Circuit Breakers
for Naval
Shipboard Use
Contents
Description
Page
Description
Page
Description
Page
Description
Page
Type NQB-A803 . . . . . . . . . . 98
Types AQB-A51,
NQB-A51 . . . . . . . . . . . . . . 23
Types AQB-A250,
NQB-A250 . . . . . . . . . . . . . 48
General Information . . . . . . . . 3
Product Selection . . . . . . . . 23
Product Selection . . . . . . . . . 48
Outline Dimensions . . . . . . 99
Design Features . . . . . . . . . . . 3
Outline Dimensions . . . . . . 25
Outline Dimensions . . . . . . . 54
Types AQB-A1601,
NQB-A1601 . . . . . . . . . . . 100
Product Selection . . . . . . . . 98
Standard Features . . . . . . . . . 4
Time-Current Curve . . . . . . 28
Time-Current Curve . . . . . . . 59
Application . . . . . . . . . . . . . . . 5
Types AQB-A100,
NQB-A100 . . . . . . . . . . . . . 29
Types AQB-LF100,
AQB-LF250 . . . . . . . . . . . . . . 60
Product Selection . . . . . . . . 29
Product Selection . . . . . . . . . 61
Marine Breaker
Application . . . . . . . . . . . . . . 5
Outline Dimensions . . . . . . 32
Outline Dimensions . . . . . . . 65
Time-Current Curve . . . . . . 33
Time-Current Curve . . . . . . . 69
Types AQB-A1602,
NQB-A1602 . . . . . . . . . . . 109
Types AQB-A101,
NQB-A101 . . . . . . . . . . . . . 34
Types AQB-A253,
AQB-L253, NQB-A253 . . . . .70
Outline Dimensions . . . . . . . 8
Product Selection . . . . . . . . 34
Product Selection . . . . . . . . . 71
Time-Current Curve . . . . . . 16
Outline Dimensions . . . . . . 38
Outline Dimensions . . . . . . . 75
Types AQB-A50,
NQB-A50 . . . . . . . . . . . . . . 17
Time-Current Curve . . . . . . 42
Time-Current Curve . . . . . . . 77
Product Selection . . . . . . . . 17
Types AQB-L400,
AQB-LL400, NQB-LL400 . . 78
Outline Dimensions . . . . . . 19
Product Selection . . . . . . . . 44
Product Selection . . . . . . . . 79
Time-Current Curve . . . . . . 22
Time-Current Curve . . . . . . 45
Outline Dimensions . . . . . . 83
General Ordering
Information . . . . . . . . . . . . . . 5
Time-Current Curve . . . . . . 86
Selection
Guide
BREAKER
TYPE
ALB-1
MIL-C-17588
MIL-S-901
5 50
NLB-1
MIL-C-17588
MIL-S-901
50
AQB-A50
MIL-C-17361
MIL-S-901
NQB-A50
AQB-A51
MIL-C-17361
MIL-C-17361
MIL-S-901
MIL-S-901
NQB-A51
AQB-A100
MIL-C-17361
MIL-C-17361
NQB-A100
2,500
5,000
Thermal
Magnetic
None
10 50
125 Vdc
125 Vac
125 Vdc
125 Vac
500 Vac
5,000
17
3
3
50
10 50
500 Vac
500 Vac
5,000
MIL-S-901
MIL-S-901
3
2, 3
50
15 100
MIL-C-17361
MIL-S-901
2, 3
100
10,000
15,000
AQB-A101
MIL-C-17361
MIL-S-901
15 100
MIL-C-17361
MIL-S-901
100
10,000
15,000
Thermal
Magnetic
None
34
NQB-A101
AQB-A103
NQB-A103
AQB-A250
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-S-901
MIL-S-901
MIL-S-901
3
3
2, 3
10 100
100
100 250
MIL-C-17361
MIL-S-901
2, 3
250
15,000
15,000
20,000
Electronic
None
Thermal
Magnetic
None
44
44
48
NQB-A250
AQB-LF100
MIL-C-17361
MIL-S-901
15 100
500 Vac
250 Vdc
500 Vac
250 Vdc
500 Vac
250 Vdc
500 Vac
250 Vdc
500 Vac
500 Vac
500 Vac
250 Vdc
500 Vac
250 Vdc
500 Vac
500 Vac
Thermal
Magnetic
None
Thermal
Magnetic
None
Thermal
Magnetic
None
100,000
60
AQB-LF250
MIL-C-17361
MIL-S-901
125 250
500 Vac
100,000
AQB-A253
AQB-L253
NQB-A253
AQB-L400
AQB-LL400
NQB-LL400
NQB-A803
NQB-A803
AQB-A1601
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-S-901
MIL-S-901
MIL-S-901
MIL-S-901
MIL-S-901
MIL-S-901
MIL-S-901
MIL-S-901
MIL-S-901
3
3
3
3
3
3
3
3
3
100 250
100 250
250
250 400
250 400
400
800 at 60 Hz
650 at 400 Hz
500 1600
500 Vac
500 Vac
500 Vac
500 Vac
500 Vac
500 Vac
500 Vac
500 Vac
500 Vac
30 kA
100 kA
150,000
100,000
75,000
NQB-A1601
AQB-A1602
NQB-A1602
ACB 1600HR
ACB 4000HR
MIL-C-17361
MIL-C-17361
MIL-C-17361
MIL-C-17587
MIL-S-901
MIL-S-901
MIL-S-901
MIL-S-901
3
3
3
3
1600
400 1600
1600
320 4000
500 Vac
500 Vac
500 Vac
500 Vac
100,000
100,000
85,000
Thermal
Magnetic
Fuses
Thermal
Magnetic
Fuses
Electronic
Electronic
None
Electronic
Electronic
None
None
None
Thermal
Magnetic
None
Electronic
None
Electronic
INTERRUPTING
VOLTAGE RATING,
TRIPPING
RATING
AMPERES
ELEMENTS PAGE
17
23
23
29
29
34
48
60
70
70
70
78
78
79
98
98
100
100
109
109
113
General
Information
Description
Operating Handle
Shown In
Off Position
Ampere Marker
Terminal
Studs
Mounting
Block
Mounting
Studs
Design Features
Plug-in
Studs
Slip Type
Connectors
Terminal
Mounting
Block
Shock-Resistant Molded
Case Housing consists of
rear base section and cover
molded of glass alkyd material.
This material, reinforced glass
lled thermosetting plastic,
has very high mechanical
strength (shock and impact
resistance), is both re and
moisture-resistant and
provides excellent dielectric
characteristics.
Anti-Shock Device Inertia
weight over center pole holds
trip bar in latched position
under shock conditions but
does not prevent thermal
or magnetic trip units from
functioning on overload and
short circuits.
Note:
Interchangeable trip units are not
available in the A101, ALB-1, A50
or A51.
Plug-in Connectors
All Navy circuit breakers are
designed for optional molded
plug-in bases in a variety of
styles. Smaller breakers
(ALB-1, A50 and A51) must
be used with the associated
bases. Other MCCBs can be
converted for direct cable or
plug-in mount. Plug in bases
are available in a variety of
styles depending upon the
circuit breaker type. See the
specic circuit breaker style
for available mounting bases
and outline drawings.
Note:
All A101, A50 or A51 breakers
have plug-in connectors. Front or
rear connectors determined by
mounting base selected.
ALB breakers have a clamp
terminal on the line end to
receive panelboard bus stab
projections.
Interrupting Ratings to
150 kA Navy circuit
breakers are available with
interrupting ratings up to
150 kA, many using modern
fuseless current-limiting
technology. Circuit breakers
rated 100 ampere and below
must be used with associated
current limiting fuses to
achieve high interrupting
capacity.
General
Information
Standard Features
Arc Chute
Moving Arm
Operating
Mechanism
Trip
Mechanism
Breaker
Front
Cover
Removed
Arc Chute
Removed
Corrosion-Resistant All
parts are specially treated to
resist corrosion. Fungusmoisture resistant treatments
for severe atmospheres are
available as modications.
Molded
Operating
Handle
Removed
Timeless Images
Application
Designed primarily for circuit
protection, Cutler-Hammer Navy
circuit breakers are used in lighting and power panels, switchboards, distribution centers and
load centers aboard ship. The
photograph above illustrates the
use of molded case circuit breakers and air circuit breakers in a
typical Navy switchboard.
General Ordering
Information
When ordering Cutler-Hammer
Navy circuit breakers, consult the
check list below to make sure
you have provided correct information. You should specify:
1. Quantity, Cutler-Hammer
Part Number and National
Stock Number of:
a. Complete breaker or
frame, trip unit, fuses
(where required) and/or
attachments where
available.
b. Plug-in mounting block or
front connecting cable
terminals.
c. Spare breakers or trip
units. (Usually one
required for each 10 units
or fraction thereof of
each current rating.)
d. Technical Manuals.
2. Shipment
Specify transportation
means, method of packaging and preservation, and
required shipping date.
3. Drawings
Specify quantity of outline
or master plan drawings
required.
4. Inspection
Indicate whether Government Source Inspection (GSI)
is required at factory prior to
shipment. This should
appear as a shipping note.
Marine Breaker
Applications
Eaton also manufactures a complete family of marine circuit
breakers for Navy non-combatant
ships, U.S. Coast Guard vessels,
Military Sealift Command vessels,
commercial vessels, offshore
drilling rigs, etc. These marine
breakers are different from high
shock MIL-spec breakers. They
meet any or all of various marine
specications such as ABS,
USCG-CFR46, IEEE45, UL 489
Supplements SA and SB,
UL 1066 Supplement SA, Lloyds
of London, DNV. Call Eaton for
more details.
Types ALB-1
and NLB-1
Interrupting Rating
10 50 ampere units:
5,000 amperes ac and 2,500
amperes dc.
5 ampere unit: 1,500 amperes
ac or dc.
High shock Navy ALB-1 circuit
breakers are designed for shipboard protection of single-phase
ac and dc circuits or three-phase
ac circuits when breakers are
connected by handle yokes for
2- and 3-pole operation.
ALB-1 AND NLB-1 CIRCUIT BREAKER PRODUCT SELECTION NET WEIGHT 8 OZ.
Note:
Clamp type stab terminal for
panelboard mounting at line end
and pressure type terminal for
front connection at load end.
Specication: MIL-C-17588
5 50 amperes, 60 or
400 cycle.
125 volts ac or dc single-pole.
TYPE
AMPERE RATING
STYLE NUMBER
ALB-1
ALB-1
ALB-1
ALB-1
ALB-1
ALB-1
ALB-1
ALB-1
ALB-1
NLB-1
5
10
15
20
25
30
35
40
50
50
454D507G01
454D507G02
454D507G03
454D507G04
454D507G05
454D507G06
454D507G07
454D507G08
454D507G09
454D507G10
5925-00-204-7494
5925-00-204-7488
5925-01-244-1756
5925-00-501-5051
5925-00-549-5359
5925-00-549-5360
5925-00-549-5362
5925-00-546-3076
5925-00-549-5365
5930-00-548-7068
Mounting Bases
TYPE
Drawings Available
Master drawing 900J396;
breaker outline 314C218;
mounting bases 455D791
and 369D592.
Technical Manual
NAVSHIPS No. 362-2228. This
booklet per MIL-M-15071. When
required, order BVR-TM-378.
Note:
These breakers are non-repairable per NAVSEA letter, serial
number 9077 Ser 03/03 EI-48,
paragraph 3 Policy, sub-paragraph 2, dated 25 October 1994.
In dc or single-phase panel
applications, basic pattern is one
molded base accommodating four
single-pole breakers. (See Pages
10 12.)
STYLE
NUMBER
NATIONAL
STOCK NUMBER
NET WEIGHT,
LBS. (KG)
454D509G01
454D509G02
454D509G03
5925-01-005-4983
5925-00-177-6349
5925-01-343-9108
.25 (0.11)
.25 (0.11)
.50 (0.23)
454D509G04
454D509G05
454D509G06
5925-00-660-3562
5925-00-201-7175
5925-00-544-5980
.67 (0.3)
.67 (0.3)
1.00 (0.5)
454D509G08
5925-00-201-7176
.67 (0.3)
Individual Reproductions
When required, reproductions of
master drawings, outline drawings and certication sheets can
be ordered as follows:
ITEM
DESCRIPTION
1
2
3
4
Handle Yokes
Provide interlocking of two or
three one-pole breakers for
simultaneous operation. Individual
pole tripping is obtained without
normal trip indicating (center)
position.
NUMBER
OF POLES
STYLE
NUMBER
NATIONAL
STOCK NUMBER
207B508H01
207B508H02
5925-00-202-0938
5930-00-862-5582
Types ALB-1
and NLB-1
Line Stab
7/16
1/2
1/2
7/8
3/32
Breaker Outline
19/32
3/8
7/32
1 Tripped
7/8
3/32
1-15/16
3/8
/
1-63/64
5/8
7/16
On
29/32
1/32 R
CL
t
29/32
15/32
29/32
1-41/64
00
Reset
3-1/2
3/16
1-5/8
Ampere Rating
3/16
3/32
Off
1/4
Mounting
Slot
1-13/32
1/4
9/32
9/16
3/32
3/16
Ampere Rating
31/32
STANDARD BREAKER
1-31/32
13/16
1/4
1/2
5/8
CL
1-5/8 1-1/4
2-5/8
1/4
5/32
1/2
5/8 1/2
2-1/4
1/32
CL of Mounting Plate
3/4
4
5/16
11/32
1/4
29/32
5/32
1/8
2-5/16
1/2
5/32
3/16
5/16
29/32
31/32
Single Base,
Front Panel Supported
(454D509G01)
CLof
Handle
Pivot
3/8
2-5/16
3/16
1/32 R
On
1-41/64
9
9
3/32
1-63/64
15/16
15/16
15/32
32
2
3/64 R
1/32
39/64
Single Base
Surface Mounted
(454D509G02)
Breaker Escutcheon
1-31/32
3-21/32
1/2
7/64
31/32
2-15/32
5/32
45/64
1/2
3/4
3/32
7/32
15/32
15/64
15/64
Critical Dimensions of
Stab and Mounting Clip
Mounting of Surface
Mounted Bases
2-21/32
21/32
7/16
5/32
1/16
3-17/64
31/32
3-1/64
19/32
1/32
11/32
SIDE VIEW
Inside of Panel or
Enclosure Front
1-29/32
2-47/64
5/16
1/2
5/64
27/64
SIDE VIEW
.195
1-15/32
.195
2-15/32
.234
.234
Types ALB-1
and NLB-1
Busbar C
1-27/32
CL
7/16
Application in dc and
Single-Phase Panels
(Two Separate Bases shown.
Basic Pattern is One Molded
Base Accommodating Four
Single-Pole Breakers)
Stab Base
Busbar A
1-27/32
454D509G04
CL
1/4
1/4
7/16
63/64
7/16
2
7/16
1/32
63/64
7/16
3/32
454D509G04
FRONT VIEW
Busbar C
63/64 1/4
CL
Busbar A
1-27/32
454D509G05
7/16
CL
CL
1
CL
1/4
1/32
1
CL
Stab
Base
Mtg.
7/16
C
454D509G04
CL
63/64
7/16
15/32
3/32
15/64
15/32
Critical
Dimensions
of Stabs and
9/16 Mtg. Clip
1/4
3-1/64
1/2
7/16
5/32
5/64 Thk.
Steel
.190-32 Thread
3/8
SIDE VIEW
Outline Dimensions
for Mounting Bases
454D509G04 or
454D509G05
13/64 Diameter
2 Holes
6-1/4
3/8
7
10
Busbar C
1-9/32
Busbar A
1-11/16
1-9/32
4
454D509G04
Stab Base
Mtg. Screws
35/64
CL
7/8
CL
CL
2
1/32
CL
454D509G04
1
1/2
.190-32 Tapped
Holes
Busbar C
Busbar B
1-9/32
1-27/32
CL
1/2
1/4
Busbar A
1-27/32
1-9/32
35/64
CL
1-15/64
63/64
CL
3-27/64
Stab Base
Mtg. Screw
1-1/2
4
CL
CL
2
4-1/2
4
1-1/2
.190-32 Tapped Holes
2
4-1/2
2
4
1/2
1/4
1/2
FRONT VIEW
11
Types ALB-1
and NLB-1
Application in dc and
Single-Phase Panels
(Two Separate Bases shown.
Basic Pattern is One Molded
Base Accommodating Four
Single-Pole Breakers)
7/16
CL
CL
7/16
63/64
4
CL
7/16
1/32
7/16
2
7/16
6
CL
63/64
63/6
3/32
/3
7/16
1
1/4
1/4
1/4
1/4
454D509G08
FRONT VIEW
Stab Base
Busbar C
1-27/32
Screw
CL
2
7/16
1/32
2
1
1
7/16
7/16
6
7/16
CL
1/4
2 454D509G08
CL
454D509G05
1/2
3/32
2
7/16
13/32
/ 2
13/64
63/64
15/32
5/32
7/16
.190-32 Thd.
