B OA- Sy s t ro n i c
Contents
Intelligent pump and valve management saves energy . . . . . . . . . . . . . 2
1
Heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10
Practical testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
10.1 Plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
10.2 Circulator selection for BOA-Systronic . . . . . . . . . . . . . . . . . . 19
10.3 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10.4 External temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10.5 Volume flow rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.6 Differential pressures of the pumps . . . . . . . . . . . . . . . . . . . . . 22
10.7 Electrical pump power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
13
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
List of figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
List of tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
060206_knowhow05_e_IS 1
060206_knowhow05_e_IS 2
Heating circuit
1
Heating circuit
Mixing or injection-type
systems produce a constant
volume flow rate through the
consumer installations1. As a
In a mixing or injection-type
installations. Conventional
terized as follows:
NENTS IN CONVENTION-
curve (p = constant or p =
NOT COORDINATED
variable).
If several heating circuits of
a mixing or injection-type
manually.
Constant volume fl ow rate through consumer installations: results from the hydraulic confi guration of the main feed circuit (e.g. 3-way mixing
valve). Whether the system is operating under nominal load or part-load conditions, the circulator pump will always deliver the nominal
volume fl ow rate calculated for the design point. Only when external heat is acting on the consumer installations will the level of this volume
fl ow rate be adjusted by the control function of the thermostats.
060206_knowhow05_e_IS 3
System concept
2
System concept
An analysis of this situation re-
heating circuit.
SAVINGS POTENTIAL BY
SYSTEM CONCEPT
circulator
pump2 .
060206_knowhow05_e_IS 4
System concept
with.
As BOA-Systronic produces
Conclusion
The savings realised by BOA - Systronic result from knowledge about the hydraulic
conditions in the heating circuit. They are completely independent from differential
pressure control of the circulator pump. With BOA - Systronic , differential pressure
control of the circulator pump is effected as before.
060206_knowhow05_e_IS 5
Components
3
Components
The transformation into a sys-
temperature).
IMS 4
BOA- CVE SuperCompact: Automated shut-off and control valve for HVAC applications with smart electric actuator. The valve is produced
in nominal sizes from DN20 to DN150 and nominal pressure class PN6/10/16. Thanks to its compact design, it is the smallest and lightest
valve of this pressure class manufactured in series production today, enabling the space-saving design of air-conditioning and heating centrals.
Due to its low weight, the valve is easy to install and handle. The self-calibration feature of the actuator is another benefi t, which does away
with the adjustment of limit switches.
BOA- Control IMS: The valve measures volume fl ow rates independently from valve travel positions and minimum differential pressures.
Unlike on conventional valve models, the measurement accuracy is constant across the entire valve travel. The measuring signal is read and
processed by a measuring computer. Valves of this kind are often insulated, and any identifi cation on their bodies may be diffi cult to read.
After start-up, the computer display therefore fi rst shows the nominal diameter of the connected valve. The operator can then choose via two
keys whether the current fl ow rate is to be indicated [in m 3 /h] or the temperature of the fl uid handled [in C]. Volume fl ow rates can be checked
within a matter of seconds in this way. BOA- Control IMS, which has a linear characteristic, can also be used as shut-off valve. Thanks to a
travel stop with a protective cap, the valve can be set exactly to its original position once the shut-off process has been completed.
-coeffi cient: describes the resistance a valve offers to the fl uid passing through it. The -coeffi cient depends on the valve type and design.
060206_knowhow05_e_IS 6
Control
4
Control
BOA-Systronic is a control sys-
HIGHER-LEVEL CONTROL-
LER IS RETAINED
valve.
060206_knowhow05_e_IS 7
5
Volume flow rates
conditions.
ature differential T.
affected.
tion).
Pth = 1.163 Q T
Conventional systems
BOA-Systronic
of BOA-Systronic regulates
ler.
mixing line.
or injection-type
systems 6
can
Qtotal =Q1supply+Q2mixing
Q 1 supply
Q total
(hot)
Q total
100
Q 2 mixing
80
60
40
20
Q 1 supply
Q 2 mixing (cold)
20
40
60
80
100
3-way configuration: In a 3-way mixing valve, the fl uids to be mixed enter the valve via two input ports and the sum of their fl ow exits
through a single output port. The ratio between the fl ow rates through both inlet ports is determined by the stem position. The sum of the
throttling cross-sections on both inlet ports is constant over the entire valve travel. The valve therefore provides a constant volume fl ow at its
outlet port, independent of stem position.
