Intrinsically explosion-proof and safety barrier introduction

Summary of Topics
1. Explosion basic knowledge
2. Explosion groups
3. Zone classification
4. Explosion-proof electrical apparatus design standards
5. Explosion-proof mark of different countries
6. Explosion-proof type of electrical apparatus
7. The basic principles of the intrinsically explosion-proof technology
8. The feature of the intrinsically explosion-proof technology
9. Intrinsically safety apparatus and associated apparatus
10. Intrinsic safety electrical apparatus type
11. Marking of apparatus
12. The basic components of intrinsically safe explosion-proof system
13. Safety barrier
14. Guidelines for use of devices with intrinsically safe circuits

Page
1
1
2
3
3
3
4
4
5
5
6
7
9
11

1. Explosion basic knowledge


Explosion is that the material produces a high-speed exothermic reaction. In order to have an explosion,
the following three components must be present simultaneously:
NO.

component

interpretation

Fuels (flammable
substances)

Flammable concentrations of gases and vapours or solids which have the


potential for igniting an explosion

Oxidizers

air (21 % Oxygen), pure Oxygen, oxygen releasing compounds (i.e. potassium
manganate)

Possible sources
of ignition

hot surfaces, flammable or explosive gases, mechanically generated sparks,


electrical installations, transient currents, static electricity, lightning,
ultrasonic energy...

Explosive limits

A mixture is only explosive when its concentration falls within certain


material specific limits. These limits are called the upper and lower explosive
limits and are listed in according tables.

2. Explosion groups
GB3836-2000 ordains that combustible materials are divided into the following classes in accordance with
the degree of the inflammable hierarchy.

Factory type

Classification
of the gases

Representative
gases

The min. energy


detonating the spark

Inflammable
hierarchy

Underground the miner

Methane

0.280mJ

he factory outside miner

Propane

0.180mJ

Difficultly

Page 1 of 12

Ethylene

0.060mJ

Hydrogen,
acetylene

0.019mJ

easily

The United States of America and Canada (NEC500) divide the explosive objects spreading in the air into
three classes firstly. The CLASS are gas and vapour. The CLASS is dust. The CLASS is
fiber. Then divide the gas and vapour into Group:
Class

CLASS

CLASS
CLASS

group

Representative gases or
dusts

China/IEC/European countries corresponding


class (GB3836.1/IEC60079-0/EN50014)

Acetylene

C (Hydrogen, Acetylene)

Hydrogen

C (Hydrogen, Acetylene)

Ethylene

B (Ethylene)

Methane

A (Propane)

Metal dusts

(Methane)

Coal dusts

Grain dusts

No grouping

To be determined()

3. Zone classification
According to EN 60079-10 and EN 1127-1 explosion hazardous areas are divided into zones such as
flammables gases, vapours, mists and combustible dust. The classification is based on the likelihood that a
dangerous explosive atmosphere occurs. The ATEX directive has re-defined the zone division as follows:

China
IEC
European
Union

Likelihood of an
explosive
atmosphere:
occasionally

Likelihood of an
explosive
atmosphere: unlikely
or infrequently - for a
short period only

European
Union

constant or long
term corresponds
to > 1000 h/year

occasionally
corresponds to
10...1000 h/year

seldom or short term


corresponds to < 10
h/year

gases and
vapours

zone 0

zone 1

zone 2

dusts

zone 20

zone 21

zone 22

Description

Zone
classification

North
America

China

Likelihood of an
explosive
atmosphere :
occasionally
continuously, for
long periods or
frequently

Description

Page 2 of 12

Under normal operating conditions, it


continuously, intermittently or
periodically exist the flammable gas
or vapor and the concentrations reach
a dangerous level.

The flammable gas or


vapor will release and
become dangerous
only when the
container rupture, the
system is failure or the
equipment anomalies

abnormal operate
occasionally.
Zone classification (gases
and dusts)

Div.1

Div.2

4. Explosion-proof electrical apparatus design standards


country

Standards Code

Standards Name

GB3836.1-2000

Electrical apparatus for explosive gas


atmospheres--Part 1:General requirements

GB3836.4-2000

Electrical apparatus for explosive gas


atmospheres--Part 4:Intrinsic safety

Country Standards

IEC60079-0:1998

IEC

IEC60079-11:1999

European Committee for


Standardization(CENELEC)

EN 50020

North American (America,


Canada)

NEC500

Intrinsic safety

Country Standards GB3836-2000 is equivalent to adopting IEC 60079.


