DC Switchgear
ETGR 21 & 22 Series

Ver. 3.0

DC Switchgear
for Railway System

Future would be derived by ENTEC s advanced


technology and endless study from DC Switchgear
in main core of Metro Power System.

DC Switchgear is the Major Equipment for Safe Operation in DC Railway


System. ETGR 21 & 22 series have been designed for DC Railway Substation,
and also designed to be affordable in heavy conditions.
ETGR 21 & 22 are optimized in order to be installed in any place with easy
handling. And the users safety is maximized by restrictedly distinguishing
all components upon adequate Insulation Voltage level.
HSCB (High Speed Circuit Breaker), DC Switchgear main component is
approved in their safety and reliability by passing International Independent
Laboratory test in IPH (CESI Group Company in Germany) in accordance with
IEC Standard.
ENTEC ETGR 21& 22 are divided into DC 1800[V] for Urban Subway System
and DC 900[V] for Light Railway System.

2 ENhanced TEChnology

Characteristics
Current Interruption
Outstanding interruption of small current(0~500A) and Mid-low current (500~3,000A).
All range of small current, load current, fault current upto rated interrupting capacity are able
to be quickly and safely managed without having any blind current range at rated voltage.

High quality DC high Speed Circuit Breaker(HSCB) and


DC Disconnector application
High quality of HSCB and DC Disconnector are evidenced by completing International
authorized Laboratory test according to International standards.

Digital Protection relay application


Fast and precise operation capability by using Digital Protection Relay in case of various
power fault. Short circuit or heavy current are managed by mechanical OCR
inside of breaker as instantaneous trip.

Information storage
System event(1,000 events), fault record(100 events, 16 waves, 0.1~6,000ms sampling) can
be stored in Digital Protection Relay and System control and management efficiency is
increased by having Protocol communication (DNP 3.0 , Modbus, IEC 60870 and etc.)
through SCADA RTU.

Cubicle inside Insulation


Through insulated barriers inside of cubicle, frame fault by Arc spewed out from CB arc
chamber is eliminated and it is even possible to maintenance job for live line work.

Convenient Handling of withdrawal type CB truck


- Four insulated rubber wheels(front : 2 free wheels, rear : 2 fixed wheels) are used and it is
easily engaged with main power Bus.
- Manual and Automatic withdrawable truck operations are available between service and
test position .

Compact design
The most advanced technology PMA is built inside of Circuit Breaker and compactsize of
Disconnector is combined in order to optimize the cubicle space use and switchgear.

Interlocks
To prevent any incident from mis-operation, Interlock mechanisms are applied among
HSCB, Disconnector and panel.

Operation reliability
Both of HSCB and Disconnector are adequate for high frequent operational duties.

ENhanced TEChnology 3

Product construction

9
6
3
7
10
5

1
4

DC HSCB(Incl. truck)
Fast fault current clearing in
a fault occasion.
Several Interlock funtions are
applied in Circuit Breaker.

Surge Arrester
Surge (Lightening Surge,
Inductive surge) prenvention.

FaultselectiveRelay(50F)
Determine faults and operate
Circuit Breaker (Digital type).

64HR (Current type)


Monitoring between DC live
bus and enclosure, Protect
earth current.

DC Power meter (kWh)


Power consumption calculation.

DC Disconnector
Power line close and open
when no load.

DC CT
Current Sensing.

DC PT
Primary voltage sensing.

4 ENhanced TEChnology

64P (Voltage type)


Monitoring earth voltage potential
increasing and protect system.

