Plant response
Drum level very low may affect natural circulation in water wall panel and if drum is empty tubes will melt in no time
Deaerator level
Hot well level
Feed water flow
Steam flow
SH/RH temp
2.
Likely causes
Plant response
3.
Plant response
Unit load
MS /RH temperature
Drum level
APH inlet O2
HP/LP bypass
4.
Plant response
Drum level
generator load
MS pressure
MS/RH temperatures
APH FG inlet O2
If rate of pressure drop is more than the given saturation temp. curve boiler drum will subjected to severe thermal shock
5.
Plant response
6.
Plant response
Drum level
MS and RH pressure
HRH temp
Shock to boiler component
7.
Likely causes
Plant response
MS/RH temperatures
MS temp at turbine inlet
HP exhaust temperature.
Spray quantity/ FCV differential pressure.
Tilt position
Metal temp. raise above design value will reduce tube life drastically
Take MS spray control to manual & raise spray quantity (stage -1 o/l temp should be around 450C & stage -2 o/l temp around
505C)
Reduce firing in top elevation
If rate of pressure rise is more, then pick up load if margin is there.
Reduce airflow based on the O2 percentage.
Check spray station is properly lined up
8.
Likely causes
Plant response
RH temperatures
RH temp at turbine inlet
HP exhaust temperature.
Spray quantity/ FCV differential pressure.
Tilt position
Metal temp raise above design value will reduce tube life drastically
9.
Likely causes
Tripping of mill
Sudden boiler pressure drop
Malfunctioning of spray control valves.
Spray station passing
Less air flow
Burner tilt fully down
High feed water temperature
Soot deposits on SH tubes
Plant response
Ms temp
Spray quantity
Burner tilt
10.
Tripping of mill
Sudden boiler pressure drop
Malfunctioning of spray control valves.
Spray station passing
Less air flow
Burner tilt fully down
High feed water temperature
Soot deposits on RH tubes
Plant response
RH temp
Spray quantity
Burner tilt
Load
Close spray station Block valve/ isolation valve if control valve is passing.
11.
PLANT RESPONSE
Down stream pressure will come down as compared with the corresponding valve position.
PARAMETERS OF CONCERN
OPERATOR ACTION
Remove pair of corresponding burner & rectify the problem with help of C&I.
PLANT RESPONSE
PARAMETERS OF CONCERN
OPERATOR ACTION
Find out the root cause & rectify the problem with help of maintenance.
12.
PLANT RESPONSE
If the trip valve has failed to close during boiler trip, the corex will vent
out from the C hdr vents & chances of increase in CO
PPM will be there.
Corex may also enter in the boiler if there is passing in any of the corner nozzle valves.
PARAMETER OF CONCERN
CO ppm in atmosphere.
Furnace draft. (If the corex trip valve has failed to close during boiler trip accompanied with the failure of closing of any corner
nozzle valves).
MS pressure. (If the corex trip valve has failed to close during boiler trip accompanied with the failure of closing of any corner nozzle
valves).
Furnace flame. (If the corex trip valve has failed to close during boiler trip accompanied with the failure of closing of any corner
nozzle valves).
OPERATOR ACTION
Find out the root cause & rectify the problem with help of maintenance.
13.
PLANT RESPONSE
OPERATOR ACTION
PARAMETERS OF CONCERN
Stack emission.
Tripping of field
14.
LIKELY CAUSES
Leakage in piping
Leakage in drain plug, instruments, connections
Leakage in threaded joints
Leakage through filter vent plug
Oil seal damage
PLANT RESPONSE
OPERATOR ACTION
PARAMETERS OF CONCERN
Oil level
Oil temperature
Bearing temperature.
Add oil through the dip stick hole until max oil level mark .
Leakage to be arrested.
Put the oil system back in to service.
15.
PLANT RESPONSE
OPERATOR ACTIONS
PARAMETERS OF CONCERN
B.
After rectifying the problem of electric motor / air motor, start air / electric motor before normalizing the dampers on air/gas side.
If the problem is due to stucking of foreign material, then outage may be required to remove the same.