1/4
9/16
3/8
SIDE VIEW
Outline Dimensions
for Mounting Bases
454D509G05 or
454D509G08
CL
Handle Pivot CL
2-7/8
1/4
1-15/32
3-5/16
1-15/32
5/64
9/16
SIDE VIEW
12
CL
Busbar C
Busbar A
1-9/32
454D509G08
CL
3-11/16
1-9/32
35/64
63/64
1-27/64
7/8
2
CL
2
1/32
CL
.190-32
Tapped Holes
2
1/2
454D509G08
1
1/4
1/2
1-9/32
1-27/32
63/64
1-27/32
1-9/32
Stab Base and
Mounting Screw
35/64
1-15/64
2-35/64
4
2-7/8
8
454D509G05
3-1/2
1/32
2-7/8
8
454D509G08
2
3-1/8
8
1
1/32
2-1/2
454D509G05
3-1/8
2-7/8
Busbar C
Busbar A
3-1/2
Busbar B
2-7/8
3-1/8
.190-32
Tapped Holes
2-1/2
3-1/8
1/4
Outline Dimensions
for Mounting Bases
454D509G05 or
454D509G08
1-31/32
63/64
3/8
1/2
1
1/2
13/64 Diameter
2 Holes
6-1/4
3/8
7
13
Types ALB-1
and NLB-1
1-27/32
CL
Busbar C
Busbar A
1-27/32
CL
454D509G06
1-31/64
15/16
CL
CL
15/16
1/4
3
15/16
CL
15/16
1/4
1-31/64
454D509G06
Outline Dimensions
for Mounting Base
454D509G06
13/64 Diameter
2 Holes
2-31/32
1-31/64
Outline Dimensions
for Mounting Bases
454D509G04, 454D509G05,
454D509G06, 454D509G08
3/8
6-1/4
3/8
CL
27/64 Diameter 2 Counter Bores 1/4 Deep
Handle Pivot
CL
Handle Pivot
CL
2-7/8
1/4
1-15/32
3-5/16
1-15/32
5/64
9/16
SIDE VIEW
14
Busbar B
Busbar C
1-27/32
1-9/32
CL
1-31/64
2-27/64
4
Busbar A
1-27/32
CL
454D509G06
35/64
4
1-47/64
4
CL
3
3
3
3
3
454D509G06
.190-32
Tapped Holes
3
3
3
1/2
1
1/4
4
1/2
FRONT VIEW
Breaker Cutout
Load End
Breaker
CL
Stab Base
1-5/8
1-15/16
31/32
CL
Breaker Cutout
1-5/8
1-21/32
1-15/16
CL
31/32
CL
2-29/32
1
Stab Base
CL
1/2
29/32
29/64
29/64
For One 3-Pole Circuit
15
Types ALB-1
and NLB-1
Characteristic Time-Current
Curve ALB-1 Breaker
Seconds
Percent Normal Rating
Characteristic
Temperature-Rating Curve
Wiring Diagram
20
10
4
2
1
40
Minutes
MIL-C-17588
4
2
1
40
20
10
4
2
Maximum
1
40
20
Minimum
10
4
2
1
0.6
0.4
0.2
1
2
3
4 5 6 7 8 910
Times Rated Current
20
30
125
120
115
110
105
100
95
90
85
80
75
70
100 90 80 70 60 50 40 30 20 10
Ambient Te
C
Line
Line
Draw-Out
Connection
Stationary
Connection
Load
Type ALB-1
T
16
Load
Type
T
NLB-1
50
70 90100
200 1300
500
Types AQB-A50,
NQB-A50
Interrupting Rating
Drawings Available
1244C62 Master drawing for
breaker and mounting bases.
STYLE NUMBER
10
15
20
25
30
35
40
50
1244C52G01
1244C52G02
1244C52G03
1244C52G04
1244C52G05
1244C52G06
1244C52G07
1244C52G08
5925-01-188-4302
5925-01-188-6298
5925-00-799-5669
5925-00-797-9693
5925-01-225-1962
5925-01-251-3455
5925-01-234-7187
5925-01-331-8636
10H
15H
20H
25H
30H
35H
40H
50H
Non-Automatic
1244C52G09
1244C52G10
1244C52G11
1244C52G12
1244C52G13
1244C52G14
1244C52G15
1244C52G16
1244C52G25
5925-01-242-7456
5925-01-240-9180
5925-01-246-0471
5925-01-234-6910
5925-00-199-9518
5925-01-234-6911
5925-00-817-7860
5925-01-234-6912
5925-00-948-3296
60 Cycles
10 50 amperes, 60 and
400 cycle.
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
400 Cycles
3-pole.
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
AQB-A50
NQB-A50
Specication: MIL-C-17361
Note:
These breakers are non-repairable per NAVSEA letter, serial
number 9077 Ser 03/03 EI-48,
paragraph 3 Policy, sub-paragraph 2, dated 25 October 1994.
17
Types AQB-A50,
NQB-A50
NET WEIGHT
STYLE
NUMBER
TYPE
1244C44G01
1244C44G02
1244C44G03
1244C45G01
5080A95G01
752B729H01
1244C59H01
DESCRIPTION
NET
WEIGHT,
LBS. (KG)
AQB-A50 Breaker
NQB-A50 Breaker
Single Mounting Base
Double Mounting Base
Handle Lock
2.3 (1.0)
1.9 (0.9)
0.7 (0.3)
1.5 (0.7)
.03 (0.01)
NATIONAL
STOCK NUMBER
5925-00-270-4004
5925-00-270-4005
5925-00-270-4006
5925-01-246-0569
5340-01-091-9432
HANDLE LOCK
18
2-15/16
13/64
3-1/2
3-3/8
9/16
CL
of
Clip
1-3/4
1-13/16
ON
ON
OFF
OFF
2-5/8
5/8
Off
Reset
CL of Clip
Load End
3/32
Dia.
Hole
59/64
1-1/2
2
3-11/32
4-1/8
FRONT VIEW
SIDE VIEW
55/64
17/32
2-3/32
On
Trip
2-5/16
4-1/8
7/8
1-5/8
1-3/4
1/2
1/4 R
2-1/16
1/4
1/4
3-1/8
1-15/32
1-15/32
2-13/16
1-1/8
Load Side
Wiring Diagram
Line
Load
Type NQB-A50
1-1/8
1-1/8
3-3/8
1-1/8
1-1/8
Line
Load
Type AQB-A50
19
Types AQB-A50,
NQB-A50
2-15/16
1-15/32
3/8
Line
1-7/16
CL
29/64
1/2
1-17/32
2-5/8
CL
10-32
Thds.
1/2
Cir.
Bkr.
1/4
Mtg
Holes (2)
5-7/8
1-13/16
Load
31/64
1-1/8
1-1/8
3-11/32
Wire Connection
2-15/16
1-15/32
1-1/16
3/8
Line
CL
29/64
1-9/64
1/2
1-17/32
2-5/8
CL
10-32
Thds.
1/2
r.
Bkr.
1/4
5-3/32
Mtg
1-21/64
Load
1-1/8
1-1/8
3-11/32
Wire Connection
2-15/16
1-15/32
1-1/16
3/8
Line 1-9/64
CL
29/64
1-17/32
1/2
2-5/8
CL
r.
Bkr.
1/2
10-32
Thds.
1/4
Mtg
Holes 1-13/16
(2)
5-37/64
Load
1-1/8
1-1/8
3-11/32
20
Wire Connection
Outline Dimensions
Double Base Assembly
Panelboard Dimensions
in Inches
CL
of Circuit
Breakers
1
1/2
Line
Load
29/64
CL
of Base
1-1/8
2-15/16
3-11/32
1-1/8
1-15/32
1/4
Load
Mounting
Holes (4)
1/4
1/2
Line
1-29/32
1-9/16
1/2
1-29/32
11-3/16
1-13/16
2-5/16
2-5/8
13/32
1-13/16
2-5/8
#10-32
Thds.
1-17/32
1-17/32
3/8
Wire
Connectors
13/32
1/2
#10-32
Thread
#10-32
Thread
21
100,000
30,000
40,000
50,000
20,000
10,000
3,000
4,000
5,000
2,000
1,000
300
400
500
5,000
5,000
3,000
3,000
2,000
2,000
1,000
1,000
1 Minute
500
500
300
300
200
200
100
100
50
50
30
30
20
20
Maximum T
Trip Time
10
10
.5
.5
.3
.3
.2
Minimum T
Trip Time
.1
.1
.05
.05
.03
.03
.02
.02
0.01
0.01
100,000
30,000
40,000
50,000
20,000
10,000
3,000
4,000
5,000
2,000
.001
1,000
.001
300
400
500
.002
200
.003
.002
100
.005
50
.005
.003
1 Minute
Time in Seconds
200
10,000
2 Hours
1 Hour
10,000
.2
22
2 Hours
1 Hour
50
Characteristic Time-Current
Curve Navy Type AQB-A50
Circuit Breaker
100
Types AQB-A50,
NQB-A50
Types AQB-A51,
NQB-A51
Interrupting Rating
TYPE
Specication: MIL-C-17361
10 50 amperes, 60 cycles.
3-pole.
STYLE NUMBER
10
15
20
25
30
35
40
50
Non-Automatic
1244C56G01
1244C56G02
1244C56G03
1244C56G04
1244C56G05
1244C56G06
1244C56G07
1244C56G08
1244C56G25
5925-01-511-0205
5925-01-458-3739
5925-01-461-1628
5925-01-511-0208
5925-01-511-1210
5925-01-511-0214
5925-01-511-0217
5925-01-511-0220
60 Cycles
AQB-A51
AQB-A51
AQB-A51
AQB-A51
AQB-A51
AQB-A51
AQB-A51
AQB-A51
NQB-A51
Note:
These breakers are non-repairable per NAVSEA letter, serial
number 9077 Ser 03/03 EI-48,
paragraph 3 Policy, sub-paragraph 2, dated 25 October 1994.
23
Types AQB-A51,
NQB-A51
NET WEIGHT
STYLE
NUMBER
TYPE
1244C44G01
1244C44G02
1244C44G03
1244C45G01
5080A95G01
752B729H01
1244C59H01
DESCRIPTION
NET
WEIGHT,
LBS. (KG)
AQB-A51 Breaker
NQB-A51 Breaker
Single Mounting Base
Double Mounting Base
Handle Lock
2.4 (1.1)
1.9 (0.9)
0.7 (0.3)
1.5 (0.7)
.03 (0.01)
NATIONAL
STOCK NUMBER
5925-00-270-4004
5925-00-270-4005
5925-00-270-4006
5925-01-246-0569
5340-01-091-9432
HANDLE LOCK
24
2-15/16
13/64
3-1/2
3-3/8
9/16
CL
of
Clip
1-3/4
1-13/16
ON
ON
OFF
OFF
2-5/8
5/8
Off
Reset
CL of Clip
Load End
3/32
Dia.
Hole
59/64
1-1/2
2
3-11/32
4-1/8
FRONT VIEW
SIDE VIEW
55/64
17/32
2-3/32
On
Trip
2-5/16
4-1/8
7/8
1-5/8
1-3/4
1/2
1/4 R
2-1/16
1/4
1/4
3-1/8
1-15/32
1-15/32
2-13/16
1-1/8
Load Side
Wiring Diagram
Line
Load
Type NQB-A51
1-1/8
1-1/8
3-3/8
1-1/8
1-1/8
Line
Load
Type AQB-A51
25
Types AQB-A51,
NQB-A51
2-15/16
1-15/32
3/8
Line
1-7/16
CL
29/64
1/2
1-17/32
2-5/8
CL
10-32
Thds.
1/2
Cir.
Bkr.
1/4
Mtg
Holes (2)
5-7/8
1-13/16
Load
31/64
1-1/8
1-1/8
3-11/32
Wire Connection
2-15/16
1-15/32
1-1/16
3/8
Line
CL
29/64
1-9/64
1/2
1-17/32
2-5/8
CL
10-32
Thds.
1/2
r.
Bkr.
1/4
5-3/32
Mtg
1-21/64
Load
1-1/8
1-1/8
3-11/32
Wire Connection
2-15/16
1-15/32
1-1/16
3/8
Line 1-9/64
CL
29/64
1-17/32
1/2
2-5/8
CL
r.
Bkr.
1/2
10-32
Thds.
1/4
Mtg
Holes 1-13/16
(2)
5-37/64
Load
1-1/8
1-1/8
3-11/32
26
Wire Connection
CL
of Circuit
Breakers
1
1/2
Line
Load
29/64
CL
of Base
1-1/8
2-15/16
3-11/32
1-1/8
1-15/32
1/4
Load
Mounting
Holes (4)
1/4
1/2
Line
1-29/32
1-9/16
1/2
1-29/32
11-3/16
1-13/16
2-5/16
2-5/8
13/32
1-13/16
2-5/8
#10-32
Thds.
1-17/32
1-17/32
3/8
Wire
Connectors
13/32
1/2
#10-32
Thread
#10-32
Thread
27
100,000
30,000
40,000
50,000
20,000
10,000
3,000
4,000
5,000
2,000
1,000
300
400
500
200
10,000
5,000
5,000
3,000
3,000
2,000
2,000
1,000
1,000
2 Hours
1 Hour
10,000
500
500
300
300
Line
Line
Time in Seconds
Ground Fault
Line Fault
200
100
100
50
50
30
30
20
20
Maximum T
Trip Time
10
10
.5
.5
.3
.3
.2
.2
Minimum T
Trip
p Time
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
100,000
30,000
40,000
50,000
20,000
10,000
3,000
4,000
5,000
2,000
.001
1,000
.001
300
400
500
.002
200
.003
.002
100
.005
50
.005
.003
1 Minute
1 Minute
200
28
2 Hours
1 Hour
50
Characteristic Time-Current
Curve Navy Type AQB-A51
Circuit Breaker
100
Types AQB-A51,
NQB-A51
Types AQB-A100,
NQB-A100
Interrupting Rating
AQB-A100
Specication: MIL-C-17361
15 100 amperes.
2- or 3-pole.
CONTINUOUS
AMPERE
RATING
15-BE
25-BE
50-BE
75-BE
100-BE
90
150
300
450
600
105
175
350
525
700
1764 676
1764 677
1764 678
1764 679
1764 680
5925-01-221-1765
1764 638
1764 638
1764 638
1764 638
1764 638
1764 640
1764 641
1764 642
1764 643
1764 644
5925-00-248-1104
5925-00-248-1108
90
105
180
210
150
175
300
350
600
700
900
1050
1200
1400
Non-Automatic
1764 681
1764 682
1764 683
1764 684
1764 685
1764 686
1764 687
1764 688
5925-00-396-2283
5925-00-699-1111
1764 638
1764 638
1764 638
1764 638
1764 638
1764 638
1764 638
1764 638
1764 645
1764 646
1764 647
1764 648
1764 649
1764 650
1764 651
1764 652
5925-00-629-0975
5925-00-628-0695
5925-00-248-1078
5925-00-248-1082
5925-00-772-0646
90
150
300
450
600
1764 689
1764 690
1764 691
1764 692
1764 693
5925-00-399-8120
5925-00-399-8127
1764 639
1764 639
1764 639
1764 639
1764 639
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
1764 653
1764 654
1764 655
1764 656
1764 657
5925-00-608-0972
5925-00-553-9745
5925-00-383-3814
5925-00-248-1371
5925-00-608-0973
15-BF
15-B
25-BF
25-B
50-B
75-B
100-B
100
3-Pole, 250 Volts dc
15-BE
25-BE
50-BE
75-BE
100-BE
105
175
350
525
700
Note:
Breakers with ratings other than
those given on this page are considered special and full description data must be provided.
29
Types AQB-A100,
NQB-A100
CONTINUOUS
AMPERE
RATING
15-BF
15-B
25-BF
25-B
50-BF
50-B
75-BF
75-B
100-BF
100-B
100
90
105
180
210
150
175
300
350
300
350
600
700
450
525
900
1050
600
700
1200
1400
Non-Automatic
1764 694
1764 695
1764 696
1764 697
1764 698
1764 699
1764 700
1764 701
1764 702
1764 703
1764 704
5925-00-113-5066
5925-00-658-9609
5925-00-265-9474
5925-00-988-5474
5925-00-396-2339
5925-00-396-2345
5925-01-265-0190
5925-00-450-6275
5930-01-300-1107
1764 639
1764 639
1764 639
1764 639
1764 639
1764 639
1764 639
1764 639
1764 639
1764 639
1764 639
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
5925-00-258-2945
Note:
Breakers with ratings other than
those given on this page are considered special and full description data must be provided.
30
1764 658
1764 659
1764 660
1764 661
1764 662
1764 663
1764 664
1764 665
1764 666
1764 667
1764 668
5925-00-502-6719
5925-00-248-1453
5925-00-215-3758
5925-00-248-1449
5925-00-248-1442
5925-00-248-1443
5925-00-248-1436
5925-00-248-1437
5925-00-248-1429
5925-00-248-1431
5925-00-699-1111
Additions
Handle Lock
CABLE
RANGE
DESCRIPTION
STYLE
NUMBER
NATIONAL
STOCK NUMBER
N3-N14
N23-N40
N50-N75
14,340
38,910
75,780
1763 660
1763 661
1763 662
Switchboard Mounting
Complete breakers and frames
include mounting hardware.
Female slip connectors are
mounted in the breaker base for
Fungus-Moisture Resistant
Treatments
(JAN-T-152, JAN-C-173 or
MIL-V-173) if specied, contact
Eaton. External parts are coated;
trip units are not treated.
NUMBER
OF POLES
DESCRIPTION
STYLE
NUMBER
NATIONAL
STOCK NUMBER
2
3
2 or 3
1764 675
1764 674
1764 240
1631 442
5940-00-643-7194
5940-00-501-9120
Individual Reproductions
When required, reproductions of
master drawings, outline drawings and certication sheets can
be ordered as follows:
ITEM
DESCRIPTION
2
MOUNTING BLOCK
ASSEMBLY
NET WEIGHT,
LBS. (KG)
2-Pole
2.75 (1.2)
3-Pole
3.25 (1.5)
FRAME
NET WEIGHT,
LBS. (KG)
2-Pole AQB
2-Pole NQB
3-Pole AQB
3-Pole NQB
7.38 (3.4)
7.38 (3.4)
7.88 (3.6)
7.88 (3.6)
COMPLETE
BREAKER
NET WEIGHT,
LBS. (KG)
TRIP
UNIT
NET WEIGHT,
LBS. (KG)
2-Pole AQB
2-Pole NQB
3-Pole AQB
3-Pole NQB
10.00 (4.5)
8.75 (4.0)
10.75 (4.9)
9.50 (4.3)
2-Pole AQB
2-Pole NQB
3-Pole AQB
3-Pole NQB
2.63 (1.2)
1.38 (0.6)
2.88 (1.3)
1.63 (0.7)
3
4
Drawings Available
Master drawing 1-JF-630; rear
connected breaker outline,
drilling and wiring diagram
20-B-2881; front connected
breaker outline, drilling and
wiring diagram 30-B-3837.
