TestingofTransformerDifferentialProtection
Author:BorisBastigkeit,OMICRONelectronics,Austria
Introduction

March2014Issue
December2013Issue
September2013Issue
June2013Issue
March2013Issue
December2012Issue
September2012Issue
June2012Issue
March2012Issue
December2011Issue
September2011Issue
June2011Issue
March2011Issue
December2010Issue
September2010Issue
June2010Issue
Editorial
Contributors
Letters
News
CoverStory
IEC61850Update
LessonsLearned
BlackoutWatch
IndianBlackout2010
ProtectionAndControlSystems
TransformerProtection
LegalIssue
AgingWorkForce
TheGuru
History
IThink
IndustryReports
ConferenceReports
PhotosOfTheIssue
BookReview
Hobby
FinalThoughts
EventsCalendars

March2010Issue
Autumn2009Issue
Summer2009Issue
Spring2009Issue
Winter2009Issue

Superfastandselectiveprotectionisrequiredtoprotectpowertransformersincaseoffaultslikeinternal
orexternalshortcircuits.Faultswithhighfaultcurrentsthatarenotclearedinstantaneouslymayleadto
longtermlossofacriticalassetandveryhighrepaircostsifarepairisstillpossible.Thereforeitis
stateofthearttoprotectpowertransformerswithdifferentialprotectionsystems.
Differentialprotectionsystemsareveryselectiveandcanactveryfast.However,sinceapower
transformertransformstheelectricitytoadifferentvoltagelevelsomecomplicationisintroducedwhenit
comestoapplyingdifferentialprotection.Whiledifferentialprotectionofgeneratorsormotorsisaquite
straightforwardtechnique,protectionofpowertransformerswithdifferentialprotectionneedsto
overcomesomechallenges.Thosechallengesarethetransformationratioofthecurrents,phaseshift
dependingonthevectorgroupofthetransformer,eliminationofthezerosequencecomponentif
networkswithdifferentgroundingsystemsarelinkedtogetherbythetransformer,inrushcurrent,etc.
(Fig.1,Fig.2)

Autumn2008Issue
Summer2008Issue
Spring2008Issue
Winter2008Issue
Autumn2007Issue
Summer2007Issue

https://www.pacw.org/issue/june_2010_issue/transformer_protection/universal_data_acquizition_platform_in_substation_for_the_future/complete_article/1.html

1/5

6/4/2015

PACWorldmagazine:TestingofTransformerDifferentialProtection
Electromechanicalrelayshavemanagedthesechallengesbyapplyinginterposingtransformersand
solutionslikedeltaconnectedCTs.(Fig.3)
Numericalrelaysapplyasoftware
transformermodeltothecurrentsreceived
fromtheCTsmakingtheuseofinterposing
transformersobsolete.Thedifferential
characteristicsoftransformerdifferential
relaysareinprincipleinlinewithother
differentialprotections.Abiased
characteristicisinplacetodesensitizethe
protectionfor:
MeasurementerrorsoftheCTs
Measurementerrorsoftherelay
Influenceofthetransformertap
changer
CTsaturationeffects
Magnetizationcurrentofthe
transformer(Fig.4)
TestingofTransformerDifferentialProtectionSystems
Inprotectionengineeringtestingplaysanimportantroleinmanyaspects.Typetesting,acceptance
testing,routinetesting,testinginthecourseoftroubleshootingetc.serveveryimportanttargets.
However,withnumericalrelaysandIEDsthecommissioningtesthasbecomeevenmoreimportantthan
italwayswas.Thereforethisarticleconcentratesontestsonewouldtypicallydowhencommissioninga
newtransformerprotectionsystem.
Theprotectionsystemconsistsoftheprotectiondeviceitself,theCTs(andVTs),thewiring,the
connectiontotheSCADAsystem,thetripcircuitincludingthecircuitbreaker,thepowersupply/battery
etc.Allthismustbetestedwhencommissioningtheprotectionsystem.However,thekeyandmost
challengingtaskistotesttheprotectionanditscorrectsettingandconfiguration.Thisshallbethefocus
ofthefollowingsections.
Recommendedtests:
Wiringcheck
Trippingcharacteristictest
Triptimeperformancetest
Inrushstabilizationtest
Stabilizationforthroughfaults
CheckSCADAmeasurementsandannunciations
Checkofthesystem:CT/protection
Checkactualtripcircuitincludingbreaker
TrippingCharacteristicTest
SinglePhaseCurrentInjection
Themethodofsinglephasecurrentinjectiontestingoriginatesfromtheeraofelectromechanicalrelays
wherenomeanswereavailabletodoaproper3or6phasetestandwhentherelayswerestillsingle
phaserelays.Thismethodhasseveralshortcomingsandshouldnotbeusedonmodernnumerical
protectiondevices.Thismethodallowstestingonly1pointonthetrippingcharacteristic.
TrippingCharacteristicTest
SixPhaseCurrentInjection
StateofthearttestequipmentallowsconvenientgenerationofsixcurrentsthatarecontrolledbyPC
basedtestsoftware.Thetestsoftwarecalculatesthesixcurrentsfromthetrippingcharacteristicplane
(Idiff/Ibiasplane)incorporatingthedataoftheprotectedtransformerandCTs.Thesetestsarenot
completelystraightforwardbecausethetestpersonhastoknowthealgorithmsofrelayundertest.Once
theprotectiondevicealgorithmsareunderstoodandtransferredtothetestsoftwarethetripping
characteristiccanbetested.
Mainpurposeoftestingthetrippingcharacteristicofmodernnumericalprotectiondevicesistocheckthe
correctparameterizationofthedevice.Suchatestverifiesthatthe
PickupvaluesI>,I>>
Characteristicslopes
CTdata
Tripconfiguration
Transformerdata
havebeencorrectlyparameterizedintheprotectiondevice.Duetothefactthatitisnotsoeasytofeed
allrequiredinformationaboutthealgorithmsoftheprotectiondevicetothetestsoftware,recentlyrelay
typespecifictesttemplateshavebeendevelopedthatalreadyincorporatealltherelaytypespecific
algorithmsandjustrequiretheinputofthesetparameterstoallowatestofthetrippingcharacteristic.
(Fig.5)
TripTimePerformanceTest
Selectiveandfastoperationisthereasonforapplyingcomplicatedprotectionfunctionsliketransformer
differential.Thereforeoneshouldverifyiftheperformanceisreallyasexpected.Unwantedchangesin
thesettingsoftherelaylogic,unwantedsettingsinthetriptimedelaysectionorjustdefectiveoutput
relaysmaybereasonsforunderperformanceoftheoperatingtime.Thereforethetriptimetestis

