Fan Unit (with Dust Filter)

1 Identification
2 Introduction

AFAN-H NB

2
2

3 Features and Application Notes


4 General Description

5 Mechanical Description

6 Fan Unit and Control Board


7 Fan Unit Characteristics
8 Dust Filter Characteristics

3EC 37533 NBAA TQZZA Ed 05

7
9
10

Released

1 / 10

AFAN-H NB
1

Fan Unit (with Dust Filter)

Identification
Table 1 provides identification of the AFAN-H:
Table 1: Unit Identification

Part Number

Mnemonic

Name

3EC 37533 NB

AFAN-H

Fan unit version H with dust filter

Introduction
This document describes the fan unit version H with dust filter.

Features and Application Notes


The AFAN-H unit provides the following features:

Provides forced air cooling in a 7302 Intelligent Services Access Manager (ISAM) FD

subrack or a 7360 ISAM FX-16 subrack.


Contains eight fixed-speed fans
Is mounted in the subrack fan area
Supported nominal voltages: -48Vdc
Contains a fan unit control board, which provides an alarm interface to the NT board
via the backplane
Is secured to the subrack by screws
Is field-replaceable and can be hot inserted
Is connected to the subrack backplane via two 15-pin male Sub-D connectors.
Equipped with dust filter (code 1AD014270005), for use in CO environment. This
dust filter must be removed when the shelf is used in closed (cabinet-like)
environments where such a filter is not applicable and where higher ambient
temperatures (higher than 45C) are expected.
Is available in two versions:

Metal version: 3EC 37533 NBAA


Plastic version: 3EC 37533 NBAC

3EC 37533 NBAA TQZZA Ed 05

Released

2 / 10

Fan Unit (with Dust Filter)


4

AFAN-H NB

General Description
The AFAN-H contains eight fixed-speed fans to cool the plug-in boards in the ISAM
subrack assembly. Figures 1 and 2 give an overall view of the AFAN-H units.
Figure 1 AFAN-H Overall View (Metal Version)

AIRFLOW

Alarm LED

Figure 2 AFAN-H Overall View (Plastic Version)

AIRFLOW

Alarm LED

3EC 37533 NBAA TQZZA Ed 05

Released

3 / 10

AFAN-H NB

Fan Unit (with Dust Filter)

The AFAN-H must be mounted in the fan area of the subrack.


When there is a malfunction of a fan blower, the fan alarm LED will turn red. Under
normal operating conditions, the fan alarm LED is not illuminated.
To prevent damage or system shutdown caused by overheating equipment following
precautions must be taken (refer to the 7302 ISAM FD Hardware Installation manual or
the 7360 ISAM FX Hardware Installation manual for specific instructions).

The AFAN-H must always be properly installed and operational before powering any
equipment in the subrack.

The AFAN-H must never be put out of operation for a longer time than specified in
the 7302 ISAM FD Hardware Installation manual and the 7302 ISAM Safety Manual
or the 7360 ISAM FX Hardware Installation manual and the 7360 ISAM FX Safety
manual.
Figure 3 shows the functional diagram of the AFAN-H.
Figure 3 AFAN-H Functional Diagram
+
ALM

x301

+
ALM

+
-

PBA-EFCU-E

Subrack Backplane

ALM

+
ALM

+
ALM

+
ALM

+
ALM

x302

+
ALM

3EC 37533 NBAA TQZZA Ed 05

Released

4 / 10

Fan Unit (with Dust Filter)


5

AFAN-H NB

Mechanical Description
Figure 4 shows the AFAN-H (metal version) and Figure 5 shows the AFAN-H (plastic
version).
Figure 4 AFAN-H Unit Views (Metal Version)

3EC 37533 NBAA TQZZA Ed 05

Released

5 / 10

AFAN-H NB

Fan Unit (with Dust Filter)


Figure 5 AFAN-H Unit Views (Plastic Version)

Dimensions
The fan has following dimensions:

Height: 60 mm
Width: 494 mm
Depth: 280 mm
Weight
Metal version: 4.9 kg
Plastic version: 3.1 kg
Front Panel
A single red alarm LED is located in the fan unit front panel. The LED is red in case of
fan failure. The LED is not illuminated during normal operation.

3EC 37533 NBAA TQZZA Ed 05

Released

6 / 10

Fan Unit (with Dust Filter)


6

AFAN-H NB

Fan Unit and Control Board


The fan unit alarm and control board provides the following functionality:

Provides fused power interface towards the different fans


Generates a common fan alarm output towards the NT boards (with integrated ACU
functionality) is case of fan failure
Provides for EMC/EMI filtering
The backpanel contains the connectors that plug into the subrack backpanel (see
Figures 6 and 7).
Figure 6 Backpanel Connectors (Metal Version)

BK
Kathode (-)

RD
Anode (+)

Backplane connectors
Dustfilter

Figure 7 Backpanel Connectors (Plastic Version)

BK
Kathode (-)

RD
Anode (+)

Backplane connectors
Dustfilter

Table 2 describes the layout of the left hand-side connector to the fan unit.