5. Explosion-proof mark of different countries
mark

signification

Ex

Explosion-proof mark of China and IEC

EEx

European economic community

AD

Italy

MSAE

France

FLP

Great Britain

ULFM

America

Germany \IEC

China National Quality Supervision and Test Centre for Explosion Protected Electrical Products (CQST):
CQST is one of the China famous professional testing and certification authorities and engages in safety
test, examination and evaluation of Ex electrical products. CQST has made deep research and obtained
extensive experience in the field of explosion protection electric safety technique and has a high reputation
in the word.
CQST has signed the cooperation agreements of mutual acceptance of test results separately with more
than ten international wellknown Ex scientific research and test bodies, such as UL (U.S.A.), FM (U.S.A.),
PTB (Germany), NEMKO (Norway), testsafe (Australia), CCVE (Russia) and LCIE (France).These
cooperation have promoted the international exchange of Ex technique and offered convenient services for
sino-foreign Ex product entering into opposing side market.
6. Explosion-proof type of electrical apparatus
GB3836-2000 (Electrical apparatus for explosive gas atmospheres) defines as follows:
Page 3 of 12

code

type

standards

explosion-proof measure

flameproof

GB3836.2

Isolate the
existing

increased safety

GB3836.3

Try to prevent producing the


ignition source

Zone1,Zone2

ia

intrinsic safe

GB3836.4

Limit the energy of the ignition


source

Zone0-2

ib

intrinsic safe

GB3836.4

Limit the energy of the ignition


source

Zone1,Zone2

Pressurized

GB3836.5

Isolate the hazardous substance


and the ignition source

Zone1,Zone2

jelly filled

GB3836.6

Isolate the hazardous substance


and the ignition source

Zone1,Zone2

sand filled

GB3836.7

Isolate the hazardous substance


and the ignition source

Zone1,Zone2

non-sparking

GB3836.8

Try to prevent producing the


ignition source

Zone2

pour enveloping

GB3836.9

Try to prevent producing the


ignition source

Zone1,Zone2

hermetically sealed

GB3836.10

Try to prevent producing the


ignition source

Zone1,Zone2

ignition

application zone
source

Zone1,Zone2

For automatic control and instrumentation, intrinsic safe, flameproof and increased safety types are used
commonly.
7. The basic principles of the intrinsically explosion-proof technology
In electrical apparatus, electric spark and thermal effect is the main ignition sources that set danger
explosive gas off. The intrinsic safety methods are considered protection devices and their function is to
avoid possible errors and faults by preventing the transfer of unsafe levels of energy to the hazardous area.
Possible faults are: 1) Excessive voltage in the hazardous area. 2) High current levels in the hazardous area
(short-circuit).
The intrinsic safety method of explosion protection always relates to intrinsically safe circuitry that
comprises an intrinsically safe apparatus, an appropriate electrical power source and the connecting cables.
In intrinsically safe circuits, an explosive environment cannot be ignited by sparking or a thermal effect
when operating normally under prescribed fault conditions. In an intrinsically safe circuit for categroy ia, 2
calculable faults (see definition EN 50020) must not cause an ignition and in category ib only 1 such fault
is permissible.
Limiting the power supply, total inductance and total capacitance within the intrinsically safe circuitry is
the basic principle of the intrinsically safe explosion protection method. The project manager or user has to
compare the permissible internal limit values for intrinsically safe electrical apparatus with the permissible
connection values of the associated electrical apparatus.
8. The feature of the intrinsically explosion-proof technology

