Anda di halaman 1dari 70

AirCon Service Center

ASC1000 / ASC2000 / ASC3000

Service Manual

Contents
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 3
A General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A - 1
1
Explanation of the symbols used in this operating manual . . . . . . . . . . . . . A - 2
2
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A - 3
3
Environmental protection and disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . A - 5
4
Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A - 6
B Maintenance and repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 1
1
Overview of AirConServiceCenter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 1
2
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 3
3
Activating the ASC 1000 printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 4
4
Putting in the containers for oil and UV additive . . . . . . . . . . . . . . . . . . . . . B - 5
5
Entering the container size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 6
6
Filling the internal refrigerant container . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 7
7
Opening the info menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 9
8
Short selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 10
9
Free selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 12
10 Flushing the air conditioning system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 13
11 Air conditioning system test without refrigerant service . . . . . . . . . . . . . . B - 16
12 Calibrating the scales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 18
13 Changing the internal filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 20
14 Changing the vacuum pump oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 22
15 Calibrating the pressure transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 24
16 Calibrating the refrigerant scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 25
17 Calibrating the oil scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 29
18 Function control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 32
19 Correcting the filling quantity for long service hoses . . . . . . . . . . . . . . . . . B - 34
20 Replacing the printer paper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 35
21 Changing the WAECO flash memory card . . . . . . . . . . . . . . . . . . . . . . . . B - 36
22 Fault table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 38
23 Activating the DATA LOGGER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 41
24 Cleaning and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B - 43
C Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C - 1
1
Exploded drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C - 1
2
Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C - 5
3
Hydraulic diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C - 10
4
General device data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C - 13
5
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C - 14
6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C - 16
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I - 1

Service Manual 09/06 - AirConServiceCenter

General information

General information
This service manual supplies you with all information required for the
maintenance and repair of the AirConServiceCenter ASC1000, ASC2000
and ASC3000.
The service manual is divided into three parts:
Part A (pages numbers beginning with A) contains general information
on how to use this service manual as well as on the topics of security,
environmental protection and support.
Part B (pages beginning with B) contains information on performing
maintenance and repair work as well as a fault table for possible
malfunctions.
You can find further information on performing maintenance and repair
work on the WAECO service CD.
Part C (pages beginning with C) contains technical data, circuit diagrams, hydraulic diagrams, spare parts lists, and so on.
The manual will be revised regularly in order to ensure that this service
manual is up-to-date. You can obtain the latest information through the
Internet at www.airconservice.de
This service manual is intended for those who perform maintenance at vehicle air conditioning service stations and have the expertise required to do so.
Also note the following:
The WAECO training manual Fundamental Technical Specifications Vehicle Air-Conditioning
The WAECO information brochure Fundamental Legal Specifications Vehicle Air-Conditioning
Information from the refrigerant manufacturer
Any special instructions on servicing vehicle air conditioning systems
which apply at your company

Service Manual 09/06 - AirConServiceCenter

A-1

General information

Explanation of the symbols used in this operating


manual
Format
Bold
Bold
Text
Text
1. Text
2. Text
3. Text
Text (1)
Text (A)

Meaning
Designations used on the device
Display messages
List in any order

Example
Press ENTER.
Short selection
Pressure monitor
Pressure relief valves
Actions to be carried out in the
1. Connect the device
order shown
2. Switch on the device.
3. Press the selection button.
Part numbers, referring to the fold- Use the keypad (7) to enter
out pages at the front of this manual the data.
Part designations which refer to
Remove the filter cartridge (E)
the diagrams shown in the section on the left side.
describing the work

Health or environmental hazard

Risk of damage to the machine or other material damage

Special information on using the device effectively

Should you have any comments or questions about this service manual,
please contact:
WAECO International GmbH
Hollefeldstrasse 63
48282 Emsdetten, Germany
Tel.: +49 (0) 25 72 / 8 79-191
Fax.: +49 (0) 25 72 / 8 79-3 91
E-mail: tdk@waeco.de

Service Manual 09/06 - AirConServiceCenter

A-2

General information

Safety instructions
This service manual is intended for those who perform maintenance at
vehicle air conditioning service stations and have the expertise required to
do so. This refers specifically to knowledge of general safety regulations
for maintenance work on electronic devices and air conditioning units.
Before performing any service tasks on the AirConServiceCenter, read the
service manual thoroughly.
Also note the following:
The WAECO training manual Fundamental Technical Specifications Vehicle Air-Conditioning
The WAECO information brochure Fundamental Legal Specifications Vehicle Air-Conditioning
Information from the refrigerant manufacturer
Any special instructions on servicing vehicle air conditioning systems
which apply at your company
Disconnect the power plug before opening the device. If you have to
need the device connected to the power supply for certain service tasks,
observe the circuit diagrams and maintain sufficient distance from live parts.
Only use spare parts and materials recommended by WAECO. If you use
products other than those recommended and approved by WAECO, damage
may be caused to the AirConServiceCenter or the vehicle air conditioner.
Wear personal safety equipment (safety goggles and protective gloves)
when handling the refrigerant and avoid coming into contact with it.
Contact with the refrigerant draws out body heat and the affected areas
can freeze. Do not inhale refrigerant vapour. Although the vapour is nontoxic, it displaces the oxygen you need to breathe.
Do not perform any changes or modifications to the AirConServiceCenter
that are not explicitly approved by WAECO.
Each time before operating the device, check whether all of the device's
functions work properly. In particular, check functions which are relevant to
safety. Only clear the device for use once you are certain it functions properly. Do not leave the device unattended if it does not function properly.

Service Manual 09/06 - AirConServiceCenter

A-3

General information

2.1

Warnings on the AirConServiceCenter


Caution
Observe the operating manual.
Only connect the device to a socket with 230 V / 50 Hz AC.
Protect the device against rain.
Wear gloves when handling refrigerants.
Wear goggles when handling refrigerants.

2.2

Safety devices
Pressure monitor: switches the compressor off if the normal operating
pressure is exceeded.
Pressure relief valves: additional safety mechanism to protect lines or
vessels from bursting if the pressure continues to rise despite the action
of the pressure monitor.

Service Manual 09/06 - AirConServiceCenter

A-4

General information

Environmental protection and disposal


Used oil is hazardous waste.
Do not mix used oil with other liquids.
Until it is disposed of, keep used oil in suitable containers.

3.1

Disposing of packaging material


The cardboard packaging material should be disposed of with other
waste paper.
Plastic packaging material should be added to other recyclable waste.

3.2

Scrapping the old unit


If you wish to scrap the AirConServiceCenter, first completely drain it of
all liquids and dispose of them in an environmentally responsible manner.
Take the old device to your nearest recycling centre or contact WAECO
customer services.