060206_knowhow05_e_IS 8
benefits.
PERATURE BY PARALLEL
CATION OF HEATING
CURVE
his planning
reduced considerably.
and costs
Normally, a circulator
rating can be selected
lator pump
eter smaller.
insulation.
Q 1 supply
(hot)
Q total
+
Q 2 mixing
(cold)
100
80
Q total
60
40
20
Q 2 mixing
Q 1 supply
0
0
20
40
60
80
100
060206_knowhow05_e_IS 9
6
Circulator pump heads
off valves.
conditions.
constant (p = constant) or is
reduced accordingly (p =
variable).
THE PUMP
energy.
independently of throughflow
flow rate
CIRCUIT
pump:
circulator pump.
H new = H old
Q new
Q old
= 100%
75%
100%
) H
old
= 0.56 H old
commissioning; it is limited by
10
060206_knowhow05_e_IS 10
ARE RETAINED
P el2
constant Q1 H1
constant Q2 H2
Q1 H1
Q2 H2
180
Chara
o f f ixedc t e r i s t i c c u r v e
speed p
ump
160
140
120
External
heat effect
Characteristic curve of
variable speed pump p = constant
100
80
External
heat effect
Characteristic curve of
variable speed pump p = constant
60
40
External
heat effect
Characteristic curve of
variable speed pump
20
Syst
urv
em c
BO
st
-Sy
ron
ic
0
0
10
20
30
40
50
60
70
80
90
100
110
120
11
060206_knowhow05_e_IS 11
7
Hydraulic balancing of
branch circuits
BOA-Systronic operates the
heating circuit with variable
volume flow rates. The question
therefore arises whether the
branch circuits are hydraulically
balanced for these variable
operating points.
The branch circuits are hydraulically balanced for the design
point (nominal load). This ensures adequate heat supply to
the consumer installations in the
individual branch circuits. In
the following, the nominal load
case is indexed N, whereas the
(Q).
nominal load:
QN
1
1
pN = w 2 =
2
2
A
Equation 1
( )
(e.g.
pN2
pN1
) and
pT2
pT1
1
1 2
= constant = c
2
A
()
Equation 2
12
060206_knowhow05_e_IS 12
Differential pressure at
nominal load:
pN = c Q 2 N
Equation 3
Equation 6
pT1 = F2 p N1
pT2 = F2 p N2
follows:
Equation 7
Differential pressure at
parl load:
pT = c (FQ N ) 2
Equation 4
where factor F describes the
4 yields
pT = F2 p N
Equation 5
resulting in the following differ-
pT2
pT1
pN2
pN1
Equation 9
Conclusion
The same law governing differential pressures in
the branch circuits can be established for part load
conditions as for nominal load conditions. It is
therefore ensured that the branch circuits are actually
supplied with the necessary volume flow rate for the
thermal output required.
13
060206_knowhow05_e_IS 13
8
Differential pressure
control elements
(p1).
NO DIFFERENTIAL
PRESSURE CONTROL
ELEMENTS REQUIRED
Conclusion
BOA -Systronic provides the circulator pump with the discharge head required for
the actual load conditions. No excess discharge heads are produced under part load
conditions, nor flow noises at the consumers. Expensive differential pressure control
elements for balancing the heating circuits can be dispensed with. For hydraulic balancing
of branch circuits, they can even be replaced by lower priced balancing valves.
14
060206_knowhow05_e_IS 14
Commissioning
9
Commissioning
circuit is known.
or injection-type system.
BOA-SYSTRONIC AUTO-
MATICALLY DETERMINES
control curves.
180
Operating point, conventional,
variable speed pump
with external heat load
160
H1
140
External
heat effect
120
100
H2
p1
80
p2
60
Operating point
BOA-Systronic
variable speed pump
with external heat load
External
heat effect
40
External
heat effect
Operating point
BOA-Systronic
variable speed pump
without external heat load
H3 p
3
BO
y
A-S
str
oni
Sy
tem
cu
rve
Hydraulic
resistance
of heating circuit
20
0
0
10
20
30
40
Q part-load 60
70
Q NS 80
90
QN
110
120
N Sys
Q
T
060206_knowhow05_e_IS 15
15
10
Practical testing
10
Practical testing
10.1
Plant
CONTROLLER TRANSMITS
SYSTRONIC
controlled (p = constant).
benefits of BOA-Systronic by
16
060206_knowhow05_e_IS 16
10
Practical testing
voltage signal.
characteristic. Configuration is
DN 65
Parameter
East wing
(3-way configuration)
West wing
(BOA-Systronic)
Unit
300.00
300.00
kW
Temperature differential
20.00
27.00
13.00
9.75
m/h
8.00
4.50
Circulator pump
Riotec 65 -100
Riotec 50 -100
p = constant
p = constant
DN65
DN50
No
+3.5
Thermal output
17
060206_knowhow05_e_IS 17
10
Practical testing
SYSTEM DIAMETERS UP TO
DN50
SYSTROBOX IS THE
valve curve.