Page 4 of 12

Intrinsically safe explosion-proof technology is actually a low-power design technology. It is a very good
apparatus for the design of industrial automation instrument. Compared with other explosion-proof type,
using the explosion-proof electrical technology has following characteristics:
1. Intrinsically electrical apparatus have simple structure, small size, light weight.
2. Installation and maintenance can be with power input.
3. High security and reliability. Do not reduce the security and reliability of the electrical apparatus for
outside structural damage.
4. Applicable range is wide range. It is the only explosion-proof technology that can be applied in the
zone 0.
9. Intrinsically safety apparatus and associated apparatus
a. Intrinsically safety apparatus
In the conditions of the national standards, any spark and thermal effects produced by this electric
apparatus can not ignite the explosive gas environment It can be used in hazardous area.
It can be divided into general electrical apparatus and simple electrical apparatus.
General electrical apparatus: Has the energy storage element, need explosion-protection
authentication. Such as intrinsically transmitter, approach switch, and so on.
Simple electrical apparatus:If Voltage is lower than 1.2V, current is lower than 0.1A,energy is lower
than 20uJ or power is lower than 25mW, it is considered as simple electrical apparatus . Do not need
explosion-protection authentication, can directly access to the intrinsically explosion-protection
system. Typical feature as followers: Internal equivalent inductance Li = 0, Internal equivalent
capacitance Ci = 0. Common simple apparatuses are: thermocouples, thermal resistors, resistor, light
emitting diode, contact switch, and so on.
b. Associated apparatus (safety barrier)
It is an apparatus installed in a safety area, connecting the intrinsically electric apparatus and
non-intrinsically electric apparatus. Safety barrier limit the energy get in to the hazardous area in the
safety rang and ensure that the field equipment, personnel and production are safety.
10. Intrinsic safety electrical apparatus type
a. Apparatus groups
According to the principle of GB3836-2000, intrinsic safety electrical apparatus has 2 types as
follows:
Group

interpretation

Device Group I

For mining underground with a potential hazard due to firedamp and/or


combustible dusts.

Device Group II

For all other locations in which a potentially explosive atmosphere exists. There
are three class of A, B and C

b. Apparatus Category
Intrinsic safety electrical apparatus and associated apparatus can be divided into ia class and ib class
according to the places used or connected and the safety standards.
Code
Page 5 of 12

interpretation

ia

Very high level of safety: devices featuring two independent means of protection;
even in the event of rare device disturbances, the device remains functional and
maintains the requisite level of protection. It can be used in the hazardous areas of
zone0, zone1 and zone2.

ib

High level of safety: devices featuring one means of protection. Even in the event of
frequently occurring device disturbances or equipment faults which normally have to
be taken into account the device provides the requisite level of safety. It can be used
in the hazardous areas of zone1 and zone2.

c. Install temperature class


The temperature class indicates the maximum surface temperature of an apparatus and must be lower
than the minimum ignition temperature of the flammable material to prevent an ignition. The ignition
temperature (defined as the temperature at which a mixture self-ignites during testing) directly relates
to the temperature class. see table below.
temperature
class

Maximum surface
temperature

ignition
temperatures of
flammable materials

Common explosive gas

T1

450

450

Hydrogen, acrylonitrile,
etc. (46 kinds)

T2

300

300

Ethane, ethylene, etc.


(47 kinds)

T3

200

200

Petrol, crotonaldehyde ,
etc. (36 kinds)

T4

135

135

Acetaldehyde,
tetrafluoroethylene, etc.
(6 kinds)

T5

100

100

carbon disulfide

T6

85

85

ethyl nitrate and ethyl


nitrite

Electrical
safety

Low

High

Intrinsically safe equipment for direct installation in hazardous areas requires temperature
classification. For associated apparatus temperature classification is not needed.
11. Marking of apparatus
Equipment for explosion protected areas must be clearly marked. There are two different types of marking.
According to CENELEC marking of an apparatus conforming to EN 50014/20 must provide the following
information:
Manufacturers name or trademark
Part number
EEx-symbol
Ignition category (e. g. ia)
Designated group together with the respective subdivision (e. g. IIC)
Temperature class or maximum surface temperature (for group II devices only)

Page 6 of 12

Serial number (may be omitted if space is restricted)


Test authority, date and file number
X after the test certificate number indicates that special conditions must be met (see certificate for
special conditions)
An intrinsically safe apparatus could have the following marking:

Ex ia C T6
temperature class
explosion group
type of protection
conform to IEC or chian standard