Service Manual 09/06 - AirConServiceCenter

A-5

General information

Support
WAECO International GmbH
Hollefeldstrasse 63
48282 Emsdetten, Germany
Tel.: +49 (0) 25 72 / 8 79-191
Fax.: +49 (0) 25 72 / 8 79-3 91
E-mail: tdk@waeco.de

Service Manual 09/06 - AirConServiceCenter

A-6

Maintenance and repairs

Maintenance and repairs

Overview of AirConServiceCenter

1.1

Front
2
1

4
3

16
6

15

7
14

8
9

13
12

10
11
1

Pressure gauge for low pressure

Red Fill lamp

Blue Evacuate lamp

Green Suction lamp

Pressure gauge for high pressure

Display

Keypad

Service coupling for low pressure connection (blue)

Service coupling for high pressure connection (red)

Service Manual 09/06 - AirConServiceCenter

B-1

Maintenance and repairs


10 Knurled screw of transport lock
(on the underside of the AirConServiceCenter)
11 Front wheels with wheel stops
12 Service hose for low pressure connection (blue)
13 Service hose for high pressure connection (red)
14 Front cover
15 Printer (ASC1000 option)
16 Display unit

1.2

Rear

21
17
18
20

19

17 Container for new oil


18 Container for UV additive
19 Container for used oil
20 Cover flap
21 Main switch

Service Manual 09/06 - AirConServiceCenter

B-2

Maintenance and repairs

Maintenance intervals

Interval
Every 4 weeks
Every 4 weeks
Every 6 months
Every 6 months

According to display
According to display

Maintenance work
Comment
Check service hoses.
Check the exterior condition.
Calibrate load cells for refrig- Set zero point.
erant, oil and UV additive.
Check quick coupler.
Check exterior condition and
functionality.
Calibrate pressure
Carry this out on a monthly
transducer.
basis if device is subjected to
strong vibrations.
Replace filter.
Change vacuum pump oil.

Service Manual 09/06 - AirConServiceCenter

B-3

Maintenance and repairs

Activating the ASC 1000 printer


1. Use the cursor keys

or

to select Other selections:

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Enter the password 7276.
6. Press ENTER to confirm. The display shows:
PAR100
Transducer offset
mbar

7. Press the cursor key

10

to confirm. The display shows:

PAR
Enable
print

8. Press the cursor key

OF_PR

PA_LPT
NO
YES

. The display shows:

PAR
Enable
print

PA_LPT
NO
YES

9. Press ENTER to confirm.


10. Press STOP to go to standby mode.

Service Manual 09/06 - AirConServiceCenter

B-4

Maintenance and repairs

Putting in the containers for oil and UV additive


The current levels are shown in the info menu (see Opening the info
menu on page 9).
1. Open the cover flap (20) on the left hand side and connect the containers to the snap locks:
- Container for new oil (17)
- Container for UV additive (18) and
- Container for used oil (19)

17

18

19

2. Close the cover flap (20).


Only for ASC 2000 and ASC 3000:
3. Enter the container size for fresh oil and UV contrast agent (see Entering the container size on page 6).

Service Manual 09/06 - AirConServiceCenter

B-5

Maintenance and repairs

Entering the container size


Only applies to ASC 2000 and ASC 3000:
Fresh oil and UV additive can be kept in containers of 500 ml (B) or 250 ml
(C). You must enter the container size in the AirConServiceCenter.
B

1. In standby mode, use the cursor keys


selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Enter the password 2688.
6. Use the cursor keys to activate the fields you want (dark fields
are activated).
7. Press ENTER to confirm.
8. Press STOP to go to standby mode.

Service Manual 09/06 - AirConServiceCenter

B-6

Maintenance and repairs

Filling the internal refrigerant container


When the AirConServiceCenter is started for the first time, the internal
refrigerant container must be filled from an external refrigerant tank with at
least 5000 g of refrigerant.

Note the instructions on the refrigerant vessels!


The current levels are shown in the info menu (see Opening the info
menu on page 9).
There are three different types of refrigerant vessel available:
Refrigerant vessels without rising pipe (for example, WAECO item
no. 8887100002)
These refrigerant vessels have one connection.
When filling the AirConServiceCenter, the connection must be at the
bottom (container turned upside down).
Refrigerant containers with a rising pipe and two valves
These refrigerant vessels have one connection.
When filling the AirConServiceCenter, the connection must be at the
bottom (container upright).
Refrigerant vessels with rising pipe:
These refrigerant vessels have two connections. To fill the
AirConServiceCenter, use the connection labelled L (= liquid).
To fill the AirConServiceCenter, the connection must be at the top (container upright).
1. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Int. vessel filling:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Follow the instructions in the display.

Service Manual 09/06 - AirConServiceCenter

B-7

Maintenance and repairs


6. After filling, the quantity of refrigerant in the internal container is shown.
Press STOP to quit the menu.
Press STOP again to go to standby mode. The device is now ready
for operation.

Service Manual 09/06 - AirConServiceCenter

B-8

Maintenance and repairs

Opening the info menu


The info menu shows you the current levels in the refrigerant, fresh oil and
UV additive containers in the AirConServiceCenter.
You can open the info menu from standby mode.
Short selection
Free selection
Other selections
ENTER-OK

1. In standby mode, press i and hold it down.


The following is displayed with the ASC 1000:
Refrigerant quantity
Time
Date
With the ASC 2000 and ASC 3000 the following is displayed:

Refrigerant quantity
Fresh oil quantity
UV additive quantity
Time
Date

Service Manual 09/06 - AirConServiceCenter

B-9

Maintenance and repairs

Short selection
Refrigerant
PAG Oil
UV Tracer
08:37:40

g.
5885
ml.
240
ml.
235
07/02/06

Fully automatic air conditioning service is started with the Short selection menu. You only have to enter the filling quantity as shown on the
label in the vehicle or the database.
The following actions are performed automatically in succession in the
Short selection menu:
- Extraction of the refrigerant
- Recycling of refrigerant (purity meets SAE J 2099)
- Pressure rise test
- Draining of used oil
- Evacuation of the system
- Leak test / vacuum check
- Filling with fresh oil to the required quantity
- Filling of UV additive
- Filling of refrigerant
After every process is performed a service report is printed.
1. Remove the valve cap
2. First fit the connections of the AirConServiceCenter to the vehicle air
conditioning system and open them.
3. In standby mode, use the cursor keys
selection:

or

to select Short

Short selection
Free selection
Other selections
ENTER-OK

4. Press ENTER to confirm.


5. Use the keypad (7) and the cursor keys to enter the vehicle data.
6. Press ENTER to confirm.
7. Enter the refrigerant filling quantity. Either use the value shown on the
filling quantities sticker in the vehicle and enter it using the keypad (7)
and the cursor keys, or use the AirConServiceCenters database.

Service Manual 09/06 - AirConServiceCenter

B - 10

Maintenance and repairs

If in doubt, use the value shown on the label in the vehicle.


