Conductor Sizing
Service Entrance (GEC)
Separately Derived Transformer (GEC)
Branch Circuits (EGC)
Notes:
1.
NEC 250.66(A) that portion of
the conductor that is the sole
connection to the grounding
electrode shall not be required to
be larger than 6 AWG copper
wire.
2.
NEC 250.66(B) that portion of
the conductor that is the sole
connection to the grounding
electrode shall not be required to
be larger than 4 AWG copper
wire.
3.
NEC 250.66(C) that portion of
the conductor that is the sole
connection to the grounding
electrode shall not be required to
be larger than the conductor
used for the ground ring.
4.
NEC 250.66, Use table 250.66
based on largest service
conductor size.
(4)
(1)
(4)
(2)
(3)
Main
Bonding
Jumper
GEC
2/0 Cu.
Main
Bonding
Jumper
Min. 6 AWG
Main
Main
Once secondary conductor sizes are determined, treat just like service
Main
10
11
GEC
Main Bonding Jumper
Main
12
13
Branch Circuits
(1) Copyright 2002, National Fire Protection Association, All Rights Reserved,
NFPA National Electrical Code Handbook, Ninth Edition, Exhibit 100.5
EGC Selection
Example
A branch circuit is to be
protected with a
20 A circuit breaker.
Determine EGC size:
Copper: _____
Aluminum: _____
EGC Selection
Example
A branch circuit is to be
protected with a
20 A circuit breaker.
Determine EGC size:
Copper: 12 AWG
Use of Copper wire for
EGC is recommended
Aluminum: 10 AWG
EGC Selection
Problem
A branch circuit is to be
protected with a
100 A circuit breaker.
Determine EGC size for
copper wire:
Copper EGC: _____