Anda di halaman 1dari 114

1.

Drum level dropping fast


Likely causes

One of the running BFP might have tripped


Sudden tripping of one or more Mills/feeder.
FW control valve/scoop might have closed/stuck.
Malfunction of auto control/scoop regulation.
BFP recirculation valve suddenly opened or valve passing
Sudden reduction of load.
Tube failure in water walls.
HPBP in open position for long time under full load condition
Inadvertent opening of EBD & low point drains.
Drum pressure very high
Drum level transmitters faulty.

Plant response

Drum level LOW alarm appears.


BFP's scoop rises to maximum.
FCV opens to 100%
Boiler will trip if drum level becomes very low

Parameters of concern / Adverse Effects

Drum level very low may affect natural circulation in water wall panel and if drum is empty tubes will melt in no time
Deaerator level
Hot well level
Feed water flow
Steam flow
SH/RH temp

Immediate expected or desirable operator action.

See that standby BFP starts on tripping of running BFP or else


Manually start standby BFP when level drops to -100 mm & load the pump immediately.
Check for any malfunction of auto control like scoop/FCV not raising or recirculation open in auto, take control in to manual &
regulate it
Close CBD if it is open.
Close BFP RC valve MIV if heavy passing is noticed
Close HPBP slowly if it is open.
Reduce boiler firing when level is about -100 mm

Final Corrective Activity.

2.

Check drum level is getting stabilised.


Ensure drum level controls are in auto.
Check feed water flows matches with steam flow for full load, if deviation is more then check for any leak in boiler area.
Ensure for the availability of standby BFP as early as possible.
Check for local level gauge & transmitters.
Check boiler low point drains & EBD.
Check for scoop controls for any linkage failures.
Drum level shooting up fast

Likely causes

Malfunction of feed control valve or BFP scoop.


Scoop /Flow control valve might have stuck.
Sudden increase of load
Drum level transmitters may be faulty.
Sudden increase of firing rate.
Sudden opening of HPBP.

Plant response

Drum level high alarm will appear.


If drum level reaches very high level boiler will trip
BFP scoop & FCV position reduces
BFP RC valves may open

Parameters of concern / Adverse Effects


Drum level very high may cause priming foaming & carry over. If Water is discharged to super heater header hammering may occur
& wet steam may enter MS line
Deaerator level
Hot well level
Feed water flow
Steam flow
SH/RH temp
Immediate expected or desirable operator action.
Open emergency blow down EBD-valve
Reduce HPBP valve position if it is open
Reduce boiler firing
If drum level is approaching trip value take drum level control on manual & regulate
Reduce load for a momentso as to control the water level (if water level is due to upward load surge).
Final correction activity
Check drum level is getting stabilised.
Ensure drum level controls are in auto.
Check feed water flow matches with steam flow.
Check for stuck of feed control valves & scoop.

3.

Check the level at local, hydrostep and transmitters are matching.

Rapid Boiler steam pressure rise


Likely causes

Corex calorific value increased drastically.


Sudden loading of mill.
High firing rate.
Feeder hunting.
Malfunction of CMC.
Sudden dropping of generator load & HPBP not opened

Plant response

Throttle pressure high alarm will come


HP/LP bypass opens on auto.
APH FG I/L O2 low alarm will appears
Boiler safety valve may float.
Drum level will vary.

Parameters of concern/Adverse effects.


Drum pressure sudden raise may cause safety valve lifting
Tube leak may start

Unit load
MS /RH temperature
Drum level
APH inlet O2
HP/LP bypass

Immediate expected or desirable operator action


Take the fuel control into manual mode if it is in CMC & reduce the fuel firing.
Trip the malfunctioning feeder/mill & reduce PA airflow through that mill.
Check for pressure drop & if it is not holding remove the corex burners.
Start standby BFP if drum level is dropping
Final correction activity
Check for reseating of safety valve
As soon as the pressure starts dropping, restore the correct fuel input.
Stop the third running BFP and keep it in standby.
Ensure drum level got stabilised.
Check for closure of HP bypass.
Ensure pressure is stable.

4.

Rapid Boiler steam pressure decrease


Likely causes

Sudden drop in corex pressure or Calorific value


Tripping of mill or feeder or oil elevation
Mill getting unloaded
HPBP got opened
Sudden rise in load.
Boiler tube leakage
Safety valve not closing after floating

Plant response

O2 at APH inlet high alarm


MS pressure will drop.
Generator load will come down.
Drum level will drop.

Parameters of concern/Adverse effects

Drum level
generator load
MS pressure
MS/RH temperatures
APH FG inlet O2
If rate of pressure drop is more than the given saturation temp. curve boiler drum will subjected to severe thermal shock

Immediate expected or desirable operator action.

Check for any mill unloading/ tripping


Reduce load set point to hold the MS pressure around 110 kg/cm2.

Close HPBP if it is opened


Check for safety valve floating
Raise boiler firing in case of mill tripping. Take oil elevation in to service if required
Check boiler flame
Monitor drums levels during this disturbance, if it is dropping very fast, start standby BFP.

Final correction activity.

5.

Ensure drum level is stable.


If mill is unloaded stop the mill & take other mill into service.
Increase to full load based on the fuel.
Remove oil if it is introduced if furnace conditions are good or bright.

EMRV floating and resetting in succession


Likely causes

Improper blow down setting for EMRV/ pressure switch malfunction


Fuel in put to boiler varying continuously.
Turbine control valve/HPBP valve hunting
MS pressure fluctuation

Plant response

Drum level will vary.


EMRV open/close indication in Control room
Drum pressure fluctuation
Ms temp and RH temp variation.
Turbine control valve may hunt due to varying throttle pressure

Parameters of concern/Adverse effects


Drum level
MS pressure.
Ms temp and RH temp
Shock to boiler component
Valve may get damaged.
Immediate expected or desirable operator action
Reduce the fuel firing if pressure is really high.
If MS pressure is less, still EMRV is operating, keep selection switch to "OFF" so that the EMRV will not operate.
Even by putting "off ", valve is still in open condition, its manual isolation valve can be closed.
Final correction activity
Ensure for proper re-seating of the valve & put back in auto.

6.

RH SV floating and resetting in succession


Likely causes

HP bypass opened & valve hunting


LP bypass opened & valve hunting
HPBP opened & LPBP not opened
Improper blow down setting of Safety valve

Plant response

HRH steam pressure high alarm will appear.


MS and RH temp variation
HRH/MS pressure variation
Generator load may vary due to turbine control valve hunting

Parameters of concern/Adverse effects

Drum level
MS and RH pressure
HRH temp
Shock to boiler component

Immediate expected or desirable operator action


If LP bypass not opened even with pressure more than sliding setpoint, reset LPBP trip & see LPBP is opened
Take HP/LP bypass valve on manual if it is hunting in auto
Reduce MS pressure, if actually high, so that HP bypass will close in auto.
Reduce the turbine load until the valve resets
Final correction activity
If Blowdown adjustment is required do it in the nearest available opportunity
If any control is malfunctioning attend to it

7.

MS temperature rising fast

Likely causes

Inadequate spray due to malfunctioning of spray control valves.


Excess airflow.
Burner tilt stuck in up position
Leakage in the spray line.
Low feed water temperature.
Boiler firing raised in top elevation
Heavy furnace slagging
Spray isolation valve in close condition

Plant response

MS temperature high alarm will appear.


Spray control valves will go for further opening.
If temperature is very high, turbine will trip.

Parameters of concern/Adverse effects

MS/RH temperatures
MS temp at turbine inlet
HP exhaust temperature.
Spray quantity/ FCV differential pressure.
Tilt position
Metal temp. raise above design value will reduce tube life drastically

Immediate expected or desirable operator action

Make burner tilt fully down

Take MS spray control to manual & raise spray quantity (stage -1 o/l temp should be around 450C & stage -2 o/l temp around
505C)
Reduce firing in top elevation
If rate of pressure rise is more, then pick up load if margin is there.
Reduce airflow based on the O2 percentage.
Check spray station is properly lined up

Final correction activity

8.

Start soot blowing, if slagging is more


Restore back the temp controls in auto if it has been taken in manual
Check for any malfunction of spray control valves & isolate such type of valve.
Burner tilt can be kept horizontal.

RH temperature rising fast

Likely causes

Inadequate spray due to malfunctioning of spray control valves.


Excess airflow.
Burner tilt stuck in up position

Leakage in the spray line.


Low feed water temperature.
Boiler firing raised in top elevation
Heavy furnace slagging
HP exhaust temp is high
Spray isolation valve in close condition

Plant response

RH temperature high alarm will appear.


Amount of spray will rise.
Turbine will trip if RH temp reaches very high

Parameters of concern/Adverse effects

RH temperatures
RH temp at turbine inlet
HP exhaust temperature.
Spray quantity/ FCV differential pressure.
Tilt position
Metal temp raise above design value will reduce tube life drastically

Immediate expected or desirable operator action

Make burner tilt fully down


Take RH spray control to manual & raise spray quantity
Reduce firing in top elevation
If rate of pressure rise is more, then pick up load if margin is there.
Reduce airflow based on the O2 percentage.
Check spray station is properly lined up
Check HP exhaust temp is normal

Final correction activity

9.

Start soot blowing if furnace slagging is there.


Keep the burner tilt in horizontal condition.
Restore back the control in auto if it has been taken in manual.

MS temperature falling fast

Likely causes

Tripping of mill
Sudden boiler pressure drop
Malfunctioning of spray control valves.
Spray station passing
Less air flow
Burner tilt fully down
High feed water temperature
Soot deposits on SH tubes

Plant response

MS temperature low alarm will appear.


Turbine will trip if MS temp goes very low.

Parameters of concern/Adverse effects

Ms temp
Spray quantity
Burner tilt

Immediate expected or desirable operator action

Close the spray control valves by taking it into manual.