Communication Device

Rating and Operation

Ratings
Model
Nominal Voltage
Rated Voltage
Insulation Voltage
Rated interrupting over voltage
Rated current
Rated making and breaking capacity
Operation duty
di/dt (Current rising rate vs time)
Mechanical operation
Power frequency withstand voltag (60Hz,1min.)
Rated operation and control voltage
Over current Release Pick-up
Max. Ambient Temp / Avg. Temp.
Altitude
Size [Width x Depth x Height mm]
Weight [kg]
IP protection (IEC 529)
Applied standard

ETGR 21

ETGR 22

DC 750V
DC 900V
DC 1,800V

DC 1,500V
DC 1,800V
DC 3,000V
1.5 ~ 2 x rated voltage
2,000A / 3,000A / 4,000A

133kAp /91.2kA
110kAp /76.8kA
O-15sec-CO-15sec-CO-60sec-CO (max fault, max energy, distant fault)
24.2 x 10 6A/S
30.7 x 10 6A/S
40,000 times
11kV
5.5kV
DC 110V / 220V
5 ~ 15kA
40 / 35
2,000m
Rectifier, Feeder (600 x 1,800 x 2,200 / 600 x 1,500 x 2,200)
Negative (1,500 x 1,800 x 2,200 / 1,200 x 1,200 x 2,200)
700
650
IP31
IEC 61992, JEC 7152 etc

Option Size [Depth] : 1,900mm(When adding a function of automatic withdrawal, for other sizes, discuss with maker)

Operation
Electrical operation

Mechanical Operation

Trip by protection Relay System

Manual Closing Device(DC HSCB)

(Fault selective Relay, DC Ground Relay, Under


voltage Relay, Reverse Current Relay, OCR,
Intertripping Signal Relay, Lock-Out Relay)

By attaching the removable manual closing device HSCB


can be closed when there is no external power supply.

Trip by Direct Fault Current


Local Close/Open
Remote Close/Open

Manual Trip Device(DC HSCB)


For trip HSCB manual tripping can be operated by manual
Handle of front Panel. Circuit Breaker can be drawn out and
inserted only on the HSCB Tripped Status in DC Cubicle.
20[kg] is required for Manual Tripping Handle.

Manual Close/Open(DC DS)


When DC Control Power is missing, it is possible to Close
or Open Disconnected Switch(DS) using Manual Handle
itself.

ENhanced TEChnology 5

Protection System
Configuration

76I

Other communication available upon user request.

6 ENhanced TEChnology

76I
76D
85
45
82
80

76I
76D
85
45
82
80

Standard type and Test Graph

Standard type

76I
76D
45
82
80

Panel Type

Rectifier

Feeder

Spare

Tie post

Neg. DS

Width [mm]

600

600

600

600

1,500

Other application available upon user request.

Test Graph

DC HSCB CO Test
Oscillogram (Interruption, 110 [kA])

Disconnector Test
Oscillogram (Short time current, 106.5 [kA, peak])

ENhanced TEChnology 7

DC High Speed
Circuit Breaker (DC HSCB)
DC HSCB is used to manage DC Power Feeding line and interrupt a fault current.
EDB Series is designed with the most advanced technology in order to protect Railway system
from abnormal phenomenon of Power feeding system.
Under high frequent switching and heavy load condition, EDB Series DC HSCB is the most reliable.
EDB Series has rated voltage of DC 900V for light weight railway system (EDB-09) and rated voltage
of DC 1800V for Urban railway system.

Ratings
Model
Nominal voltage
Rated voltage
Rated current
Rated interrupting over voltage
Operation duty
Mechanical Operation
Rated making and breaking capacity
Rated operation voltage
Insulation Phase-Phase
Phase-Ground
voltage
Control Circuit
Over current trip device(76I)
Size[Width x Depth x Height]
Applied standard

EDB-09

EDB-18

DC 750V
DC 1,500V
DC 900V
DC 1,800V
2,000A /3,000A /4,000A
1.5~2.5Ue
O-15sec-CO-15sec-CO-60sec-CO
(max fault, max energy, distant fault)
40,000 times
133kAp /91.2kA
110kAp /76.8kA
DC 110V / 220V
AC 11kV/1min
AC 9.2kV/1min
AC 2kV/1min
5~15kA
345913831.5
345913881.5
IEC, JEC

Characteristics
Enhanced small current interruption
Own patent of small current interruption technology apply. Through capability of clearing all ranges
of current(0 Amp~Rated making and breaking current), eliminates blind spot of system protection.