8. Select the setting (which then flashes) and press ENTER to confirm.
Then follow the instructions on the display (6).
9. If necessary, enter the desired data with the keypad (7) and cursor
keys and press ENTER to confirm.
If you do not want to enter any data here press ENTER to advance to
the next program step.

If you press i in database mode, the display (6) shows information on


the oil quantities and oil types.

After the air conditioning service has finished, you are prompted to disconnect the hoses (12) and (13) of the AirConServiceCenter from the
vehicle air conditioning system.

10. Disconnect the service hoses (12) and (13) and press ENTER to confirm.
The service hoses are then emptied. The device is then ready for
further use.
11. Put the valve caps of the vehicle air conditioning system back on
the connections.

Service Manual 09/06 - AirConServiceCenter

B - 11

Maintenance and repairs

Free selection
The Free selection menu is used to conduct air conditioner servicing
step-by-step. You can perform the same processes as in the short selection menu, but also leave certain procedures out. In addition, it is possible
to enter the values for each individual process using the keypad. You can
also enter vehicle data for the service report in this menu.
The following processes can be performed in the Free selection menu:
- Extracting and recycling the refrigerant, checking the pressure rise
and draining the used oil
- Evacuation of the system
- Leak test / vacuum check
- Filling with fresh oil
- Filling of UV additive
- Filling of refrigerant
After every process is performed a service report is printed.
1. First fit the connections of the AirConServiceCenter to the vehicle air
conditioning system and open them.
2. In standby mode, use the cursor keys
selection:

or

to select Free

Short selection
Free selection
Other selections
ENTER-OK

3. Press ENTER to confirm.


4. Then follow the instructions in the display:
Select the setting (which then flashes) and press ENTER to confirm.
5. If necessary, enter the desired data with the keypad and cursor keys
and press ENTER to confirm.
If you do not want to enter any data here press ENTER to advance to
the next program step.

After the air conditioning service has finished, you are prompted to disconnect the hoses of the AirConServiceCenter from the vehicle air
conditioning system.

6. Disconnect the service hoses (12) and (13) and press ENTER to confirm.

The service hoses are then emptied. The device is then ready for
further use.

7. Put the valve caps of the vehicle air conditioning system back on the
connections.

Service Manual 09/06 - AirConServiceCenter

B - 12

Maintenance and repairs

10

Flushing the air conditioning system


The Fluxing menu is used to flush the vehicle air conditioning system
with fresh refrigerant. Flushing is especially suitable for replacing old compressor oil or removing most metallic residue from the system.
WAECO recommends the use of the WAECO Recycle Guard (item
no. 8885200060).
Before flushing, the refrigerant must first be extracted from the vehicle air
conditioning system. Afterwards the system components which cannot be
flushed must be disconnected from the refrigerant circuit (for example, the
compressor or filter). After that, the components to be flushed are connected to the service ports of the AirConServiceCenter using special
adapters to form a flushing circuit.
1. First fit the connections of the AirConServiceCenter to the vehicle air
conditioning system and open them.
2. In standby mode, use the cursor keys
selection:

or

to select Free

Short selection
Free selection
Other selections
ENTER-OK

3. Press ENTER to confirm.


4. If necessary, enter the desired data with the keypad (7) and press
ENTER to confirm.
If you do not want to enter any data here, press ENTER to advance to
the next program step.
5. Select Rec/Recycling phase (which then flashes) and press ENTER
to confirm.
6. For the Pressure increase Test time, enter 1 minute and press
ENTER to confirm.
7. Deselect Vacuum phase with No (the chosen setting flashes) and
press ENTER to confirm.
8. Deselect Filling phase with No (the chosen setting flashes) and
press ENTER to confirm.
9. Select Process start with ENTER.

After flushing is completed, the AirConServiceCenter goes into


standby mode.

Service Manual 09/06 - AirConServiceCenter

B - 13

Maintenance and repairs


10. Disconnect the system components from the refrigerant circuit which
cannot be flushed. These components are, for example:
- Compressor
- Line filter
- Fixed choke
- Collection containers
- Filter drying units
- Expansion valve
11. Connect the components to be flushed to the service ports (8) and
(9) of the AirConServiceCenter using special adapters to form a flushing circuit.
12. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

13. Press ENTER to confirm.


14. Use the cursor keys

or

to select Fluxing:

Int. vessel filling


Fluxing
Reset scales
Service

15. If necessary, enter the desired data with the keypad (7) and press
ENTER to confirm.
If you do not want to enter any data here, press ENTER to advance to
the next program step.
16. Use the cursor keys
or
to select whether to flush the entire air
conditioning system or just individual components:
Full fluxing
Fast fluxing
ENTER-OK STOP-EXIT

17. Press ENTER to confirm.


18. Follow the instructions in the display.

After flushing is completed, the AirConServiceCenter goes into


standby mode.

Service Manual 09/06 - AirConServiceCenter

B - 14

Maintenance and repairs


19. If necessary, remove the adapter from the flushing circuit and reconnect all the components to the refrigerant circuit.
Fit the connections of the AirConServiceCenter to the vehicle air conditioning system and open them.
20. In standby mode, use the cursor keys
selection:

or

to select Free

Short selection
Free selection
Other selections
ENTER-OK

21. Press ENTER to confirm.


22. If necessary, enter the desired data with the keypad (7) and press
ENTER to confirm.
If you do not want to enter any data here, press ENTER to advance to
the next program step.
23. Deselect Rec/Recycling phase with No (the chosen setting flashes)
and press ENTER to confirm.
24. Select Vacuum phase (the chosen setting flashes) and press
ENTER to confirm.
25. If necessary, enter the desired data with the keypad (7) and press
ENTER to confirm.
If you do not want to enter any data here, press ENTER to advance to
the next program step.
26. Select Filling phase (the chosen setting flashes) and press ENTER
to confirm.
27. Enter the refrigerant filling quantity.
28. Then follow the instructions in the display (6):
Select the setting (which then flashes) and press ENTER to confirm.
29. Select Process start with ENTER.

After the filling is complete, you are prompted to disconnect the hoses
of the AirConServiceCenter from the vehicle air conditioning system.

30. Disconnect the service hoses (12) and (13) and press ENTER to confirm.
The service hoses are then emptied. The device is then ready for
further use.
31. Put the valve caps of the vehicle air conditioning system back on
the connections.

Service Manual 09/06 - AirConServiceCenter

B - 15

Maintenance and repairs

11

Air conditioning system test without refrigerant


service
The air conditioning can only be tested on vehicles with a low pressure
port and a high pressure port, or with a low pressure port only.

The air conditioning test is a test to check a vehicle air conditioning system. No refrigerant is either extracted or added during this process.