Make burner tilt upward.
Check airflow &Rise if necessary.
Increase firing in top elevation
Reduce turbine load if pressure is dropping
Close spray station Block valve/ isolation valve if control valve is passing.

Final correction activity

Start LRSB operation


Observe for improvement in temperature.
Restore back the controls in auto (spray control)
Check for any malfunction of control valve & isolate it.

10.

RH temperature falling fast


Likely causes

Tripping of mill
Sudden boiler pressure drop
Malfunctioning of spray control valves.
Spray station passing
Less air flow
Burner tilt fully down
High feed water temperature
Soot deposits on RH tubes

Plant response

RH temperature low alarm will appear.


Turbine will trip if RH temp goes very low 450C

Parameters of concern/Adverse effects

RH temp
Spray quantity
Burner tilt
Load

Immediate expected or desirable operator action

Close the spray control valves by taking it into manual


Make burner tilt upward
Check airflow &Rise if necessary
Increase firing in top elevation
Reduce turbine load if pressure is dropping

Close spray station Block valve/ isolation valve if control valve is passing.

Final correction activity

Start LRSB operation


Observe for improvement in temperature.
Restore back the controls in auto (spray control)
Check for any malfunction of control valve & isolate it.

11.

COREX VENT VALVE FAIL TO CLOSE.


(A) INDIVIDUAL CORNER VENT NOT CLOSING
LIKELY CAUSES

Inadequate Air supply to the valves


Command from DCS to field not extended
Feedback problems in nozzle valves

PLANT RESPONSE

Down stream pressure will come down as compared with the corresponding valve position.

PARAMETERS OF CONCERN

Corex header pressure.


CO ppm in the atmosphere.

OPERATOR ACTION

Check the valve position at local.


Take out pair of corresponding burners.

FINAL CORRECTIVE ACTION

Remove pair of corresponding burner & rectify the problem with help of C&I.

(B) COREX C- HEADER VENT VALVE OPENED


LIKELY CAUSES

Inadequate air supply to the valves


Command from DCS to field not extended

PLANT RESPONSE

Corex pressure will come down at faster rate


Corex leak alarm may come

PARAMETERS OF CONCERN

Corex header pressure.


CO ppm in the atmosphere.

OPERATOR ACTION

Take out burners in pairs.


Close trip valve

FINAL CORRECTIVE ACTION

Find out the root cause & rectify the problem with help of maintenance.

12.

COREX TRIP VALVE FAILS TO CLOSE.


LIKELY CAUSES

Inst. air supply failure


Mechanical failure.
Command from DCS to field not extended.

PLANT RESPONSE

If the trip valve has failed to close during boiler trip, the corex will vent
out from the C hdr vents & chances of increase in CO
PPM will be there.
Corex may also enter in the boiler if there is passing in any of the corner nozzle valves.

PARAMETER OF CONCERN

CO ppm in atmosphere.
Furnace draft. (If the corex trip valve has failed to close during boiler trip accompanied with the failure of closing of any corner
nozzle valves).
MS pressure. (If the corex trip valve has failed to close during boiler trip accompanied with the failure of closing of any corner nozzle
valves).
Furnace flame. (If the corex trip valve has failed to close during boiler trip accompanied with the failure of closing of any corner
nozzle valves).

OPERATOR ACTION

Close UNIT supply goggle valve &


Ensure that the C header pressure reduces to atmospheric pressure.
Ensure the furnace purge cycle completion.

FINAL CORRECTIVE ACTION

Find out the root cause & rectify the problem with help of maintenance.

13.

HEAVY ASH BUILD UP IN ONE OF THE HOPPERS.


LIKELY CAUSES

Failure to carry out ash evacuation in time.


Problems with electronic controller and transformer rectifier of the fields in service.
Under voltage tripping of the fields in service.
Transformer protection acted of the fields in service.
Choked ash lines preventing hopper from being evacuated
Moist ash. Rat hole in hopper

Struck up of foreign material in the conveying system


Failure of heating element-ash may stick to the hopper
Insufficient vacuum developed by blower.
Problem with air intake valve
Insufficient loading of succeeding fields.

PLANT RESPONSE

EP fields trip on low voltage.


Build up to high tension emitting system, causing short circuit
Buckling of collecting electrode/Dislocation
Ash level high alarm will come, will trip the field
Dust carry over from chimney.
CEMS will indicate high SPM.

OPERATOR ACTION

Check ash-handling system.


Switch off the field
Try to charge possible fields as early as possible
Switch over to corex fuel. (If it is going to take longer period to rectify the problem). Reduce coal firing.
Manual poking of hopper to be done (ensure that particular field is off)
If vacuum is not developing change the blower.
Switch on heaters.
Check rapping frequency
The ash evacuation should be continued due to gravity settlement

PARAMETERS OF CONCERN

Stack emission.
Tripping of field

FINAL CORRECTIVE ACTION

Arrange for ash evacuation.


After evacuation charge the field.

14.

OIL LEVEL LOSS IN APH BEARINGS

LIKELY CAUSES

Leakage in piping
Leakage in drain plug, instruments, connections
Leakage in threaded joints
Leakage through filter vent plug
Oil seal damage

PLANT RESPONSE

Rapid rise in oil temperature


Noise may come if bearing is damaged
Bearing temp will raise.
If leakage is there near the hot end, may cause fire break-out.

OPERATOR ACTION

Find out the leakage point.


Stop the oil pump to avoid further loss of oil.
Make up the oil level in the bearing housing.
Run the stand by oil pump only if the leakage point is not from the common piping.
In case of any fire, extinguish it with the help of proper extinguisher at the earliest possible.

PARAMETERS OF CONCERN

Oil level
Oil temperature
Bearing temperature.

FINAL CORRECTIVE ACTION

Add oil through the dip stick hole until max oil level mark .

Leakage to be arrested.
Put the oil system back in to service.

15.

AIR-PREHEATER MOTOR TRIPS/ AIR MOTOR DOES NOT START

A. ONE APH MOTOR TRIPS/AIR MOTOR DOES NOT START.


LIKELY CAUSES

Motor may trip on overload.


Power supply to the motor failed.
Air motor failure or solenoid failure
No compressed air available.
Lube oil system fail.

Some foreign material fallen on the APH & got stuck.


Seal of the APH has got disturbed.

PLANT RESPONSE

Rapid fall of hot air temperature on one side.


Rapid rise of gas temperature of stopped APH.
Possibility of deformation of APH.
Alarm at ECP/ DCS electrical motor stop- appears.
Furnace draft will fluctuate due to ingress of cold FD air.
Mill temp will drop as a result of drop in hot PA temperature.

OPERATOR ACTIONS

Reduce boiler/generator load to 60% MCR gradually.


Attempt for starting the electric motor, if the power has resumed or after resetting the over load.
If the air motor has not started because of air solenoid problem open the bypass valve of the solenoid.
Isolate affected air heater on the gas side first if all the attempts of starting the air motor or electric motor has failed. (Keep watch on
draft)
Isolate the affected APH at airside (keep watch on total airflow)
Try to rotate air heater manually.
Maintain generator load depending upon the parameters of the running AH.
Watch hot air temperatures to mills
Cut in oil burners, when load is reduced.
Reduce corex to minimum.
Checks lube oil system & restore lubrication.

PARAMETERS OF CONCERN

Flue gas temp at APH I/L & O/L.


Furnace draft.

Mill o/l temp / hot PA temperature


Secondary air temperature.

FINAL CORRECTIVE ACTION

B.

After rectifying the problem of electric motor / air motor, start air / electric motor before normalizing the dampers on air/gas side.
If the problem is due to stucking of foreign material, then outage may be required to remove the same.

WHEN BOTH APH MOTOR TRIP/AIR MOTORS DO NOT START

LIKELY CAUSES

Power supply failure/ motor failure.


Compressed air failure

PLANT RESPONSE

Rapid fall of hot air temperature


Rapid increase in flue gas temperature
Possible distortion in air heater rotor
Air heaters A/B electrical motor stop & APH rotor stop alarm at ECP/DCS.

OPERATOR ACTION

Reduce the fuel firing drastically as early as possible.


Parallel attempts to be made for electric/air motor
If failed to restore APH rotation within ten minutes, shut down the boiler.
Manually rotate APH till alternate arrangement is made.

PARAMETERS OF CONCERN

Flue gas temp at APH I/L & O/L.


Furnace draft.
Mill o/l temp / hot PA ,SA temperatures.
Secondary air temperature

FINAL CORRECTIVE ACTION

16.

After rectifying the problem of electric motor / air motor, start air / electric motor before normalizing the dampers on air/gas side.

SUDDEN INCREASE IN STEAM SILICA

LIKELY CAUSES

DM make water silica may be high.


Condenser tube leakage.
System taken into service after major over haul & maintenance.

OPERATOR ACTION

Ask chemist to confirm panel instrument readings of silica by actual analysis.


Increase the drum blow down.
Reduce drum pressure as per the curve silica in boiler water/boiler pressure" taking into account solubility of silica in steam at
elevated pressures.
Maintain phosphate concentration in Drum around 5ppm.
If the steam quality is affected by the process within the system, shutdown the turbine & start dumping through bypass to improve
the steam quality before rolling the turbine.

If steam quality cannot be improved because of the make up water faulty/ condenser tube leakage, shutdown the unit.

PARAMETERS OF CONCERN

Silica concentration in drum, steam.


Phosphate concentration.
Drum pressure.

PLANT RESPONSE

Drum silica & steam silica high alarms will appear.


Silica carry over in steam>0.02ppm leads to deposits on turbine blades.

FINAL CORRECTIVE ACTION

17.

Check &Correct DM make up quality.


If condenser tube leakage is there after attending only, boiler to be lighted up.
Hot blowdown is to be given to displace impure water & level to be made up with fresh DM water.
After restart of the boiler, don't take condensate into the system into service until quality of condensate is satisfactory.