31
Types AQB-A100,
NQB-A100
Outline Dimensions
AQB-A100 and NQB-A100
Breakers Dimensions
in Inches
5/16 18 Thd.
3/8 16 Thd.
13/16
7/16
Line End
15-1/2
-7/8
1-29/32
2-27/32 R
1/8
Min.
7-1/2
Off
f
1-5/8 1-5/8
1/4 20 Thd.
1/2 D.ctbr
ct
Load End
CL Studs
15/16
9/16 Rad.
1-1/8 Min. Slot
Sl
Load End
Min.
5
3
2-1/4
1-1/2
Bkr. Frame Outline
1/2 Dia. Megger Test
Holes Omit Middle
Hole for 2-Pole
1-5/8
2-3/16
1-3/16
3//
4-9/16
Mounting Bolts
and Washers
(Furnished with
Terminal Blocks)
(4) 1/4 20 x
1-7/8 L.G.
Slotted Hex
Heads Bolts
1-3/8
1/8
7/16 Dia.
4 Holes
10
-1/4
3-9/16
15/16
4-3/4
5-1/2
/
4-11/32
15/16
4-1/16
8-3/4
7/8 7/8
Line End
1/8 R
1-1/4
4-3/16
1-25/32
Drilling Plan
2-1/2
3/16
1-7/8
Terminal Blocks
are not Supplied
with Breakers but
must be Ordered
Separately
(2 Requried Per
Breakers) Refer
to Dwg. 1-A-4457
32
5/8
7
15/16
7
7/16
6 10
5/8
1-5/8
5/8
/
Visible Ampere Rating
Interchangeable
Trip Unit
1-5/8 2-21/64
4-21/32
For 2-Pole
Breaker Center
Pole Current
Carrying Parts
are Omitted
AQB-A100 Breakers
5
4
3
2
Hours
Characteristic Time-Current
Curves
Instantaneous
Trip at 1200% to
1400% Rating
Instantaneous
Trip at 600% to
g
1
40
30
20
Operating Characteristics
Seconds
Time
Minutes
90
80
70
60
10
50
5
4
3
2
Maximum
40
30
20
1
40
30
20
15
10
10
Minimum
5
4
3
2
3000
2000
1500
800
1000
600
400
300
200
100
4
3
2
50 1
40
30
20
30
15
1
40
20
10
4 5
3
2
3000
1500
2000
800
1000
600
400
300
200
100
1
0
Specication MIL-C-17361
10
4 5
3
2
Time, Minutes
Operating Characteristics
Seconds
Hours
33
Types AQB-A101,
NQB-A101
Interrupting Rating
Specication: MIL-C-17361
15 100 amperes.
3-pole.
TYPE
AQB-A101
AQB-A101
AQB-A101
AQB-A101
AQB-A101
AQB-A101
NQB-A101
Generator Breakers
(Designated with a G) are also
available in other congurations.
Consult Eaton.
HI
LO
THERMAL
MAGNETIC
NATIONAL
MAGNETIC
STYLE NUMBER STOCK NUMBER ONLY STYLE
NATIONAL
STOCK NUMBER
15
25
50
75
100
100G
100
180 210
300 350
600 700
900 1050
1200 1400
1200 1400
Non-Automatic
75 105
125 175
250 350
375 525
500 700
500 700
458D509G11
458D509G12
458D509G13
458D509G14
458D509G15
458D509G16
458D509G20
5925-00-876-9216
5925-00-876-9217
5925-00-876-9218
5925-01-136-5633
5925-00-876-9220
5925-00-619-0412
5930-00-969-2477
458D511G11
458D511G12
458D511G13
458D511G14
458D511G15
5925-00-397-8258
5925-00-546-3258
5925-01-022-5086
15H
25H
50H
75H
100H
100GH
180 210
300 350
600 700
900 1050
1200 1400
1200 1400
75 105
125 175
250 350
375 525
500 700
500 700
458D510G11
458D510G12
458D510G13
458D510G14
458D510G15
458D510G16
5925-00-867-7328
5925-00-867-7329
5925-00-986-7313
5925-00-986-7314
5925-00-972-3000
5925-01-200-7813
458D512G11
458D512G12
458D512G13
458D512G14
458D512G15
TRIP UNIT
AMPERE
RATING
400 Cycle
AQB-A101
AQB-A101
AQB-A101
AQB-A101
AQB-A101
AQB-A101
Note:
These breakers are non-repairable
per NAVSEA letter, serial number
9077 Ser 03/03 EI-48, paragraph
3 Policy, sub-paragraph 2, dated
25 October 1994.
34
AQB-A101 AND NQB-A101 CIRCUIT BREAKER PRODUCT SELECTION BREAKERS WITH ATTACHMENTS
TYPE
HIGH
LOW
STYLE
NUMBER
ATTACHMENT
NATIONAL
STOCK NUMBER
15
25
50
75
100
100
180 210
300 350
600 700
900 1050
1200 1400
Non-Automatic
75 105
125 175
250 350
375 525
500 700
5682D24G13
5682D24G14
5682D24G15
5682D24G16
5682D24G17
5682D24G19
5925-00-813-2470
5925-01-028-6500
5925-01-241-3396
5925-00-167-7513
5925-00-938-3446
5930-01-197-4752
15H
25H
50H
75H
100H
180 210
300 350
600 700
900 1050
1200 1400
75 105
125 175
250 350
375 525
500 700
5682D24G36
5682D24G37
5682D24G38
5682D24G39
5682D24G40
5925-01-359-1968
5925-01-339-4840
5925-01-339-4839
5925-01-359-1969
5925-01-293-9163
TRIP UNIT
RATING
60 Hz
AQB-A101
AQB-A101
AQB-A101
AQB-A101
AQB-A101
NQB-A101
400 Hz
AQB-A101
AQB-A101
AQB-A101
AQB-A101
AQB-A101
Note:
These breakers are non-repairable
per NAVSEA letter, serial number
9077 Ser 03/03 EI-48, paragraph
3 Policy, sub-paragraph 2, dated
25 October 1994.
35
Types AQB-A101,
NQB-A101
SWITCHBOARD/PANELBOARD MOUNTING
TYPE
STYLE
NUMBER
NET WEIGHT,
LBS. (KG)
NATIONAL
STOCK NUMBER
315C364G03
315C364G02
2.75 (1.2)
3.00 (1.4)
5925-00-832-6143
5925-00-521-2526
315C364G07
458D569G02
458D569G03
3.00 (1.4)
3.50 (1.6)
4.00 (1.8)
5925-00-728-5217
5925-01-221-8617
NET WEIGHT
DESCRIPTION
AQB-A101 Breaker
NQB-A101 Breaker
AQB-F101A Fuse Unit
AQB-F101B Fuse Unit
Fuse Unit
Mounting Base
NET WEIGHT,
LBS. (KG)
6.00 (2.7)
5.75 (2.6)
2.00 (0.9)
2.00 (0.9)
3.00 (1.4)
SHIPPED AS:
FUSE UNIT
STYLE
NUMBER
AMPERE
RATING
CONNECTION
TYPE
STYLE NUMBER
NATIONAL
STOCK NUMBER STYLE NUMBER
372B155G01
372B155G02
372B155G03
372B155G04
15 25
15 25
50, 75 and 100
50, 75 and 100
Front
Rear
Front
Rear
AQB-F101A
AQB-F101A
AQB-F101B
AQB-F101B
504C010H01
504C010H01
504C010H02
504C010H02
5920-00-215-4727
5920-00-215-4727
5920-01-281-4158
5920-01-281-4158
36
655D258G01
655D258G05
655D258G03
655D258G06
NATIONAL
STOCK NUMBER
5925-00-998-1965
5920-01-216-6127
5920-01-138-0548
5920-01-216-6128
Additions
Auxiliary Switch
Handle Lock
Drawings Available
Shunt Trip
NSN 5930-00-669-7524.
Note:
One auxiliary switch normally
supplied with shunt trip attachments for cut-off switch and
additional switches cannot be
supplied on breakers with
shunt trips.
Handle Boot
When specied, order style
number 752B729H01.
Rear Stud
Complete with 4 nuts, style
number 208B801G01.
Fungus-Moisture Resistant
Treatment
(JAN-T-152, JAN-C-173 or
MIL-V-173). If specied, contact
Eaton. External parts are coated.
Technical Manual
Individual Reproductions
When required, reproduction of
master drawings, outline drawings and certication sheets can
be ordered as follows:
ITEM
DESCRIPTION
2
3
4
37
Types AQB-A101,
NQB-A101, AQB-A103,
NQB-A103
Outline Dimensions
AQB-A101 and AQB-A103
Breakers Dimensions
in Inches
Copper Extensions
for Megger Readings.
Copper Extensions Can
Be Broken Off With
(Recommended)
)
6-1/4
4-1/8
2-1/16
11/16
/
1-3/8
1-3/8
1-1/32
2-1/2
1/16 Thick
Insulation
5-1/4
3/16
3/8
3/16
1-3/8
1/64
1-7/16
7/32
15/32
5/32
3/8-16 Thd.
1-15/16
1/64
Line
e End
3/4 Dia.
1/4
5-9/16
6-1/2
2-5/8
1/32
19/32
3-15/16
3-13/16
1/4
1/4
Dia.
19/32
1/4
1/16
1/4
Load
d End
7/16
1-3/32
9/32 Diameter
(4 Mtg. Holes)
NamePlate
2-3/16
1/8
Style 315C364602
1-11/16
1-1/32
4-1/8
2-1/16
1-11/32
11/16
1-11/32
11/32
Single Breaker
(Rear Mounted)
On
Off
Style 1614485
(Not Supplied With Circuit Breaker)
7/32
3-11/16
3/16
1/16 R
1/2
1-3/8
13/16
1-7/16
4-1/16
3-7/8
3/16
11/16
1-3/8
1/4
4-7/8
7/16
2-5/16
7/32
WARNING
1-23/64
1-9/32
1/16 R
On
3/8 R
2-51/64
ON
2-7/8
3-5/16
6-1/2
11/16
17-1/2
2-11/16
Tripped
8-1/2
9/3
11/32
R
Pivot
Line
11-1/2
4-1/2 Off 5/16 Thk.
OFF
F
Reset
1-33/64
7/32
3-15/16
3/32
5 T
2 Inserts (Insert
Remove Breaker)
1-9/32
Mtg. Bkr.
1-3/32
Drilling Plan
1-1/4
38
1-11/32
1-11/32
r. Mtg. Base
.098 Diameter Hole for Handle Locking Device or Warning Tag
1-5/8
13/16
Breaker
Outline
3/16
5/16
Diameter
Megger
4-1/8 Test
Holes
Outline Dimensions
AQB-A101 and AQB-A103
Breaker Mounting Bases
Dimensions in Inches
4-1/8
1-3/8
11/16
3/8
3/16
1-3/8
1-3/8
1-3/8
5-1/4
3/16
1-3/8
11/32
6-1/32
1/2
3-55/64
Load
7
1/4
1-1/32
6-1/4
1
2
Pivot
Line
1/4-20 Tap
(2 Holes)
1/2
9/16
4-1/8
3-1/2
14
1-3/4
1/4
Maximum
Width and
3-1/2
Maximum
Thick Copper
Bus
4-1/8
5-19/32
12-1/16
3-1/2
13-5/16
1/4-20 Tap
(2 Holes)
Line
Complete
Hardware
3-1/2
6-1/32
Pivot
Line
4-1/8
Except for
Copper
Bus Bars
Hardware
upplied
Copper
Bus Bars
1/4
Insulation Sheet
(Not Supplied)
Load
1/4-20 Tap
(2 Holes)
14
1/4 Dia.
1/4 Dia.
Front Cover
Mounting Bolt
Hole (6)
Nameplate
2-1/16
5/16 Dia.
Megger
Test Holes
17/32 C
1-5/8
13/16
3/16
.190-32 X 3-3/4
Round Head Screw
2-1/2
Mounting Plate
Cable Entrance
1-1/32
Base
Outline
Breaker
Outline
1-1/4 2-15/16
13
14
1-1/4
2-15/16
1-3/8
6-1/2
1-3/8
3/16
2-1/16
4-1/8
39
Types AQB-A101,
NQB-A101, AQB-A103,
NQB-A103
4-1/8
6-1/4
2-1/16
5-1/4
Front Panel
1-15/16
15/32
AQB-A101
6-1/2
2-5/8
6-11/16
9-1/16
10
Rejection
Screw
Insulation Sheet
(Not Supplied)
1/16 R
1-3/8
2-1/2
AQB-F101A
or
AQB-F101B
.190-32 Inserts
(2) for Fuse
Puller Screws
2-3/4
1-5/8
3/8-16 Thd.
1/2
13/16
3-1/4
2-1/2
1-11/16
6-1/16
1-11/16
Terminal for Minimum Navy Cable Thfa-3-2828 C.M.
T
and Maximum Navy Thfa-100-100,000 C.M.
3-3/8
1-7/8
3-3/4
Drilling Plan
9-1/16
15/32
2-3/4
1-3/8
1-11/16
Base Outline
2-5/8
1-15/16
6-9/16
2-3/4
11/32
2-3/4
CL of Breaker
1-5/8
2
13/16
1-1/4
40
2-15/16
Breaker Outline
1-3/8
Outline Dimensions
AQB-A101 and AQB-A103
Breakers, Double Base with
Fuse Units Dimensions in
Inches
1/16 R
3-3/4
1-7/8
3-1/4
1-5/8
6-1/4
6-1/16
1-11/16
AQB-F101A or
AQB-F101B
2-1/2
23/32 Max.
Across
Corners
13-5/16
13
19-1/6
AQB-A101
15-7/8
20
1-3/4
Insulation
Sheet
(Not
Supplied)
1-3/4
6-21/32
6-11/16
13/16
7-15/16
AQB-A101
10 6-1/2
9-17/32
.375-16
Thd.
2-1/2
AQB-F101A or
AQB-F101B
1-3/8
2-3/4
1-11/16
3-3/8
2-1/16
4-1/8
Drilling Plan
19-1/6
9-17/32
15-7/8
7-15/16
Base Outline
2-3/4
1-3/4
1-3/8
3-3/8
11/16
1-3/4
1-3/8
1-11/16
.250-20 Tap (10 Holes)
for Mounting Bases
6-21/32
13-5/6
11/32
2-3/4
6-9/16
6-9/16
2-3/4
11/32
1-3/8
1-5/8
4
2-3/4
2
13/16
2-15/16
1-1/4
2-15/16
Breaker Outline
41
Types AQB-A101,
NQB-A101, AQB-A103,
NQB-A103
Instantaneous
Trip at 1200% to
1400% Rating
Instantaneous
Trip at 500% to
g
1
40
30
20
AQB-A101 Breakers
Seconds
Time
Minutes
Operating Characteristics
Trip Unit Rating 15 100
Amperes 50C Ambient
Cold Start, 60 Cycle, ac or dc,
Thermal-Magnetic.
5
4
3
2
Hours
Characteristic Time-Current
Curves
90
80
70
60
10
50
5
4
3
2
40
30
20
1
40
30
20
15
10
10
0
0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
Factor
5
4
3
2
3000
2000
1500
800
1000
600
400
300
200
100
Operating Characteristics
Trip Unit Rating 15 100
Amperes 50C Ambient
Cold Start 400 Cycle ac, ThermalMagnetic Trip Unit Rating.
Time, Minutes
Hours
4
3
2
50 1
40
30
20
Specication MIL-C-17361
10
4 5
3
2
30
1
40
Seconds
20
10
4 5
3
2
3000
1500
2000
800
1000
600
400
300
200
100
1
0
42
400 Hz
Instantaneous
1
40
30
20
10
5
4
3
2
5
4
3
2
3000
1500
2000
600
3000
1500
2000
600
300
400
1
200
5
4
3
2
100
5
4
3
2
300
1
40
30
20
15
10
400
1
40
30
20
15
10
Time
10
Trip at 500% to
700% Rating
200
Trip at 850% to
1150% Rating
1400% Rating
100
2300% Rating
Time
5
4
3
2
800
1000
60 Hz
Instantaneous
1
40
30
20
Generator Breakers
Hours
5
4
3
2
800
1000
Hours
Characteristic Time-Current
Curves
43
Types AQB-A103RMS,
NQB-A103
Interrupting Rating
Specications: MIL-C-17361
10 100 amperes.
60/400 Hz (Universal).
3-pole.
AQB-A103RMS Characteristics
Net Weight
Drawings Available
1376D98 Master
Technical Manual
1376D60 Outline
1244C68H01
AMPERES
STYLE
NUMBER
10 25
40 100
10 25
40 100
100
1376D96G01
1376D96G02
1376D96G07 with 115 Vac ST
1376D96G08 with 115 Vac ST
1376D96G51 NQB-A103
44
5925-01-455-8639
5925-01-455-8635
5925-01-482-1112
5925-01-482-1134
5925-01-456-0004
Types AQB-A103,
NQB-A103
60
70
40
50
30
20
7
8
9
10
1.44x
.5
.7
.8
.9
1
.6
2 HOUR S
1.76x
6000
1.60x
3000
Available Settings
2000
Frame Rating
(I n)
25
10
12.5
15
18.75
20
25
20 - 140
25 - 175
30 - 210
37.5 - 262.5
40 - 280
50 - 350
100
40
50
60
75
80
100
80
100
120
150
160
200
1000
900
800
700
600
Long
Time
Delay
500
400
300
Long
Time
Delay
1 MINUTE
200
100
90
80
70
Breaker Type
Voltage Rating
Short Delay
Setting x (CCS)
(2x - 14x)
- 560
- 700
- 840
- 1050
- 1120
- 1400
500 Vac
60
AQB-A103 RMS
(Without Fuse)
50
40
Frequency
See Note 6
60 Hz
Interrupting Current
400 Hz
15 kA
7.5 kA
30
Notes:
20
1 . Curve accuracy applies from -20 Cto +55 C ambient. For possible
10
9
8
7
6
3. AQB-A103 RMS breakers are suitable for functional field testing with test kit
catalog number STK2.