High Durability and Reliability


The most reliable and simplest Magnetic Actuator Mechanism application, over 40,000 times
of operation and high speed overcurrent tripping are encountered.

Quality Assurance
International authorized laboratory(IPH CESI, KERI) type test was successfully completed
with International standard(IEC).

Sufficient current and thermal capacity


Sufficient electric current capacity to keep lower then regulated temperature (85) when
rated current becomes saturated.

High Insulation capacity and increased interruption capability


Sufficient insulation capacity(AC 11kV) to protect users from abnormal condition and
increased electric current capacity and interruption capacity of Breaker to comply in large
capacity of heavy load DC system.

Optimized design with simple structure


CAD and 3D design contributes more optimized structure design and convenient maintenance.

Panel Interface
Simple interface structure between Panel and Protection Relay.

ENhanced TEChnology 8

ETCPU200

Overview
DC protection relay ETCPU200 includes Fault Selective Relay(50F), Overcurrent Relay(76D),
Voltage Relay(45,80), Ground Fault Relay(64P) and Reclosing Relay(82) in order to protect
Metro DC system.
For remote control and monitoring DNP3.0, IEC60870, MODBUS and etc. protocols are used.

54F LINE FEEDER

ETCPU200 Panel

HMI(Human Machine Interface) Panel

Features

ETCPU200

Consist of DC protection relay(ETCPU200) and Human Machine Interface(ETCPU200HMI).


Monitoring function - Current, Voltage, Delta-I, di/dt etc.
4 Analog input port - Feeder current, Voltage, Rectifier voltage, Compensation current.
(Option: 4 user channel)
Storage function - Operation and Fault event, Fault waves, Load waves etc.
ETCPU200 has PLC function.
Communication port: 4, PLC port: DO: 24, DI: 40.
Human Machine Interface - Graphic LCD 240 x 128 Dot (English, Chinese and Korean font)
HMI uses 485 communication and remote monitoring is available.
User Interface PC Software available upon newly Window OS
System event(1,000events), Fault event(100events), Fault wave(16waves, 0.1~6,000ms), Load
profile (42days / daily: 3years) are downloaded and manageable by user Interface Software.

ENhanced TEChnology 9

DC Disconnector
DC Disconnector is used for no load switching in DC feeder system.
ET-DS design is compact and optimized in order to apply DC panel and Other applications.
In addition, sufficient insulation capacity and electric current capacity increase the product safety.
Fast operation time accommodate the user convenience.

Ratings
Model

ET-DS

Nominal voltage
Rated voltage
Rated current
Rated short time current
Operation voltage
Operation method
Mechanical Operation
Operation time
Insulation Phase-Phase
Phase-Ground
voltage
Control Circuit
Size[Width x Depth x Height]
Weight
Applied standard

DC 750/1500V
DC 900/1800V
2,000A/3,000A/4,000A/5,000A
106.5kAp / 75kA
DC 110V / 220V
Auto / Manual
100,000 times
Below 2sec
AC11kV/1min
AC9.2kV/1min
AC 2kV/1min
300507450mm
32kg
IEC

Characteristics
High durability and reliability
Regular operation time and good electrical mechanical characteristics by using of
high quality materials.

Reduction of Closing and Opening time


Fast operation by reducing time of opening and closing with adopting relevant Motor Gearbox.

High grade Insulation and Sufficient electric current capacity


Sufficient current capacity and high grade insulation to protect users from
abnormal condition.

Compact and light weight


Size and weight are compact and more optimized in order to provide more convenience
in handling.

Various operation method


Normally use electrical operation however manual operation of DC Disconnector is
accomplished in case of unstable power source or power-off.

Various installation arrangement


Free Installation directions to accommodate convenience in construction.

Interlock provision
To prevent mis-operation, interlock function are applied with Manual Lock and Position Lock.

Ver. 3.0