The existing standard function processes Short selection and Free


selection already have a compensation function for service hoses, which
means the final air conditioning function test can be carried out in the
usual manner (air conditioning hoses are drained by the device).
1. Fit the connections of the AirConServiceCenter to the vehicle air conditioning system and open them.
2. Start the vehicle's engine and switch on the air conditioner.
3. In standby mode, use the cursor keys

or

to select Other

4. selections:
Short selection
Free selection
Other selections
ENTER-OK

5. Press ENTER to confirm.


6. Use the cursor keys
test:

or

to select Air conditioning system

Check the A/C System


test
Service
ENTER-OK STOP-EXIT

A request appears asking you to check the air conditioning system:


Check the A/C System

STOP-EXIT

Service Manual 09/06 - AirConServiceCenter

B - 16

Maintenance and repairs


7. Check the high and low pressure system of the air conditioning system.
8. To end the air conditioning system test, press STOP.

A request to remove the HP quick coupling of the air conditioner appears:


HP connectors
removed?
Enter-OK

9. Close the HP quick coupling and detach it from the air conditioner.
10. Press ENTER to confirm.

If you have turned off the vehicle engine to uncouple the HP quick coupling,
restart the engine and turn on the air conditioner.

The following display messages are shown:


Wait !
Recovery from the
service hoses

Process completed.

STOP-EXIT

11. To end the air conditioning system test press STOP.

Service Manual 09/06 - AirConServiceCenter

B - 17

Maintenance and repairs

12

Calibrating the scales


It is not necessary to calibrate the oil scales of the ASC 1000 series.

In order for the oil quantities and the UV additive to be measured correctly,
the zero point of the scales must be checked regularly and reset if necessary.
Resetting is necessary:
If the quantity in a container deviates by more than 10ml from the
target value
If the AirConServiceCenter has been shaken, for example during transport on bumpy roads
Every 150 operating hours
1. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Reset scales:

Int. vessel filling


Fluxing
Reset scales
Service

4. Select the scale with the cursor keys


or , and confirm with ENTER.
A request to remove the container from the scale appears:
Scale empty ?

ENTER-OK
STOP-EXIT

Service Manual 09/06 - AirConServiceCenter

B - 18

Maintenance and repairs

In order to check the zero points of the scales for the oils and the
UV additive, open the cover flap (20) on the left hand side and disconnect the containers from the snap locks:
- Container for new oil (17)
- Container for UV additive (18)
- Container for used oil (19)

17

18

19

To check the zero point of the refrigerant scales, screw in the


knurled screw (10) of the transport lock on the underside of the
AirConServiceCenter as far as it will go. This slightly lifts the refrigerant container and relieves the scales.

5. When the scales are relieved, press ENTER to confirm. The prompt to
take the container off the scales flashes.

Once you have set the zero point, the selection menu for the scales
appears again.

6. Check the zero points for the other scales in the same way if necessary.
7. Return the container to the operating position.
Attach the containers for oil (17) and (19) and for UV additive (18)
to the catches again and close the cover (20).
Undo the knurled screw (10) of the transport lock on the bottom of
the AirConServiceCenter as far as it will go.
8. Press STOP twice to go to standby mode.

Service Manual 09/06 - AirConServiceCenter

B - 19

Maintenance and repairs

13

Changing the internal filter


1. In standby mode, use the cursor keys
selection:

or

to select Free

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Skip the query requesting CAR DATA.
4. Select Rec/Recycling phase.
5. Set the Pressure increase Test time min. to 1.
Press ENTER to confirm.
6. Deselect Vacuum phase with No.
Press ENTER to confirm.
7. Deselect Filling phase ? with No.
Press ENTER to confirm.
8. Select Process start ?.
Confirm with ENTER.
The service hoses are drained and the AirConServiceCenter is in
standby mode.

Switch off the device before opening it and pull out the mains plug.
9. Take off the front panel:
Unscrew the tool storage tray screws (C) and remove the tool
storage tray.
Unscrew the keypad screws (D) and lift it up. Then undo the screws
(E) on the bottom of the front panel and take it off.

Service Manual 09/06 - AirConServiceCenter

B - 20

Maintenance and repairs

C
C
D

E
E
10. Remove the filter cartridge (F) on the left side and replace it with a
new one (WAECO filter item no. 4440400008). When inserting a new
filter cartridge, pay attention to the flow direction (FLOW arrow must
point downwards).

11. Check the connections do not leak.


12. Put the front panel, the tool storage tray and control panel back on and
reconnect the power plug.

Service Manual 09/06 - AirConServiceCenter

B - 21

Maintenance and repairs

14

Changing the vacuum pump oil


Switch off the AirConServiceCenter and unplug it from the power supply
before opening the housing.
1. Take off the front panel:
Unscrew the tool storage tray screws (C) and remove the tool
storage tray.
Unscrew the keypad screws (D) and lift it up. Then undo the screws
(E) on the bottom of the front panel and take it off.

C
C
D

E
E
2. Place a receptacle with a capacity of at least 1/2 litre under the
AirConServiceCenter. The oil from the vacuum pump flows through
the opening (I) in the base of the device.
3. Unscrew the oil filling plug (G).
4. To drain the oil, unscrew the oil drain plug (J).

Service Manual 09/06 - AirConServiceCenter

B - 22

Maintenance and repairs

H
I

5. Once the oil has been completely drained from the pump housing,
screw the oil drain plug (J) back in.
6. Top up with new vacuum pump oil (vacuum pump oil item no.
8887200003, quantity 400 ml) to the middle of the sight glass (H) and
screw the oil filler plug (G) back in.
7. Put the front panel, the tool storage tray and control panel back on and
reconnect the power plug.

Service Manual 09/06 - AirConServiceCenter

B - 23

Maintenance and repairs

15

Calibrating the pressure transducer


The pressure transducer has to be correctly calibrated in order to make
accurate pressure measurements.
Calibration is required:
Every time the vacuum pump oil is changed
When the display shows implausible pressure readings
1. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Enter the password 2224.
6. Select Pressure transducer with ENTER.
7. Then follow the instructions in the display.
Unscrew the service couplings (8) and (9) from the service hoses
(12) and (13).
Use the keypad (7) to enter the current local atmospheric pressure
and press ENTER to confirm.
8. When calibration has been completed, press ENTER to quit the menu.
9. Press STOP twice to go to standby mode.
10. Screw the service couplings (8) and (9) hand-tight onto the service
hoses (12) and (13), taking care not to mix up the red and blue markings on the couplings and hoses.

Service Manual 09/06 - AirConServiceCenter

B - 24

Maintenance and repairs

16

Calibrating the refrigerant scale


1. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Enter the password 5623.
6. Use the cursor keys

or

to select Refrigerant:

select device
Refrigerant
Fresh Oil Scale
ENTER-OK STOP-EXIT

7. Press ENTER to confirm.


-- Refrigerant scale -Scale
empty?
ENTER-OK STOP-EXIT

8. Screw on the knurled screw (10) of the transport lock on the bottom of
the AirConServiceCenter as far as it will go.
Wait ten seconds so the load cell can stabilise.
9. Press ENTER to confirm.