LIKELY CAUSES
PLANT RESPONSE
OPERATOR ACTION
PARAMETERS OF CONCERN
16.
After rectifying the problem of electric motor / air motor, start air / electric motor before normalizing the dampers on air/gas side.
LIKELY CAUSES
OPERATOR ACTION
If steam quality cannot be improved because of the make up water faulty/ condenser tube leakage, shutdown the unit.
PARAMETERS OF CONCERN
PLANT RESPONSE
17.
LIKELY CAUSE
PLANT RESPONSE
PARAMETERS OF CONCERN
OPERATOR ACTIONS
Find the root cause of the problem; if it is due to faulty dosing then check concentration of the dose. If it is due to passing get it
arrested. ask chemist to check DM water quality.
18.
LIKELY CAUSE
PLANT RESPONSE
PARAMETERS OF CONCERN
OPERATOR ACTIONS
19.
Likely causes
DC fan fails to start after AC fan trip
Both fan getting over load/electrical fault
Plant response
Scanner air to furnace DP low alarm
Scanner air fan tripped alarm
Inadequate cooling of scanners may cause damage to scanner sensing element
Parameters of concern/Adverse effects
Scanner air to furnace DP low
Flame scanner cooling is not taking place
Operator action
Try to start fan by resetting overload relay
Increase FD fan discharge pressure so that some air will always available for scanner
If not happening reduce load to minimum & get the fan started at the earliest.
If Scanner air fan could not be restarted even after reasonable time delay trip the boiler
19.
ID/FD trip
Probable Causes
ID trip
Motor protection acted.
Lub oil pressure v.lo 0.2ksc
H.C oil pressure v.lo 0.6ksc
H.C oil tank temp high 110oc
H.C oil cooler o/l temp 90oc
Winding temp v.hi 120oc
Bearing temp (fan/motor) v.hi (75oc/95oc)
FD trip
Motor protection acted.
Fan/motor bearing temp v.hi 95oc
Winding temp v.hi 120oc
Plant response
On ID trip, corresponding stream FD fan will trip.
Running ID/FD fans will get loaded to maintain draft and airflow.
When in CMC, runback will act and reduce load SP to 90/100MW @ 20MW/min
Mill-C will trip (On FD fan trip), if 3 mills are in service.
Parameters to watch
Furnace draft, drum level, airflow, ID & FD currents, mill loading, TG load, MS pressure & temperature, RH temperature, WB to furnace
DP, O2 at APH i/l.
Operator action
20.
APH fire
Likely causes
Defective oil burner, leading to deposition of un burnt oil particles on APH heating elements.
Soot deposit on APH heating element
In effective APH soot blowing.
Guide bearing oil leakage in to APH.
Plant response
Flue gas/ secondary air temp high alarm should come(presently not commissioned)
Parameters of concern.
Flue gas temp after Air heater
Sec air and primary air temp after APH
Damage to APH
Immediate expected or desirable operator action.
Reduce boiler load
Close Flue gas inlet damper
Close PA &Secondary air side inlet & outlet dampers
Open APH hopper drain plug
Open cold end side & hot end side hydrant valve and quench fire
Final correction activity.
Stop the oil guns with smoky flame if they are in service.
Isolate APH and open for inspection if fire is extensive
21.
LIKELY CAUSES
High mill outlet temp.
Running mill with less air flow for long time can cause coal accumulation in mill discharge pipe & cause fire
High % of volatile mater in coal
If mill rejects are more & not removed regularly may cause fire in rejects chamber.
Tramp Iron Gate stuck in close position, causing fire in rejects chamber.
Coal accumulation in hot air duct
Fire conveyed from bunker coal
PLANT RESPONSE :
Mill out let temp. high alarm
Mill DP & air flow , current variation.
Fire coming from reject hopper
Red hot mill body/ reject chamber
Parameters of concern
Mill puffing
Mill o/l temp.
Air i/l temp.
Mill airflow.
Mill DP
Mill rejects.
22.
LIKELY CAUSES
Forward/Reverse motor trip
Lance jammed after advancing
LRSB clutch de coupled after advancing
Electrical supply failure during operation
Chain broken.