4. There is memory effect that can act to shorten the long delay. The memory
effect comes into play if a current above the Long Delay Pick Up value exists
for a time and then is cleared by the tripping of a downstream device or the
circuit breaker itself. A subsequent overload will cause the circuit breaker to
trip in shorter time than normal. The amount of time delay reduction is
inverse to the amount of time that has elapsed since the previous overload.
Approximately five minutes is required between overloads to completely reset
memory.
Short Delay
Pickup - 2X
4
3
2X
3X
5X
7X
Short Delay
Pickup - 14X
14X
1
.9
.8
.7
10%.
9X
10X
.6
10%.
10%.
.5
.5
.4
.4
13X
300ms
.3
.2
200ms
.2
.1
.09
.08
.07
100ms
.10
.09
.08
.07
Instantaneous
Setting
Determines
End of Curve
.06
.05
.04
.06
.05
.04
7000
8000
9000
10000
6000
4000
5000
3000
2000
500
600
700
800
900
1000
300
400
60
70
80
90
100
50
40
30
20
7
8
9
10
.01
.01
.02
.02
.7
.8
.9
1
.03
.6
.03
.3
.5
1 HOUR
5000
4000
200
Characteristic Time-Current
Curve Navy Type AQB-A103
RMS Circuit Breaker
45
Types AQB-A103,
NQB-A103
1.44x
1 HOUR
30
20
7
8
9
10
1.76x
6000
1.60x
5000
.5
.6
.7
.8
.9
1
2 HOUR S
Characteristic Time-Current
Curve Navy Type AQB-A103
RMS Circuit Breaker
4000
Long
Time
Delay
3000
Available Settings
2000
Frame Rating
(I n)
25
10
12.5
15
18.75
20
25
20 - 140
25 - 175
30 - 210
37.5 - 262.5
40 - 280
50 - 350
100
40
50
60
75
80
100
80
100
120
150
160
200
1000
900
800
700
600
Short Delay
Setting x (CCS)
(2x - 14x)
500
Long Time
Delay
Minimum
Clearing
Time
400
300
200
1 MINUTE
Breaker Type
500 Vac
Frequency
60 Hz
Interrupting Current
15 kA
400 Hz
7.5 kA
Notes:
60
50
1 . Curve accuracy applies from -20 Cto +55 C ambient. For possible continuous ampere derating
See Note 6
40
30
3. AQB-A103 RMS breakers are suitable for functional field testing with test kit catalog number STK2.
20
4. There is memory effect that can act to shorten the Long Delay. The memory effect comes into play
if a current above the Long Delay Pick Up value exists for a time and then is cleared by the tripping
of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit
breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the
amount of time that has elapsed since the previous overload. Approximately five minutes is
required between overloads to completely reset memory.
@ 4X, SD Band
Max = 16 seconds
#3 = 8 seconds
#2 = 4 seconds
#1 = 2 seconds
10
9
8
7
6
10%.
5
SD
At 2.25x i
s < 1 hour.
At 1.5x i s > 1 hour.
Ba
Voltage Rating
AQB-A103 RMS
(Without Fuse)
100
90
80
70
- 560
- 700
- 840
- 1050
- 1120
- 1400
nd
(M
ax
SD
im
)
nd
um
Ba
(3)
9. Short Delay I 2Tresponse reverts to a flat response at current levels greater than 16x CCS.
SD
10%.
SD
d (2
Ban
Instantaneous Setting
Determines End of Curve
Ba
nd
1
.9
.8
(1)
1
.9
.8
.7
3X
.7
.6
See
Note 9
.5
.6
.5
.4
.4
SD Band (Maximum)
5X
.3
.2
.2
SD Band (3)
Short Delay
Pick Up
2X
.1
.09
.08
.07
.06
SD Band (2)
.10
.09
.08
.07
SD Band (1)
.06
.05
.05
.04
.04
.03
.03
SD Band
(Minimum)
.02
Short Delay
Pick Up
14X
16X
.02
.01
46
7000
8000
9000
10000
5000
6000
4000
2000
3000
600
500
700
800
900
1000
300
400
200
60
50
70
80
90
100
30
40
20
7
8
9
10
.5
.6
.7
.8
.9
1
.01
.3
300
400
200
70
80
90
100
60
40
50
30
20
6
7
8
9
10
1 HOUR 2 HOURS
10000
9000
8000
7000
6000
5000
4000
3000
2000
1000
900
800
700
Breaker Type
Voltage Rating
AQB-A103 RMS
(Without Fuse)
Frequency
500 Vac
60 Hz
Interrupting Current
400 Hz
15 kA Asym.
7.5 kA Asym.
600
500
Frame Rating
In
400
Instantaneous Setting
x (In)
Instantaneous Current
(Amperes)
300
25
6
8
10
12
15
20
30
40
150
200
250
300
375
500
750
1000
100
6
8
10
12
15
20
30
40
600
800
1000
1200
1500
2000
3000
4000
200
1 MINUTE
100
90
80
70
60
50
40
30
20
Notes:
1. Instantaneous Pick Up is 15%
2. Curve accuracy applies from -20C to +55C ambient. For possible
continuous ampere derating for ambient above 50C, refer to Cutler-Hammer.
3. AQB-A103 RMS breakers are suitable for functional field testing with test kit
catalog number STK2.
10
9
8
7
6
5
4
6X
3
10
Instantaneous
Pick-up (x In )
6
25 A Frame (In)
3 Pole 500 V.A.C.
60 or 400 Hz
12.5
10X
12
40
15
30
9
10
13
2
14
Style number
NSN number
2
1
3
18.75
20
Short Delay
Band
25
Max.
Min.
100
FLAT(ms)
Cutler-Hammer
Short Delay
Pickup (xCCS)
20
Continuous
10
Current
Setting (Amps, CCS)
1
.9
.8
.7
.6
15
200
300
Date:
.5
.4
8X
15X
Inst antaneous
Pick-up (x In )
.2
10
30X
50
12X
Continuous
40
Cur ren t
Setting (Amp s, CCS)
20X
15
40
60
30
10
75
Short Delay
Band
80
Max.
Min.
100
FLAT (ms)
Cutler-Hammer
13
14
Style number
NSN No.
2
1
3
100
200
.04
3
2
.06
.05
Short Delay
Pickup (xCCS)
20
.10
.09
.08
.07
12
300
Date:
.03
.03
60000
70000
80000
90000
100000
50000
30000
40000
20000
6000
7000
8000
9000
10000
4000
5000
3000
2000
600
700
800
900
1000
500
300
400
200
60
70
80
90
100
50
40
30
.01
20
.01
7
8
9
10
.02
.02
TIME IN SECONDS
.3
CURRENT IN MULTIPLES OF In
TIME IN SECONDS
Characteristic Time-Current
Curve Navy Type AQB-A103
RMS Circuit Breaker
CURRENT IN MULTIPLES OF In
47
Types AQB-A250,
NQB-A250
Specication: MIL-C-17361
2- and 3-pole.
Interrupting Ratings
COMPLETE BREAKER
DC
HIGH
LOW
HIGH
STYLE
NUMBER
313C682G03
313C682G04
313C682G05
313C682G06
313C682G07
313C682G08
313C682G09
313C682G10
313C682G11
313C682G12
313C682G31
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
5925-01-233-6525
452D370G01
452D370G01
452D370G01
452D370G01
452D370G01
452D370G01
452D370G01
452D370G01
452D370G01
452D370G01
452D370G03
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
452D371G03
452D371G04
452D371G05
452D371G06
452D371G07
452D371G08
452D371G09
452D371G10
452D371G11
452D371G12
29B2710G05
5925-00-793-6865
5925-00-175-5058
5925-00-064-7834
452D370G01
452D370G01
452D370G01
5925-00-796-4371 452D371G13
5925-00-796-4371 452D371G14
5925-00-796-4371 452D371G15
125-N
125-NM
150-N
150-NM
175-N
175-NM
225-N
225-NM
250-N
250-NM
250
650
1300
1950
3900
650
1300
1950
3900
650
1300
1950
3900
650
1300
1500
3000
650
1300
1700
3400
Non-Auto
650
1300
2250
4100
650
1300
2250
4100
650
1300
2250
4100
650
1300
1770
3550
650
1300
1850
3800
Non-Auto
2-Pole 500 Volts ac, 250 Volts dc Generator Circuit Breaker Applications
100-NG
160-NG
250-NG
1175
1950
2350
3900
650
1300
313C682G13
313C682G14
313C682G15
Note:
Breakers with ratings other than
those given on this page are
considered as special and full
description data must be provided.
48
COMPLETE BREAKER
DC
HIGH
LOW
HIGH
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
313C682G18
313C682G19
313C682G20
313C682G21
313C682G22
313C682G23
313C682G24
313C682G25
313C682G26
313C682G27
313C682G36
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
5925-01-173-1114
5925-01-031-9909
5925-01-229-4448
5925-01-303-8381
5925-00-499-0088
5925-01-305-6194
5925-01-306-0120
5925-01-210-5267
5925-01-452-0162
5925-01-272-3805
5930-00-900-0247
452D370G02
452D370G02
452D370G02
452D370G02
452D370G02
452D370G02
452D370G02
452D370G02
452D370G02
452D370G02
452D370G04
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-831-8801
452D371G18
452D371G19
452D371G20
452D371G21
452D371G22
452D371G23
452D371G24
452D371G25
452D371G26
452D371G27
29B2710G06
5925-00-795-4958
5925-00-839-0289
5925-00-795-4957
5925-00-839-0290
5925-00-796-4439
5925-00-839-0291
5925-00-839-0292
5925-00-839-0293
5925-00-690-7568
5925-00-831-8800
5925-01-080-2226
5925-01-104-4625
452D370G02
452D370G02
452D370G02
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
452D371G28
452D371G29
452D371G30
5925-00-852-7809
5925-00-795-4956
125-N
125-NM
150-N
150-NM
175-N
175-NM
225-N
225-NM
250-N
250-NM
250
650
1300
1950
3900
650
1300
1950
3900
650
1300
1950
3900
650
1300
1500
3000
650
1300
1700
3400
Non-Auto
650
1300
2250
4100
650
1300
2250
4100
650
1300
2250
4100
650
1300
1770
3550
650
1300
1850
3800
Non-Auto
3-Pole 500 Volts ac, 250 Volts dc Generator Circuit Breaker Applications
100-NG
160-NG
250-NG
1175
1950
2350
3900
650
1300
313C682G28
313C682G29
313C682G30
Note:
Breakers with ratings other than
those given on this page are
considered as special and full
description data must be
provided.
49
Types AQB-A250,
NQB-A250
COMPLETE BREAKER
DC
HIGH
LOW
HIGH
STYLE
NUMBER
315C574G03
315C574G05
315C574G07
315C574G09
315C574G11
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
452D370G01
452D370G01
452D370G01
452D370G01
452D370G01
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
5925-00-796-4371
457D446G03
457D446G05
457D446G07
457D446G09
457D446G11
125-NH
150-NH
175-NH
225-NH
250-NH
910
910
910
910
910
1560
1560
1560
1560
1560
100-NGH
160-NGH
250-NGH
2020
2020
2520
3420
3420
4200
315C574G13
315C574G14
315C574G15
452D370G01
452D370G01
452D370G01
5925-00-796-4371 457D446G13
5925-00-796-4371 457D446G14
5925-00-796-4371 457D446G15
5925-00-758-6227
315C574G18
315C574G20
315C574G22
315C574G24
315C574G26
5925-01-075-8931
5925-01-100-4027
5925-01-193-6055
5925-01-050-9032
452D370G02
452D370G02
452D370G02
452D370G02
452D370G02
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
5925-00-789-3718
457D446G18
457D446G20
457D446G22
457D446G24
457D446G26
5925-00-803-5491
5925-00-803-5488
5925-00-899-9904
5925-01-193-6056
5925-01-149-4269
125-NH
150-NH
175-NH
225-NH
250-NH
910
910
910
910
910
1560
1560
1560
1560
1560
100-NGH
160-NGH
250-NGH
2020
2020
2520
3420
3420
4200
315C574G28
315C574G29
315C574G30
452D370G02
5925-01-330-7615 452D370G02
5925-01-238-5706 452D370G02
5925-00-789-3718 457D446G28
5925-00-789-3718 457D446G29
5925-00-789-3718 457D446G30
5925-00-238-5198
5925-00-803-5489
5925-00-906-7803
504C191G18
504C191G19
504C191G20
504C191G21
504C191G22
504C191G23
504C191G24
504C191G25
504C191G26
504C191G27
504C191G36
5925-01-415-4641
5925-01-437-4675
5925-01-415-4638
5925-01-415-4639
5925-01-345-3653
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-178-8962
5925-01-413-1629
5925-00-795-4958
5925-00-839-0289
5925-00-795-4957
5925-00-839-0290
5925-00-796-4439
5925-01-305-8589
5925-00-839-0291
5925-00-839-0292
5925-00-839-0293
5925-00-690-7568
5925-00-831-8800
3-Pole, 500 Volts ac, 250 Volts dc Front Connect With Lugs
125-N
125-NM
150-N
150-NM
175-N
175-NM
225-N
225-NM
250-N
250-NM
250
650
1300
1950
3900
650
1300
1950
3900
650
1300
1950
3900
650
1300
1500
3000
650
1300
1700
3400
Non-Auto
650
1300
2250
4100
650
1300
2250
4100
650
1300
2250
4100
650
1300
1770
3550
650
1300
1850
3800
Non-Auto
452D370G06
452D370G06
452D370G06
452D370G06
452D370G06
452D370G06
452D370G06
452D370G06
452D370G06
452D370G06
452D370G08
Note:
Breakers with ratings other than
those given on this page are
considered as special and full
description data must be provided.
50
452D371G18
452D371G19
452D371G20
452D371G21
452D371G22
452D371G23
452D371G24
452D371G25
452D371G26
452D371G27
29B2710G06
Switchboard Mounting
Complete breakers and frames
include mounting hardware.
Female slip connectors are
mounted in breaker base to plug
onto stud projections of terminal
mounting block assemblies. Order
one mounting block assembly for
each end of breaker.
DESCRIPTION
STYLE
NUMBER
NET WEIGHT,
LBS. (KG)
NATIONAL
STOCK NUMBER
1631 443
313C681G01
313C680G02
1 (0.5)
1 (0.5)
1.50 (0.7)
2920-01-354-4811
5940-01-146-6806
CABLE
RANGE
AMPERES
DESCRIPTION
STYLE
NUMBER
NATIONAL
STOCK NUMBER
N40-N74
N100-N125
N150-N200
125
150 175
250
Solderless
Connector
20B3055H14
20B3055H15
20B3055H16
5925-01-414-2467
5940-01-429-4972
5999-01-413-1588
NET WEIGHT
DESCRIPTION
NET WEIGHT,
LBS. (KG)
20.50 (9.3)
17.50 (7.9)
17.00 (7.7)
3.50 (1.6)
18.00 (8.2)
POLES
STYLE
NUMBER
3
2
29B2710G06
29B2710G05
NATIONAL
STOCK NUMBER
NET WEIGHT,
LBS. (KG)
5925-00-831-8800
.50 (0.2)
.50 (0.2)
Note:
Breaker with ratings other than
those given on this page are
considered as special and full
description data must be provided.
51
Types AQB-A250,
NQB-A250
Additions
Handle Lock
If required, order style
28B4596G01. One furnished no
charge per 10 breakers ordered,
when requested. Net weight
0.15 lbs. (0.07 kg).
Fungus Moisture
Resistant Treatments
Technical Manual
NAVSHIPS No. 362-2164
Motor Operator
6590C87G01 115 Vac, 60 Hz
Mechanical Interlock
If mechanical interlock (switchboard use) is desired for a pair of
breakers, order by description.
(Not submitted for Navy approval.)
Shunt Trip
Shunt trip attachments for tripping the breaker electrically from
a remote point are listed in table
below. Shunt trips have momentary rating only and for protection
must be connected in series
with auxiliary switch. Net weight,
0.70 lb. (0.3 kg) Contact Eaton
for 400 Hz. shunt trips.
Auxiliary Switch
NOMINAL
VOLTAGE
VOLTAGE
RANGE
STYLE
NUMBER
NATIONAL
STOCK NUMBER (NSN)
28 Vdc
115 Vac
28 Vdc
115 Vac
120 Vdc
450 Vac
120 Vdc
450 Vac
28 Vdc
115 Vac
28 Vdc
115 Vac
120 Vdc
450 Vac
120 Vdc
450 Vac
26 36
90 130
26 36
90 130
70 140
360 500
70 140
360 500
26 36
90 130
26 36
90 130
70 140
360 500
70 140
360 500
452D377G01
452D377G01
5925-00-831-8802
5925-00-831-8802
5925-00-831-8806
5925-00-831-8806
5925-00-840-1790
5925-00-840-1790
5925-00-831-8807
5925-00-831-8807
5925-00-831-8808
5925-00-831-8808
5925-00-831-8809
5925-00-831-8809
5925-01-007-5836
5925-01-007-5836
5925-00-831-8812
5925-00-831-8812
452D377G02
452D377G02
452D377G03
452D377G03
452D377G04
452D377G04
452D377G05
452D377G05
452D377G06
452D377G06
452D377G07
452D377G07
452D377G08
452D377G08
52
Undervoltage Device
Automatically trips breaker when
line voltage drops below 40 to
60% of normal. After undervoltage coil has dropped out and
tripped breaker on reduced
voltage, it automatically resets
by breaker action. (If undervoltage coil is energized to 80% of
normal). Select device from table
to the right. Net weight, 1.12 lbs.