HEART OF BOA-
SYSTRONIC. IT RECEIVES
SIGNALS.
BOA-Systronic
to installation. Operating on a
BOA-Systronic
18
060206_knowhow05_e_IS 18
10
Practical testing
10.2
Circulator selection
for BOA -Systronic
k heating circuit =
8
= 0.0473
132
Equation 11
perature differential of T =
controlled by BOA-Systronic, is
reduced by 25%.
H
Q2
Equation 10
and 3.
Riotec 65 100
1,825.11
Riotec 50 60
1,223.20
Difference []
602.91
19
060206_knowhow05_e_IS 19
10
Practical testing
10.3
Measurements
To verify the function of the
BOA-Systronic system, the
following quantities were
measured, among others. (Table 03)
Measurements were taken on
External temperature
External temperature
measured quantity.
be confirmed by a comparison
10.4
External temperature
22. Oct 02
22. Sep 02
23. Aug 02
24. Jul 02
24. Jun 02
25. May 02
25. Apr 02
26. Mar 02
24. Feb 02
25. Jan 02
26. Dec 01
26. Nov 01
27. Oct 01
27. Sep 01
28. Aug 01
29. Jul 01
29. Jun 01
30. May 01
30. Apr 01
31. Mar 01
1. Mar 01
30. Jan 01
31. Dec 00
1. Dec 00
1. Nov 00
-10
Years
External temperature
20
060206_knowhow05_e_IS 20
10
Practical testing
ed as follows:
Qnom =
10.5
Volume flow rates
1.163 T
Equation 14
300
1.163 20
m 3 /h = 13m 3 /h.
t2
water volume flow = Q(t) dt
t1
Volume flow rates Heidelberg test installation Savings by BOA-Systronic approx. 65%
16
14
12
10
8
5
4
2
22. Oct 02
22. Sep 02
23. Aug 02
24. Jul 02
24. Jun 02
25. May 02
25. Apr 02
26. Mar 02
24. Feb 02
25. Jan 02
26. Dec 01
26. Nov 01
27. Oct 01
27. Sep 01
28. Aug 01
29. Jul 01
29. Jun 01
30. May 01
30. Apr 01
31. Mar 01
1. Mar 01
30. Jan 01
31. Dec 00
1. Dec 00
1. Nov 00
Years
3-way configuration
BOA-Systronic
Fig. 19 Volume flow rates measured at the main feed manifold in 2000 2002
21
060206_knowhow05_e_IS 21
10
Practical testing
Measured Quantity
Heating circuit
3-way configuration
[m /h]
Mean value
BOA-Systronic
Unit
Ratio
[m /h]
11.2
3.2
0.29
10.6
Differential pressures
of the pumps
Measured Quantity
Heating circuit
3-way configuration
Unit
[m]
Mean value
4.4
Ratio
H Systronic /H 3 - way configuration
BOA-Systronic
[m]
2.9
0.66
Pump differential pressures Heidelberg test installation Savings by BOA-Systronic approx. 37%
800
700
600
500
400
300
200
100
22. Oct 02
22. Sep 02
23. Aug 02
24. Jul 02
24. Jun 02
25. May 02
25. Apr 02
26. Mar 02
24. Feb 02
25. Jan 02
26. Dec 01
26. Nov 01
27. Oct 01
27. Sep 01
28. Aug 01
29. Jul 01
29. Jun 01
30. May 01
30. Apr 01
31. Mar 01
1. Mar 01
30. Jan 01
31. Dec 00
1. Dec 00
22
1. Nov 00
Years
3-way configuration
BOA-Systronic
22
060206_knowhow05_e_IS 22
10
Practical testing
10.7
Pump input
power
The pump input power, and
electrical energy.