PLANT RESPONSE
Soot blower not retracted alarm
Soot blower overload acted alarm
Parameters of concern
Steam jet hitting boiler tubes
LRSB getting damaged
Immediate /expected or desirable operator action
Reset the module & give retract command from local push button. If it fails to retract even after module is reset, switch-off the
module.
Reduce soot blower header pressure to 3- 4Ksc.
Disengage the clutch and try to retract manually from handle. If it is retracting do not release handle in the middle ( If handle is to be
released in the middle, first engage the clutch & then only release) .
Inform maintenance if it is not retracting manually also.
Try retracting with additional assistance for max. one hour.
If it could not be retracted within 1hour, reduce pressure to 0 ksc & try again.
Still if it is not retracting ask maintenance to insert dummy in steam supply line flange so that other blower operation can be carried
out.
Final correction activity
23.
FIRE IN ESP
LIKELY CAUSES
OIL/soot deposit on ESP fields
Very high un burnt in fly ash & hopper heating element Not switching off
ESP transformer fire
PLANT RESPONSE
ESP transformer trip.
Furnace Draft variation
Parameters of concern
ESP O/L temperature
ID fan loading
Furnace Draft
Damage to ESP
Immediate /expected or desirable operator action
Trip ESP field
Isolate the power supply of all related ESP pass/field.
If fire is outside ESP, use extinguisher & douse the fire.
If it is inside ESP reduce unit load & close ESP inlet & outlet gate.
Inform fire man
Open ESP man holes
Open ESP ash hopper drain plugs/man hole
Quench the fire with fire hydrant water
Final correction activity
Identify the reason and rectify it.
While reducing load, it will not reduce below certain MW even if load set point is less.
Stuck Valve position feed back will show open position control room whereas other valve will go for close.
B. Likely cause
C. Operator action
Immediate action
If turbine has tripped. close MS1.2.3 &4 & depressurise MS & RH line.
Subsequent action
If valve has stuck. Reduce boiler pressure & shut down the unit for attending the problem.
27. ONE PHASE OF THE GT POLES FAIL TO OPEN AFTER UNIT TRIP
A. Symptom /parameter effected
LBB protection will trip all the breaker connected to that bus.
B. Likely cause
C. Operator action
Immediate action
Trip all the 220 kV breaker connected to the particular bus including bus coupler.(If LBB not acted).
Subsequent action
B. Likely cause
C. Operator action
Immediate action
+
Subsequent action
C. Operator action
Immediate action
Positive differential expansion
Reduce steam temp if it is more.
Bring machine to soaking speed if it is during rolling.
Reduce turbine loading if it is after synchronisation.
Check and control gland steam temperature.
Check MAL drains are operating properly.
Subsequent action
Lub oil return line oil temp. gauge showing more than normal.
B. Likely cause
ACW pump tripped or ACW to lub oil cooler not charged after synchronisation.
Bearing failure.
C. Operator action
Immediate action
Trip the turbine if bearing temp reaches 120 0C(atleast 2 indications in metal temp overview screen).
Subsequent action
Check lube oil flow & pressure to bearing.
Check Lub oil cooler is charged on ACW side & ACW flow is adequate.
Check return oil temp from each bearing.
Verify babit temperature by other means (to rule out faulty measurement)
If thrust bearing temperature is increasing check for axial shift.
Start Standby AOP if oil pressure is low.
B. Likely cause
Alignment/centering problems.
C. Operator action
Immediate action
Reduce turbine load by load limiter and trip the machine if bearing vibration is >11mm/sec(for Brg No. 6 >18mm/sec.
Subsequent action.
Check locally whether vibration is actually high.
Listen to bearing sounds using a vibration sensing stick.
Maintain steam parameters normal.
Check lube oil pressure and after cooler temperature.
Check any sudden MVR change is there.
Wait for frequency change.
Trip the machine if it does not trip on high vibration.
Final corrective action
32. TURBINE STARTS ROLLING ON ESV OPENING
A. Symptom /parameter effected
B. Likely cause
C. Operator action
Immediate action
Close ESV by tripping turbine.
Check whether control valves are fully closed (in DCS as well as local).
Check for the EHTC output (has to be zero).