An associated apparatus could have the following marking:


associated apparatus

[Ex ia]C
explosion group
type of protection
conform to IEC or chian standard

12. The basic components of intrinsically safe explosion-proof system


Hazardous Area

Intrinsically
Safety

apparatus

cable

Safe Area

Associated
apparatus
(safety
barrier)

Centralized
Control
System/
PLC/
Operation
Terminal

Intrinsically performance certification parameter of intrinsically electrical apparatus:


Maximal Input Voltage (Ui):The maximal voltage put on the intrinsically safety apparatus, and can not
lead to the intrinsically performance failure (AC peak or DC).
Maximal Input Current (Ii):The maximal current put on the intrinsically safety apparatus, and can not
lead to the intrinsically performance failure (AC peak or DC).
Maximum Input Power (Pi):The intrinsically current maximum input power that may consume in the
intrinsically safety apparatus inside when the intrinsically safety apparatus connects with the external
power and do not lead to the intrinsically performances failure.
Page 7 of 12

Maximum internal Equivalent Capacitance (Ci): Total equivalent capacitance inductance appearing by
the intrinsically safety apparatus.
Maximum internal Equivalent Inductance (Li): Total equivalent internal inductance appearing by the
intrinsically safety apparatus.
Intrinsically performance certification parameter of associated apparatus (safety barrier):
Maximal Voltage (AC RMS or DC Um):The maximal voltage put on the associated apparatus (safety
barrier), and can not lead to the intrinsically performance failure
Maximum Output Voltage (Uo):The maximum Output Voltage that may appear in the intrinsically
current when open circuit and the intrinsically safety apparatus voltage (including the Um and Ui ) is
maximal (AC peak or DC).
Maximum Output Current (Io):The intrinsically current maximum current that come from the
intrinsically safety apparatus (AC peak or DC).
Maximum Output Power (Po):The intrinsically current maximum power that can from the intrinsically
safety apparatus.
Maximum external Capacitance (Co):The intrinsically current maximum capacitance that can connects
to the intrinsically safety apparatus and do not lead to the intrinsically performances failure.
Maximum external Inductance (Lo):The intrinsically current maximum inductance that can connects to
the intrinsically safety apparatus and do not lead to the intrinsically performances failure.
Patch cable:Intrinsically cable is a low capacitance and low inductance cable. Compared with other cable
has excellent shielding and anti-interference performance. It suits for explosion hazardous area and having
high explosion-proof security requirement. Its intrinsically performance as follows:
Maximum distribution capacitance that the cable allow: Cc = Ck * L
Maximum distribution inductance that the cable allow: Lc = Lk * L
Ck Distributed capacitance per unit length of the cable
Lk Distributed inductance per unit length of the cable
L The actual length of the cable
The various configuration of the intrinsically explosion-protection system must meet the following
conditions:
1. The explosion-protection mark class of the intrinsically safety apparatus can not higher than the
associated apparatus (safety barrier).
2. Authentication parameters have to satisfy the following inequality between the associated apparatus,
intrinsically safety apparatus and the cable.
Associated
apparatus