Heating circuit
3-way configuration
Unit
BOA-Systronic
[W]
Mean value
Ratio
[W]
561
184
0.33
Pump input power Heidelberg test installation Savings by BOA-Systronic approx. 70%
900
800
700
600
500
400
300
200
100
22. Oct 02
22. Sep 02
23. Aug 02
24. Jul 02
24. Jun 02
25. May 02
25. Apr 02
26. Mar 02
24. Feb 02
25. Jan 02
26. Dec 01
26. Nov 01
27. Oct 01
27. Sep 01
28. Aug 01
29. Jul 01
29. Jun 01
30. May 01
30. Apr 01
31. Mar 01
1. Mar 01
30. Jan 01
31. Dec 00
1. Dec 00
1. Nov 00
Years
3-way configuration
BOA-Systronic
Conclusion
In our example, both heating circuits on average require only 21% of the thermal
output at design point. By comparison, BOA - Systronic consumes only about 30 % of
the electricity required by the conventional set- up ( here : 3 - way mixing system) .
23
060206_knowhow05_e_IS 23
11
11
Payback period
for BOA -Systronic
11.1
Control valve investment and energy
savings
fold.
with BOA-Systronic.
so that
nents:
ing line
balancing valve
a conventional mixing-type
diameter smaller
6. differential pressure controllers for balancing the heat-
Nominal
system diameter
DN25 to DN50
DN65 to DN80
DN100 to DN150
13 %
Heating circuit
Unit
Value
1,673
1,858
217
Difference
+402
Tab. 08: Extra price for BOA-Systronic with Riotec pump (example: DN50)
24
060206_knowhow05_e_IS 24
11
Heating circuit
Unit
Value
Difference
1,673
1,858
187
+372
Table 09: Extra price for BOA-Systronic with Rio-Eco pump (example: DN 50)
Cost factor
Unit
Value
/kWh
Difference
0.11
6,800
35
kWh
5,000
kWh
1,200
548
131
-3,800
- 417
11.2
Investment costs for
heating circuit with
Riotec pump
results in an additional 45
saved.
Investment in BOA-Systronic
by 1,059.
duced substantially.
Cost factor
Unit
Difference
(1)
-75
(2)
-123
(3)
-29
(4)
- 602
see above
-230
-1,059
(5)
(6) No differential pressure controller required (1 no. per heating circuit, 1.5 -inch)
Sum total of factors (1) to (6)
Tab. 11: Reduced investment costs for heating circuit with Riotec pump, example (prices 2005)
25
060206_knowhow05_e_IS 25
11
11.3
Investment costs for
heating circuit with
Rio - Eco pump
Investment in BOA-Systronic
reduced substantially.
by 933.
(Table 12)
Cost factor
Unit
Difference
(1)
-75
(2)
-123
(3)
-29
(4)
- 476
(5)
see above
-230
-933
(6) No differential pressure controller required (1 no. per heating circuit, 1.5 -inch)
Sum total of factors (1) to (6)
Table 12: Reduced investment costs for heating circuit with Rio-Eco pump, example (prices 2005)
11.4
Total savings compari son Riotec / Rio - Eco
In the present example, the
Rio-Eco pump could be expected to pay back after approximately three years, compared to
the Riotec pump.
26
060206_knowhow05_e_IS 26
11
-1,119
-34
-1,503
-933
372
Year 02
-455
-1,608
-48
Year 03
-455
-2,111
Year 04
-493
Year 05
-45
- 456
-1,062
-32
-1,094
0,11
6,800
-1,656
- 498
-1,592
- 48
-1,640
0.12
6,800
-63
-2,174
- 498
-2,138
- 64
-2,202
0.12
6,800
-2,667
-80
-2,747
-539
-2,741
- 82
-2,283
0.13
6,800
-493
-3,240
-97
-3,337
-539
-3,362
-101
-3,463
0.13
6,800
Year 06
-531
-3,868
-116
-3,984
-581
- 4,044
-121
- 4,165
0.14
6,800
Year 07
-531
-4,515
-135
-4,651
-581
- 4,746
-142
- 4,889
0.14
6,800
Year 08
-569
-5,220
-157
-5,376
- 622
-5,511
-165
-5,676
0.15
6,800
Year 09
-569
-5,945
-178
-6,124
- 622
- 6,298
-189
- 6,487
0.15
6,800
Year 10
-607
-6,731
-202
-6,933
- 664
-7,151
-215
-7,365
0.16
6,800
Year 11
-607
-7,540
-226
-7,766
- 664
- 8,029
-241
- 8,270
0.16
6,800
Year 12
-645
-8,411
-252
-8,663
-705
- 8,975
-269
-9,244