3EC 37533 NBAA TQZZA Ed 05

Released

7 / 10

AFAN-H NB

Fan Unit (with Dust Filter)


Table 2: 15-Pin SUB-D Connectors to Fan Unit (Left)
Signal Name

Type

Pin Nr.

Description

FAN_ALM0_A

'FAN-Unit 0' Alarm (A wire)

FAN_ALM0_B

FAN-Unit 0' Alarm (B wire)

FAN_ALM1_A

FAN-Unit 1' Alarm (A wire)

FAN_ALM1_B

10

'FAN-Unit 1' Alarm (B wire)

FAN_BATRET

Ref

FAN Battery Return Voltage

FAN_BATRET

Ref

15

FAN Battery Return Voltage

FAN_BATA

FAN Battery Supply Voltage, branch A

FAN_BATB

14

FAN Battery Supply Voltage, branch B

FAN_VAR0_A

Not used

FAN_VAR0_B

11

Not used

FAN_VAR1_A

Not used

FAN_VAR1_B

12

Not used

FAN_SP0

Not used

FAN_SP1

Not used

FAN_SP2

13

Not used

Table 3 describes the layout of the right hand-side connector to the fan unit.
Table 3: 15-Pin SUB-D Connectors to Fan Unit (Right)
Signal Name

Type

Pin Nr.

Description

FAN_ALM2_A

FAN-Unit 2' Alarm (A wire)

FAN_ALM2_B

FAN-Unit 2' Alarm (B wire)

FAN_ALM3_A

FAN-Unit 3' Alarm (A wire)

FAN_ALM3_B

10

FAN-Unit 3' Alarm (B wire)

FAN_BATRET

Ref

FAN Battery Return Voltage

FAN_BATRET

Ref

15

FAN Battery Return Voltage

FAN_BATA

FAN Battery Supply Voltage, branch A

FAN_BATB

14

FAN Battery Supply Voltage, branch B

FAN_VAR2_A

Not used

FAN_VAR2_B

11

Not used

FAN_VAR3_A

Not used

FAN_VAR3_B

12

Not used

FAN_SP3

Not used

3EC 37533 NBAA TQZZA Ed 05

Released

8 / 10

Fan Unit (with Dust Filter)

AFAN-H NB

Signal Name

Type

Pin Nr.

Description

FAN_SP4

Not used

FAN_SP5

13

Not used

Table 4 describes the layout of the fan connector.


Table 4: Layout for Fan Connector
Pin

Function

POWER (+48V)

Tacho CONTROL SIGNAL (output)

GND

Function control (input)

Table 5 describes the connector layout for LED connection.


Table 5: Layout for LED Connection

Pin

Function

FrontLed +

A48VL -

Fan Unit Characteristics


The fan unit has the following characteristics:

Maximum (free air) air flow: 8 x 172 m3/h = 1376m3 per hour (-48 Vdc)
Voltage range: -40 Vdc to -57 Vdc
Power consumption:
at -40 Vdc: 42.12 W +/- 5%
at -48 Vdc: 60.12 W +/- 5%
at -57 Vdc: 85 W +/- 5%
L-10 lifetime at ambient temperatures of 40C:
Metal version: 75000 h
Plastic version: 70000 h
Operating temperature range: -40C to +70C
Storage temperature range: -40C to +75C
Flammability according to UL94V-0
Acoustic noise sound power level (at 25C ambient and at 48Vdc): 75dB(A).

3EC 37533 NBAA TQZZA Ed 05

Released

9 / 10

AFAN-H NB
8

Fan Unit (with Dust Filter)

Dust Filter Characteristics


The dust filter (code 1AD014270005) has the following characteristics:

Made from non-woven synthetic material with a minimum dust arrestance of 80%.
Initial pressure <35 Pa
EN779 Classification E3
Dimensions: 7.6 mm x 465 mm x 205 mm
Dust filter life depends on the physical surroundings of the ISAM, typically 3 to 6
months (with an inspection every 2 months). Refer to the 7302 ISAM FD Hardware
Installation manual or the 7360 ISAM FX Hardware Installation manual for specific
instructions.
Complies to UL Class1 / UL94 HF-1
The dust filter is slid into a dedicated slot on the fan unit (see Figures 6 and 7).

3EC 37533 NBAA TQZZA Ed 05

Released

10 / 10