(0.5 kg).
Individual Reproductions
When required, reproduction of
master drawings, outline drawings and certication sheets can
be ordered as follows:
NOMINAL
VOLTAGE
VOLTAGE
RANGE
PICKUP AND
SEAL VOLTS
(MINIMUM)
DROPCUT
VOLTAGE
STYLE
NUMBER
360 500
360 500
175 355
30 36
90 135
360
360
150
22
90
290 Maximum
45 Minimum
25 Minimum
5 Minimum
80 Maximum
452D837G01
452D837G01
452D837G02
452D837G03
452D837G04
NATIONAL
STOCK NUMBER
5925-00-920-3099
5925-00-920-3099
5950-00-501-2065
5950-00-790-4869
5925-01-385-2027
DESCRIPTION
1
2
3
4
Drawings Available
Master drawing 900-J-376;
front and rear connected breaker
outline, drilling and wiring
diagram 452-D-834.
For ordering information,
see Page 5.
53
Types AQB-A250,
NQB-A250
Outline Dimensions
AQB-A250 Breaker
Dimensions in Inches
Note:
The auxiliary switch must be
used with each shunt trip. Connect one side of shunt trip in
series with A contact (Closed
when breaker is closed) of auxiliary switch when connecting to
power supply.
7
4-13/16
4-9/16
4-7/16
3-1/16
8-1/4
Line End
4-1/8
7-5/8
1/4
9/16
3-13/16
5/8
3/8-16 Stud
1/4-20
Mtg.
Screws
5-3/8
5-15/16
3-1/4
2-7/16
11
1-11/16
5-1/16
3-9/16
CL
of
Handle
1-7/32
4-1/2
1/4
5/16
Warning
Nameplate
9-7/8
4-7/8 R
11-1/2
15
1-3/32
Closed
1/4
Reset
5/8
4-1/2
1/4
9/16
1/4
1/2-13
Thd. 5-3/8
2-1/8
19-1/2
1 Tripped
1-7/8
1-3/32
On
CL of Breaker
2-5/16
1-5/8
25/32
25/32
1-1/2
4-7/16
11/16
3/8-16 Stud
Load End
8-7/8
3-1/32
4-5/8
5/16
Front Sheet
1-15/16
4-21/32
2-3/4
11-5/16
Front Connected
Solderless T
Terminals
Line End
Load
End
1-13/32
1-9/16
1-23/32
1/16
1-5/16
1" Dia.
Flat Washers,
3/8-16 Thd.
3
and Nuts
Terminal
T
Mounting Blocks
1-5/32
1
MINIMUM
STYLE
NUMBER
75
125
200
50
100
150
12-11/16
13
13-5/16
6-25/32
6-15/16
7-3/32
5-29/32
6-1/16
6-7/32
20B3055H14
20B3055H15
20B3055H16
54
Outline Dimensions
AQB-A250 Breaker
Dimensions in Inches
1/16
13/16
2-3/4
Line End
5-1/4
4-3/16
3/8 Diameter . 2 Holes for
Undervoltage Release Shunt Trip
or Auxiliary Switch Leads. Hole
to be Drilled in Switchboard
Breaker Support
Bottom of
Mtg. Block
CL Top
reaker
Stud
2-13/16
CL
Bkr.
7-1/8
2-5/8
1/4 R
9/16
Bottom of
Breaker
13/16
Load End
3
1-1/2
1/16
Left Hand
Side of
Breaker
9-7/8
1-1/8
3
9/16
Top of Breaker
T
9-1/8
CL of
9/16 Breaker
Recommended Minimum
Distance Between Units
Top of Breaker
T
On
Off
Wiring Diagrams
AQB
NQB
Line End
Line End
When UnderVoltage
Release is Provided
Load End
Undervoltage
Release 2
Leads 18" Long
Shunt Trip 2
Leads 18" Long
Note:
The auxiliary switch must be
used with each shunt trip.
Connect one side of shunt trip in
series with A contact (Closed
when breaker is closed) of auxiliary switch when connecting to
power supply.
55
Types AQB-A250,
NQB-A250
VOLTAGE
STYLE
NUMBER
NATIONAL
STOCK NUMBER
115 Vac
6590C87G01
6105-01-431-5680
56
Outline Dimensions
AQB-A250 or NQB-A250
Circuit Breaker and Motor
Operator Dimensions
in Inches
CL
.25
8.31
Breaker
1.50
Mounting
Blocks
Breaker
Outline
Front
Sheet
CL
Handle
11.00 4.44
8.25
(Breaker)
1.68
.25
Motor Operator
Nameplate
8.88
11.00
Ref.
O
On
Tripped
19.5
8.46R
2-1/8
15 11.5
Off
Reset
.19
Front Sheet
8.18
10.58
57
Types AQB-A250,
NQB-A250
Motor Operator
Identication
115 Vac Motor Operator:
6590C87G01.
Pan Head
Mounting Screw
On and Relay
Control Limit
Switches
Motor
Terminal Block
Handle Extension
External Power
Yellow (On)
Motor
115 Vac
450 Vac
Black
If Applicable
Relay Control LS3
6
UVR
COM B2
OFF
ON
Remote Switches
(Momentary)
3
2 1
Relay
Socket
Breaker
Aux Sw
NC
COM
NC
Red (Off)
NO
On Switch LS1
A
8
7
9
Terminal
Blocks
L
Breaker Open
Indicator Light
MOTOR OPERATOR WIRING DIAGRAM
58
COM
On Switch LS2
COM
NC
NO
Term Block
Legend
1=1
3 = Line
4 = Off
6 = On
20
Minimum
Maximum
1
40
20
20
10
7
5
10
7
5
Operating Characteristics
Trip Unit Rating 125 250
Amperes 50C Ambient
Cold Start, 400 Cycle ac.
3
2
1
.8
.6
.5
10,000
15,000
20,000
30,000
100
150
200
300
400
500
600
800
Percent Rated Current
1,500
2,000
3,000
4,000
6,000
Cycles
1
40
3000
10
8
6
1500
20
4
3
2
3
2
10
4 5
3
2
2000
Time
Seconds
10
8
6
4
3
2
1
40
600
Maximum
20
30
800
1000
40
10
4 5
3
2
300
40
50 1
40
30
20
400
Minutes
1,500
2,000
3,000
4,000
6,000
Minutes
Time
Seconds
Cycles
10
8
6
4
3
2
1
.8
.6
.5
1 to 2 Min.
5 to 15 Min.
20 Min. or More
20
10
8
6
4
3
2
Minimum
300
200
150
4
3
2
30
1
50
30
20
90
80
70
AQB-A250
Operating Characteristics
Operating Characteristics
60
50
Ambient Temperature, C
T
Tripping
t Time
Rating
200
25%
600
225
150
Percent of
Seconds
1
50
100
ripping
me
Hours
t
Rating
Time, Minutes
100
150
200
300
400
500
600
800
Specication MIL-C-17361
Hours
Hours
Characteristic Time-Current
Curves
40
30
20
10
0
0
0.5
Factor
1.0
1.5
2.0
2.5
3.0
3.5
4.0 4.5
59
Types AQB-LF100,
AQB-LF250
Application
AQB-LF100 and AQB-LF250
circuit breakers are for use in
low-voltage distribution systems
where available fault current
exceeds the interrupting ratings
of standard molded case breakers but does not exceed 100,000
amperes.
Like standard Navy breakers,
they are designed for use in
switchboards, loadcenters and
panelboards.
AQB-LF circuit breakers are available in three-pole design and for
rear connection only.
Description
Fuse
Trip
Lever
Instantaneous
Trip Adjusting
Wheels
Operation
The thermal-magnetic trip unit of
the standard breaker provides
protection on overloads and
short circuits below a predetermined value without affecting
the fuses. However, these specially coordinated fuses assume
the fault clearing duty on high
magnitude short circuits and
extend the interrupting capacity
to 100,000 amperes.
The common trip feature of the
circuit breaker is retained so that
all poles open when any fuse
blows. Fast acting current limiting fuses clear short circuits in
less than one-half cycle. Consequently, peak let-through currents are greatly reduced and
bus-supporting members or current carrying parts do not have to
be designed to meet maximum
peak current.
Fuse
Housing
Interlock
Slide Type
Connectors
for Fuse
Contacts
Current
Limiting Fuses
Fuse Plug-In
Contacts
Fuse Housing
Unit Removed
AQB-LF250 Fused Navy Circuit Breaker
Note:
AQB-LF100 breakers are sold for
replacement only. They are no
longer on the Navy Qualied
Product List.
60
Interrupting Rating
Specication: MIL-C-17361
100,000 Amperes
Note:
AQB-LF100 breakers are sold
for replacement only. They are
no longer on Navy Qualied
Product List.
CONTINUOUS
AMPERE
RATING
INSTANTANEOUS BREAKER
TRIP SETTING COMPLETE
AMPERES
LOW
HIGH
STYLE
NUMBER
90
180
180
300
300
600
450
900
600
1200
105
210
210
350
350
700
525
1050
700
1400
452D391G16
452D391G17
452D391G18
452D391G19
452D391G20
452D391G21
452D391G22
452D391G23
452D391G24
452D391G25
BREAKER
FRAME
TRIP UNIT
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
452D390G02
452D390G02
452D390G02
452D390G02
452D390G02
452D390G02
452D390G02
452D390G02
452D390G02
452D390G02
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
5925-00-617-8312
FUSES
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
452D385G13
452D384G13
452D385G15
452D384G15
452D385G17
452D384G17
452D385G20
452D384G20
452D385G23
452D384G23
5925-00-849-8481
5925-00-655-1156
5925-00-655-1157
5925-00-655-1158
5925-00-655-1159
5925-00-655-1160
5925-00-655-1161
5925-00-655-1162
5925-00-655-1163
5925-00-655-1164
313C743H02
313C743H02
313C743H02
313C743H02
313C743H03
313C743H03
313C743H03
313C743H03
313C743H03
313C743H03
QUANTITY
REQUIRED
15-DF
15-D
25-DF
25-D
50-DF
50-D
75-DF
75-D
100-DF
100-D
3
3
3
3
3
3
3
3
3
3
Switchboard Mounting
Breaker frame includes mounting hardware. Female slip connectors are mounted on the rear
for plugging onto stud projections of terminal mounting block
assemblies. Order one for each
end of the breaker.
DESCRIPTION
STYLE NUMBER
1631 442
1764 240
01A4457G23
5940-00-501-9120
61
Types AQB-LF100,
AQB-LF250
Drawings Available
Technical Manual
Additions
Cutler-Hammer NAVSHIPS
number 362-2166. This booklet
per MIL-M-15071. When
required, order BVR-TM-380.
Individual Reproductions
When required, reproductions of
master drawings, outline drawings and certication sheets can
be ordered as follows:
ITEM
1
2
3
4
62
DESCRIPTION
Fungus-Moisture-Resistant
Treatments (JAN-T-152;
JAN-C-173 or MIL-V-173)
If specied, contact Eaton.
External parts are coated; trip
units are not treated.
NATIONAL
STOCK NUMBER
313C742G01
6605-00-799-3521
NET WEIGHT
DESCRIPTION
NET WEIGHT,
LBS. (KG)
13.62 (6.2)
9.68 (4.4)
2.62 (1.2)
1.62 (0.7)
1.62 (0.7)
0.45 (0.2)
0.25 (0.1)
Interrupting Rating
100,000 amperes.
BREAKER FRAME
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
452D820G02
452D820G02
452D820G02
452D820G02
452D820G02
452D820G02
452D820G02
452D820G02
452D820G02
452D820G02
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
5925-00-617-8313
TRIP UNIT
FUSES
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
452D821G18
452D821G19
452D821G20
452D821G21
452D821G22
452D821G23
452D821G24
452D821G25
452D821G26
452D821G27
5925-00-655-1165
5925-00-655-1166
5925-00-655-1167
5925-00-655-1168
5925-00-655-1169
5925-00-655-1170
5925-00-655-1171
5925-00-655-1172
5925-00-655-1174
5925-00-655-1173
313C743H04
313C743H04
313C743H04
313C743H04
313C743H04
313C743H04
313C743H04
313C743H04
313C743H04
313C743H04
QUANTITY
REQUIRED
3-Pole 500 Volts ac (Refer to Eaton for 2-Pole Styles and Prices)
125-L
125-LM
150-L
150-LM
175-L
175-LM
225-L
225-LM
250-L
250-LM
650
1500
650
1500
650
1500
650
1500
650
1500
1300
3000
1300
3000
1300
3000
1300
3000
1300
3000
313C748G18
313C748G19
313C748G20
313C748G21
313C748G22
313C748G23
313C748G24
313C748G25
313C748G26
313C748G27
5925-01-360-8673
5925-01-233-5623
5925-00-998-1960
5925-01-229-4444
5925-01-189-9250
5925-01-507-2391
5925-01-233-5173
5925-01-378-1838
5925-01-243-1611
5925-01-434-3687
3
3
3
3
3
3
3
3
3
3
Switchboard Mounting
Breaker frame includes mounting hardware. Female slip connectors are mounted on the rear
for plugging onto stud projections of terminal mounting block
assemblies. Order one for each
end of the breaker.
DESCRIPTION
STYLE NUMBER
1631 443
313C681G01
313C680G02
5940-00-501-9119
2920-01-354-4811
5940-01-146-6806
63
Types AQB-LF100,
AQB-LF250
Additions
Drawings Available
Undervoltage Device
Technical Manual
Individual Reproductions
DESCRIPTION
2
3
4
Auxiliary Switch
STYLE
NUMBER
NATIONAL
STOCK NUMBER
NET WEIGHT,
LBS. (KG)
452D832G01
5920-01-218-3803
4.50 (2.0)
64
Ordering Information
See Page 5.
Net Weights
See table above.
Outline Dimensions
AQB-LF100 Breakers
Dimensions in Inches
5
Line End
2-1/2
4-3/4
1-5/8
1-1/4
1-1/4
13/16
5/8
4-11/32
3-15/16
13/16
Mtg. Sheet
5/8
15/16
5/64
4-9/16
2-5/16
1-5/8 1-5/8
4-3/4
CL Breaker
3 Megger Holes
5/16 Diameter
8-3/4
7 Tripped
7-1/2
1/4-20 Mtg.
Screws
(Captive)
1/8 Min.
2-27/32 R
15/16
5/16-18 Thd. 4-9/16
13/16
13/16
45/64
4-3/16
15-1/2
CL
Off
5/8
3/4 Dia.
1-29/32
2-3/32 2-11/16
3-7/8
3-1/2
10
8-3/4
10-5/32
On
3-1/4
2-5/8
Front
Sheet
Load End
Flat Washers,
Lock Washers
and Nuts
Supplied
with Terminal
Mtg. Block
5/64
3/8-16 Thd.
1/16
1-39/64
3-31/64
2-3/16
2-3/8
5-43/64
5-1/64
10-1/64
1-5/8 1-5/8
4-21/32
2-15/32
4-15/16
65
Types AQB-LF100,
AQB-LF250
Line End
Removable Fuse
Unit Assembly
Removable
Trip Unit
Load End
Top of Breaker
15/16
7/16 Dia.
(4 Holes)
CL reaker
CL Breaker
Load End
3-7/16
5
Load
End
On
(Not Supplied with
Circuit Breaker)
Off
66
1/4 R
8
2-1/2
Studs
DRILLING PLANS
CL
9/16 R Min.
Line
End
4-13/16
1-1/2
8-3/4
15/16
1-5/8
4-3/16
3-1/4
Handle
2-1/4
1/4 R
9/16 R Min.
Top of Breaker
T
Warning
Nameplate
1/4-20 Mtg.
Screws
8-7/8
4-7/16
1/4
2-3/16
1-7/8
3-9/16
5/16
Visible Amp
Rating Inter
changeable
Trip Unit
Off
1-1/2
3/32 R
CL
9-7/8
5-9/16
1
1-5/32
1/16
4-5/8
4-3/8 1/8 R
1/16
5/16
1/2-13 Thd.
4-5/8
11-23/32
Load End
11/16
Front Sheet
4-5/16
4-7/8 R
15
1/2-13 Thd.
2-1/8
19-1/2
1 ripped
12
2-5/16
Support Blocks
Are Not Supplied
with Breaker, But
Must Be Ordered
Separately. Refer
to Dwg. 313C680.
All Parts Necessary
to Convert a Bkr.
Are Included
3-1/16
On
7-1/8
9-3/4
5-1/2
1/64
2-7/16
4-9/16
4-7/8
Frame
Nameplate
7
Line End
8-1/4
4-1/4
Outline Dimensions
AQB-LF250 Breakers
Dimensions in Inches
1-5/8
8
4
5-1/2
2-3/4
1-19/32
7-1/16
11-23/32
1/4-20 Mtg.
Screws for
Bkr. For
Access
Remove
4-21/32
5/16 Diameter
3 Holes for
Megger Tests
3
6
3/8-16 Thd.
Line End
Undervoltage Release
2 Leads 18" Long
Removable
Trip Unit
Removable
Fuse Unit
Assy.
A and B Aux.
Switch 3 Leads
18" Long
Shunt Trip
2 Leads
18" Long
AQB Breaker
with Overcurrent,
Short Circuit Trip
and Fuses
Load End
WHEN UNDERVOLTAGE
RELEASE IS PROVIDED
67
Types AQB-LF100,
AQB-LF250
R
M
4-1/8
4-7/8
5-9/16
4-3/16
3/8 Dia.
2 Holes
1/16
5-1/4
Breaker Support
r
L.H. Side
of Breaker
13/16
Bottom of
Mtg. Block
6
Bottom of Breaker
2-1/8
CL
Breaker
1/4
8-1/4
Load End
On
Off
Note:
The auxiliary switch must be
used with each shunt trip, connect one side of shunt trip in
series with A contact (closed
when breaker is closed) of auxiliary switch when connecting to
power supply.