0.17
6,800
Year 13
-645
-9,308
-279
-9,588
-705
-9,949
-298
-10,248
0.17
6,800
Year 14
-682
-10,270
-308
-10,578
-747
-10,995
-330
-11,325
0.18
6,800
Year 15
-682
-11,260
-338
-11,597
-747
-12,072
-362
-12,434
0.18
6,800
Year 16
-720
-12,317
-370
-12,687
-788
-13,222
-397
-13,619
0.19
6,800
Year 17
-720
-13,407
-402
-13,809
-788
-14,407
- 432
-14,839
0.19
6,800
Year 18
-758
-14,567
-437
-15,004
- 830
-15,669
- 470
-16,139
0.20
6,800
Year 19
-758
-15,762
-473
-16,235
- 830
-16,969
-509
-17,478
0.20
6,800
Year 20
-758
-16,993
-510
-17,503
- 830
-18,308
-549
-18,857
0.20
6,800
Savings []
-45
402
-417
-1,059
Year 01
Savings []
Period
Riotec ( =35%)
27
060206_knowhow05_e_IS 27
11
0
-1000
-2000
-3000
-4000
-5000
-6000
-7000
Savings []
-8000
-9000
-10.000
-11.000
-12.000
-13.000
-14.000
-15.000
-16.000
-17.000
-18.000
-19.000
-20.000
-21.000
0
10
11
12
13
14
15
16
17
18
19
20
Years [a]
Riotec pump: Savings plus interest (parallel shift)
Riotec pump: Savings plus interest (slope modification)
Fig. 22 Savings realized by Riotec and Rio-Eco pumps with slope modifi cation and parallel shift (example)
Period [a]
10
15
20
Reduced costs
Unit
Riotec
-702
Rio - Eco
- 606
Difference
96
Pump operation
-2,313
-2,530
-217
Interest on savings (3 %)
-322
-327
-4
Total
-3,337
-3,463
-125
Annual savings
- 667
- 693
-25
-702
- 606
96
Pump operation
-5,120
-5,600
- 480
Interest on savings (3 %)
-1,111
-1,159
- 49
Total
- 6,933
-7,365
- 433
Annual savings
- 693
-737
- 43
-702
- 606
-96
Pump operation
- 8,381
-9,168
-787
Interest on savings (3 %)
-2,514
-2,660
-146
Total
-11,597
-12,434
- 837
Annual savings
-773
- 829
-56
-702
- 606
-96
Pump operation
-12,095
-13,234
-1,139
Interest on savings (3 %)
- 4,706
-5,017
-311
Total
-17,503
-18,857
-1,354
Annual savings
- 875
-943
- 68
28
060206_knowhow05_e_IS 28
12
References
12
References
Since being released for sale in
2003, BOA-Systronic has been
in operation in many heating
systems in public and industrial
buildings throughout Germany.
The photo below shows three
heating circuits equipped with
BOA-Systronic systems of
nominal diameter DN32.
29
060206_knowhow05_e_IS 29
13
Conclusion
13
Conclusion
are avoided.
ing costs.
environment.
heating circuit.
BOA-Systronic, by contrast,
onmental protection.
comfort of use.
circuit.
The hydraulic operation of the
In new or replacement installa-
30
060206_knowhow05_e_IS 30
List of figures
Fig. 1
Fig. 2
Comparison of systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Fig. 3
BOA-Systronic components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
Fig. 9
Two-boiler system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fig. 10
Return manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fig. 11
Control cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fig. 12
Fig. 13
Fig. 14
Fig. 15
Fig. 16
Fig. 17
Fig. 18
Fig. 19
Volume flow rates measured at the main feed manifold in 2000 2002 . . . . . . . . . . . . . . . 21
Fig. 20
Fig. 21
Fig. 22
Savings realized by Riotec and Rio-Eco pumps with slope modification and parallel shift . . 29
Fig. 23
List of tables
Table 1
Table 2
Table 3
Measured quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
31
060206_knowhow05_e_IS 31
KSB Know-how
Selecting
Centrifugal Pumps
KSB Know-how
Volume 01
KSB Know-how
Volume 02
Water Hammer
Boa-Systronic
KSB Aktiengesellschaft
Johann-Klein-Strae 9
67227 Frankenthal
Tel.: +49 (62 33) 86 21 18
Fax: +49 (62 33) 86 34 39
www.ksb.com
060206_knowhow05_e_IS 32
kubbli
11/06