Subsequent action
If all rolling criteria are ok and if only minor passing only is there and speed is reaching to say 800rpm roll to 3000rpm if it is a
hot startup.
Final corrective action
B. Likely cause
C. Operator action
Immediate action
Subsequent action
If main valve creeping is started due to loss of oil pressure then reduce turbine load slowly to 60 MW.
Bring down boiler pressure to 85Ksc. and get the leak attended.
If leak is attended charge the line slowly and raise the load
If leak could not be attended trip the boiler after reducing load.
B. Likely cause
C. Operator action
Immediate action
Close isolation valve (at control oil skid) of leaking line if leak is in individual lines.
If leak is in common block & leak does not stop after change over, reduce turbine load & trip Control oil Pumps immediately.
Subsequent action
Inform fireman and keep fire extinguisher ready if oil is spilled over valve body or steam line.
B. Likely cause
H2 cooler leakage.
DPRV malfunctioning and maintaining higher DP.
Defective seals component and oil entering generator casing.
C. Operator action
Immediate action
Open LLD drains after isolation and empty it. See whether oil or water is coming.
After draining, normalise and wait for further liquid level sensing.
If water is coming reduce generator load & isolate one hydrogen cooler & find out leaky cooler .
If oil is coming see seal oil to H2 DP is normal.
Subsequent action
Find out reason for liquid entry in casing and rectify it.
B. Likely cause
C. Operator action
Immediate action
Subsequent action
Alarm at local / DCS will come depending upon location of leak.( 08 static CO detector in blower area, 8 CO detector & 8 H 2 detector
in different elevation on both the boiler & 01 detector in control room AC duct are connected to DCS system in Control room).
- orange
- red
In addition Siren will be activated from control room for corex leak emergency.
B. Likely cause
Passing of valves.
Major leakage can occur in the unlikely event of natural calamities such as earthquake etc.
C. Operator action
Check CO concentration with portable detectors and confirm with that of control room indications.
If the CO-detected by permanent / portable detectors is reading 200ppm and above, effect local area evacuation and parallel
start reduction of corex in the corresponding unit (if the leakage is sensed in blower area reduction to be done in both the
units). If greater than 400ppm for 15 min, stop A/C plant and remove corex elevation of the corresponding unit. (if the
leakage is sensed in blower area remove the corex completely in both the unit & close the bypass goggle valve and JVSL
double gate valve). And if greater than 500ppm for 30 min, declare emergency by actuating siren for totally evacuation of the
personnel.
Inform safety officer / fire control room in any of the above case.
Check for leakage, all the source of ignition should be kept away, Self-contained breathing apparatus (SCBA) to be used
while checking and attending leak.
In case fire takes place during leak, first the pressure in the supply line should be reduced to shorten the flame & then the fire
should be extinguished. Only after the fire is extinguished, the main gas should be closed completely. Never close the main
valve, when the fire is still there and the pressure in the gas main should not be reduced below 100mmwc.
In case anyone notices an emergency type situation, shift-in-charge should immediately reach the location of emergency with
necessary safety gadgets and assess the situation. He will declare the emergency by informing control room to send coded
siren (15 seconds on & off for 3 minutes). At the same time he will decide about the emergency shut down of the plant
Perform the head count at the assembly point (Old admin. Bldg).
All clear signals (2 min- continuous) siren to be raised if the declarer of emergency clears the emergency after attending the
leakage.
Subsequent action
Purge the corex system with nitrogen & achieve the co ppm less than allowable range of 50 ppm
B. Likely cause
C. Operator action
Immediate action
If C- header vent valve fails to close. then remove corex totally from that unit.
Subsequent action
B. Likely cause
C. Operator action
Immediate action
Close UNIT supply goggle valve and purge supply line & C header with N 2.
Subsequent action
Final corrective action
Emergency Procedure
1. APH FIRE
Symptoms / parameter
effected
1. Flue gas temp. at APH
outlet goes above
3500C suddenly from
normal value
2. Secondary air temp. at
APH outlet goes above
Immediate Operator
Action
1. Reduce unit load to 65
Likely cause
MW
2. Close Flue gas inlet
deposit on APH.
damper of particular
APH.
