

Relay is not getting powered up / no display on relay / display is not working :

Check the current flowing from the CT, it should be more than 20% of rated in any
one phases or more than 12 % in any two phases or more than 8% in all the
phases.
Relay is not getting powered up on battery :

1. Confirm that batteries are properly placed in battery socket.


2. Check the voltage of the batteries with digital multimeter; it should be more
than 3.2 V. If the batteries are proper and unused then it will be 4.5V.
Relay is not getting powered up at all (on load current nor on battery) :

Check all the above points and if all the things are ok but still it is not getting
ON then contact ASHIDA for the further rectification.
Trip not working / relay is not tripping :

1. Check the connections of tripping coil.


2. Check the TRIP BLOCK setting in General Settings Menu (for details please
refer Chapter No. 17 in this manual), Trip block should be in disable mode.
Latching type relay contacts are not working :

Check the External Relay Enable/disable settings in General Settings Menu


(for details refer chapter no 17.14). To operate the relay contacts External relay
should be in enable mode.
Relay Tripping with 3Ph overload :

1. Check the settings of 3Ph Overload & OL delay (refer Chapter No. 19).
2. If you want to bypass the 3ph overload function, set the 3ph overload setting
and 3ph OL delay at maximum position i.e. 200% & 30000s respectively.
Cold load trip function is not working properly :

1. Ensure that the CB NO contact is properly wired up at the CB NO status


input.
2. Check the settings of cold load (Refer chapter 3.3 and 21 for details).
Display showing error code 016 :
Set the date and time of the relay in general Settings Menu as per the current date &
time (refer Chapter no 17 in this Manual).

In case of any further difficulties, please mail us the on


support@ashidaelectronics.com or contact us on +91-22-25822830 /
25823482.
Required details for launching a complaint:
1. Relay Type
2. Sr. No. of the relay (written inside the battery door of front fascia).
3. Details of the concern person (Name & contact number etc.) to whom our
support team can co-ordinate to resolve the issue.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 67 of 68
Ref.: ADR241S_V_06_SD
Rev.: 06 Dt. 10.01.2013

38.0

Revision Notes: -

Revision
No.

Date

Revision Note

01

29.01.08

Original Revision for Software version V1.01

02

29.08.08

1. Software version changed i.e V1.02 to reduce HF time


Delay.

02A

20.02.09

Software Version changed to V1.03 to remove default


settings.

02B

01.04.09

Software Version changed to V1.04 to reduce pickup


dropout ratio.

2. Change in Battery Specification.

03

10.04.09

Revised as per specific requirement. (Not for this Manual)

04

01.07.09

Model no. definition revised.

04A

15.07.09

Software Version changed to V1.05, for Battery ON delay


adjustment

04B

01.08.09

Software Version changed to V1.06 for rectifying NonBank setting View

04C

12.11.09

Software Version changed to V1.07 for Battery ON delay


adjustment as per new hardware changes

04D

08.12.09

Software Version changed to V1.08 for improvement in


displaying Date and Time.

04E

15.12.09

Software Version changed to V1.09 for Battery ON delay


adjustment for tripping conditions.

Cabinet aesthetic changed

04F

16.04.10

Drawing for Testing Relay using Test Block added.

05

20.04.12

Menu sequence change and Cold Load Setting added

06

10.01.13

Software version changed to V3.08, Error codes added


and troubleshooting guide line added.

ASHIDA Electronics Pvt. Ltd.


Operating Manual for Ashida Numerical Self-Powered
Protection Relay ADR 241S

Page: 68 of 68
Ref.: ADR241S_V_06_SD