The display flashes four times:


Wait !
Dont touch
the unit !

Service Manual 09/06 - AirConServiceCenter

B - 25

Maintenance and repairs

The display then shows:


Scale charged ?

ENTER-OK STOP-EXIT

10. Undo the knurled screw (10) of the transport lock on the bottom of the
AirConServiceCenter as far as it will go.
Wait ten seconds so the load cell can stabilise.
11. Press ENTER to confirm.

The display flashes four times:


Wait !
Dont touch
the unit !

The display then shows:


-- Refrigerant -Place the sample
weight on the scale.
ENTER-OK STOP-EXIT

12. Unscrew the screw cap (S) from the tank valve.

Service Manual 09/06 - AirConServiceCenter

B - 26

Maintenance and repairs


13. Lay the sample weight (G) horizontally on the tank value.

G
S
M
S

The sample weight has a different weight. The specific weight is indicated on each sample weight (M).
14. After placing the sample weight down, press ENTER to confirm. The
display flashes four times:
Wait !
Dont touch
the unit !

The display then shows:


-- Refrigerant scale -Enter the right
value!
g.
ENTER-OK STOP-EXIT

15. Enter the weight (M) of the sample weight using the keypad.
Wait ten seconds so the load cell can stabilise.
16. Press ENTER to confirm. The display blinks four times:
Calibration ok!
ENTER-OK

Service Manual 09/06 - AirConServiceCenter

B - 27

Maintenance and repairs


17. When calibration has been completed, press ENTER to quit the menu.
18. Press STOP twice to go to standby mode.
19. Remove the sample weight and screw the screw top back onto the
tank valve.

Service Manual 09/06 - AirConServiceCenter

B - 28

Maintenance and repairs

17

Calibrating the oil scale


It is not necessary to calibrate the oil scales of the ASC 1000 series.

The following section describes the calibration process for the fresh oil
scale. This description also applies to the contrast agent and old oil scale.
Required tools: Sample weight 300 g.
1. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Enter the password 5623.
6. Use the cursor keys
Fresh oil):

or

to select the desired scale (for example:

Select device
Refrigerant
Fresh Oil
ENTER-OK STOP-EXIT

7. Press ENTER to confirm. The display shows:


-- Fresh oil -Scale empty ?

ENTER-OK STOP-EXIT

Service Manual 09/06 - AirConServiceCenter

B - 29

Maintenance and repairs


8. Remove the cover flap (20) on the left hand side and connect the relevant containers to the snap locks:
- Container for new oil (17)
- Container for UV additive (18)
- Container for used oil (19)

17

18

19

9. Disconnect the container for fresh oil (17) from the fresh oil scale and
remove it from the device.
Wait ten seconds so the load cell can stabilise.
10. Press ENTER to confirm. The display flashes four times:
Wait !
Dont touch
the unit !

The display then shows:


-- Fresh oil -Scale empty ?
ENTER-OK STOP-EXIT

11. Press ENTER to confirm. The display flashes four times again:
Wait !
Dont touch
the unit !

The display then shows:


-- Fresh oil -Place the sample
weight on the scale.
ENTER-OK STOP-EXIT

Service Manual 09/06 - AirConServiceCenter

B - 30

Maintenance and repairs


12. Connect the sample weight to the fresh oil scale.
Wait ten seconds so the load cell can stabilise.
13. After connecting sample weight, press ENTER to confirm. The display
flashes four times:
Wait !
Dont touch
the unit !

The display then shows:


-- Fresh oil -Enter the right
value !
g.
ENTER-OK STOP-EXIT

14. Enter the weight (300 g) of the sample weight using the keypad.
Wait ten seconds so the load cell can stabilise.
15. Press ENTER to confirm. The display flashes four times:
Calibration ok!
ENTER-OK

16. When calibration has been completed, press ENTER to quit the menu.
17. Press STOP twice to go to standby mode.
18. Remove the sample weight and reconnect the oil container.

Service Manual 09/06 - AirConServiceCenter

B - 31

Maintenance and repairs

18

Function control
The following section describes the function control of all solenoid valves
and processes. This description is for the purpose of accessing the individual processes without having to connect the device to an air conditioner.
1. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Enter the password 1212.
6. Press ENTER to confirm.
The display then shows:
1 CX
5 HB
9 HP
PS=

2 DO
6 UV
0 RE
1mb

Service Manual 09/06 - AirConServiceCenter

3 OI
7 FA

4 VC
8 LP
SS=ON
9999 gr.

B - 32

Maintenance and repairs


Key assignments:
Code

Key assignment

CX

Button 1: Start manual recovery phase

DO

Button 2: Start manual draining of old oil

OI

Button 3: Start manual fresh oil injection

VC

Button 4: Start manual vacuum phase

HB

Button 5: Start heating strap manually

UV

Button 6: Start manual contrast agent injection

FA

Button 7: Start condenser fan manually

LP

Button 8: Open the solenoid valve for low pressure manually

HP

Button 9: Open the solenoid valve for high pressure manually

RE

Button 0: Start filling phase manually

7. Press STOP twice to go to standby mode.

Service Manual 09/06 - AirConServiceCenter

B - 33

Maintenance and repairs

19

Correcting the filling quantity for long service hoses


1. In standby mode, use the cursor keys
selections:

or

to select Other

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

4. Press ENTER to confirm.


5. Enter the password 7732.

You are asked to enter the length of the HP hose:


Set the HP hose
length (cm):
300
ENTER-OK STOP-EXIT

6. Press ENTER to confirm.

Service Manual 09/06 - AirConServiceCenter

B - 34

Maintenance and repairs

20

Replacing the printer paper


1. To replace the printer paper roll (15), open the cover (K).

2. Put in the new paper roll (paper roll item no. 4445900088) as shown
and close the cover (K).

Service Manual 09/06 - AirConServiceCenter

B - 35

Maintenance and repairs

21

Changing the WAECO flash memory card


The AirConServiceCenter contains a WAECO flash memory card. The
WAECO flash memory card contains:
The software of the AirConServiceCenter
A database with all the common vehicle types and corresponding
filling quantities
In order that the information is always kept up-to-date, the latest WAECO
flash memory card must always be installed.
For information on the latest WAECO flash memory card version, call the
WAECO hotline (Tel.: +49 (0) 25 72 / 8 79-1 91).

When you replace an old WAECO flash memory card with a new one, the
individual device data (such as company information and counter) is kept.
The old flash memory card is no longer required and can be taken for disposal in the appropriate manner.

Switch off the device before opening it and pull out the mains plug.
1. Unscrew the screws (C) from the tool storage tray and remove it.
2. Undo the screws (D) on the control panel and lift it up.