BOILER WATER pH IS FALLING FAST

LIKELY CAUSE

Improper phosphate dosing


make up water faulty
Due to continuous passing in IBD/CBD.

PLANT RESPONSE

pH low alarm will appear

Leads to accelerated corrosion of boiler tubes and consequent tube failure


conductivity of boiler drum also comes down

PARAMETERS OF CONCERN

pH of the drum water


pH of condensate.
Conductivity

OPERATOR ACTIONS

Increase phosphate dosing.


Check for passing in CBD/IBD.
Consult the chemist. Check whole regime of the system.

FINAL CORRECTIVE ACTION

Find the root cause of the problem; if it is due to faulty dosing then check concentration of the dose. If it is due to passing get it
arrested. ask chemist to check DM water quality.

18.

REPEATED TRIPPING OF COLLECTING RAPPING MOTORS OF ESP

LIKELY CAUSE

High ash level in hoppers.


Improper setting of motor overload relay

PLANT RESPONSE

Inefficient ash collection in ESP.


Stack SPM may increase

PARAMETERS OF CONCERN

Ash level, field current,SPM

OPERATOR ACTIONS

Switch off the motor supply


Switch off the fields if tripping on ash level high and empty the hopper.
Switch on available /stand by field in the same pass.

FINAL CORRECTIVE ACTION

Switch on the field and take rapping motor into service


Get over load setting checked rectify the problem.

19.

AC Scanner fan tripped & DC failed to pickup

Likely causes
DC fan fails to start after AC fan trip
Both fan getting over load/electrical fault
Plant response
Scanner air to furnace DP low alarm
Scanner air fan tripped alarm
Inadequate cooling of scanners may cause damage to scanner sensing element
Parameters of concern/Adverse effects
Scanner air to furnace DP low
Flame scanner cooling is not taking place
Operator action
Try to start fan by resetting overload relay
Increase FD fan discharge pressure so that some air will always available for scanner
If not happening reduce load to minimum & get the fan started at the earliest.
If Scanner air fan could not be restarted even after reasonable time delay trip the boiler

19.

ID/FD trip

Probable Causes
ID trip
Motor protection acted.
Lub oil pressure v.lo 0.2ksc
H.C oil pressure v.lo 0.6ksc
H.C oil tank temp high 110oc
H.C oil cooler o/l temp 90oc
Winding temp v.hi 120oc
Bearing temp (fan/motor) v.hi (75oc/95oc)
FD trip
Motor protection acted.
Fan/motor bearing temp v.hi 95oc
Winding temp v.hi 120oc
Plant response
On ID trip, corresponding stream FD fan will trip.
Running ID/FD fans will get loaded to maintain draft and airflow.
When in CMC, runback will act and reduce load SP to 90/100MW @ 20MW/min
Mill-C will trip (On FD fan trip), if 3 mills are in service.
Parameters to watch
Furnace draft, drum level, airflow, ID & FD currents, mill loading, TG load, MS pressure & temperature, RH temperature, WB to furnace
DP, O2 at APH i/l.
Operator action

Case1: 3 mills in service without corex


Mill-C will trip on FD fan trip. After 1-min timer, cut-in oil guns.
Mill-A & B is to be increased to max. Hold pressure at 110ksc by reducing load.
Cut-in corex if available & restore load, keeping a watch on ID/FD fan current.
Start the tripped ID/FD fan after investigation and raise the load to full.
Case2: 1 mill with corex at 3 elevations
1. Remove corex on X3 elevation. Hold pressure at 110ksc by reducing load.
2. Start another mill and restore load keeping a watch on ID/FD fan current.
3. Start the tripped ID/FD fan after investigation and raise the load to full.

20.

APH fire

Likely causes
Defective oil burner, leading to deposition of un burnt oil particles on APH heating elements.
Soot deposit on APH heating element
In effective APH soot blowing.
Guide bearing oil leakage in to APH.
Plant response
Flue gas/ secondary air temp high alarm should come(presently not commissioned)

Flue gas temp after Air heater rises sharply


Sec air and primary air temp after APH rises sharply.
At worst case APH may get damaged

Parameters of concern.
Flue gas temp after Air heater
Sec air and primary air temp after APH
Damage to APH
Immediate expected or desirable operator action.
Reduce boiler load
Close Flue gas inlet damper
Close PA &Secondary air side inlet & outlet dampers
Open APH hopper drain plug
Open cold end side & hot end side hydrant valve and quench fire
Final correction activity.
Stop the oil guns with smoky flame if they are in service.
Isolate APH and open for inspection if fire is extensive

21.

FIRE NEAR MILL AREA

LIKELY CAUSES
High mill outlet temp.
Running mill with less air flow for long time can cause coal accumulation in mill discharge pipe & cause fire
High % of volatile mater in coal
If mill rejects are more & not removed regularly may cause fire in rejects chamber.
Tramp Iron Gate stuck in close position, causing fire in rejects chamber.
Coal accumulation in hot air duct
Fire conveyed from bunker coal
PLANT RESPONSE :
Mill out let temp. high alarm
Mill DP & air flow , current variation.
Fire coming from reject hopper
Red hot mill body/ reject chamber
Parameters of concern

Mill puffing
Mill o/l temp.
Air i/l temp.
Mill airflow.
Mill DP
Mill rejects.

Immediate /expected or desirable operator action


Reduce hot air flow to mill & continue to run with more coal.
Mill rejects hopper to be cleared
If fire is not reduced stop feeder & open Mill inheriting steam valve & Hydrant water valve
Stop Mill & release for clearing after fire is quenched
Final correction activity
Inspect mill internals and feeder for healthiness.

22.

LRSB NOT RETRACTED

LIKELY CAUSES
Forward/Reverse motor trip
Lance jammed after advancing
LRSB clutch de coupled after advancing
Electrical supply failure during operation
Chain broken.
PLANT RESPONSE
Soot blower not retracted alarm
Soot blower overload acted alarm
Parameters of concern
Steam jet hitting boiler tubes
LRSB getting damaged
Immediate /expected or desirable operator action
Reset the module & give retract command from local push button. If it fails to retract even after module is reset, switch-off the
module.
Reduce soot blower header pressure to 3- 4Ksc.
Disengage the clutch and try to retract manually from handle. If it is retracting do not release handle in the middle ( If handle is to be
released in the middle, first engage the clutch & then only release) .
Inform maintenance if it is not retracting manually also.
Try retracting with additional assistance for max. one hour.
If it could not be retracted within 1hour, reduce pressure to 0 ksc & try again.
Still if it is not retracting ask maintenance to insert dummy in steam supply line flange so that other blower operation can be carried
out.
Final correction activity

23.

If the lance is deformed change with new one

FIRE IN ESP

LIKELY CAUSES
OIL/soot deposit on ESP fields
Very high un burnt in fly ash & hopper heating element Not switching off
ESP transformer fire
PLANT RESPONSE
ESP transformer trip.
Furnace Draft variation

Parameters of concern
ESP O/L temperature
ID fan loading
Furnace Draft
Damage to ESP
Immediate /expected or desirable operator action
Trip ESP field
Isolate the power supply of all related ESP pass/field.
If fire is outside ESP, use extinguisher & douse the fire.
If it is inside ESP reduce unit load & close ESP inlet & outlet gate.
Inform fire man
Open ESP man holes
Open ESP ash hopper drain plugs/man hole
Quench the fire with fire hydrant water
Final correction activity
Identify the reason and rectify it.

26. ONE OF THE TURBINE CONTROL VALVE FAIL TO CLOSE


A. Symptom /parameter effected

While reducing load, it will not reduce below certain MW even if load set point is less.

Stuck Valve position feed back will show open position control room whereas other valve will go for close.

High speed control acting.

B. Likely cause

Valve mechanically stuck.

Trip mechanism not working.

Oil not getting drained from actuator.

C. Operator action
Immediate action

Reduce turbine load to 100MW if unit is in service.

If turbine has tripped. close MS1.2.3 &4 & depressurise MS & RH line.

Open corresponding MAL drain before & after control valve(Partially).

Subsequent action
If valve has stuck. Reduce boiler pressure & shut down the unit for attending the problem.

Final corrective action

Start turbine only after valve problem is attended.

27. ONE PHASE OF THE GT POLES FAIL TO OPEN AFTER UNIT TRIP
A. Symptom /parameter effected

Pole Discrepancy alarm will come.

LBB protection will trip all the breaker connected to that bus.

TG speed does not drop after trip.

TG draws current from grid (reverse power).

Negative sequence current in Generator.

LP exhaust temperature may shoot up.

B. Likely cause

Breaker contact mechanically stuck.

C. Operator action
Immediate action

Trip all the 220 kV breaker connected to the particular bus including bus coupler.(If LBB not acted).

Trip field breaker manually. If it did not opened.

Open isolators of GT breaker.

Subsequent action

Normalise supply by charging Lines .STs and Bus coupler.

Final corrective action

Attend GT breaker before restarting Turbine.

28. SCANNER FAN TRIPPED & DC FAN FAIL TO START


A. Symptom /parameter effected

Scanner air to furnace DP low alarm.


Scanner air fans tripped alarm.

B. Likely cause

Dc fan fails to start after AC fan trips.


Both fan getting over load/electrical fault.

C. Operator action
Immediate action

Trip the boiler

+
Subsequent action

Try to start fan by resetting overload relay.


Increase FD fan discharge pressure so that some air will always available for scanner.
If not happening reduce load to minimum & get the fan started at the earliest.
If Scanner air fan could not be restarted even after reasonable time delay trip the boiler.

Final corrective action

Lightup boiler only after starting scanner air fan.

29. HIGH DIFFERENTIAL EXPANSION IN TURBINE


A. Symptom /parameter effected

Difference between shaft & casing expansion more than normal.