https://www.pacw.org/issue/june_2010_issue/transformer_protection/universal_data_acquizition_platform_in_substation_for_the_future/complete_article/1.html

2/5

6/4/2015

PACWorldmagazine:TestingofTransformerDifferentialProtection
recommendedinallcases.
InrushStabilizationTest
Whenapowertransformerisenergized,instantloadingoftheinductivitycausesasocalledinrush
current.Thismagnetizationcurrentwouldcausethedifferentialprotectiondevicetotrip.Thereforethe
differentialprotectionelementisblockedbyafunctionthatmonitorsthespecificcharacteristicsofan
inrushcurrentuntilthetransformerismagnetized.Typicalmethodstodetectinrushcurrentsarethe
monitoringofthe2ndharmonicorasocalledgapdetectionfunction.Itisimportanttotestifthe
stabilizationforinrushcurrentsisworkingproperly.Thetypicaltestmethodistheverificationofthe
blockingmechanismbyinjectingfaultcurrentswithdifferentamountsofsuperimposed2ndharmonic.If
onehasthechancetomeasuretheinrushcurrentofthepowertransformerwithatransientrecorderitis
alsobeneficialtousesuchatransientrecordfortestinghowtheprotectionreacts.(Fig.6)

StabilizationForThroughFaults
Ifthedifferentialprotectionsystemisnotconfiguredandparameterizedcorrectly,anexternalfaultthat
shouldnotcausetherelaytooperatemaycauseanunwantedoperation.Thismustbepreventedby
simulatingexternalfaultsandassuringthattheprotectionremainsstableforsuchfaults.Especially
criticalarefaultswithzerosequencecomponentlikephasetogroundfaults.Inmostcasespower
transformersdonottransferzerosequencecomponentstotheothervoltagelevel.Thereforethe
protectionsystemisrequiredtoeliminatesuchazerosequencecomponentaswell.Otherwiseoperation
forexternalfaultswouldbetheresult.Testingthestabilizationforexternalfaultsisdonebysimulating
externalfaultsandmodellinghowthefaultcurrentsaretransformedbyatransformermodel.Stateofthe
arttestequipmentprovidestestsoftwaresupportingsuchsimulationsandallowsinjectionof
correspondingtestcurrents.(Fig.7)
CheckoftheSystem:CTandProtection
Thebestsecondaryinjectiontestcannotpreventthetransformerdifferentialsystemfromfailingifthereis
somethingwrongintheCTdimensioning,wiring,burdenandinstallation.Justasanexampleif
accidentallythemeasuringcoreoftheCTwouldbeconnectedatoneoftheCTsinsteadofthe
protectioncore,anexternalfaultwouldtripthetransformerevenatlowfaultcurrents.Or,onecould
imaginewhatwouldhappenifoneoftheCTswouldbe1Ainsteadof5A.Also,topreventCTsfrom
differentlysaturatingitisimportantthatthecorrectCTburdeningischecked.Recentdevelopmentsin
protectiontestequipmentmadeitpossibletouse6phaseprimaryinjectiontechniquestoverifythe
completesystemCTprotectionCT.However,usingmodernprotectiontestequipmentforprimary
injectioncanonlyproducesome510%oftheprimarynominalcurrentoftheCTs.With5%to10%of
theprimarynominalcurrentitwilloftennotbepossibletostimulatetheprotectionsysteminorderto
operateortoverifythedifferentialoperationcharacteristic.Still,themeasurementfunctionsprovidedby