C
C
D

3. Open the fastening of the WAECO flash memory card and pull out the
card (L).

Service Manual 09/06 - AirConServiceCenter

B - 36

Maintenance and repairs

L
4. Insert the new WAECO flash memory card and fasten it.
Flash memory card for ASC 1000: Item no. 4441000041
Flash memory card for ASC 2000: Item no. 4441000042
Flash memory card for ASC 3000: Item no. 4441000043
5. Lower the control panel and screw it down.
6. Replace the tool storage tray and screw it tightly.
7. Reconnect the power plug.

Service Manual 09/06 - AirConServiceCenter

B - 37

Maintenance and repairs

22

Fault table

Fault
The display shows
WARNING!
Internal vessel overpressure.
The display shows
WARNING!
Internal vessel filled.
The display shows
WARNING!
Pressure inside the A/C
system.
Recovery start.
The display shows
WARNING!
Pressure inside the in A/C
system.
The display shows
Not enough vacuum to
carry on?

The display shows


A/C system leakage.
cary on?

The display shows


Drained oil glass emptying.

The display shows


WARNING!
Not enough vacuum for
injection!
The display shows
Not enough refrigerant.
Add.

Cause
Remedy
This message is normal
To continue, press ENTER
during the recycling process. for three seconds.
If the message appears
more than once, inform a
technician.
The internal refrigerant
Drain the internal refrigerant
container is too full to hold
container in the proper
the quantity to be extracted. manner.
This message is normal
No action is required.
at the start of the vacuum
The process continues
process. There is still pres- automatically.
sure present in the air conditioning system.
Message during the vacuum No action is required.
process. There is pressure in The process continues
the air conditioning system. automatically.
This message appears
during the vacuum process
when the pressure in the air
conditioning system after
8 minutes is still more than
50 mbar.
Message at the end of the
vacuum process. The air
conditioning system shows
a vacuum loss of more than
120 mbar during the checking time.
This message appears
during the extraction or recycling process if there is more
than 150 ml of used oil in the
container.
This message appears
during the filling phase if the
vacuum in the air conditioning system is insufficient to
end the process.
This message appears
during the process input if
there is not enough refrigerant in the internal container
to complete the process.

Service Manual 09/06 - AirConServiceCenter

Check the air conditioning


system or the connections
between it and the
AirConServiceCenter for
leaks.
Check the air conditioning
system or the connections
between it and the
AirConServiceCenter for
leaks.
Dispose of the content of
the used oil container in an
environmentally responsible
manner.
Check the air conditioning
system or the connections
between it and the
AirConServiceCenter for
leaks.
Fill the refrigerant container.

B - 38

Maintenance and repairs


Fault
The display shows
Not enough UV. Add.

The display shows


Not enough oil. Add.

The display shows


Max. filling time
exceeded! Carry on?
The display shows
External tank empty or
closed valve ! Check!

The display shows


Change the equipment
drier filter. Go on ?
The display shows
Change the vacuum pump
oil! Gon on ?
The display shows
Printer not in line. Carry
on ?

No print image.
The yellow lamp of the
printer flashes.

Cause
This message appears
during the filling process if
there is not enough UV additive in the container to finish
the process.
This message appears
during the filling process if
there is not enough fresh oil
in the container to finish the
process.
This message appears
during the filling process if
the set amount of refrigerant
cannot be filled.
This message appears at
the start or during the filling
of the internal refrigerant
container if the set refrigerant
quantity cannot be attained.
This message appears
when you switch on the
AirConServiceCenter.

Remedy
Fill the UV additive container.

This message appears


when you switch on the
AirConServiceCenter.

Change the vacuum pump oil


as soon as possible.

This message indicates a


printer fault.

Check if there is paper in


the printer.
Check if the printer is
switched on (yellow LED
must light up constantly)
Check that the flap is
closed properly.
Install correct thermal paper.

Wrong printing paper


installed.
Flap not closed.
Paper missing.
Serial data transmission
incorrect.

Recovery phase not starting.


Recovery phase ends
instantly.
Recovery phase does not
Pressure transducer
end; pressure gauge shows not calibrated.
less than 0 bar.
Pressure transducer
defective.

Service Manual 09/06 - AirConServiceCenter

Fill the oil container.

Check that
AirConServiceCenter connections are not blocked.
Check if the external
refrigerant container enough
refrigerant or if the valves of
the external refrigerant container are open.
Change the internal filter as
soon as possible.

Close flap.
Install new paper roll.

Calibrate pressure transducer.


Replace pressure transducer.

B - 39

Maintenance and repairs


Fault
Recovery phase does not
end; pressure gauge shows
more than 0 bar.

Cause
Defective compressor.
Solenoid valve Fill not
closed.

Recovery phase does not


end, but pressure gauge
shows more than 0.6 bar.

Pressure transducer
not calibrated.
Pressure transducer
Replace pressure transducer.
defective.
Pressure transducer is incor- Calibrate pressure
rectly calibrated or defective. transducer; replace where
necessary.
Solenoid valve does not
Check the electronic conopen.
trols for the solenoid valve;
clean solenoid valve.
No pass between the fresh Check the hose in the fresh
oil container and the solenoid oil container, the quick couvalve block.
pling of the fresh oil container
and the connection hose to
the solenoid valve block all
have enough space.
Scale measures an incorrect Check tare setting; reset
valve.
zero point.
Pressure transducer is incor- Calibrate pressure transrectly calibrated or defective. ducer; replace where necessary.
Solenoid valve does not
Check the electronic conopen.
trols for the solenoid valve;
clean solenoid valve.
Scale measures an incorrect Check tare setting; reset
valve.
zero point.
No pass between the UV
Check the hose in the
contrast agent container and contrast agent container, the
the solenoid valve block.
quick coupling of the contrast
agent container and the connection hose to the solenoid
valve block all have enough
space.
No pass between the fresh Check the hose in the fresh
oil container and the solenoid oil container, the quick couvalve block.
pling of the fresh oil container
and the connection hose to
the solenoid valve block all
have enough space.

Fresh oil is not injected.

Contrast agent is not


injected.

Service Manual 09/06 - AirConServiceCenter

Remedy
Replace compressor.
Remove solenoid valve and
clean it; install replacement
where necessary.
Calibrate pressure transducer.

B - 40

Maintenance and repairs

23

Activating the DATA LOGGER


You can measure and print out trends in pressure and temperature with
the help of the data logger in AirConServiceCenter.
All measured data is subsequently printed out in the process report.
1. In standby mode, use the cursor keys
selection:

or

to select Short

Short selection
Free selection
Other selections
ENTER-OK

2. Press ENTER to confirm.


3. Use the cursor keys

or

to select Other selections:

Short selection
Free selection
Other selections
ENTER-OK

4. Press ENTER to confirm.


5. Use the cursor keys

or

to select Service:

Int. vessel filling


Fluxing
Reset scales
Service

6. Press ENTER to confirm.


7. Enter the password 7276.
8. Press ENTER to confirm. The display shows:
PAR100
Transducer offset
mbar

OF_PR

10

Service Manual 09/06 - AirConServiceCenter

B - 41

Maintenance and repairs


9. To confirm
ASC 1000: Press the cursor key
twice.
ASC 2000 / ASC 3000: Press the cursor key
The display shows:
PAR
Enable
Log print

10. Press the cursor key

once.