3. Close ESP inlet damper
Heavy unburnt
Poor combustion of
Subsequent operator
action
1. Open APH hopper drain
plug.
2. If the fire is confirmed
fuel oil.
blowing regularly
of the corresponding
normal value
APH.
elevation was in
service
Motor if possible.
4. Close PA &Secondary
thermocouple gives
hooked up)
Final corrective
action
Isolate APH and
release for
inspection.
Do APH soot
blowing every shift if
oil is in service
Subsequent operator
action
Motor tripped on 1. If the air motor has not
Likely cause
overload.
Power supply to
or
APH outlet(>3000C)
failure
2. APH
rotor
MW
stopped 2. Close Flue gas inlet
alarm.
3. Rapid rise in flue gas
damper of particular
APH.
No
solenoid
compressed
start then
2. Attempt for starting the
electric
motor
if
the
foreign
material fallen on
nor
stuck.
Some
electrical
motor
rotor
stopped
alarm.
Likely cause
tripped
are tripped
overload.
Power supply to
both
Both
Subsequent operator
action
Motor 1. If the air motor has not
on
motors
failed.
start then
failure
APH outlet.
solenoid failure
electric
No
compressed
power failure.
Some
nor
foreign
motor
electrical
if
the
motor
material fallen on
stuck.
sufficient/filter
becomes standstill.
choked
if it is choked
2. Close
standby
pump
passing
3. If
Turning
gear
solenoid
disconnect
is
solenoid
solenoid problem
bearing pedestal
oil
Turbine
internals
rubbing
test
closed condition
faulty
Hydro motor
problem
Subsequent operator
action
JOPs not in AUTO 1. Check module fuse
Likely cause
2. Reset module
Pump
module
problem
Module tripping on
overload
Pump
damage
mechanical
in service.
Likely cause
APH Fire
Inadvertent closure
of any of the APH
inlet/outlet damper.
Improper
Subsequent operator
action
1. Refer
APH
fire
procedure
4. Reduce Air flow if it is
more
5. Make up seal trough
water if it is broken
6. Check all APH dampers
and open if any damper
is closed.
operation of
SADC
procedure
9. Do soot blowing.
boiler
Subsequent operator
action
Depressurise
MS
&
If LPT diaphragm is
ruptured replace it
>900C
MS drain to atmosphere
open.
E-Stop pressed
Subsequent operator
action
1. Release E-stop
DG not in auto
2. Start DG manually
started
Over speed
Likely cause
shutdown
3. Charge KB bus by
manually closing 415 V
breaker if it is not
closed on auto.
DG is running
motors
High water
CRH-105 manually if
temperature
DG supply is not
available
6. All other activities of
black out to be
performed.
Symptoms / parameter
Immediate Operator
effected
Action
1. Acoustic leak detector 1. Start reducing unit
alarm
load
draft
Fluctuation
4. Sound
Likely cause
from
stuck in advanced
time.
inside
boiler
Blocked tubes
Scale
formation/corrosion
inside tubes
reducing load
3. Box up boiler
temperature.
to soot blowing
Subsequent operator
action
1. Maintain drum level
depressurisation and
isolate it
Improper setting of
safety valve.
9. Fire near MOT/Control oil system
Symptoms / parameter
Immediate Operator
effected
Action
1. Fire
noticed
by 1. If fire is isolated one
personnel.
2. Fire alarm. if actuated
in local by any persons
after observing fire
3. Burning smell
quench with
appropriate
extinguisher
near MOT
of affected area if
required.
with
2. Inform firemen.
3. If it is big in nature.
Subsequent operator
action
Electrical short circuit 1. Isolate electrical supply
Likely cause
out
precaution
Replace MOT/control
oil if contaminated
Likely cause
Excessive mill
temperature.
Excessive
Subsequent operator
action
1. Wait for mill outlet
temp to drop below
500C.
accumulation of pyrites
2. Stop feeder.
or coal in scrapper
chamber
down
coming
the mill
out
be cleared
in
rejects hopper*.
collecting in mill.
accumulation in mill
discharge pipe &
cause fire
Coal accumulation in
hot air duct
Fire conveyed from
bunker coal
inspection.