Change in axial shift.
High turbine vibration.
B. Likely cause
Positive differential expansion.
More than rated steam pressure & temp. for rolling.
Inadequate soaking during rolling.
Too fast load pickup of load.
Sudden raise in MS/RH temp.
Casing not moving freely over its slide/ restriction for casing expansion.
High gland steam temperature.
Improper drain operation.
Negative differential expansion
Less than rated steam pressure & temperature for rolling.
Sudden drop in MS /RH temperature.
Improper drain operation.
Wet steam entry in to turbine.

C. Operator action
Immediate action
Positive differential expansion
Reduce steam temp if it is more.
Bring machine to soaking speed if it is during rolling.
Reduce turbine loading if it is after synchronisation.
Check and control gland steam temperature.
Check MAL drains are operating properly.

Negative differential expansion


Increase steam temperature if it is less.
increase turbine load if it is after synchronisation.
Check MAL drains are working properly.
Check gland steam temperature.

Check MAL drains are operating properly.

Subsequent action

Maintain steam temperature steady.

Final corrective action

30. TURBINE BEARING TEMPERATURE RAISING FAST


A. Symptom /parameter effected

Turbine/generator bearing temp. high alarm.

Lub oil return line oil temp. gauge showing more than normal.

Turbine oil cooler inlet/outlet temp. more than normal.

Change in turbine vibration pattern.

B. Likely cause

ACW pump tripped or ACW to lub oil cooler not charged after synchronisation.

High lube oil inlet temperature.

Bearing failure.

Thermostatic valve failure.

Inadequate lub oil flow or pressure.

Excessive bearing vibration.

High axial thrust.

Lub oil cooler not vented properly.

C. Operator action
Immediate action

Trip the turbine if bearing temp reaches 120 0C(atleast 2 indications in metal temp overview screen).

If temp is with in 1200C then try the Subsequent action.

Subsequent action
Check lube oil flow & pressure to bearing.
Check Lub oil cooler is charged on ACW side & ACW flow is adequate.
Check return oil temp from each bearing.
Verify babit temperature by other means (to rule out faulty measurement)
If thrust bearing temperature is increasing check for axial shift.
Start Standby AOP if oil pressure is low.

Vent lub oil cooler properly.

Final corrective action

Find out reason for bearing temp raise.

31. TURBINE VIBRATION SHOOTS UP


A. Symptom /parameter effected

Turbine bearing/shaft vibration high alarm.

Turbine will trip if shaft vibration reaches trip value.

B. Likely cause

Turbine bearing damage.

Rotor eccentricity high/ Shaft distortion.

Turbine blade damage.

Turbine glands rubbing.

Sudden change in steam inlet temperature.

Lube oil temperature too low.

Uneven cylinder expansion/restriction for expansion.

Foundation bolts loose.

Alignment/centering problems.

Change in axial shift.

Sudden MVAR load change.

Improper drain Operation

High grid frequency

Machine coasting down rate too slow after trip.

C. Operator action
Immediate action

Reduce turbine load by load limiter and trip the machine if bearing vibration is >11mm/sec(for Brg No. 6 >18mm/sec.

Subsequent action.
Check locally whether vibration is actually high.
Listen to bearing sounds using a vibration sensing stick.
Maintain steam parameters normal.
Check lube oil pressure and after cooler temperature.
Check any sudden MVR change is there.
Wait for frequency change.
Trip the machine if it does not trip on high vibration.
Final corrective action
32. TURBINE STARTS ROLLING ON ESV OPENING
A. Symptom /parameter effected

Turbine speed may rise without giving command for rolling.

B. Likely cause

Control valve passing.

Control valve stuck in open position.

C. Operator action
Immediate action
Close ESV by tripping turbine.
Check whether control valves are fully closed (in DCS as well as local).
Check for the EHTC output (has to be zero).
Subsequent action
If all rolling criteria are ok and if only minor passing only is there and speed is reaching to say 800rpm roll to 3000rpm if it is a
hot startup.
Final corrective action

Attend valve problem in nearest shut down.

33. HPBP OIL LINE LEAK


A. Symptom /parameter effected

Oil leak noticed by personnel.


HPBP oil pump continuously running.
HPBP oil pressure low alarm.
HPBP valve creep opening without open signal.

B. Likely cause

Oil leaking from ferules.

Servo valves leaking.


Flexible hoses bursting out.

C. Operator action
Immediate action

Isolate leaking oil line/valve.

Switch off HPBP oil pump supply.

Isolate spray line MIV if leak is in spray line.

Subsequent action

If main valve creeping is started due to loss of oil pressure then reduce turbine load slowly to 60 MW.

Bring down boiler pressure to 85Ksc. and get the leak attended.

Trip boiler if HPBP downstream steam temp. could not be maintained.

Close MS-1.2.3 & 4 and depressurise MS line in that case.

Final corrective action

If leak is attended charge the line slowly and raise the load

If leak could not be attended trip the boiler after reducing load.

34. CONTROL OIL LINE LEAK


A. Symptom /parameter effected

Oil leak noticed by personnel.


Control oil tank level low alarm.
Control oil pressure dip.
Oil leak detected from LPBP/IPSV tray switch.
Oil leak detected from Control oil skid tray switch.

B. Likely cause

Oil leaking due to O ring failure.


Servo valves leaking.
Joint leak/welding failure.
Excessive control oil pressure.

C. Operator action
Immediate action

Close isolation valve (at control oil skid) of leaking line if leak is in individual lines.

Reduce turbine load to 100MW.if any turbine valve has closed.

Open corresponding MAL valve partially.

Change over to standby pump if leak is in pumping unit.

If leak is in common block & leak does not stop after change over, reduce turbine load & trip Control oil Pumps immediately.

Subsequent action

Inform fireman and keep fire extinguisher ready if oil is spilled over valve body or steam line.

After attending leaky point charge line very slowly.

Final corrective action

Arrange to clean leaked out oil.

35. WATER/OIL DETECTED IN GENERATOR CASING.


A. Symptom /parameter effected

Liquid in Generator casing alarm.


TG trip on LLD sensing level in Generator bushing top.

B. Likely cause

H2 cooler leakage.
DPRV malfunctioning and maintaining higher DP.
Defective seals component and oil entering generator casing.

C. Operator action
Immediate action

Open LLD drains after isolation and empty it. See whether oil or water is coming.

After draining, normalise and wait for further liquid level sensing.
If water is coming reduce generator load & isolate one hydrogen cooler & find out leaky cooler .
If oil is coming see seal oil to H2 DP is normal.
Subsequent action

If liquid from drain is continuos plan for unit shut down.


If liquid is because of DPR malfunctioning get it attended.

Final corrective action

Find out reason for liquid entry in casing and rectify it.

36. WATER HAMMER IN PIPELINE


B. Symptom /parameter effected

Abnormal / intermittent sound in pipe line.


Pipeline. Hanger or supporting structure damages.
To & pro movement of pipeline.

B. Likely cause

Proper charging procedure not followed.

Sudden entry of steam into water lines.

Sudden entry of steam into improperly drained pipelines.

Improper warm up during charging steam lines.

Faulty drain traps or ill designed drain valves.

Sudden opening of high pressure valves.

C. Operator action
Immediate action

Cut off steam supply to the line in which hammering is occurring.

Subsequent action

Open drains & trap bypass valves of that line.

Wait for full draining/proper warm up.

Slowly open valve and allow steam to come out of drains.

Allow system pressure to build up.

Close drains & put trap in to service.

If it is a water line ensure no steam is entering pipe line.

Final corrective action

Follow proper charging procedure.

37. COREX GAS LEAK


Symptom /parameter effected

Alarm at local / DCS will come depending upon location of leak.( 08 static CO detector in blower area, 8 CO detector & 8 H 2 detector
in different elevation on both the boiler & 01 detector in control room AC duct are connected to DCS system in Control room).

Lamp indication with hooter near DM plant water tanks


For > 50 ppm
For > 100 ppm

- orange
- red

In addition Siren will be activated from control room for corex leak emergency.

B. Likely cause

Corex leak due to seal pot water seal breaking

Flange. valve gland leakage.

Passing of valves.

Explosion in pipe line.

Leakage from adjacent steel plant process

Major leakage can occur in the unlikely event of natural calamities such as earthquake etc.

C. Operator action

Check CO concentration with portable detectors and confirm with that of control room indications.

If the CO-detected by permanent / portable detectors is reading 200ppm and above, effect local area evacuation and parallel
start reduction of corex in the corresponding unit (if the leakage is sensed in blower area reduction to be done in both the
units). If greater than 400ppm for 15 min, stop A/C plant and remove corex elevation of the corresponding unit. (if the
leakage is sensed in blower area remove the corex completely in both the unit & close the bypass goggle valve and JVSL
double gate valve). And if greater than 500ppm for 30 min, declare emergency by actuating siren for totally evacuation of the
personnel.

Inform safety officer / fire control room in any of the above case.

Check for leakage, all the source of ignition should be kept away, Self-contained breathing apparatus (SCBA) to be used
while checking and attending leak.

In case fire takes place during leak, first the pressure in the supply line should be reduced to shorten the flame & then the fire
should be extinguished. Only after the fire is extinguished, the main gas should be closed completely. Never close the main
valve, when the fire is still there and the pressure in the gas main should not be reduced below 100mmwc.

In case anyone notices an emergency type situation, shift-in-charge should immediately reach the location of emergency with
necessary safety gadgets and assess the situation. He will declare the emergency by informing control room to send coded
siren (15 seconds on & off for 3 minutes). At the same time he will decide about the emergency shut down of the plant

Perform the head count at the assembly point (Old admin. Bldg).

All clear signals (2 min- continuous) siren to be raised if the declarer of emergency clears the emergency after attending the
leakage.

Subsequent action

Purge the corex system with nitrogen & achieve the co ppm less than allowable range of 50 ppm

Find out the exact location of the leakage.

Arrest the leakage point & check for leakage

Final corrective action

Take corex in to service only after clearance from safety dept.