PA_LPT_LOG
No
YES

. The display shows:

PAR
Enable
Log print

PA_LPT_LOG
NO
YES

11. Press ENTER to confirm.


12. Press STOP to go to standby mode.
Data description
PR1 = xxxxx mb xxC

Pressure / Temperature of the internal refrigerant


vessels prior to the recovery phase

PR2 = xxxxx mb xxC

Pressure / Temperature of the internal refrigerant


vessels after to the recovery phase

PR3 = xxxxx mb xxC

Pressure / Temperature of the internal refrigerant


vessels prior to the vacuum phase

PR4 = xxxxx mb xxC

Pressure / Temperature of the internal refrigerant


vessels before the filling phase

PR5 = xxxxx mb xxC

Pressure / Temperature of the internal refrigerant


vessels after the filling phase

Service Manual 09/06 - AirConServiceCenter

B - 42

Maintenance and repairs

24

Cleaning and maintenance


Clean the exterior of the device with a damp cloth as required. If necessary, use a small amount of dishwashing detergent. Do not use solvents
or scouring agents.
Regularly check the service hoses and adapters for damage. Do not
start up the AirConServiceCenter if it is damaged.

Service Manual 09/06 - AirConServiceCenter

B - 43

Technical data

Technical data

Exploded drawings

Service Manual 09/06 - AirConServiceCenter

C-1

Technical data

Service Manual 09/06 - AirConServiceCenter

C-2

Technical data

Service Manual 09/06 - AirConServiceCenter

C-3

Technical data

Service Manual 09/06 - AirConServiceCenter

C-4

Technical data

Circuit diagrams

Service Manual 09/06 - AirConServiceCenter

C-5

Technical data

Service Manual 09/06 - AirConServiceCenter

C-6

Technical data

Service Manual 09/06 - AirConServiceCenter

C-7

Technical data

Service Manual 09/06 - AirConServiceCenter

C-8

Technical data

Service Manual 09/06 - AirConServiceCenter

C-9

Technical data

Hydraulic diagrams

3.1

ASC-1000

Service Manual 09/06 - AirConServiceCenter

C - 10

Technical data

3.2

ASC-2000

Service Manual 09/06 - AirConServiceCenter

C - 11

Technical data

3.3

ASC-3000

Service Manual 09/06 - AirConServiceCenter

C - 12

Technical data

General device data

ASC1000
Weight
Power supply
Refrigerant extraction rate
Vacuum pump output
Hermetic compressor output
Drier filter output
Filling cylinder accumulator capacity
Noise emission
Accuracy of the electronic scales for refrigerant
Accuracy of the electronic scales for old/new oil
Accuracy of the electronic scales for UV additive

560 mm x 1300 mm x 650 mm


95 kg
230 V/240 V - 50 Hz/60 Hz
18 kg / hr
4 cars / h
0.2 kW
150 kg
12.0 l (10.0 kg)
55.5 dB (A)
+/- 10 g
+/- 1 g
+/- 1 g

ASC2000
Dimensions (width x height x depth)
Weight
Power supply
Refrigerant extraction rate
Vacuum pump output
Hermetic compressor output
Drier filter output
Filling cylinder accumulator capacity
Noise emission
Accuracy of the electronic scales for refrigerant
Accuracy of the electronic scales for old/new oil
Accuracy of the electronic scales for UV additive

560 mm x 1300 mm x 650 mm


100 kg
230 V/240 V - 50 Hz/60 Hz
30 kg / hr
5 cars / h
0.32 kW
150 kg
24.0 l (21.0 kg)
55.5 dB (A)
+/- 10 g
+/- 1 g
+/- 1 g

ASC3000
Dimensions (width x height x depth)
Weight
Power supply
Refrigerant extraction rate
Vacuum pump output
Hermetic compressor output
Drier filter output
Filling cylinder accumulator capacity
Noise emission
Accuracy of the electronic scales for refrigerant
Accuracy of the electronic scales for old/new oil
Accuracy of the electronic scales for UV additive

560 mm x 1300 mm x 650 mm


105 kg
230 V/240 V - 50 Hz/60 Hz
30 kg / hr
153 l / h
0.32 kW
150 kg
24.0 l (21.0 kg)
55.5 dB (A)
+/- 10 g
+/- 1g
+/- 1g

Service Manual 09/06 - AirConServiceCenter

C - 13

Technical data

5
Item
01
04
04
05
05
06
07
08
09
10
10
11
12
13
14
15
16
17
17
17
18
18
19
20
21
22
23
24
25
25
25
25
28
29
30
31
32

Spare parts
Description
Compressor
Condenser ASC 1000
Condenser ASC 2000
Refrigerant container ASC 1000
Refrigerant container ASC 2000
ASC drying unit
Solenoid valve
Expansion valve
Solenoid valve
Valve block ASC 1000
Valve block ASC 2000
Safety valve installation kit
Safety valve installation kit
ASC pressure switch
Oil drain valve ASC
Coarse filter
Pressure transducer
Vacuum pump ASC 1000
Vacuum pump ASC 2000
Vacuum pump ASC 3000
CU pipe int. vessel ASC 1000
CU pipe 6x0.9 int. vessel ASC 2000
Low-pressure pressure gauge, complete
High-pressure pressure gauge, complete
Quick coupler LP, inside thread
Quick coupler HP, inside thread
Filling hose LP, 3 m, 1/2"
Filling hose HP, 3 m, 1/2"
Load cell 8 kg + plug connector
Load cell 60 kg oil/UV+ plug connector
Load cell 8 kg + plug connector
Load cell 8 kg + plug connector
Load cell 60 kg cooling + plug connector
Connection hose ASC with external valve
Capillary tube
Return valve
Fluid pump ASC 3000

Service Manual 09/06 - AirConServiceCenter

Item number
4440100013
4440200022
4440200020
4440600036
4440600018
4440400008
4440600043
4440600013
4440600043
4440600031
4440600022
4440600029
4440600029
4440600017
4440600014
4440600044
4440600045
4440600030
4440600019
4440600035
4440450055
4440450054
4440600046
4440600047
4440500009
4440500010
4440600040
4440600041
4441600095
4441600093
4441600095
4441600095
4441600094
4440600016
4440450056
4440600048
4441600091

C - 14

Technical data
Item
40
41
42
42
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
56
57
57
57
58
59
60
61
62
63
64

Description
Wheel diametre 250, black
Wheel diametre 100 + brake
Front cover ASC 1000
Front cover ASC 2000
Front cover ASC 3000
Tool storage tray ASC
Pressure gauge cover
Used oil container
Fresh oil/UV container
Adapter for oil/UV vessel ASC