Symptoms / parameter
effected
1. Fire alarm in fire
Immediate Operator
Action
1. If transformer has not
monitor system
tripped, trip it
console.
Likely cause
Transformer Internal
faults causing fire
Fire from external
source carried to
transformer
Subsequent operator
action
1. If Spray system not
operated Open by
pass valve of deluge
valve
2. Inform fireman.
3. Drain transformer oil
to burnt oil pit
4. Prevent fire from
spreading to other
equipment by fire
fighting measures
Release transformer
for inspection
Immediate Operator
Action
1. Trip the unit.
Likely cause
Short circuit.
Cable insulation failure
due to over loading
Fire from external
source
Subsequent operator
action
1. Isolate AC supply as
per the condition and
if required trip the
station transformer.
2. If hydrant system not
operated Open deluge
valve bypass
3. Inform fireman
Immediate Operator
Likely cause
Action
1. Switches off Conveyer Burning coal loaded on
supply modules.
2. Inform fireman.
the conveyer.
Electrical short-circuits.
Fire in the spilled coal
around conveyer.
Subsequent operator
action
1. If hydrant deluge
valve not opened
open bypass valve
2. Use the nearest
hydrant point for
additional spray
Immediate Operator
Action
1. Stop feeding to that
bunker.
Likely cause
Spontaneous ignition
Subsequent operator
action
1. If possible run the mill
bunker
at the earliest or
visible)
Immediate Operator
Action
1. Reduce unit load to
ESP
Likely cause
Oil/soot deposit on
ESP fields
Very high unburnt in fly
Subsequent operator
action
1. If fire is outside ESP,
use extinguisher &
douse the fire.
off
supply of particular
pass/field.
hopper drain
plugs/man hole
Symptoms / parameter
Immediate Operator
effected
Action
1. Fire
noticed
by 1. Stop HFO /LFO
personnel.
pumps
equipments.
Subsequent operator
action
1. Inform fireman
Likely cause
temperature.
External fire conveyed
to oil tank
3. Burning smell
Improper earthling
corresponding
Likely cause
Subsequent operator
Final corrective
action
1. Isolate leaking point
action
Attend leaking
puncture by any
2. Inform fireman
discharge line.
means.
3. Arrange to clean
point
leaked oil
Symptoms / parameter
effected
1. Generator winding
temp. high alarm.
2. Generator hot gas
temp>600C.
Likely cause
generator
load
Final corrective
action
1. Check ACW pressure
action
Overloading of
at Hydrogen cooler. If
generator
ACW flow to
ACW pump.
hydrogen cooler
low
Subsequent operator
locked
19. Flash over
Symptoms / parameter
effected
1. Observed by personnel
2. Fire alarm
flash
occurred
over
Subsequent operator
Final corrective
action
Loose contacts
action
If flashover is observed in
Short-circuits
Likely cause
has
Over load
Insulation failure
Switching/lightning
voltage surges
Likely cause
Subsequent operator
Final corrective
action
1. Check level locally and
action
If tube leak is
failure.
confirm level
confirmed
transmitter is reading
isolate heater
control due to
correct.
totally and
valve partially to
confirm whether
heater tube is leaking
release for
maintenance.
load
to
reduce
axial shift
uniformly open
action
Abrupt change in 1. Maintain
drop
Sudden closure of
extraction valves
Turbine overload
has opened
3. Check
vibrations
Final corrective
action
steam
parameter steady
load
Subsequent operator
Likely cause
coasting
down
time
5. If salting is suspected
Silica deposits on
turbine blades
washing of turbine or
Turbine
other methods of
internal
damaged
cleaning
If hydrogen pressure
reaches <1 ksc trip
Likely cause
Subsequent operator
Final corrective
action
Try to establish seal oil
2.
action
pressure by starting
alarm
2. Seal oil system fault
standby AC & DC
stand by pump or by
alarm
3. If seal oil pressure is
seal is low
DPR malfunction
will start.
Hydrogen leakage
4. Winding temperature
developed in
may increase
3.