38. COREX VENT VALVE FAIL TO CLOSE


A. Symptom /parameter effected

Valve fail to close alarm


Corex leak alarm
Valve close indication not coming in DCS

B. Likely cause

No or inadequate air supply to the valve actuator.

Command from DCS to field not extended.

Valve mechanically stuck in open condition.

C. Operator action
Immediate action

If C- header vent valve fails to close. then remove corex totally from that unit.

Ensure Nitrogen purge valve is open.

If it is corner vent valve. remove that corex pair from service.

Subsequent action

Check instrument air supply is normal to valve actuator.

Arrange to get vent valve closed from maintenance.

Final corrective action

Take corex in to service only after the satisfactory valve stroking

39. COREX TRIP VALVE FAILS TO CLOSE.


A. Symptom /parameter effected

Valve fail to close alarm.


Corex leak alarm.
Valve close indication not coming in DCS.

B. Likely cause

Valve Mechanically stuck.

Command from DCS to field not extended.

C. Operator action

Immediate action

Ensure all corner nozzle valves are closed.

Close corex control valve.

Close UNIT supply goggle valve and purge supply line & C header with N 2.

Subsequent action
Final corrective action

Take corex in to service only after the valve is made operational.

Emergency Procedure
1. APH FIRE
Symptoms / parameter
effected
1. Flue gas temp. at APH
outlet goes above
3500C suddenly from
normal value
2. Secondary air temp. at
APH outlet goes above

Immediate Operator
Action
1. Reduce unit load to 65

Likely cause

MW
2. Close Flue gas inlet

deposit on APH.

damper of particular
APH.
3. Close ESP inlet damper

Heavy unburnt

Poor combustion of

Subsequent operator
action
1. Open APH hopper drain
plug.
2. If the fire is confirmed

fuel oil.

open cold end side & hot

Not doing APH soot

end side hydrant valve

blowing regularly

and quench fire

3500C suddenly from

of the corresponding

especially during oil

normal value

APH.

elevation was in

with air motor/electrical

service

Motor if possible.

3. APH fire sensing

4. Close PA &Secondary

thermocouple gives

air side outlet & inlet

alarm (presently not

dampers of that APH.

hooked up)

3. Continue running APH

Final corrective
action
Isolate APH and
release for
inspection.

Do APH soot
blowing every shift if
oil is in service

2. AIR-PREHEATER MOTOR TRIPS/ AIR MOTOR DOES NOT START

A. ONE APH MOTOR TRIPS/AIR MOTOR DOES NOT START.


Symptoms / parameter
Immediate Operator
effected
Action
1. APH Electrical motor 1. Reduce unit load to 65
trip alarm.

Subsequent operator
action
Motor tripped on 1. If the air motor has not

Likely cause

overload.

started because of air

Power supply to

solenoid problem open

the motor failed.

the bypass valve of the

Air motor failure

solenoid and air motor

temperature of tripped 3. Close PA &Secondary

or

will start, If it does not

APH outlet(>3000C)

air side outlet & inlet

failure

4. Rapid fall in secondary

dampers of that APH.

2. APH

rotor

MW
stopped 2. Close Flue gas inlet

alarm.
3. Rapid rise in flue gas

& primary air temp at


APH outlet.(<1000C)

damper of particular
APH.

No

solenoid
compressed

air available after


power failure.

start then
2. Attempt for starting the
electric

motor

if

the

power has resumed, or

Final corrective action

foreign

after resetting the over

material fallen on

load. If neither air motor

the APH & got

nor

stuck.

came in to service then

Some

electrical

motor

try to rotate by putting


handle on motor shaft.
(Module to be switched
off before trying this)

B. WHEN BOTH APH MOTOR TRIP/AIR MOTORS DO NOT START


Symptoms / parameter
Immediate Operator
effected
Action
1. APH Electrical motor 1. Confirm from DCS
trip alarm.
2. APH

rotor

stopped

alarm.

Likely cause

alarm that both APHs

tripped

are tripped

overload.

solenoid problem open

Power supply to

the bypass valve of the

both

solenoid and air motor

2. Manually Trip the boiler

3. Rapid rise in flue gas


temperature of tripped
APH outlet(>3000C)

Both

Subsequent operator
action
Motor 1. If the air motor has not

on

motors

started because of air

failed.

will start, If it does not

Both air motor

start then

Final corrective action

4. Rapid fall in secondary

failure

& primary air temp at

APH outlet.

or 2. Attempt for starting the

solenoid failure

electric

No

compressed

power has resumed, or

air available after

after resetting the over

power failure.

load. If neither air motor

Some

nor

foreign

motor

electrical

if

the

motor

material fallen on

came in to service then

the APH & got

try to rotate by putting

stuck.

handle on motor shaft.


(Module to be switched
off before trying this)

3. TG barring gear does not established after turbine trip


Symptoms / parameter
Immediate Operator
Subsequent operator
Likely cause
effected
Action
action
1. Turbine speed <10 rpm 1. Start manual hand Lift oil pressure not 1. Change over lift oil filter
alarm.

barring when TG shaft

sufficient/filter

becomes standstill.

choked

Stand by pump NRV

if it is choked
2. Close

standby

pump

discharge valve if NRV


is passing

Final corrective action

passing

3. If

Turning

gear

solenoid

disconnect

is

solenoid

solenoid problem

connection near front

Lift oil line pressure

bearing pedestal

regulator problem or 4. Close regulator


valve if it is open
test valve open

oil

Lift oil pump relief


valve problem

Leakage in lift oil


line

Bearing lift improper

Turbine

internals

rubbing

test

pump 5. Open pump discharge


valve if it is close
discharge valves in
Lift

closed condition

faulty

Hydro motor
problem

4.Both JOPS fails during coasting down


Symptoms / parameter
Immediate Operator
effected
Action
1. Turbine speed <510 1. Start JOP manually

rpm and JOP not in


service alarm
2. Turbine speed <10 rpm
alarm.

Subsequent operator
action
JOPs not in AUTO 1. Check module fuse

Likely cause

and or SLC not on

2. Reset module

AC/DC power failure

3. Ensure Lub oil pump is

Fuses blown out

Pump

module

problem

Module tripping on
overload

Pump
damage

mechanical

in service.

Final corrective action

5.Boiler flue gas temperature shoots up


Symptoms / parameter
Immediate Operator
effected
Action
1. Flue gas temp at APH 3. Reduce boiler load to
outlet >3000C
2. Secondary air temp at
APH outlet >3000C

Likely cause

APH Fire

bring down flue gas

More Air Flow

temp within limits

Loss of seal trough


water

Inadvertent closure
of any of the APH
inlet/outlet damper.

Improper

Subsequent operator
action
1. Refer
APH
fire
procedure
4. Reduce Air flow if it is
more
5. Make up seal trough
water if it is broken
6. Check all APH dampers
and open if any damper
is closed.

operation of

7. Set SADC correctly

SADC

8. Refer boiler tube leak

Boiler tube leakage

Heavy soot deposit in

procedure
9. Do soot blowing.

Final corrective action

boiler

6. Condenser pressure raises on vacuum loss


Symptoms / parameter
Immediate Operator
Likely cause
effected
Action
1. Condenser vacuum low 1. Open vacuum breaker Vacuum breaker
alarm
valve manually if
valve close.
2. LP exhaust hood temp
vacuum is less than - Any Drains to
high alarm
0.2Ksc
condenser open.
3. Condenser
pressure 2. Open LP exhaust
CW pump not
Transmitter
showing
hood spray main/
running.
+ve value
bypass valve if
exhaust hot temp is

Seal steam supply


not cut off.

Subsequent operator
action

Final corrective action

Close all drain MIV


connected to
condenser.

Close seal steam


supply valve from
PRDS

Depressurise

MS

&

HRH lines by opening

If LPT diaphragm is
ruptured replace it

>900C

LPBP valve drift

MS drain to atmosphere

open.

& HRH vent

7. Emergency DG not starting after Blackout


Symptoms / parameter
Immediate Operator
effected
Action
1. DG
trouble/tripped 1. Ensure DC EOP.JOP.
alarm
Seal oil pump.
2. KB bus under voltage
alarm

E-Stop pressed

Subsequent operator
action
1. Release E-stop

DG not in auto

2. Start DG manually

Scanner air fan are

Over crank shutdown

started

Over speed

2. Close DG switch gear


bus coupler if other

Likely cause

shutdown

3. Charge KB bus by
manually closing 415 V
breaker if it is not
closed on auto.

Final corrective action

Find out cause for


DG trouble and
rectify it

DG is running

Started & tripped on

4. Start the AC motors

Low oil pressure

where DC motors are

Started & tripped on

running and stop DC

Low water tank level

motors

Started & tripped on

5. Close MS-1 & 2, AS-9,

High water

CRH-105 manually if

temperature

DG supply is not
available
6. All other activities of
black out to be
performed.

8. Boiler Tube leakage

Symptoms / parameter
Immediate Operator
effected
Action
1. Acoustic leak detector 1. Start reducing unit
alarm

load

2. Drum level fluctuation


3. Furnace

draft

Fluctuation
4. Sound

Likely cause

from

2. Confirm tube leakage


by observing sound &
boiler parameters.

5. Not able to maintain


hotwell level even with
makeup valve full open

stuck in advanced

normal & if required

condition for long

start Standby BFP

time.

inside

boiler

Wall blower / LRSB

Sustained high metal


Erosion of tubes due

4. Drain boiler after

Erosion on tube due


coal.

Blocked tubes
Scale
formation/corrosion
inside tubes

reducing load
3. Box up boiler

to high ash content in

2. Shut down the unit after

temperature.
to soot blowing

Subsequent operator
action
1. Maintain drum level

Operating boiler with


faulty drum level
transmitter.

depressurisation and
isolate it

Final corrective action

Replace leaky tubes

Bursting of tube due


to pressure
fluctuation.