68
1/4
CL
4-1/8
Handle
2-3/4
2-3/16
1/16 R
R.H. Side
of Breaker
3
1-1/2
9/32
Undervoltage
t
Release
or Shunt T
Trip and Aux.
Switch Lead Holes to be
L Breaker
1/4 R
4-1/2
9-1/2
9/16
1-1/2
1/4
9/16
CL T
Top Bkr. Stud
4-7/8
4-5/16
T
Top of Breaker
Line End
9-1/8
1/16
Drilling Plans
12-1/4
7-3/8
Outline Dimensions
AQB-LF250 Breakers
Dimensions in Inches
Characteristic Time-Current
Curves AQB-LF100 and
AQB-LF250 Breakers
AQB - LF 250
AQB - LF 100
10,000
10,000
Percent of
Tripping
Trip Element Time
Rating
5,000
4,000
3,000
2,000
25 Seconds 25%
Less Than 1 Hour
More Than 1 Hour
600
225
150
1,000
500
400
300
200
5,000
4,000
3,000
2,000
50
40
30
20
10
100
50
40
30
20
10
75 Amp.
50 Amp.
25 Amp.
15 Amp.
1
.5
.4
.3
.2
Time, Seconds
Time, Seconds
.05
.03
.02
600
3,000
30,000
100
300
1,200
10,000
100,000
Percent Rated Current
AQB-LF100 BREAKERS
3.5
3.0
5
4
3
2
250 Amp.
175 Amp.
.5
.4
.3
.2
150 Amp.
225 Amp.
125 Amp.
.1
.1
.01
25 Seconds 25%
Less Than 1 Hour
More Than 1 Hour
Operating Characteristics
Thermal Magnetic and Current
Limiting Fuse 50C Ambient
Cold Start Ac Instantaneous
Trip Range of 250 Amp. Trip
Unit Shown
650 to 1,300 Amp.
1,500 to 3,000 Amp.
See Table for Instantaneous
Range of Other Trip Unit
500
400
300
200
100 Amp.
5
4
3
2
600
225
150
1,000
Operating Characteristics
Thermal Magnetic and Current
Limiting Fuse
50C Ambient - Cold Start Ac
Instantaneous Trip at
1,200 to 1,400 % Rating
Instantaneous Trip at
600 to 700% Rating
100
Percent of
Tripping
Trip Element Time
Rating
.05
.03
.02
.01
600
3,000
100
300
1,200
Percent Rated Current
10,000
30,000
100,000
AQB-LF250 BREAKERS
2.5
2.0
Factor
1.5
1.0
.5
0
0
10
20
Te
30
40
50
C
60
70
80
90 100
69
Types AQB-A253,
AQB-L253 and
NQB-A253
Interrupting Rating
Description
The AQB-A253, 250 ampere circuit breaker, is form and t interchangeable with the AQB-A250
but has an electronic trip unit and
higher interrupting capacity. It is
available in a 3-pole, ac current
version only. If used to protect
two ac poles, connect only the
outer poles. It is a universal style
with a common trip unit and
60 Hz and 400 Hz ratings.
Specications: MIL-C-17361
70
Principle of Operation
These circuit breakers are
designed to provide the most
modern form of low voltage circuit protection technology available, providing high interruption
ratings and exible coordination
without the need for current
limiting fuses. The breakers use
modern electromagnetic design
principles to increase the interrupting capacity (IC) to signicantly higher levels than
comparable AQB-A250 breakers.
The AQB-L253 uses a reverse
loop conductor design and
magnetically unlatched contact arms to provide very high
interrupting capacity while limiting the let-through current and
limiting the fault duration to a
few milliseconds.
Ordering
The circuit breaker is available in
three styles, an AQB-A253 (standard IC), an AQB-L253 (high IC)
and an NQB-A253 (non-automatic) switch. The breaker is
completed by adding one of two
styles of rating plugs, one which
covers the continuous current
range from 250 175 amperes
and another which covers the
range from 160 100 amperes.
An internally mounted auxiliary
switch, a shunt trip and an undervoltage release are also available.
AQB-A253, AQB-L253
Characteristics
Continuous Current Setting
(4-Position Selector Switch)
100 160 amperes (100,125,
150,160) rating plug
175 250 amperes (175, 200,
225, 250) rating plug
Instantaneous Pickup Fixed
at 30 X Frame rating (7500 A).
Short Delay Pickup Adjustable in multiples of continuous
current settings (2x, 3x, 4x, 6x,
8x, 10x, 12x, 13x).
Short Time Delay Adjustable
at response with bands:
BREAKER
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
1483D82G03
1483D82G04
FRAME ONLY
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
5925-01-493-8105
5925-01-532-5569
1483D82G01
1483D82G02
5925-01-495-3022
5925-01-481-5876
1483D73G04
1483D73G04
5925-01-481-5874
5925-01-481-5874
1483D82G13
1483D82G14
1483D82G01
1483D82G02
5925-01-495-3022
5925-01-483-1953
1483D73G07
1483D73G07
1483D82G06
5925-01-548-7748
1483D82G01
5925-01-495-3022
1483D73G06
Standard LSI
AQB-A253
AQB-L253
Instantaneous Only
AQB-A253
AQB-L253
Non-Automatic
NQB-A253
BREAKER
STYLE
NUMBER
NATIONAL
STOCK NUMBER
AMPERE
RATING
STYLE
NUMBER
NATIONAL
STOCK NUMBER
AQB-A253
AQB-L253
NQB-A253
1483D82G09
1483D82G10
1483D82G11
5925-01-527-6915
5925-01-554-4936
5925-01-527-6914
100 160
175 250
6603C02G52
6603C02G51
5935-01-481-2133
5935-01-481-2131
BREAKER
STYLE
NUMBER
NATIONAL
STOCK NUMBER
NQB-A253
1483D82G12
AQB-L253
1483D82G15
AQB-A253
1483D82G16
Note:
Please contact Technical
Resource Center for specialty
part number with accessories
factory installed.
Note:
AIC ratings are based on 3-phase
average asymmetrical current.
71
Types AQB-A253,
AQB-L253 and
NQB-A253
Circuit Breaker
Mounting Blocks
Complete circuit breaker
includes mounting hardware.
Female slip connectors are
included in the breaker base to
DESCRIPTION
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
NET WEIGHT,
LBS. (KG)
313C680G02
313C681G01
1631443
5940-01-146-6806
2920-01-354-4811
1.5 (0.7)
1.0 (0.5)
1.0 (0.5)
Front-Connected
Circuit Breakers
For cable connections made at
front terminals, pressure-type
lugs are required. If specied on
DESCRIPTION
Solderless Connector
CABLE
RANGE
AMPERES
STYLE
NUMBER
NATIONAL
STOCK NUMBER
N40-N70
N100-N125
N150-N200
125
150 175
250
20B3055H14
20B3055H15
20B3055H16
5925-01-414-2467
5925-01-429-4972
5925-01-413-1588
Auxiliary Switch
The auxiliary switch (AS)
changes state with the circuit
breaker. Auxiliary switches
supplied with this breaker are
form C (SPDT) with 3 lead wires.
72
DESCRIPTION
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
NET WEIGHT,
LBS. (KG)
1483D90G01
1483D90G02
5930-01-558-9236
5930-01-559-4835
0.5 (0.2)
0.5 (0.2)
Shunt Trip
The Shunt Trip (ST) is provided
to remotely trip (open) the circuit
breaker in response to a remote
signal applied to the accessory
device. It is available in a variety
of voltage ratings (see below).
NOMINAL
VOLTAGE
STYLE
NUMBER
1483D92G03
1483D92G04
1483D92G05
1483D92G01
1483D92G02
1483D92G06
NATIONAL
STOCK
NUMBER
5925-01-481-5863
5925-01-515-6353
5925-01-559-6023
5925-01-558-9230
NET WEIGHT,
LBS. (KG)
0.5 (0.2)
0.5 (0.2)
0.5 (0.2)
0.5 (0.2)
0.5 (0.2)
0.5 (0.2)
Undervoltage Release
The undervoltage release (UVR)
will trip the circuit breaker and
hold it in a tripped condition if the
control voltage to the UVR drops
below 40% to 60% of nominal.
After the UVR has tripped the
breaker it will be mechanically
reset by the opening action of
the breaker and electromagnetically latched if the applied voltage returns to at least 80% of
nominal. It mounts in the left
pole of the circuit breaker cover
and can only be used in the
absence of a shunt trip device.
FACTORY INSTALL ONLY.
NOMINAL
VOLTAGE
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
NET WEIGHT,
LBS. (KG)
1483D91G01
1483D91G02
1483D91G03
1483D91G04
0.5 (0.2)
0.5 (0.2)
0.5 (0.2)
0.5 (0.2)
DESCRIPTION
STYLE
NUMBER
NATIONAL
STOCK
NUMBER
NET WEIGHT,
LBS. (KG)
6603C76G01
5895-01-483-1936
0.14 (0.1)
73
Types AQB-A253,
AQB-L253 and
NQB-A253
Motor Operator
An electrical motor operator is
available which mounts on the
front face of the circuit breaker
and can be used for remotely
opening or closing the breaker.
NOMINAL VOLTAGE
1483D93G01
22.0 (10.0)
Handle Lock
A handle lock can be furnished to
lock the handle in either the ON
5925-01-542-4620
DESCRIPTION
Handle Lock
1720101
0.15 (0.07)
Handle Extension
5103A34G01
DESCRIPTION
1232C50G10
6625-01-419-1910
THREAD
TORQUE, IN-LBS
.250-20
.164-32
.375-16
.312-24
.500-13
.375-15
.250-20
.164-32
144
23
144
81
250
144
144
23
NET WEIGHTS
74
DESCRIPTION
AQB-A253 Frame
AQB-L253 Frame
Single AQB-A253 Breaker with Rating Plug
Single AQB-L253 Breaker with Rating Plug
Trip Units
Rating Plug
18.31 (8.3)
18.96 (8.6)
21.97 (10.0)
21.97 (10.0)
2.82 (1.3)
0.03 (0.01)
Outline Dimensions
AQB-A253, AQB-L253
and NQB-A253 Breakers
Dimensions in Inches
8.50
4.25
3.00
AQB-L253 or
AQB-A253 Breaker
.22
1.62
.407
3.03
2.43
5.70 Maximum
4.78
4.56
2
3.81
.44
14.3 2.0
11.00
OFF
4.06
6.00
3.00
.313
R .218
3.00
4.43
Load End
.43
3 2 1
Line
.37
4.50
1.41
Line End
9.75
4.43
4.50
9.87
1.37
6.10
9.87
9.87
Pivot
L
3 2 1
3.06
5.37
19.7
24.7
6.00
Line End
CL Handle
Pivot
.62
5.93
3.00
4.03
Load End
1.50
Load
NQB Breaker
Non-Automatic
AQB Breaker,
with Overcurrent
and Short Circuit
Trip Protection
75
Types AQB-A253,
AQB-L253 and
NQB-A253
Outline Dimensions
AQB-A253, AQB-L253
and NQB-A253 Breakers
Dimensions in Inches
3.00
3.00
.18
.18
.53
4.65
1.62
.25
3.03
5.21
.65
.56
5.37
9.87
.563
.81
.251
Reverse Position
of Lock to Prevent
Breaker from Opening
12.14
Cross Section
.19
.19
76
1 HOUR
2 HOURS
5000
4000
3000
CH Cutler-Hammer
Push To
Trip
250A
1 MINUTE
2000
1000
900
800
700
600
500
Short Delay
Pick-upxCCS
Time ms
300
200
100
INST
Engaged
6 8 10
4
12
3
13
2
Remove
Continuous 225A
Current Setting
400
175A
200A
Type
Adjustable
Adjustable
TEST
Rating Plug
Catalog
Number
6603C02G52
6603C02G51
Short Delay
Pickup Range
Amperes
200-2080
350-3250
1.55 10%
300
Long Delay
Maximum Total
Clearing Time
200
100
90
80
70
60
Breaker
Type
A253
L253
Long Delay
Minimum Total
Clearing Time
500 VAC
Voltage Rating
Frequency
Interrupting
Current
60 Hz
30 kA
100 kA
400 Hz
10 kA
Notes
1. Curve accuracy applies from 20C to +55C ambient. For possible continuous ampere
derating for ambient above 50C, refer to Cutler-Hammer.
50
40
2. For high fault current level a fixed instantaneous override is provided at 7500A.
(Tolerance 20%).
30
3. The end of the curve is determined by the interrupting rating of the circuit breaker.
20
TIME IN SECONDS
4. AQB-A/L253s are suitable for functional field testing with test kit Cat. Number STK2.
5. Calibration response in short delay pickup range is same for 1, 2 or 3 poles in series.
6. There are memory effects that can act to shorten the long delay. The memory effects
come into play if a current above the long delay pickup value exists for a time and
then is cleared by the tripping of a downstream device or the circuit breaker itself.
A subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time delay reduction is inverse to the amount of time that has elapsed
since the previous overload. Approximately five minutes are required between overloads
to completely reset the memory.
Short Delay
Pickup Settings
(Tolerance 10%)
10
09
08
07
06
05
4
3
13
6
12
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
.5
300ms
10
.4
.3
.4
.3
200ms
.2
.2
100ms
.1
.09
.08
.07
.06
INST. .08
.05
.05
.1
.09
.07
.06
CURRENT IN AMPS
60,000
70,000
80,000
90,000
100,000
.01
50,000
20
40,000
6 7 8 9 10
20,000
30,000
5000
7000
8000
9000
10,000
Fixed Instantaneous
Override is Provided
@ 7500A
.02
6000
.01
.5 .6 .7 .8 .9 1
.03
4000
.02
.04
3000
.03
2000
.04
1000
TIME IN SECONDS
77
Types AQB-L400,
AQB-LL400
AQB-LL400QS Breaker
Description
The Navy Type AQB-L400QF,
AQB-L400QM, and AQBLL400QS molded case circuit
breakers are 500 Vac maximum
rated devices with electronic
trip units rated at 400 amperes
maximum continuous current at
60 Hz. The circuit breakers are
assembled as 3-pole units which
may be used as 2- or 3-pole
devices.
The circuit breakers are designed
to MIL-C-17361 and meet the
requirements of Class HI-shock,
MIL-S-901. The circuit breaker
electronic trip unit has adjustable
short delay time and pickup trip
settings which can be readily
changed at the operator level to
meet the shipboard system trip
requirements. Four interchangeable rating-plugs are available to
select the continuous current
rating of 250, 300, 350 or 400
amperes. Also provided is a
non-adjustable inverse time
delay tripping action for overload
conditions, and instantaneous
tripping for protection against
short circuit conditions that
exceed the preset short delay
pickup setting. In open air at
50C, the circuit breaker will
carry continuously a current
equal to the ampere rating of the
installed rating plug. The calibration of the trip unit is insensitive
to ambient temperatures over a
range of -20C to +70C.
Operation
The AQB-L400QF, AQBL400QM, and AQB-LL400QS
current limiting circuit breakers
(without the need for current limiting fuses) are designed to provide circuit protection for low
voltage distribution systems. The
circuit breakers will disconnect a
load from an electrical supply
when the handle is operated,
when an overcurrent or short circuit condition develops, or when
the push-to-trip button in the trip
unit is manually pressed. A complete breaker consists of a
breaker, rating plug plus mounting blocks and is available with
numerous attachments such as
electrical operator, shunt trip,
undervoltage release and auxiliary switches to perform varied
auxiliary functions.
The circuit breaker has a springloaded independent over-toggle
operating mechanism that provides a quick-make quick-break
trip-free operation.
The operating mechanism also
provides the electro-mechanical
means to open the contacts
when trip conditions occur.
When current is owing through
the contacts of the circuit
breaker, the positions of the
lower contact arms and the moving contact arms induce opposing magnetic elds. The resulting
opposing forces along the magnetic ux lines cause rapid contact blow-apart under high
current fault conditions. The
AQB-L400QF and AQB-L400QM
circuit breakers have slot motors
for each moving contact arm to
intensify the magnetic eld and
further increase the blow-apart
effect.
Specications
AQB-L400QF
150,000 Amperes
AQB-L400QM
150,000 Amperes
AQB-LL400QS
100,000 Amperes
Protective Functions
Protective Functions
Short Delay Pickup
(Adjustable)
AQB-L400QF
650 1500 Amperes
AQB-L400QM
1700 3200 Amperes
AQB-LL400QS
3600 5800 Amperes
78
AQB-L400QF, AQB-L400QM
and AQB-LL400QS Current
Limiting Navy Circuit
Breakers.