If leaking point is
identified, try to isolate
it. If not possible,
generator system
may increase
Likely cause
Final
corrective
action
1. LRSB not retracted
alarm
2. Observed from local
after advancing
advancing
If LRSB could
header pressure to 3-
not retracted,
4Ksc.
ask
maintenance to
LRSB clutch de
insert dummy
coupled after
handle. If it is retracting do
in steam supply
advancing
line flange so
middle ( If handle is to be
that other
blower
operation can
only release) .
be carried out.
Electrical supply
failure during
operation
Chain broken.
3. Inform maintenance if it is
not retracting manually
also.
4. Try retracting with
additional assistance for
max. one hour.
5. If it could not be retracted
within one hour, reduce
Likely cause
leak
is
less
and
MOT
drain
Subsequent operator
Final corrective
action
action
is 1. Check any drain in Stop turbine
opened
open close it
after turbine
2. If leakage is before
leakage
comes to
barring gear
/filter leakage
and arrange
Leakage from TG
(change
for attending
will
bearings
over
oil
leak.
Clean oil
leaked out to
seal
Charging
draining out
of
break
and
oil
avoid fire
hazard
Oil
Likely cause
Burner in service
Subsequent operator
Final corrective
action
1. Check for the passing
action
local
corner immediately
without flame
passing
Atomising steam/air
and adjust it
Oil specification
different from
designed one.
Likely cause
100MW(if unit is in
line
2. Open corresponding MAL
valve(Partially)
Valve mechanically
Final corrective
action
1. If valve has stuck.
action
stuck
working
Subsequent operator
27. One phase of the GT poles fail to open after unit trip
Symptoms / parameter
effected
1. Pole Discrepancy alarm
will come
2. LBB protection will trip
all the breaker
connected to that bus
3. TG speed does not
drop after trip
4. TG draws current from
grid (reverse power)
5. Negative sequence
current in Generator
6. LP exhaust temperature
going high
Likely cause
Breaker contact
mechanically stuck
Subsequent operator
Final corrective
action
1. Normalise supply by
action
Attend GT
breaker before
Bus coupler.
restarting
Turbine
Likely cause
Subsequent operator
Final corrective
action
action
1. Try to start fan by
Lightup boiler
resetting overload
only after
relay
2. Increase FD fan
starting
discharge pressure so
scanner air
that some air will
always available for
fam
scanner
3. If not happening
reduce load to
minimum & get the fan
started at the earliest.
4. If Scanner air fan could
not be restarted even
after reasonable time
delay trip the boiler
Likely cause
Subsequent operator
Final corrective
action
action
1
a
c
d
2
a
b
c
d
drops to -100 mmwc & load the pump to the running pumps scoop.
Check for any malfunction of auto control like scoop not raising or recirculation open
in auto, take control into manual & make up drum level.
Close CBD if it is open.
Close HPBP if it is open.
Remove corex burners (when level is above (-100 mmwc)).
Caution: Do not do any major removal of fuel at drum level (-100 mm & above., like
mill tripping, burner removal)
Final correction activity.
Check drum level is getting stabilised.
Ensure drum level controls are in auto.
Check feedwater flows matches with steam flow for full load, if deviation is more then
check for any leak in boiler area.
Ensure for the availability of standby BFP as early as possible.
Check for local level gauge & transmitters.
Check boiler low point drains & EBD.
Check for scoop controls for any linkage failures.
Drum level shooting up fast
Likely causes
Malfunction of feed controls.
Sudden increase of load (due to malfunction of EHTC)
Drum level transmitters may be faulty.
Sudden increase of firing rate.
Scoop /control valves might have stucked.
Sudden opening of HPBP.
Plant response
Drum level high alarm will appears.
On drum level high high, boiler will trip.
Parameters of concern.
SH/RH temperatures drum level.
Immediate expected or desirable operator action.
Check the hydrostep level, if it is high take drum level control to manual & match
3
a
c
d
4
a
c
d
Trip the malbehaving feeder/mill & reduce PA airflow through that mill.
Check for pressure drop & if it is not holding remove the corex burners.