Improper setting of
safety valve.
9. Fire near MOT/Control oil system
Symptoms / parameter
Immediate Operator
effected
Action
1. Fire
noticed
by 1. If fire is isolated one
personnel.
2. Fire alarm. if actuated
in local by any persons
after observing fire
3. Burning smell

Final corrective action

quench with
appropriate

extinguisher

Trip the unit.


4. Operate
corresponding deluge
valve.
5. Stop control oil
system

near MOT

of affected area if

Welding on oil lines

required.

with

2. Inform firemen.
3. If it is big in nature.

Subsequent operator
action
Electrical short circuit 1. Isolate electrical supply

Likely cause

out

precaution

safety 2. Isolate oil lines if


possible

Oil leakage Catching


fire oil spillage on
high temperature
steam line

3. Use hydrant system for


fire fighting.

Replace MOT/control
oil if contaminated

10. Fire in Coal mill


Symptoms / parameter
Immediate Operator
effected
Action
1. Mill outlet temp. high 1. Close hot air gate &
alarm
2. Mill outlet temp going
out of range.

continue to run mill


with more coal without
overloading.

3. Mill body & coal pipe 2. Open mill inheriting


paint peeling off

steam valve to cool

Likely cause
Excessive mill
temperature.
Excessive

Subsequent operator
action
1. Wait for mill outlet
temp to drop below
500C.

accumulation of pyrites

2. Stop feeder.

or coal in scrapper

3. Purge mill completely.

chamber

4. Stop mill for

Final corrective action

Clear mill internals


Change gear box oil
if carbonising is
noticed

4. Mill outlet temp. not


coming

down

after 3. Mill rejects hopper to

closing hot air damper


5. Fire

coming

the mill

out

be cleared
in

rejects hopper*.

Foreign material such


as rags. Wood. Paper

*Note: Normally fire in

collecting in mill.

reject hopper will not

Running mill with less

contribute to above bowl

air flow for long time

fire. Clearing the hopper

can cause coal

will suffice in such cases.

accumulation in mill
discharge pipe &
cause fire
Coal accumulation in
hot air duct
Fire conveyed from
bunker coal

11. Fire in transformers

inspection.

Symptoms / parameter
effected
1. Fire alarm in fire

Immediate Operator
Action
1. If transformer has not

monitor system

tripped, trip it

console.

manually & isolate it.

2. Spray system deluge


valve operated alarm
3. Fire noticed from
personnel.

Likely cause
Transformer Internal
faults causing fire
Fire from external
source carried to
transformer

Subsequent operator
action
1. If Spray system not
operated Open by
pass valve of deluge
valve
2. Inform fireman.
3. Drain transformer oil
to burnt oil pit
4. Prevent fire from
spreading to other
equipment by fire
fighting measures

Final corrective action

Release transformer
for inspection

12. Fire in cable gallery


Symptoms / parameter
effected
1. Fire alarm in fire
monitor system
console.
2. Spray system deluge
valve operated alarm.
3. Fire noticed from
personnel.

Immediate Operator
Action
1. Trip the unit.

Likely cause
Short circuit.
Cable insulation failure
due to over loading
Fire from external
source

Subsequent operator
action
1. Isolate AC supply as
per the condition and
if required trip the
station transformer.
2. If hydrant system not
operated Open deluge
valve bypass
3. Inform fireman

Final corrective action

Isolate faulty cables


& recharge electrical
system.

13. Fire in coal conveyer


Symptoms / parameter
effected
1. Fire alarm in fire
monitor system
console.
2. Spray system deluge
valve operated alarm.
3. Fire noticed from
personnel

Immediate Operator
Likely cause
Action
1. Switches off Conveyer Burning coal loaded on
supply modules.
2. Inform fireman.

the conveyer.
Electrical short-circuits.
Fire in the spilled coal
around conveyer.

Subsequent operator
action
1. If hydrant deluge
valve not opened
open bypass valve
2. Use the nearest
hydrant point for
additional spray

Final corrective action

Remove burnt coal


from conveyer.
Repair damaged
component

14. Fire in coal bunker


Symptoms / parameter
effected
1. Smoke coming out of
bunker opening.
2. Paint peeling off on
bunker surface.

Immediate Operator
Action
1. Stop feeding to that
bunker.

Likely cause
Spontaneous ignition

Subsequent operator
action
1. If possible run the mill

due stagnant coal in

& empty that bunker

bunker

at the earliest or

Coal coming from stock 2. Empty the bunker by


other means
itself having fire
3. Use minimum water
(only if flames are

Final corrective action

Use nitrogen blanket


in bunker for storing
coal for longer
duration

visible)

15. Fire in ESP


Symptoms / parameter
effected
1. Flue gas temp at ESP

Immediate Operator
Action
1. Reduce unit load to

outlet is much higher

65MW if fire is inside

than ESP inlet temp.

ESP

Likely cause
Oil/soot deposit on
ESP fields
Very high unburnt in fly

Subsequent operator
action
1. If fire is outside ESP,
use extinguisher &
douse the fire.

Final corrective action

2. Outside fire noticed by


personnel
3. ESP insulation showing
signs of internal fire

2. Trip ESP field

ash & hopper heating

2. Inform fire man

3. Isolate the power

element Not switching

3. Open ESP man holes

off

4. Open ESP ash

supply of particular
pass/field.

ESP transformer fire

hopper drain

4. Close particular ESP

plugs/man hole

inlet & outlet gate

5. Quench the fire with


fire hydrant water

16. Fire in fuel oil storage

Symptoms / parameter
Immediate Operator
effected
Action
1. Fire
noticed
by 1. Stop HFO /LFO
personnel.

pumps

2. Fire alarm. if actuated 2. Isolate electrical


in local by any persons

supply for all related

after observing fire

equipments.

Electrical short circuit

Subsequent operator
action
1. Inform fireman

Very high Oil

2. Put hydrant system

Likely cause

temperature.
External fire conveyed
to oil tank

3. Burning smell

Improper earthling

Final corrective action

with foam into service


& quench fire
3. If it is local fire douse
with extinguisher.

causing spark due to


static current
Emergency Procedure
17. Fuel oil leakage
Symptoms / parameter
effected
1. Oil leak noticed by
personnel
2. Oil pressure low alarm

Immediate Operator Action


1. Stop

corresponding

Likely cause

oil Fuel oil pipe

Subsequent operator

Final corrective

action
1. Isolate leaking point

action
Attend leaking

pump. If leak is in pump

puncture by any

2. Inform fireman

discharge line.

means.

3. Arrange to clean

point

Any control valve,


isolation valve,
pump gland/flange
leak
Gun leak due to
washer damaged.

18. Generator winding temp raising fast

leaked oil

Symptoms / parameter
effected
1. Generator winding
temp. high alarm.
2. Generator hot gas
temp>600C.

Immediate Operator Action

Likely cause

1. Reduce generator MVAR


loading to zero.
2. Reduce

generator

load

gradually till winding temp.


Raising trend reverses.

High MVAR loading

Final corrective

action
1. Check ACW pressure

action

Overloading of

at Hydrogen cooler. If

generator

required start standby

ACW flow to

ACW pump.

hydrogen cooler
low

Subsequent operator

Hydrogen cooler air

2. Vent hydrogen cooler.


3. Fill hydrogen if
pressure is low.

locked
19. Flash over
Symptoms / parameter
effected
1. Observed by personnel
2. Fire alarm

Immediate Operator Action

1. Trip the switch gear in


which

flash

occurred

over

Subsequent operator

Final corrective
action

Loose contacts

action
If flashover is observed in

Short-circuits

an equipment, then isolate

Likely cause

has

Over load

Insulation failure

Switching/lightning
voltage surges

that equipment electrically

20. Heater level going high


Symptoms / parameter
effected
1. Heater level high alarm

Immediate Operator Action

Likely cause

1. If heater is not bypassed in

auto, bypass it on feed


water/condensate side.

2. Take heater level controls


in to manual and open it
fully

Drip control valve

Subsequent operator

Final corrective

action
1. Check level locally and

action
If tube leak is

failure.

confirm level

confirmed

Failure of drip auto

transmitter is reading

isolate heater

control due to

correct.

totally and

wrong level sensing 2. Open feed water side


IBV /condensate side
Heater Tube
leakage/failure

valve partially to
confirm whether
heater tube is leaking

release for
maintenance.

21. High axial shift


Symptoms / parameter
effected
1. Axial shift high alarm
2. Turbine will trip at axial

Immediate Operator Action


1. Reduce

load

to

reduce

axial shift

uniformly open

pads & thrust bearing


/return oil temp raise

action
Abrupt change in 1. Maintain

of 2. If turbine has tripped


check vacuum breaker
steam temperature
Sudden

drop

Sudden closure of
extraction valves

Too fast pick up of


load

Turbine overload

has opened
3. Check

vibrations

during coasting down


4. Note

Final corrective
action

steam

parameter steady

load

shift very high limit of 2. Check all stop valves /


0.5mm
governing
valves
are
3. Overloading of thrust

Subsequent operator

Likely cause

coasting

down

time
5. If salting is suspected

Silica deposits on

arrange for early steam

turbine blades

washing of turbine or

Turbine

other methods of

internal

damaged

cleaning

GSC fan not


functioning

22. Hydrogen leak from generator


Symptoms / parameter
effected
1. H2 pressure in
generator casing low

Immediate Operator Action


1.

If hydrogen pressure
reaches <1 ksc trip

Likely cause

Seal oil running


pump trips &

Subsequent operator

Final corrective

action
Try to establish seal oil
2.

action

pressure by starting

alarm
2. Seal oil system fault

generator & purge

standby AC & DC

stand by pump or by

generator with CO2

pump fails to start

closing DPRV inlet MIV

Seal oil pressure to

alarm
3. If seal oil pressure is

if seal oil pressure is


low.

seal is low

low standby oil pump

DPR malfunction

will start.