AQB-L400QF
1850 Amperes
AQB-L400QM
3280 Amperes
AQB-LL400QS
6300 Amperes
Up
Upper
pper
Co
ontact
Arm
Slot Motor
Lower
Contact
m
Line End
Conductor
STYLE
NUMBER
NATIONAL
STOCK NUMBER
Circuit Breaker, Navy Type (Supplied with male plug-in adapters installed f
or rear connection)
AQB-LL400QS
AQB-L400QF
AQB-L400QM
NQB-LL400
AQB-LL400QS Mag Only
AQB-L400QM Mag Only
1230C83G01
1230C83G02
1230C83G03
1230C83G04
1230C83G05
1230C83G06
5925-01-356-4514
5925-01-440-3934
5925-01-360-5605
5925-01-512-5100
1230C84G01
1230C84G02
1230C84G03
1230C84G04
5925-01-356-8864
5925-01-356-5973
5925-01-356-5974
5925-01-356-5975
Rating Plug
Motor Operator
The motor operator is designed
to remotely switch a circuit
breaker to its ON, OFF and
relatch positions. The relatch
function will occur automatically
after a circuit breaker trip operation. The motor operator is selfcontained and assembled in
its own mounting frame which
mounts on the front of the circuit
breaker. When the ON or OFF
remote control button is pressed,
TYPE
STYLE
NUMBER
NATIONAL
STOCK NUMBER
1234C53G01
5925-01-348-9823
79
Types AQB-L400,
AQB-LL400
MOUNTING BLOCK
STYLE
NUMBER
NATIONAL
STOCK NUMBER
1230C81G01
5975-01-457-5094
1230C81G05
1230C81G04
504C497G01
TYPE
STYLE
NUMBER
NATIONAL
STOCK NUMBER
1220C86G01
1220C86G02
1220C86G05
1220C86G06
1220C86G07
5930-01-358-5608
5930-01-356-5780
STYLE
NUMBER
NATIONAL
STOCK NUMBER
1220C86G03
1220C86G04
6625-01-356-5176
5925-01-368-1501
1220C86G08
1220C86G09
1220C86G10
1220C86G11
5925-01-358-4082
5925-01-445-7323
TYPE
STYLE
NUMBER
NATIONAL
STOCK NUMBER
1241C42G01
5925-01-407-3083
TYPE
STYLE
NUMBER
NATIONAL
STOCK NUMBER
1241C34G02
5925-01-442-3696
TYPE
SHUNT TRIP
TYPE
CIRCUIT BREAKERS, NAVY TYPE,
AQB-L400QF, AQB-L400QM, AND
AQB-LL400QS (TOP) AND MOTOR
OPERATOR (BOTTOM)
115 Vac/28-120 Vdc Shunt Trip and 115-450 Vac Auxiliary Switch
115 Vac/28-120 Vdc Shunt Trip and 120 Vdc Auxiliary Switch
450 Vac Shunt Trip and 115-450 Vac Auxiliary Switch
450 Vac Shunt Trip and 120 Vdc Auxiliary Switch
80
Individual Reproduction
(Only Left-Pole) UVR and Circuit Breaker must be ordered as an integral unit.
TYPE
STYLE
NUMBER
NATIONAL
STOCK NUMBER
1230C83G15
1230C83G16
1230C83G17
1230C83G18
1230C83G19
1230C83G20
1230C83G21
1230C83G22
1230C83G11
1230C83G12
1230C83G13
1230C83G14
5925-01-521-6181
5925-01-514-3469
5925-01-356-4518
Using externally-mounted
step-down transformer supplied.
Not eld mountable.
Switchboard Mounting
Technical Manual
Fungus-Moisture-Resistance
Treatments
Handle Lock
ITEM
DESCRIPTION
2
3
NET WEIGHT
DESCRIPTION
Circuit Breaker
Motor Operator
Mounting Block
Front Connected
Terminals
(Set of Three)
Portable Test Kit
Rating Plug
Shunt Trip
Auxiliary Switch
NET
WEIGHT
30 lbs.
22 lbs.
10 lbs.
1 lb.-10-1/4 ozs.
12 lb.-14-1/4 ozs.
2 ozs.
3 ozs.
2.5 ozs.
81
Types AQB-L400,
AQB-LL400
82
Net Weight
34 Lbs. (15 kg) (Breaker plus
adapter).
L400/LL400 BREAKER WITH ADAPTER KIT (CALL EATON FOR OTHER CONFIGURATIONS)
BREAKER
CONSISTS OF
PLUS
STYLE NUMBER BREAKER FRAME PLUG
PLUS
ATTACHMENTS
PLUS
ADAPTER KIT
1241C54G01
1241C54G02
1241C54G03
1241C54G04
1241C54G05
1241C54G06
1241C54G07
1241C54G08
1241C54G09
1241C54G10
1241C54G11
1241C54G12
1241C54G13
LL400QS
L400QF
LL400QS
LL400QS
L400QM
LL400QS
LL400QS
L400QM
LL400QS
L400QM
LL400QS
L400QM
L400QM
400Q
250Q
400Q
400Q
300Q
400Q
300Q
350Q
350Q
400Q
400Q
350Q
300Q
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
6590C82G01
1241C54G14
1241C54G15
1241C54G16
L400QM
LL400QS
LL400QS
400Q
400Q
350Q
6590C82G01
6590C82G01
6590C82G01
Outline Dimensions
AQB-L400, AQB-LL400
Dimensions in Inches
6-1/16
2-3/4
5-1/4
4-7/8
Line
1-3/8
3-3/8
4-1/16
1-1/8
1-3/4
21/64
Automatic
matic
Trippe
ed
11-7/32
1-7/32
-7/3
9-9/16
Front Surface
of Mounting
Panel
9-17/32
-17/3
17/3
10-3/16
0-3/1
On
18-1/16
8-1/1
14-3/4
16
1-7///8
19 30'
CL
3-3/
3-3/4
15
3-1///16
6-27/32
27/3
2-3/16
5-5/
5-5/32
5-13/16
-13/
Reset
Max
21/64
Center Line of
Circuit Breaker
Handle
19-32
3-7/8
Radius
5-3/16
5-3/16
1-3/4
1-1/8
Load
11/16
8-1/4
/
4-1/8
/
3-1/16
1-27/32
1-17/32
59/64
2-3/4
5-1/2
4
8
83
Types AQB-L400,
AQB-LL400
Outline Dimensions
AQB-L400, AQB-LL400
with Motor Operator
Dimensions in Inches
Nut Depth
5/16
Line End
1-3/4
2.45
11-7/32
1-7/3
9-9/16
10-3/16
0-3/1
14-3/4
18-1/16
-1/16
On
19 30
0'
0
Tripped
16
2-3/16
CL
Circuit Breaker
Handle
Of
8.008
5-13/16
-13/
5-3/16
6-27/32
27/3
1-3/4
Load End
3/16
8-1/4
5/16-18
Mounting
Hardware
8-1/8
10-3/16
1
1-7/8
7-13/16
2-3/4
5-1/2
4
8
84
3-3/8
5-1/4
Wiring Diagrams
Line
Load
5.188
.312 Dia.
Megger Holes
CL Handle
.250 R
5.500
7.000
3.250
1.625
2.750
3.500
.188 R
1.969
2.078
6.016
17.000
14.750
1.125
Line End
9.562
1.125
5.188
Load End
1.375
2.750
CL
Stud
CL
CL Breaker
5.500
Stud
2.750
CL Handle
1.750
.500
1.000
85
Types AQB-L400,
AQB-LL400
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
5,000
3,000
3,000
2,000
Curve Tolerance
T
Applies
Over T
-20C to +70C
250 Amperes
1,000
500
1,000
300
300
200
200
100
50
50
30
30
20
20
10
10
TIME IN SECONDS
1 MINUTE
1 MINUTE
2,000
500
100
TIME IN SECONDS
1 HOUR
1 HOUR
CURRENT IN AMPERES
.5
.5
.3
.3
MAX Setting
.2
.2
.1
.1
MIN Setting
.05
.03
.05
.03
Maximum Interrupting
Time at 500 Volts AC
.02
.02
Fixed Instantaneous
(Override) Pick-Up
1850 A 15%
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QF CIRCUIT BREAKER WITH 250 AMPERE RATING PLUG
86
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
3,000
3,000
2,000
Curve T
Tolerance Applies
Over T
-20C to +70C
1,000
500
1,000
300
300
200
200
100
50
30
30
20
20
10
10
TIME IN SECONDS
1 MINUTE
1 MINUTE
2,000
500
100
TIME IN SECONDS
1 HOUR
1 HOUR
5,000
.5
.5
.3
.3
MAX Setting
.2
.2
.1
.1
MIN Setting
Current Limiting Threshold
.05
.03
.05
.03
Fixed Instantaneous
(Override) Pick-Up
.02
Maximum Interrupting
Time at 500 Volts AC
1850 A 15%
.01
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
.001
500
.001
400
.002
300
.003
.002
200
.005
.003
60
70
80
90
100
.005
50
CURRENT IN AMPERES
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QF CIRCUIT BREAKER WITH 300 AMPERE RATING PLUG
87
Types AQB-L400,
AQB-LL400
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
5,000
3,000
3,000
2,000
Curve T
Tolerance Applies
Over T
-20C to +70C
350 Amperes
1,000
500
1,000
300
300
200
200
100
50
30
30
20
20
1 MINUTE
1 MINUTE
2,000
500
100
10
10
TIME IN SECONDS
TIME IN SECONDS
1 HOUR
1 HOUR
CURRENT IN AMPERES
.5
.5
.3
.3
MAX Setting
.2
.2
.1
.1
MIN Setting
.05
.03
.05
.03
Fixed Instantaneous
(Override) Pick-Up
.02
Maximum Interrupting
Time at 500 Volts AC
1850 A 15%
.01
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QF CIRCUIT BREAKER WITH 350 AMPERE RATING PLUG
88
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
3,000
3,000
2,000
Curve Tolerance
T
Applies
Over T
-20C to +70C
400 Amperes
1,000
500
1,000
300
300
200
200
100
50
50
30
30
20
20
1 MINUTE
1 MINUTE
2,000
500
100
10
10
TIME IN SECONDS
TIME IN SECONDS
1 HOUR
1 HOUR
5,000
.5
.5
.3
.3
MAX Setting
.2
.2
.1
.1
MIN Setting
.05
.03
.05
.03
Fixed Instantaneous
(Override) Pick-Up
.02
.02
Maximum Interrupting
Time at 500 Volts AC
1850 A 15%
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
.001
600
700
800
900
1,000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
CURRENT IN AMPERES
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QF CIRCUIT BREAKER WITH 400 AMPERE RATING PLUG
89
Types AQB-L400,
AQB-LL400
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
5,000
3,000
3,000
2,000
Curve Tolerance
T
Applies
Over T
-20C to +70C
250 Amperes
1,000
500
1,000
300
300
200
200
100
50
50
30
30
20
20
10
10
1 MINUTE
1 MINUTE
2,000
500
100
.5
.5
.3
TIME IN SECONDS
TIME IN SECONDS
1 HOUR
1 HOUR
CURRENT IN AMPERES
.3
.2
.1
.1
MAX Setting
.05
MIN Setting
.03
.02
.05
.03
Maximum Interrupting
Time at 500 Volts AC
Fixed Instantaneous
(Override) Pick-Up
.02
3280 A 15%
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
.001
500
.001
400
.002
300
.002
200
.003
60
70
80
90
100
.005
.003
50
.005
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QM CIRCUIT BREAKER WITH 250 AMPERE RATING PLUG
90
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
3,000
3,000
2,000
Curve T
Tolerance Applies
Over T
-20C to +70C
300 Amperes
1,000
500
1,000
300
300
200
200
100
50
30
30
20
20
10
10
1 MINUTE
1 MINUTE
2,000
500
100
TIME IN SECONDS
TIME IN SECONDS
1 HOUR
1 HOUR
5,000
.5
.5
.3
.2
.2
MAX Setting
.1
.1
MIN Setting
.05
.03
.05
.03
Fixed Instantaneous
(Override) Pick-Up
.02
Maximum Interrupting
Time at 500 Volts AC
3280 A 15%
.01
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
.001
600
700
800
900
1,000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
CURRENT IN AMPERES
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QM CIRCUIT BREAKER WITH 300 AMPERE RATING PLUG
91
Types AQB-L400,
AQB-LL400
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
5,000
3,000
3,000
2,000
Curve T
Tolerance Applies
Over T
-20C to +70C
350 Amperes
1,000
500
1 HOUR
1 HOUR
CURRENT IN AMPERES
2,000
1,000
500
300
300
200
200
50
30
30
20
20
10
10
.5
.5
.3
TIME IN SECONDS
TIME IN SECONDS
1 MINUTE
1 MINUTE
100
.3
.2
.1
.1
MAX Setting
.05
.05
MIN Setting
.03
.03
Fixed Instantaneous
(Override) Pick-Up
.02
3280 A 15%
Maximum Interrupting
Time at 500 Volts AC
.01
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QM CIRCUIT BREAKER WITH 350 AMPERE RATING PLUG
92
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
3,000
3,000
2,000
Curve Tolerance
T
Applies
Over T
-20C to +70C
400 Amperes
1,000
500
1 HOUR
1 HOUR
5,000
2,000
1,000
500
300
300
200
200
100
50
50
30
30
20
20
10
10
.5
.5
.3
.3
.2
.2
TIME IN SECONDS
TIME IN SECONDS
1 MINUTE
1 MINUTE
.1
MAX Setting
.05
MIN Setting
.03
.05
.03
Fixed Instantaneous
(Override) Pick-Up
32 8 0 A 1 5 %
.02
.02
Maximum Interrupting
Time at 500 Volts AC
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
.001
600
700
800
900
1,000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
CURRENT IN AMPERES
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-L400QM CIRCUIT BREAKER WITH 400 AMPERE RATING PLUG
93
Types AQB-L400,
AQB-LL400
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
5,000
3,000
3,000
2,000
Curve Tolerance
T
Applies
Over T
-20C to +70C
250 Amperes
1,000
500
1,000
300
300
200
200
100
50
50
30
20
10
10
TIME IN SECONDS
30
20
1 MINUTE
1 MINUTE
2,000
500
100
TIME IN SECONDS
1 HOUR
1 HOUR
CURRENT IN AMPERES
.5
.5
.3
.3
.2
.2
.1
.1
MAX Setting
MIN Setting
.03
.03
Fixed Instantaneous
(Override) Pick-Up
.02
.05
Maximum Interrupting
Time at 500 Volts AC
6300 A 15%
.01
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-LL400QS CIRCUIT BREAKER WITH 250 AMPERE RATING PLUG
94
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
3,000
3,000
2,000
Curve T
Tolerance Applies
Over T
-20C to +70C
300 Amperes
1,000
500
1,000
300
300
200
200
100
50
50
30
20
10
10
TIME IN SECONDS
30
20
1 MINUTE
1 MINUTE
2,000
500
100
TIME IN SECONDS
1 HOUR
1 HOUR
5,000
.5
.5
.3
.3
.2
.2
.1
.1
.05
MAX Setting
.03
.05
.03
MIN Setting
.02
Maximum Interrupting
Time at 500 Volts AC
Fixed Instantaneous
(Override) Pick-Up
6300 A 15%
.01
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
.001
600
700
800
900
1,000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
CURRENT IN AMPERES
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-LL400QS CIRCUIT BREAKER WITH 300 AMPERE RATING PLUG
95
Types AQB-L400,
AQB-LL400
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
50
60
70
80
90
100
10,000
2 HOURS
10,000
2 HOURS
5,000
5,000
3,000
3,000
2,000
Curve T
Tolerance Applies
Over T
-20C to +70C
350 Amperes
1,000
500
1 HOUR
1 HOUR
CURRENT IN AMPERES
2,000
1,000
500
300
300
200
200
50
50
30
30
20
20
10
10
TIME IN SECONDS
TIME IN SECONDS
1 MINUTE
1 MINUTE
100
.5
.5
.3
.3
.2
.2
.1
.1
MAX Setting
.05
MIN Setting
.03
.03
Fixed Instantaneous
(Override) Pick-Up
.02
.05
Maximum Interrupting
Time at 500 Volts AC
6300 A 15%
.01
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-LL400QS CIRCUIT BREAKER WITH 350 AMPERE RATING PLUG
96
Characteristic Time-Current
Curves
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
600
700
800
900
1,000
500
400
300
200
60
70
80
90
100
50
10,000
2 HOURS
10,000
2 HOURS
5,000
3,000
3,000
2,000
Curve Tolerance
T
Applies
Over T
-20C to +70C
400 Amperes
1,000
500
1 HOUR
1 HOUR
5,000
2,000
1,000
500
300
300
200
200
100
30
30
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
TIME IN SECONDS
TIME IN SECONDS
50
50
1 MINUTE
1 MINUTE
.1
.05
.03
MIN Setting
.05
.03
.02
.02
Maximum Interrupting
Time at 500 Volts AC
Fixed Instantaneous
(Override) Pick-Up
6300 A 15%
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6,000
7,000
8,000
9,000
10,000
5,000
4,000
3,000
2,000
.001
600
700
800
900
1,000
.001
500
.002
400
.002
300
.003
200
.005
.003
60
70
80
90
100
.005
50
CURRENT IN AMPERES
CURRENT IN AMPERES
TIME-CURRENT CURVES FOR AQB-LL400QS CIRCUIT BREAKER WITH 400 AMPERE RATING PLUG
97
Type NQB-A803
COMPLETE BREAKER
TYPE
NQB-A803
STYLE
NUMBER
NATIONAL
STOCK NUMBER
Rear Connect
Front Connect
Front Connect with 1A1B Aux. Contact
Front Connect with 1A1B Aux. Contact and
Long Studs (BIW Style)
1488D90G10
1488D90G20
1488D90G30
1488D90G31
ACCESSORIES
Specications: MIL-C-17361
3-Pole.
DESCRIPTION
STYLE
NUMBER
2614D53G07
4214B63G01
Note:
AIC ratings are based on 3-phase
average asymmetrical current.
Interrupting Rating
98
Non-overcurrent protection.
Class: Hi Shock MIL-S-901D,
50C ambient.
Outline Dimensions
NQB-A803 Dimensions
in Inches
Removable Terminal
Cover Must Be In
Place While In Service
2X .500-13 Tap
CL
3.23
.125 x .750
Slots for
Attachment
Wires
7.00
16.00
Overall
Length
.94
14.75
Centerline
of Mounting
Holes
Push
To
Trip
13 2
R 3.85
21 2
ON
.29
11.50
.53
Line End
9.25
8.62
1.15
Through for
Attachment
Leads
1.06
.750
.375
CL
0 2
Contact Position
Indicator
Red I/ON
Green O/OFF
White Tripped
3.81
2.79
CL
R .312
2.49
.35
.37
15 2
B
A
Handle
Pivot
.53
1.09
Removable
Terminal Cover
Must Be In Place
While In Service
1.37
2.75
2.34
Load End
8.25
2.98
1.03
3.34
5.18
5.24
5.50
6.00
7.12
Breaker
Status
Dimension
A
B
Handle Forces
In Handle at Center Line Hole
On
Off
Tripped
Reset
7.9
6.5
5.7
5.6
Off On
On Off
Trip Reset
8.3
6.9
6.1
6.0
130 Lb.
105 Lb.
160 Lb.
99
Types AQB-A1601,
NQB-A1601
Note:
AQB-A1601 are sold for replacement only. They are no longer on
the Navy Qualied Products List.