Demonstration of intrinsic
safety apparatus

Intrinsically safe
apparatus + cable

Uo

Ui

Io

Ii

Po

Pi

Co

Ci + Cc

Lo

Li + Lc

Page 8 of 12

13. Safety barrier


Some special industrial fields not only need the two-wire transmission for signal isolation and providing
power input, but also need the explosion-protection performance about safety spark-proof and reliably
avoiding the high voltage and signal contacting. Using the current and voltage double limiting loop,
limiting the energy getting into the hazardous area lower than the ration, these can improve the
explosion-protection performance of the intrinsically system, at the same time increase the
anti-interference ability greatly enhanced the reliability greatly of the system. These field products having
specific function are safety barrier.
Safety barrier is used in the design of an intrinsically explosion-proof system. It is installed in a safety area.
Safety barrier is an apparatus with intrinsically current and non-intrinsically. These current limits the
energy get in to the hazardous area by limiting the current and limiting the voltage, then avoid the
hazardous energy enter into the hazardous area. Safety barrier is named associated apparatus, it is an
important component of the intrinsically system.
Because the safety barrier is designed as an interface between the field apparatus and the control room
apparatus, no matter the control room apparatus is in normal or fault, safety barrier both can ensure the
energy send to the field through it is intrinsically safe.
According to signal direction, Safety barrier have two types as follow:
. Detection type safety barrier:
Detection type safety barriers usually are used with the transmitter at hazardous area. The functions as
follow: a. Convert the signal from the hazardous area to standard current or voltage signal, isolate,
and transmit it to safety area. B. Limit the risk energy getting into s hazardous area from intrinsic
safety terminal. C. Give isolation power distribution to the field transmitter.
. Operation type safety barrier:
Operation type safety barrier usually are used with the current to pneumatic converter or electric
appliance valve positioner at hazardous area. The functions as follow: a. Isolate and transmit the
current signal from the safety area to the hazardous area, and driver the field actuating element
(current to pneumatic converter ), etc. b. Limit the risk energy getting into s hazardous area from
intrinsic safety terminal. C. Give isolation power distribution to the safety area.
Safety barrier can be devided into zener safety barrier and isolation safety barrier according to
construction.
. Zener safety barrier
The current uses the rapid fuse, current-limiting resistance or voltage-limiting diode to limit the input
energy, thus ensue the energy output to the hazardous area. The principle as follows:
Hazardous
Area

Safe
Area

Zener safety barrier have simple principle. Its current can achieve easily and the price is cheap. But the
Page 9 of 12

application reliability is affected greatly for its principle defect and this limits its application range. The
reason as follows:
a. Installation location must have reliable ground system, and the ground must be less than 1,
otherwise it would lose the explosion-protection performance and reduce signal anti-interference
capacity directly, affect the stability of the system.
b. The instrument from hazardous area must is isolation type, or the signal connected to the ground by
the ground terminal of the zener safety barrier can not transmit correctly, and because of signal
grounding, it will reduce signal anti-interference capacity directly, affect the stability of the system.
c. Zener safety barrier has greater impact on the power supply, at the same time it can be damaged
easily for the instability of the power supply.
d. Using zener safety barrier, signal negative pole all need to the intrinsically ground, it will reduce
signal anti-interference capacity directly, affect the stability of the system., the impact on the DCS
system is sharp prominent.
. Isolation safety barrier
Isolation safety barrier is composed of limiting energy unit, isolation unit, signal process unit, power
supply unit, etc. The principle as follows:
Safe
Area

Hazardous
Area
limiting
energy
unit

Isolation
unit

signal
process
unit

Isolation safety barrier not only has limiting energy function, but also has isolation function, at the same
time in accordance with intrinsically limiting energy requirements. Compared to zener safety barrier,
although the price is slightly higher, but its others outstanding advantage give more benefits to user.
a. Transformer isolated barriers do not require grounding, because the transformer in the barrier
galvanically isolates the hazardous area from the safe area.
b. Transformer isolated barriers have an internal voltage regulator. The function necessary to the
application is thereby assured.A regulated power supply is only necessary for Zener barriers. If the
power supply for Zener barriers is too low, the field device can no longer operate. The same applies to:
If the power supply becomes too high, the Zener diodes divert the current and the fuse blows when
the current exceeds its maximum rating.
c. Any process monitoring signal circuit (mA- or mV-signal) that is connected to a transformer isolated
barrier is not grounded. In contrast to this, Zener barriers require a suitable ground. From an
instrumentation point of view this is best achieved through a quasi ungrounded system.
d. Transformer isolated barriers from MORNSUN can be repaired; Zener barriers cannot, because they
are filled with an epoxy resin.
e. Transformer isolated barriers have an internal current limit. The fuse is not activated if there is a short
circuit at the exterminal.
f. Instead of using diagrams and Ohm's Law to determine the proper barrier, each transformer isolated
barrier is designed for special applications (i. e. 4 mA~20 mA amplifier, thermocouple amplifier,
solenoid drivers, etc.)
Page 10 of 12