modernrelaysallowverifyingifthephasecurrentsandcalculateddifferentialandstabilizationcurrentsfor
thedifferenttestcasesareseenandcalculatedcorrectlybytheprotectionsystemallowingtoverifythat
thesystemworkscorrectly.(Fig.8)
Oncethepowertransformerhasbeenenergizedthecorrectconfigurationcanalsobeverifiedtoacertain
extentbycomparingandcheckingthemeasurementsandcalculationsprovidedbymodernprotection
equipment.However,itisadvisabletocheckeverythingpriortoenergizingthetransformerforthefirst
time.
NewTestingPossibilities
Duetotheavailabilityoftransientnetworksimulationtoolsthatcanbeusedinthesubstation,plausibility
testsoftransformerdifferentialdevicesanditsparameterizationcouldbedonedifferentlyeasier,and
morerealistic.Thistestcanbeconsideredeasierbecauseitisablackboxtest.Onedoesnotneedto
knowhowtheprotectionalgorithmsworkindetail.Pickupvalues,characteristicslopesandothersettings
arenotconsideredanddon'thavetobemodelledforsuchatest.Especiallywithmodernprotection
equipmentthatprovidestheflexibilitytosetahugeamountofparameters,thiscanbeaclear
advantage.Theonlydatathatarerequiredareavailableonthenameplatesofthepowertransformer
andtheCTs:
PowerTransformer:
NominalVoltageHV/LVside
NominalPower
VectorGroup
TypeofGroundingforHV/LVside
CTsHVside:
NominalCurrentprimaryside
NominalCurrentsecondaryside
CTconnection
CTsLVside:

https://www.pacw.org/issue/june_2010_issue/transformer_protection/universal_data_acquizition_platform_in_substation_for_the_future/complete_article/1.html

3/5

6/4/2015

PACWorldmagazine:TestingofTransformerDifferentialProtection
NominalCurrentprimaryside
NominalCurrentsecondaryside
CTconnection(Fig.9)
Recentdevelopmentsallowtheapplicationoftransientsimulationtoolsinthesubstationandwithstate
ofthearttestequipment.Thestabilityforexternalfaultsandoperationforinternalfaultscanbetested
withsuchatool.Simulationofdifferentfaulttypeslike3phase,2phase,phaseground,etc.are
possible.Oncesuchatestispassed,onecanbesurethattheprotectiondevicehasbeenbasically
configuredcorrectlytoprotectthecorrespondingpowertransformer.Majormistakeslikeawrongvector
grouporgroundingsystemcanberuledout.
Anadditionalaspectofusingtransientsimulationsoftwaretotesttransformerdifferentialprotection
devicesisthatthesimulationofCTsaturationphenomenabecomespossibleaswell.Ifoneisunsureif
CTsaturationmightbeaprobleminaspecificcase,newpossibilitiesexisttodirectlymeasuretheCT
characteristicandburdenandthentransferthemeasureddatatotransientsimulationsoftware.Theextra
effortformeasuringtheCTdatawouldbeacceptable.OncetheCTdataareavailable,usingthesedata
forextratestsforCTsaturationsimulationisaquestionofsomeextraminutesiftransientsimulationis
usedforplausibilitytestingofthetransformerdifferentialdeviceanyway.Thiswaypossibleproblems
withCTsaturationcanbedetectedalreadyattheinstantofcommissioning.However,fortroubleshooting
ofunwantedoperationsthataresuspectedtooriginatefromCTsaturationsuchsimulationpossibilities
findtheirtargetapplication.