Hydrogen leakage

4. Winding temperature

developed in

may increase

3.

If leaking point is
identified, try to isolate
it. If not possible,

generator system

5. Hot Gas temperature

may increase

Seal oil leakage


from
piping/valve/flanges

23. LRSB not retracting


Symptoms / parameter
effected

Immediate Operator Action

Likely cause

Subsequent operator action

Final
corrective

action
1. LRSB not retracted
alarm
2. Observed from local

1. Reset the module & give

Forward motor trip

retract command from

after advancing

local push button. If it

Lance jammed after

fails to retract even after


module is reset, switchoff the module.

advancing

1. Reduce soot blower

If LRSB could

header pressure to 3-

not retracted,

4Ksc.

ask

2. Disengage the clutch and

maintenance to

LRSB clutch de

try to retract manually from

insert dummy

coupled after

handle. If it is retracting do

in steam supply

advancing

not release handle in the

line flange so

middle ( If handle is to be

that other

released in the middle, first

blower

engage the clutch & then

operation can

only release) .

be carried out.

Electrical supply
failure during
operation
Chain broken.

3. Inform maintenance if it is
not retracting manually
also.
4. Try retracting with
additional assistance for
max. one hour.
5. If it could not be retracted
within one hour, reduce

pressure to zero ksc & try


again.

24. Lube oil leak/MOT level going low


Symptoms / parameter
effected
1. MOT level low alarm
2. Oil pressure low alarm
if oil leak is from oil
supply line to bearing.
3. Oil leak observed from
local
4. Oil collected in drain oil
tank/CEP pit

Immediate Operator Action

Likely cause

1. If leak is more and could


not be isolated, reduce
load & trip the unit.
2. If

leak

is

less

and

MOT

drain

Subsequent operator

Final corrective

action
action
is 1. Check any drain in Stop turbine

opened

MOT area is open, if

lube oil pump

Lube oil cooler tube

open close it

after turbine

2. If leakage is before

leakage

comes to

confinable. Top up MOT


and inform firemen.

Lube oil line/ flange

lube oil pump NRV

barring gear

/filter leakage

change over the pump

and arrange

Leakage from TG

(change

for attending

Seal oil system oil


leakage/seal

will

happen in auto on lube

bearings

over

oil

oil pressure low)


3. Check centrifuge for

leak.

Clean oil
leaked out to

cooler tube leakage

seal

Charging

draining out

of

standby oil cooler

break

and

oil

avoid fire
hazard

4. Check oil channel

entering 5. Check lube oil cooler


water side drain/vent
generator
casing
for presence of oil
from seals

Oil

Oil draining out


through centrifuge.

6. Check seal oil cooler


water side drain/vent
for presence of oil
7. If any cooler leak is
noticed change over
that cooler.

25. Oil spill noticed in bottom ash hopper


Symptoms / parameter
effected
1. Oil traces noticed in

Immediate Operator Action

Likely cause

1. If any burner is in service

Burner in service

Subsequent operator

Final corrective

action
1. Check for the passing

action

bottom ash hopper from

without flame, trip that

local

corner immediately

without flame

2. Oil burner flame not


visible from peep hole

Oil nozzle valve

2. Check for atomising

passing

steam / air pressure

Atomising steam/air

and adjust it

pressure very low

oil gun & isolate it

Oil specification
different from
designed one.

26. One of the turbine control valve fail to close


Symptoms / parameter
effected
1. While reducing load, it

Immediate Operator Action

Likely cause

1. Reduce turbine load to

will not reduce below

100MW(if unit is in

certain MW even if load

service). If turbine has

set point is less

tripped. close MS1.2.3 &4

2. Stuck Valve position

& depressurise MS & RH

feed back will show


open position control

line
2. Open corresponding MAL

room whereas other

drain before & after control

valve will go for close.

valve(Partially)

3. High speed control will


act

Valve mechanically

Final corrective

action
1. If valve has stuck.

action

stuck

Reduce boiler pressure

Trip mechanism not

& shut down unit.

working

Subsequent operator

Oil not getting


drained from
actuator

27. One phase of the GT poles fail to open after unit trip
Symptoms / parameter
effected
1. Pole Discrepancy alarm
will come
2. LBB protection will trip
all the breaker
connected to that bus
3. TG speed does not
drop after trip
4. TG draws current from
grid (reverse power)
5. Negative sequence
current in Generator
6. LP exhaust temperature
going high

Immediate Operator Action

Likely cause

1. Trip all the 220 kV breaker

connected to the particular


bus including bus coupler.
(If LBB not acted)
2. Trip field breaker manually.
if it did not opened.
3. Open isolators of GT
breaker

Breaker contact
mechanically stuck

Subsequent operator

Final corrective

action
1. Normalise supply by

action
Attend GT

charging Line .ST and

breaker before

Bus coupler.

restarting
Turbine

28. scanner fan tripped & DC fan fail to start


Symptoms / parameter
effected
Scanner air to furnace
DP low alarm
Scanner air fans tripped
alarm

Immediate Operator Action

Likely cause

1. Trip the boiler

Dc fan fails to start


after AC fan trips
Both fan getting
over load/electrical
fault

Subsequent operator

Final corrective

action
action
1. Try to start fan by
Lightup boiler
resetting overload
only after
relay
2. Increase FD fan
starting
discharge pressure so
scanner air
that some air will
always available for
fam
scanner
3. If not happening
reduce load to
minimum & get the fan
started at the earliest.
4. If Scanner air fan could
not be restarted even
after reasonable time
delay trip the boiler

29. seal oil pressure going low


Symptoms / parameter
effected

Immediate Operator Action

Likely cause

Subsequent operator

Final corrective

action

action

1
a

c
d

Drum level dropping fast


Likely causes
One of the running BFP might have tripped
Sudden tripping of one or more Mills.
Feeder might have tripped.
FW control valve might have closed/stucked.
Malfunction of auto control/scoop regulation.
BFP recirculation might have opened of the running pump.
Sudden reduction of load because of malfunction of EHTC.
Sudden tube failure in water walls.
HPBP might have opened.
Inadvertent opening of EBD & low point drains.
Drum pressure may be high.
Drum level transmitters may be faulty.
Plant response
Drum level LOW alarm appears.
BFP's scoop rises to meet the demand if it is in auto.
Boiler will trip on drum level very low.
In extreme case, if water level falls below visible range of gauge glass, may affect the
flow through downcomers & may lead to tube failure.
Parameters of concern.
Main steam /reheater temperatures ,drum level,dearator level
Immediate expected or desirable operator action.
See that standby BFP starts on tripping of running BFP or manually start when level

2
a

b
c
d

drops to -100 mmwc & load the pump to the running pumps scoop.
Check for any malfunction of auto control like scoop not raising or recirculation open
in auto, take control into manual & make up drum level.
Close CBD if it is open.
Close HPBP if it is open.
Remove corex burners (when level is above (-100 mmwc)).
Caution: Do not do any major removal of fuel at drum level (-100 mm & above., like
mill tripping, burner removal)
Final correction activity.
Check drum level is getting stabilised.
Ensure drum level controls are in auto.
Check feedwater flows matches with steam flow for full load, if deviation is more then
check for any leak in boiler area.
Ensure for the availability of standby BFP as early as possible.
Check for local level gauge & transmitters.
Check boiler low point drains & EBD.
Check for scoop controls for any linkage failures.
Drum level shooting up fast
Likely causes
Malfunction of feed controls.
Sudden increase of load (due to malfunction of EHTC)
Drum level transmitters may be faulty.
Sudden increase of firing rate.
Scoop /control valves might have stucked.
Sudden opening of HPBP.
Plant response
Drum level high alarm will appears.
On drum level high high, boiler will trip.
Parameters of concern.
SH/RH temperatures drum level.
Immediate expected or desirable operator action.
Check the hydrostep level, if it is high take drum level control to manual & match

3
a

c
d

feedwater flow with steam flow.


Open emergency drain/CBD drain.
Open MS strainer drains.
Try to reduce the load so as to control the water level (if water level is due to upward
load surge).
Final correction activity.
Check drum level is getting stabilised.
Ensure drum level controls are in auto.
Check feedwater flow matches with steam flow.
Check for stuck of feed control valves & scoop.
Check the level at local, hydrostep and transmitters are matching.
Rapid Boiler steam pressure rise
Likely causes
Corex calorific value might have changed drastically.
Sudden loading of mill.
High firing rate.
Feeder hunting.
Malfunction of CMC.
Sudden dropping of generator load.
Plant response
HPBP will open if it is in auto.
Reheater safety valve will popup first & then on high steam pressure, reaching in
stages may blow EMRV & superheater SV & drum safety valves.
Throttle pressure high alarm will appears
APH FG I/L O2 low alarm will appears
Drum level will vary.
Generator will get more loaded because of pressure correction of EHTC.
Parameters of concern.
MS /RH temperature, Drum level, APH inlet O2, HP/LP bypass,
Immediate expected or desirable operator action.
Take the unit into manual mode if it is in CMC & reduce the fuel firing.
For momentary action additional load can be taken

4
a

c
d

Trip the malbehaving feeder/mill & reduce PA airflow through that mill.
Check for pressure drop & if it is not holding remove the corex burners.
Caution:Donot reduce the fuel when the drum level is around -100mm
Start standby BFP when drum level reaches -100mm & rise the scoop to running BFP
scoop.
Final correction activity.
Check for reseating of safety valve
As soon as the pressure starts dropping, restore the correct fuel input.
Stop the third running BFP and keep it in standby.
Ensure drum level got stabilised.
Check for closure of HP bypass.
Ensure pressure is stable.
Bring back the unit load to normal.
EMRV floating and reseating in succession
Likely causes
Maloperation of valve.
High fuel firing rate.
MS pressure fluctuation.
Maloperation of turbine control valve.
Plant response
Drum level will vary.
Generator load will vary.
Hp bypass will open if it is in auto & may hunt.
Ms temp and RH temp variation.
Parameters of concern.
Drum level, Ms temp and RH temp, MS pressure.
Immediate expected or desirable operator action.
Reduce the fuel firing if pressure is really high.
If MS pressure is less, still EMRV is operating, keep selection switch to "OFF" so that
the EMRV will not operate.
Even by putting "off ", valve is still in open condition, its manual isolation valve can
be closed.