According to the function, the types of safety barrier commonly used are as follows: switch safety
barrier, analog safety barrier, digital safety barrier, resistance thermometry safety barrier, thermocouple
safety barrier, frequency safety barrier, and so on.
14. Guidelines for use of devices with intrinsically safe circuits
The principle of selecting the intrinsic safety electrical apparatus
Simple electrical apparatus:
According to the principle of GB3836.4-2000 about explosion-protection standards, if voltage is lower than
1.2V, current is lower than 0.1A, energy is lower than 20uJ or power is lower than 25mW, it is considered
as simple electrical apparatus. Typical feature as followers: Internal equivalent inductance Li = 0, Internal
equivalent capacitance Ci = 0. Common simple apparatuses are: thermocouples, thermal resistors, pH
electrode, strain gauge, switch, and so on.
General electrical apparatus:
a. The design whether or not in accordance with the GB3836.1-2000 and GB3836.4-2000 requirements and
if the electrical apparatus had been approved by the explosion-proof inspection agency which was
authorized by the national.
b. If the explosion-proof mark class is applicable to the safety requirements of the hazardous area.
c. Clear the authentication parameters of Ui, Ii, Pi, Ci and Li.
d. If intrinsically safety current ground or if it is isolated effectively between the grounding intrinsically
current and the safety barrier interface current.
e. What is the method of the signal transmission?
f. Clear the minimum operating voltage and loop normal operating current of the intrinsically electrical
apparatus.
The principle of selecting the safety barrier
a. Safety barriers explosion-proof mark class is not lower than the class of the intrinsically field apparatus.
b. Make sure the end and circuit resistances can meet the minimum operating voltage of the intrinsically
field apparatus.
c. Safety barriers safety parameters of the intrinsically port can conform to UoUi, IoIi, CoCi+Cc,
LoLi+Lc.
d. The safety and the signal transmission mode between the safety barrier and the intrinsically field
instrument must be best match.
e. Do protection well. Avoid leakage current of the safety barrier affects the normal operation of the
field intrinsically safety apparatus.
f. Safety barrier have two types: one is zener safety barrier, the other is isolation safety barrier.
The principle of selecting the cables
The governing regulations cover installation of intrinsically safe circuits, mounting to external connections,
cable characteristics and cable installation. Cables and terminals with intrinsically safe circuits must be
marked and separated from nonintrinsically safe circuits or feature appropriate isolation (> 1.500 VAC).
Following an excerpt from the requirements according to EN 60079-14:
a. Protection against external electrical or magnetic fields (e.g. power current cables).
b. Prevent conductor splicing of fine wires through wire sleeves.
c. Min. cross section of 0.1 mm (also single wires of a conductor).
d. Protection against damaging (mechanical, chemical, thermic...)
e. Armouring, metal cladding, shielding of cables and lines
Page 11 of 12

f. Common use of single-core nonsheathed cables of intrinsically and nonsafe circuits in one line is not
permitted.
g. Separate error assessment when using multi-conductor cables and lines.
h. When marking cables by colour, light-blue must be used.
Installation of cables
Electrical cables are the connection between field and interface devices and are important functional
components of an automation system. Therefore it is advisable to observe some frame conditions when
installing cables. Cables must be protected against negative environmental influences.
Chemical resistance, temperature rating, resistance against ultraviolet radiation and applicable operation
standards are just some of the parameters which should be taken into account.
By choosing an appropriate installation method it is possible to prevent damages, e.g. through vehicles.
When connected to field devices, the cable should be routed in a conduit. If connected to vibrating
machines or moving parts, some extra cable should be added as a reserve. The minimum bending radius
must also be observed. Cable manufacturers provide information on cable installation and valuable
installation hints. Data integrity and reliability depend strongly on the cable types and installation methods.
Sensor cables should always be installed separately from the power cables. Electromagnetic interferences
must also be avoided. Cable connections to motors which are controlled via frequency converters should be
protected according to the manufacturers safety specifications. If long cables are needed, it is
recommended to use shielded and earthed cables. The line resistance of sensors may not exceed 50 (EN
60947-5-6); the maximum cable length is determined by the cable' cross-section:

L=
R = line resistance []
S = cable cross-section [mm2]
= resistivity [mm2/m]
L = cable length [m]

Page 12 of 12