Specication: MIL-C-17361
Interrupting Rating
Note:
Breakers with ratings other than
those listed above are considered as special and full descriptive data must be provided.
TYPE
CONT.
AMPERE
RATING LOW
HIGH
TRIP UNIT
STYLE
NUMBER
NATIONAL
STYLE
STOCK NUMBER NUMBER
NATIONAL
STOCK NUMBER
372D522G02
372D522G02
372D522G02
372D522G02
372D522G02
372D522G02
372D522G02
372D522G02
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
372D523G01
372D523G03
372D523G07
372D524G03
372D524G05
372D524G07
372D524G09
372D524G10
5925-00-520-4743
5925-00-406-6131
374D211G01
374D211G07
374D212G03
374D212G05
374D212G09
5925-00-102-6086
5925-00-727-7574
374D221G01
374D221G07
374D222G05
374D222G09
5925-00-727-7555
5925-00-103-4248
AQB
AQB
AQB
AQB
AQB
AQB
AQB
NQB
600X
600XM
800X
1000X
1200X
1400X
1600X
1600
2000
4000
2000
2000
2000
4000
4000
6000
12000
6000
6000
6000
12000
12000
With Delayed Instantaneous Trip (XT1 Minimum Time Delay .0417 .0458 Seconds)
Breaker and Mounting Base
AQB
AQB
AQB
AQB
AQB
500XT1
800XT1
1000XT1
1200XT1
1600XT1
2000
2000
2000
2000
4000
6000
6000
6000
6000
12000
372D522G02
372D522G02
372D522G02
372D522G02
372D522G02
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
With Delayed Instantaneous Trip (XT2 Maximum Time Delay .0750 .0708 Seconds)
AQB
AQB
AQB
AQB
100
500XT2
800XT2
1200XT2
1600XT2
2000
2000
2000
4000
6000
6000
6000
12000
372D522G02
372D522G02
372D522G02
372D522G02
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
5925-01-105-4401
Mounting Base
Electrical Operator
Undervoltage Release
Individual Reproductions
Note:
Breaker can be supplied with
either shunt trip or undervoltage
release, but not both.
Auxiliary Switch
120 Vac
450 Vac
NATIONAL
STOCK
NUMBER
1371D38G06 None
1371D38G08 Assigned
Optional Additions
Note:
Can be eld mounted. Consult
factory for information.
Cable Connector
Mounts to bus connector for
cable connection. Each lug
accepts four cables, 600 kcmil
maximum 1 lug required per bus
connector.
Style Number: 505C706G03
Fungus, Moisture-Resistant
Treatment
(JAN-C-173 or MIL-V-173):
If specied, contact Eaton.
External parts are coated; trip
units are not treated.
Drawings
Master plan: 900J442
Shunt Trip
Mounts in right pole only. Has
momentary rating only; coil leads
must be wired in series with 1A
contact of auxiliary switch. (28
Vdc/120 Vac or 120 Vdc/450 Vac.)
TYPE REPRODUCTION
Vellum
Prints (Paper)
Technical Manual
NAVSHIPS No. 0962-014-5000.
This booklet per MIL-M-15071.
When required, order BVR-TM576.
Dimensions: Pages 102, 103,
104, 105 and 106.
Characteristic Curves:
Pages 107 and 108.
NET WEIGHT, LBS.
DESCRIPTION
Breaker Only
AQB
NQB
Breaker Frame
(AQB and NQB)
Trip Unit
AQB
NQB
Mounting Base Only
Electrical Operator, 115 Volt
Electrical Operator, 450 Volt
Shunt Trip
Undervoltage Release
Auxiliary Switch
Cable Connector
WEIGHT
151
148
128
23
20
75
27
35
3/4
1-1/4
1-3/4
3
Note:
Breaker can be supplied with
either shunt trip or undervoltage
release, but not both.
101
Types AQB-A1601,
NQB-A1601
4-1/2
3-3/4
Removable Handle
Extension Supplied
with Breaker
12
6
1-1/8
Mounting Screws
3-25/32
4-1/2
2-1/4
Line
6-1/4 R
3-1/2
5
13-5/8
6-1/4
18 On
14-3/8
3 Tripped
T
5-19/32
3/8-16 Thd.
4 Screws
12 Off
f
22
18
M
10-1/2 R
Mounting Screws
l
6-1/8
B
C
CLof Breaker
2-11/32
Top End of Breaker
4-11/16
3-21/32
7-25/32
6-7/16
5/16 Radius
6-21/32
102
m
9
4-3/4
7-7/8
11
Load
9-7/8
Wiring Diagrams
Line
Line
Load
Load
AQB
NQB
4 A and 4 B
and
16 Leads 18" Long
Switches 16
Leads 18" Long
Shunt Trip
2 Leads
18" Long
Undervoltage
Release 2 Leads
18" Long
103
Types AQB-A1601,
NQB-A1601
Outline Dimensions
Mounting Base
Dimensions in Inches
2-1/2
3/4
4
1
7/16 Dia.
1-1//2
1-1//2
1-1/16
3/4
5-1/8
Switchboard
Mounting Angle
4-5/8
1/4 13-5/8
Switchboard
Back Panel
1-25/32
MOUNTING BASE
12-7/16
TOP VIEW
1-25/32
13/16
14-3/8
4
9-3/8 Approximate
All Connectors
May Be Rotated 90
1-9/32
3/32
Switchboard
Front Panel
6-13/16
Line
Stab
22-1/4
6-13/16
14-3/8
4-11/16
6-5/16
3/4
6-1/8
Load
Stab
16
1-1/4
1/4
14-3/8
7-3/16
CLof Breaker
13/32 Dia.
8 Holes
4-11/16
3-21/32
6-13/16
22-1/2
7-25/32
6-13/16
6-1/8
6-7/16
Outline of
Mounting
Base
5/16 Radius
1/8
104
19/32
SIDE VIEW
FRONT VIEW
6-7/16
12-7/8
BACK PANEL
1-3/8
6-21/32
4
8
3 Holes for
Megger Test
5/16 Diameter
Outline Dimensions
Electrical Operator
Dimensions in Inches
Line End
12
ripped
3/4 Dia.
22
12 Offf
15-7/16 Rad.
Reset
M
11
Removable Handle
Used for Manual
Operation Only
Load End
AQB-A1601 Breaker
Wiring Diagrams
5-19/32
Y w
Yello
Motor
NC COM
Black
120 Volts
ac Suppl y
1 Line Off On
Brown
COM
Terminal Blocks
T
LS2
Automatic Reset
Switch (Optional)
Off/Reset
On
Y w
Yello
NC COM
120 Volts ac
Motor
450 Volts
ac Supply
Black
Brown
COM
Terminal Blocks
T
LS2
Automatic Reset
Switch (Optional)
Off/Reset
On
105
Types AQB-A1601,
NQB-A1601
Cover Plate
(Picture on 1
Right)
Mounting Holes
for Mounting Base
1/2
Cutout
9-1/2
8-1/2
Provisions Required
for Removable
Handle Storage
5-1/8
1/2
7-3/16
Insert Handle Here
CL of Breaker
3/16-32 Tap
(2) Holes
Gasketed Cover
1/2
10-1/2
9-1/2
Captive Screw
1-1/2
3
GASKETED COVER FOR
SWITCHBOARD DOOR CUTOUT
(GASKET CEMENTED TO COVER)
Electrical Operator
NOMINAL
VOLTAGE
VOLTAGE
RANGE
STYLE
NUMBER
120 Volts ac
450 Volts ac
90 130
360 500
1371D38G06
1371D38G08
106
1 HOUR 2 HOURS
500
300
200
500
300
200
100
60
30
20
10
2000
6000
5
3
2
30
20
10
4000
12,000
1.0
20,000
7,000
10,000
4,000
5,000
2,000
3,000
Amperes Times 10
700
.001
1,000
20,000
7,000
10,000
300
200
150
100
Without Ti
.01
300
400
500
.1
.05
.03
.02
.05
.03
.02
200
Minimum Time
Delay Unit
150
.5
.3
.2
Minimum Time
t
.1
70
1.0
Maximum Time
Delay Unit
r
alues
Time in Seconds
See Ta
.5
.3
.2
Instantaneous Trip
100
5
3
2
Time in Seconds
Minimum
1,000
100
60
.01
Maximum
5.000
3,000
2,000
1 MINUTE
Minimum
1,000
4,000
5,000
60 cycles.
10,000
Maximum
2,000
5.000
3,000
2,000
3,000
Cold start.
1 MINUTE
10,000
700
1,000
400
500
Operating Characteristics
1 HOUR 2 HOURS
Characteristic Time-Current
Curves
PERCENT OF
TRIP ELEMENT
RATING
TRIPPING
TIME
600
225
150
20 to 60 Seconds
Less Than 1 Hour
1 Hour or More
AMPERE
RATING
LOW
HIGH
500XT1
500XT2
600X
600XM
800X
800XT1
800XT2
1000X
1000XT1
1200X
1200XT1
1200XT2
1400X
1600X
1600XT1
1600XT2
2000
2000
2000
4000
2000
2000
2000
2000
2000
2000
2000
2000
4000
4000
4000
4000
3600
3600
3600
7500
3600
3600
3600
3600
3600
3600
3600
3600
7500
7500
7500
7500
4000
4000
4000
8000
4000
4000
4000
4000
4000
4000
4000
4000
8000
8000
8000
8000
4800
4800
4800
10,000
4800
4800
4800
4800
4800
4800
4800
4800
10,000
10,000
10,000
10,000
6000
6000
6000
12,000
6000
6000
6000
6000
6000
6000
6000
6000
12,000
12,000
12,000
12,000
107
Types AQB-A1601,
NQB-A1601
Characteristic Time-Current
Curves, Continued
100
90
80
Application
70
1. Known Conditions:
(A) Ambient
(B) Load Current
60
50
40
Ambient Te
30
20
10
0
0
.5
Factor
1.0
1.5
2.0
DERATING CURVE
2. Known Conditions:
(A) Ambient
(B) Load Current
To determine the load current on which a trip unit may
be used when ambient is
known, divide the trip unit
rating by the value obtained
from this curve for the
known ambient. The result
will be the maximum load
current on which the trip
unit should be used.
108
Types AQB-A1602,
NQB-A1602
Ratings
AQB-A1602, NQB-A1602.
Affordable.
6591C33H01
Applications
50 kA symmetrical rms,
0.3 seconds short-time
withstand rating.
1376D08
Technical Manual
Master Drawing
85 kA symmetrical rms
interrupting rating or 100 kA
asymmetrical rms.
Outline Drawing
1377D30
Features
109
Types AQB-A1602,
NQB-A1602
TYPE
STYLE
NUMBER
NATIONAL
STOCK NUMBER
6649C53G01
6649C53G02
6649C53G03
1377D26G01
6605C06G02
6635C58G12
6635C58G11
6635C58G10
6635C58G09
6635C58G08
6635C58G07
6635C58G06
6635C58G05
6635C58G04
6635C58G03
6635C58G02
6635C58G01
6591C53G01
6591C53G02
6591C54G01
6591C25G51
6591C25G51
5075A33H01
6591C55G01
6591C56G01
1375D91G01
5925-01-437-3920
110
17.00
8.50
.688
Hole 2 Per
Conductor
8.63
Connectors Can
Be Installed in
the Horzonal or
Vertical Position
17.25
CL Breaker
15.00
7.50
.531
.75
17.47
.75
.31
23.00 Rail
Extention
21.50
In Stored
Position
CL
Breaker 9.50
20.11
12.50
6.25
11.50
16.80
23.31
47
12.72
18.00
15.00
13.00
7.50
6.50
10.05
4.38
.531
4 Holes
13.50
6.86
20.30
5.12
CL
Breaker
10.25
21.50
10.15
10.75
CL
Breaker Front Panel Cutout
CL
Breaker Back Panel Cutout
NET WEIGHT
DESCRIPTION
NET WEIGHT,
LBS. (KG)
Circuit Breaker
Motor Operator
Mounting Block
Front Connected Terminals (Set of Three)
159 (72)
145 (66)
80 (36)
5 (2)
111
Type AQB-A1602
Characteristic Time-Current
Curves
Navy Type AQB-A1602
Circuit Breaker
.5 .6 .7 .8 .9 1
1,000
900
800
700
600
6 7 8 9 10
20
30
500
400
Amperes
300
200
100
90
80
70
60
Maximum
Trip Time
50
40
30
Plug Rating
(amperes)
6635C58G01
6635C58G02
6635C58G03
6635C58G04
6635C58G05
6635C58G06
6635C58G07
6635C58G08
6635C58G09
6635C58G10
6635C58G11
6635C58G12
1600
1400
1200
1000
900
800
800
700
640
560
480
400
Minimum
Trip Time
Note
Trip units are suitable for functional field testing with Test Kit Cat.
No. STK2. For field testing using primarily injection method follow
NEMA publication AB-2-1984.
20
10
9
8
7
6
2.5X
5
4
3
2X
TIME IN SECONDS
Style No.
8X
1
.9
.8
.7
.6
1
.9
.8
.7
.6
7X
4X
300 MS
.4
3X
.5
.3
.2
100MS
.1
.09
.08
.07
.06
.05
TIME IN SECONDS
.2
200 ms
200 MS
4X
.3
300 ms
.5
6X
.5
100 ms
.1
.09
.08
.07
.06
Fixed Instantaneous
Overide (Factory Selectable at 10X,
15X, or 20X)
.05
.04
6 7 8 9 10
20
30
.01
8 9 10
112
20
30
40 50 6070 8090
600
700
800
900
1000
500
.01
.5 .6 .7 .8 .9 1
400
.02
300
.03
.02
200
.03
100
.04
Types ACB
1600/2000HR
3200/4000HR
113
Types ACB
1600/2000HR
3200/4000HR
ACB 1600/2000HR
3200/4000HR Breakers,
Continued
Directly beneath the operating
mechanism is the solenoid
closing coil mechanism which
provides the closing force for
electrical closing of the circuit
breaker.
NET WEIGHT
114
DESCRIPTION
NET WEIGHT,
LBS. (KG)
2000 A Breaker
2000 A Cassette
4000 A Breaker
4000 A Cassette
318 (144)
180 (82)
658 (299)
495 (225)
Outline Dimensions
ACB 1600/2000HR Breaker
Dimensions in Inches
11
9-1/2
1-1/2
Solid-State
Sensors
11
9-1/2
8 Holes
3/8-16 UNC Tap
10
0
4-1/2
29-1/8
24-5/8
8
27
20-1/2
0-1/2
11-1/
11-1/2
14
5-1/2
2
4-1/2
3
6
6
19
9
Secondary
Disconnects
2-1/2
Cut-Out in Switchboard
From Door
REAR VIEW
FRONT VIEW
20-15/16
4-1/2
3/4
Exhaust V
Vent This Area
to Be Kept Clear
3/4
11/16 Dia.
T
Typical
3-1/2 x 1/2
Thick T
Typical
3/4
Lifting Point
3-3/8
-3/8
Solid State
Sensors
19-1/8
9-1/
4 Holes
13/16 Dia.
10
1-3/4
8 3/8
8-3/8
8 3/8
8-3/8
1-3/4
115
Types ACB
1600/2000HR
3200/4000HR
Outline Dimensions
ACB 3200/4000HR Breaker
Dimensions in Inches
Exhaust Vent
This Area to
Be Kept Clear
12-7/8
11-5/8
1-1/8
11-5/8
7
6 Holes
9/16 Dia.
9 15/16
9-15/16
10
4-7/8
26-3/8
8
30-1/2
25-1/
25-1/2
17-1/2
2
11-1/
11-1/2
4-1/2
-1/2
Solid
State
Sensors
23-1/4
/
Area to Be Kept Clear
5-5/8
8
3
Secondary
3-5/16 Disconnects
REAR VIEW
15
FRONT VIEW
25-3/8
Clearance to Remove from Switchboard
Exhaust Vent This
A
22-1/4
T
Bus Connections
4 5 x 1/4
19-3/8
Maintenance Position
1
27
1-1/4
5 Typ
4-7/8
11/16 Dia.
Typical
4-1/2
Lifting Point
25-1/4
3-7/8
8 Holes
13/16 Dia.
1-3/4
6-5/16
5-3/8
3-7/8
5-3/8
6-5/16
Solid State
Sensors
116
1-3/4
Characteristic Time-Current
Curve
1000
1
9
5 6 7
91
5 6
8 91
5 6 7 8 91
5 6 7
7
6
5
7
6
5
100
1
9
8
7
6
5
1
9
8
7
6
5
Time In Seconds
10
1
9
8
7
6
5
1
9
8
7
6
5
1
9
8
7
6
5
1
9
8
7
6
5
Note:
Bands Include Manufacturing
To
Temp.
E
0.36
.01
1
9
8
7
6
5
1
9
8
7
6
5
1
1
0.1
5 6 7
91
5 6
8 91
1.0
5 6 78
10
5 6 7891
100
g
Example of T
Typical Settings:
Short
117
Notes
118
PowerChain Management
solutions help enterprises
achieve sustainable and
competitive advantages through
proactive management of the
power system as a strategic,
integrated asset throughout
its life cycle, resulting in
enhanced safety, greater
reliability and energy efficiency.
For more information, visit
www.eaton.com/electrical.
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
2010 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. PG01218003E / Z9397
January 2010