Item number
4443900162
4443900163
4443000178
4443000177
4443000187
4443000179
4443900178
4440600024
4440600025
4440600026

Main switch ASC


Mains cable 230
Heating strap 580 ASC 1000
Heating strap 790 ASC 2000/3000

4441400013
4441300086
4441600089
4441600078

Switch electronics P11 ASC


Keypad ASC 1000
Keypad ASC 2000/3000
Memory card ASC 1000
Memory card ASC 2000
Memory card ASC 3000
Printer ASC
Printing paper ASC VPE=4 pieces

4441000034
4441000038
4441000037
4441000041
4441000042
4441000043
4441600077
4445900088

Inductor, solenoid valve


Piston diametre 2.5 (1 point)
Piston diametre 2.5 (2 point)
Piston diametre 4.5

4440600049
4440600050
4440600051
4440600052

Service Manual 09/06 - AirConServiceCenter

C - 15

Technical data

6
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Accessories
Description
PAG fresh oil bottle ISO 46, 500 ml
PAG fresh oil bottle ISO 100, 500 ml
UV contrast agent bottle, 500 ml
Adapter for 500 ml fresh oil and UV contrast agent bottle
Container for additional oil type
Used oil container, 500 ml
Spare filter for maintenance
Filling cylinder 4.4 g as refrigerant storage
Protective device cover
Supply bottle for tracer filling apparatus, 236 ml
Supply bottle for tracer filling apparatus, 475 ml
Tracer filling apparatus (separate additive vessel)
Spare printer roll (thermal paper) (VPE 4)
Service hose for high pressure side (SAE standard) 5 m
Service hose for low pressure side (SAE standard) 5 m
Safety goggles
Protective gloves
Recycle Guard

Service Manual 09/06 - AirConServiceCenter

Item number
8887200013
8887200014
TP-3820-500
4440600026
4440600034
4440600033
4440400008
8885200003
4445900081
TP-3820-0008
TP-3820-0016
4440600034
4445900088
8885100026
8885100025
8885400066
8885400065
8885200060

C - 16

Index
A

Exploded drawings C - 1
Accessories C - 16
Activating
DATA LOGGER B - 41

F
Fault table B - 38
Filling
phase B - 20

Activating the printer B - 4


Air conditioning system
Fill B - 13
Flushing B - 13
Phase B - 13, B - 15

Filling the (internal) refrigerant


container B - 7
Fluxing B - 14

Air conditioning system test B - 16


without refrigerant service B - 16

Function control B - 32

General device data C - 13

Calibrating the
oil scale B - 29
refrigerant scale B - 25
scales B - 18

Calibrating the oil scale B - 29

Hydraulic diagrams C - 10

Calibrating the
pressure transducer B - 24
Calibrating the refrigerant scale B - 25

Knurled screw B - 26

Car data B - 20

Maintenance B - 1, B - 43

Changing the filter B - 20

Maintenance intervals B - 3

Changing the flash memory card B - 36


Changing the memory card B - 36

O
Opening the info menu B - 9

Changing the vacuum pump oil B - 22


Cleaning B - 43

Correcting the filling quantity


Long service hoses B - 34

Pressure monitor A - 4
Pressure relief valves A - 4
Process start B - 15

Putting in the containers


(oil and UV additive) B - 5

Database B - 36
Device data B - 36
Disposal A - 5

R
Recycling
phase B - 20

E
Entering the container size B - 6

Repairs B - 1

Environmental protection A - 5

Replenishing printer paper B - 35

Service Manual 09/06 - AirConServiceCenter

I-1

S
Safety devices A - 4
Safety instructions A - 3
Sample weight B - 27
Selection B - 12
Software B - 36
Spare parts C - 14
Start processes B - 13
Support A - 6
Symbols A - 2

T
Technical data C - 1
Transport lock B - 26

V
Vacuum phase B - 13, B - 15, B - 20
Vehicle types B - 36

W
WAECO hotline B - 36
Warnings A - 4

Service Manual 09/06 - AirConServiceCenter

I-2

WAECO Headquarters
WAECO International GmbH Hollefeldstrasse 63 48282 Emsdetten, Germany
: +49 2572 879-0 : +49-2572 879-300 E-mail: info@waeco.de Internet: www.waeco.de

WAECO Subsidiaries
CH

WAECO Switzerland AG
Riedackerstrasse 7a
8153 Rmlang (Zurich), Switzerland
: +41 44 8187171
: +41 44 8187191
E-mail: info@waeco.ch

DK

WAECO Denmark A/S


Tvrvej 2
6640 Lunderskov, Denmark
: +45 75585966
: +45 75586307
E-mail: waeco@waeco.dk

WAECO Distribution SARL


ZAC 2 Les Portes de LOise
Rue Isaac Newton
60230 Chambly (Paris), France
: +33 1 30282020
: +33 1 30282010
E-mail: info@waeco.fr

WAECO Importers
FIN WAECO Finland OY

Mestarintie 4
01730 Vantaa, Finland
: +358 20 7413220
: +358 9 7593700
E-mail: waeco@waeco.fi

WAECO Norway AS
Leif Weldingsvei 16
3208 Sandefjord, Norway
: +47 33428450
: +47 33428459
E-mail: firmapost@waeco.no

NL WAECO Benelux B.V.

Ecustraat 3
4879 NP Etten Leur, Holland
: +31 76 5029000
: +31 76 5029090
E-mail: verkoop@waeco.nl

www.airconservice.de

WAECO Sweden AB
Gustaf Melins gata 7
S-42131 Vstra Frlunda (Gothenburg),
Sweden
: +46 31 7341100
: +46 31 7341101
E-mail: info@waeco.se

CZ Univer s.r.o.

Preperska 1809
51101 Turnov, Czech Republic
: +420 481 32 33 81
: +420 481 32 12 72
E-mail: univer@univer.cz

HR Silco - AT d.o.o.

Gorenska 62a
10225 Gornji Stupnik - Zagreb, Croatia
: +38 63 700 18 96
: +38 63,570 11 68
E-mail: saso.kronovsek@silco.si

PL Webasto Petemar Sp. z.o.o.

UI. Warsaw 205/219


05-092 Lomianki, Poland
: +48 22 751 77 87
: +48 22,751 77 88
E-mail: webasto.petemar@webasto.pl

SLO SILCO D. O.O.

Orla vas 27a


3314 Braslovce, Slovenia
: +38 63 700 18 96
: +38 63,570 11 68
E-mail: saso.kronovsek@silco.si

TR ELTESAN

Sogutma Sistemleri San ve Tic A.S.


Bayraktar Bulvari, Nutuk Sokak No : 9
Y. Dudullu
mraniye-Istanbul, Turkey
: +90 216 540 51 51
: +90,216,540 50 70
E-mail: mail@eltesan.com

YU Polar Klima D.O.O.

Vajara Djoke Jovanovica 4