TestingofIEC61850basedSystems
IEC61850ischangingtheworldofprotectionengineeringcurrently,especiallyinregardstohowtheIED
isconnectedtotheSCADAsystemandbyusingGOOSEmessagesforexchangingbinaryinformationin
thesubstation.IEC61850,theinternationalstandardforcommunicationnetworksandsystemsin
substations,defines(amongmanyotheritems)mechanismsforrealtimemessagingoverEthernet
networks,socalledGOOSEmessages.Asitisthecasewithotherprotectionfunctions,alsotransformer
differentialfunctionsthatuseIEC61850GOOSEmessagescanbetestedwithtestequipmentthatcan
receiveandsimulateGOOSEmessagesinconformancewiththecorrespondingstandard.Testingwith
GOOSEmessagesisnotreallydifferentfromtestingwithconventionaldryorwetcontacts.However,the
aspectof"GOOSEperformance"mustbeconsideredforperformancetestsbecausefirst
implementationsshowedthatGOOSEmessagesmightbedelayedbyseveralmillisecondscomparedto
conventionaldry/wetcontacts.InordertotesttheGOOSEperformanceoftheprotectionIEDoneshould
investigatetheGOOSEperformanceofthetestequipmentpriortotestingtomakesurewhichtiming
delayisintroducedbytheIEDandwhichdelaymightbeintroducedbythetestequipment.Test
equipmentwithhighperformanceintroducingamaximumtimedelayoflessthan1millisecondin
connectionwithGOOSEmessagesisavailable.(Fig.10)
AnotheraspectinregardstotestinginconnectionwithGOOSEmessagesisthepossibilitytoenhance
the"testability"ofprotectionequipmentbydesigningextraGOOSEmessagestomaketestingeasier.
TheproblemthatcanbesolvedisthefactthatmultifunctionalprotectionIEDshaveseveraloverlapping
protectionfunctionsactiveinparallel.Designingatestplanthattestseachfunctionindetailwithout
interferingwithotherfunctionsisoftenimpossible.Oftenthenfunctionsaredisabledforthepurposeof
testingatthecostofpossibleintroductionofnewerrorse.g.whenareactivationofthedisabledfunction
isforgotten.GOOSEmessagescanbeusedtosolvethisproblembysimplydesigningspecificGOOSE
messagesforeveryfunctionoftheIEDtoallowsimpletestingwithouttheneedofdisablingfunctionsfor
testingpurposes.However,tobenefitfromthispossibility,atestfriendlydesignoftheIEDhastobe
consideredalreadyintheplanningphaseoftheprotectionsystem.Forsuchapplicationsthetest
equipmentshouldallowthesimultaneousmappingandmonitoringofhighnumberofGOOSEmessages,
atleast20to30.
LookingintothenearfutureIEC61850"SampledValues"processbusapplicationswillhavetobe
consideredwhentesting.SampledValues(SV)(sometimesalsocalledSampledMeasuredValues
(SMV)orSampledAnalogValues(SAV))servicesaredefinedinIEC6185072.TheUCAInternational
UsersGrouppublishedthedocument"ImplementationGuidelineforDigitalInterfacetoInstrument
TransformersusingIEC6185092".AsthisimplementationguidelinedefinesasubsetofIEC6185092,

https://www.pacw.org/issue/june_2010_issue/transformer_protection/universal_data_acquizition_platform_in_substation_for_the_future/complete_article/1.html

4/5

6/4/2015

PACWorldmagazine:TestingofTransformerDifferentialProtection
itiscommonlyreferredtoas"92LightEdition"orshort"92LE".FirstIEDsthatsupportsampledvalues
arecommerciallyavailableandpilotinstallationsapplyingsampledvaluesinthesubstationhavebeen
realized.EspeciallyforapplicationsthataresensitivetoCTsaturationproblemslikedifferential
protectionnonconventionalCTswithoutsaturationeffectsareaninterestingtopic.Combiningsuch
nonconventionalCTswithIEC61850sampledvaluesiswhatneedstobeconsideredtodayifwethinkof
testingrequirementsfortransformerdifferentialprotectionoftomorrow.Suchsolutionshavesevere
effectsontesting.Conventionaltestequipmentthatcannotgeneratemultiplesynchronizedsampled
valuesstreamscannotbeappliedinsuchscenarios.Testequipmentfortransformerdifferential
protectionscenariosmustprovideatleast2synchronizedsampledvaluesstreams.AccordingtoIEC
6185092LEonesampledvaluesstreamprovidesthedataofonemeasuringpointwith4voltages(3
Phases+NeuralVoltage)and4currents(3Phases+NeutralCurrent).Thusitbecomesobviousthat
testingdifferentialprotectionapplicationsrequirestestequipmentthatcansimulateatleast2
synchronizedsampledvaluesstreamsandreceiveandsimulateGOOSEmessageswithhigh
performanceatthesametime.
Biography
BorisBastigkeit(Dipl.Ing.IEEE,OVE)wasbornin1969inKemptonPark/SouthAfrica.He
receivedhismasterdegreeinElectricalEngineeringattheTechnicalUniversityofGraz(Austria)in1998.
HejoinedOMICRONelectronicsinAustria1997whereheheldvariouspositionsindevelopmentand
salesbeforehewasappointedtohiscurrentpositionasheadofproductmanagementinthefieldof
testingsolutionsforprotectionandmeasurementsystems.Heistheconvenerandnationalexpertofthe
MR95/Austria.HeismemberoftheworkinggroupIECTC95MT4.