Caution:Donot reduce the fuel when the drum level is around -100mm
Start standby BFP when drum level reaches -100mm & rise the scoop to running BFP
scoop.
Final correction activity.
Check for reseating of safety valve
As soon as the pressure starts dropping, restore the correct fuel input.
Stop the third running BFP and keep it in standby.
Ensure drum level got stabilised.
Check for closure of HP bypass.
Ensure pressure is stable.
Bring back the unit load to normal.
EMRV floating and reseating in succession
Likely causes
Maloperation of valve.
High fuel firing rate.
MS pressure fluctuation.
Maloperation of turbine control valve.
Plant response
Drum level will vary.
Generator load will vary.
Hp bypass will open if it is in auto & may hunt.
Ms temp and RH temp variation.
Parameters of concern.
Drum level, Ms temp and RH temp, MS pressure.
Immediate expected or desirable operator action.
Reduce the fuel firing if pressure is really high.
If MS pressure is less, still EMRV is operating, keep selection switch to "OFF" so that
the EMRV will not operate.
Even by putting "off ", valve is still in open condition, its manual isolation valve can
be closed.
5
a
c
d
6
a
b
Corex CV decrease
Likely causes
Malfunction of COREX process.
Variation in corex constituents %.
Plant response
Ms pressure will drop fast
Generator Load will drop.
O2 at APH FG inlet will rise & high alarm may appears.
c
d
7
a
c
d
Parameters of concern.
MS pressure, load, APH flue gas inlet oxygen.
Immediate expected or desirable operator action.
Reduce load set point inorder to hold the boiler pressure
Enquire EMD Dept about CV variation & if corex is stable then raise the feeding on
running mills.
Final correction activity.
Ensure O2 at APH i/t is normal
Restore the fuel input to boiler once the CV of corex stabilises.
Rapid Boiler steam pressure decrease
Likely causes
Sudden drop in Calorific value or pressure of corex.
Tripping of mill or feeder.
Sudden rise in load.
Disturbed combustion conditions in furnace.
Mill might have got unloaded.
Plant response
MS pressure will drop.
Generator load will come down.
Drum level will drop.
O2 at APH FG inlet will rise.
Parameters of concern.
Drum level, generator load, MS/RH temperatures, APH FG inlet O2.
Immediate expected or desirable operator action.
Check for any mill unloading.
Reduce load set point to hold the MS pressure around 110 kg/cm2.
Check boiler flame, take oil elevation into service.(don't take oil when combustion
conditions are very poor)
Monitor drum levels during this disturbance, if it is dropping very fast, start standby
BFP & load the scoop equal to running pump scoops.
Final correction activity.
c
d
quantity is more..
Restore back the temp controls in auto if it has been taken in manual
Check for any malfunction of spray control valves & isolate such type of valve.
Burner tilt can be kept horizontal.
9
a
c
d
10
a
c
d
11
a
c
d
12
a
c
d
e
13
a
b
c
d
e
14
c
d
Likely causes
Damage in pipe line/pin hole puncture.
N2 accumulator diaphragm might have punctured.
Control oil pressure may be very high.
Plant response
Standby pump will pick up on header pressure low
Because of low pressure ,control valves may go for close
MS pressure may rise.
LP bypass malfunction.
Unit may trip.
Parameters of concern.
Unit load ,pressure, HSU pressure.
Immediate expected or desirable operator action.
If leakage is heavy, turbine to be tripped on fire protection channel.
If leakage is heavy personal safety to be ensured and fire fighting dept to be informed.
15
a
c
d
control valve.
HP exhaust temperature will rise.
RH pressure will rise than the normal.
RH Safety valves may pop.
Thrust loading/axial shift may vary
Load hunting
Load cannot be varied as per requirement
Speed fluctuation will occur during synchronising time
Parameters of concern.
Load, pressure, control oil pressure, drum level, HP exhaust temperature, axial shift.
Immediate expected or desirable operator action.
Maintenance dept., to be informed immediately
Check for control oil pressure
Keep standby pump running in manual mode.
If possible reduces load and pressure.
Control boiler firing.
Control SH & RH temperature.
Final correction activity.
Ensure proper functioning of control valves.
Restore back all the parameters.