Final correction activity.


Ensure for proper re-seating of the valve & put back in auto.

5
a

RH SV floating and reseating in succession


Likely causes
HP bypass might have opened in auto & LP bypass has not opened.
Maloperation of valve.
Opening /hunting of HP bypass.
Plant response
HRH steam pressure high alarm will appear.
MS and RH temp variation
Generator load will rise.
Drum level will vary.
Parameters of concern.
Drum level, MS and RH temperature
Immediate expected or desirable operator action.
If LP bypass not opened, trip reset & open the valve by around 10% & put back in
auto.
Reduce the MS pressure, if it is actually high, so that HP bypass will close in auto.
Reduce the load until the valve re-seat
Final correction activity.
Check for proper seating of the valve.
Inform to maintenance isf & it is not re-seating at lower pressure also.

c
d

6
a
b

Corex CV decrease
Likely causes
Malfunction of COREX process.
Variation in corex constituents %.
Plant response
Ms pressure will drop fast
Generator Load will drop.
O2 at APH FG inlet will rise & high alarm may appears.

c
d

7
a

c
d

Parameters of concern.
MS pressure, load, APH flue gas inlet oxygen.
Immediate expected or desirable operator action.
Reduce load set point inorder to hold the boiler pressure
Enquire EMD Dept about CV variation & if corex is stable then raise the feeding on
running mills.
Final correction activity.
Ensure O2 at APH i/t is normal
Restore the fuel input to boiler once the CV of corex stabilises.
Rapid Boiler steam pressure decrease
Likely causes
Sudden drop in Calorific value or pressure of corex.
Tripping of mill or feeder.
Sudden rise in load.
Disturbed combustion conditions in furnace.
Mill might have got unloaded.
Plant response
MS pressure will drop.
Generator load will come down.
Drum level will drop.
O2 at APH FG inlet will rise.
Parameters of concern.
Drum level, generator load, MS/RH temperatures, APH FG inlet O2.
Immediate expected or desirable operator action.
Check for any mill unloading.
Reduce load set point to hold the MS pressure around 110 kg/cm2.
Check boiler flame, take oil elevation into service.(don't take oil when combustion
conditions are very poor)
Monitor drum levels during this disturbance, if it is dropping very fast, start standby
BFP & load the scoop equal to running pump scoops.
Final correction activity.

Ensure drum level is stable.


If mill is unloaded stop the mill & take other mill into service.
Increase load set point to full load based on the fuel.
Remove oil if it is introduced if furnace conditions are good or bright.
8
a

c
d

MS temperature rising fast


Likely causes
Inadequate spray due to malfunctions of spray control valves.
Excess airflow.
Instrument air pressure may not be adequate.
Burner tilt Maloperation.
Leakage in the spray line.
Low feed water temperature.
Ms pressure may be high.
Heavy furnace slagging
Plant response
MS/RH temperature high alarm will appear.
Spray control valves will go for further opening.
Load will rise for the same pressure.
If temperature is very high ,turbine will trip.
"Positive" turbine expansion
Parameters of concern.
MS/RH temperatures, feedwater flow, drum level, HP exhaust temperature.
Immediate expected or desirable operator action.
Tilt burner down.
Control the spray flow in manual so that stage -1 o/l temp will be around 450 deg.C &
stage -2 o/l temp around 505 deg.C, if temp control response is poor in auto
If rate of pressure rise is more, then pick up load if margin is there.
Reduce firing rate (preferably top elevation).
Reduce airflow based on the O2 percentage.
Final correction activity.
Introduce soot blowing if MS/RH temperatures are still maintaining high & spray

quantity is more..
Restore back the temp controls in auto if it has been taken in manual
Check for any malfunction of spray control valves & isolate such type of valve.
Burner tilt can be kept horizontal.
9
a

c
d

RH temperature rising fast


Likely causes
Inadequate spray due to malfunctions of spray control valves.
Cutting in of Top mill into service.
Instrument air pressure may not be adequate.
Cutting in corex in quick succession.
Excess airflow.
MS temperature may be high.
MS pressure may be high.
Leakage in the spray line.
Heavy furnace slagging.
Burner tilt Maloperation.
Plant response
RH temperature high alarm will appear.
RH metal temperatures high alarm will appear.
Amount of spray will rise.
Load will rise for the same pressure.
"Positive" turbine expansion.
Parameters of concern.
RH temp, drum level, feed water flow, feedwater differential pressure.
Immediate expected or desirable operator action.
Control the spray flow manually at RH inlet around 250 deg.C, if temp control
response is poor in auto.
Tilt burner down.
Check for MIV's open before & after spray control valves
Reduce air flow if its more.
If rate of pressure rise is more, then pick up load if margin is there.

10
a

c
d

Reduce firing rate.


Final correction activity.
Introduce soot blowing if temperature is maintaining high & spray is high.
Keep the burner tilt in horizontal condition.
Restore back the control in auto if it has been taken in manual.
MS temperature falling fast
Likely causes
Tripping of top elevation mill
Malfunctioning of spray control valves.
Less air flow
Instrument air pressure may not be adequate.
Low burner tilt
More spray
High feed water temperature
Plant response
MS temperature low alarm will appear.
Unit may trip on MS temp very low.
Turbine expansion may become Negative.
Parameters of concern.
Ms temp, drum level, feed water flow.
Immediate expected or desirable operator action.
Close the spray control valves by taking into manual.
Tilt burner upward.
Check airflow &Rise if necessary.
Top elevation mill can be taken into service /firing can be raised
Check for MIV open before & after control valves.
Final correction activity.
Initiate LRSB soot blowing if temperatures are maintaining still less.
Observe for improvement in temperature.
Restore back the controls in auto (spray control)
Check for any malfunction of control valve & isolate it.

11
a

c
d

12
a

RH temperature falling fast


Likely causes
Less air flow
Tripping of top elevation mill
Instrument air pressure may not be adequate.
Low burner tilt.
More spray.
Malfunctioning of spray control valves.
Plant response
RH temperature low alarm will appear.
Negative expansion of turbine
Unit may trip on RH temp very low.
Parameters of concern.
MS/RH temp, drum level, feed water flow.
Immediate expected or desirable operator action.
Close the spray control valves by taking in manual.
Tilt burner upward.
Rise the Airflow.
Top elevation mill can be taken into service /firing can be raised.
Final correction activity.
Initiate LRSB soot blowing if temperatures are maintaining still less.
Observe for improvement in temperature.
Restore back the controls in auto (spray control)
Check for any malfunction of control valve & isolate it.
One of the Turbine control valve fails to close
Likely causes
Trip SOV may be problem.
Trip coil faulty
Choking in servo valve ports
Problem in control valve linkage.

c
d

e
13
a
b

c
d
e
14

Airlock in control oil system


Mechanical problem
Plant response
Load hunting
Load cannot be varied as per requirement
EHTC controller O/P will reduce very much to maintain same load .
Speed fluctuation will occur during synchronising time.
Parameters of concern.
Speeds, Load, pressure, control oil pressure, and drum level, HP exhaust temperature.
Immediate expected or desirable operator action.
Inform immediately to Maintenance dept.
Trip the unit ,if there is no any ready solution
Check control oil pressure.
Final correction activity.
Ensure proper functioning of control valves
Control oil circulation pump failed
Likely causes
Pump may be tripped on any electrical protections
Plant response
Control oil tank temperature will rise.
Control oil pressure may drop because of viscosity reduction.
HSU Tank temperature high alarm will appear.
Parameters of concern.
Control oil temperature, HSU header pressure,
Immediate expected or desirable operator action.
Check pump module along with electrical maintenance.
Try to restart the pump as early as possible.
Final correction activity.
Ensure continuous running of the pump.
Control oil leakage

c
d

Likely causes
Damage in pipe line/pin hole puncture.
N2 accumulator diaphragm might have punctured.
Control oil pressure may be very high.
Plant response
Standby pump will pick up on header pressure low
Because of low pressure ,control valves may go for close
MS pressure may rise.
LP bypass malfunction.
Unit may trip.
Parameters of concern.
Unit load ,pressure, HSU pressure.
Immediate expected or desirable operator action.
If leakage is heavy, turbine to be tripped on fire protection channel.
If leakage is heavy personal safety to be ensured and fire fighting dept to be informed.

15
a

Locate point of leakage.


Final correction activity.
Stop S/B pump
Ensure leakage has been arrested fully
Ensure all the parameters are restored back
Ensure control oil pressure is normal.
One of the Turbine control valve closes
Likely causes
Trip drain SOV may be problem.
Trip coil faulty
Problem in control valve linkage.
Mechanical problem.
Airlock in control oil system
Choking in servo valve ports.
Plant response
First stage pressure will rise than the normal value, if at all problem is there with IP

c
d

control valve.
HP exhaust temperature will rise.
RH pressure will rise than the normal.
RH Safety valves may pop.
Thrust loading/axial shift may vary
Load hunting
Load cannot be varied as per requirement
Speed fluctuation will occur during synchronising time
Parameters of concern.
Load, pressure, control oil pressure, drum level, HP exhaust temperature, axial shift.
Immediate expected or desirable operator action.
Maintenance dept., to be informed immediately
Check for control oil pressure
Keep standby pump running in manual mode.
If possible reduces load and pressure.
Control boiler firing.
Control SH & RH temperature.
Final correction activity.
Ensure proper functioning of control valves.
Restore back all the parameters.

Anda mungkin juga menyukai