CONDITIONER
P/No. MFL39754865_V3
MFL39754865
Regd. Office: LG Electronics India Pvt. Ltd., A Wing (3rd Floor), D-3, District Center, Saket, New Delhi - 110017
15 ADVANCED FUNCTIONS
3
4 SAFETY INSTRUCTION
8
BEFORE
Prior to operation
Components
Electrical Safety
Using the remote control
Inserting Batteries
Installing the remote control holder
Wireless Remote Control
12 BASIC FUNCTIONS
Cooling your room
Heating your room
Removing humidity
Airing your room
Adjusting the fan speed
Adjusting the air flow direction
Setting the timer
Setting the current time
Turning ON the air conditioner
automatically at a set time
Turning OFF the air conditioner
automatically at a set time
Cancelling the timer setting
- Setting sleep mode
18 MAINTENANCE
Cleaning the air filter
Cleaning the anti-allergy filter
Cleaning the plasma filter
Cleaning the Micro Protection filter.
Outdoor Unit
21 TROUBLESHOOTING
Self-diagnosis function
Before requesting service
CAUTION
Contact the authorized service technician for repair or
maintenance of this unit.
Please install your air-conditioner by company
authorised service franchisee / authorised service
and sales dealer.
The air conditioner is not intended for use by young
children or invalids without supervision.
Young children should be supervised to ensure that
they do not play with the air conditioner.
When the power cord is to be replaced, replacement
work shall be performed by authorized personnel only,
using only genuine replacement parts.
AC TONNAGE
STABILIZER KVA
(3-STEP STABILIZER)
1.0
1.5
2.0
3
4
5
SAFETY INSTRUCTIONS
SAFETY INSTRUCTIONS
Do not install the air conditioner on an unstable surface or where there may be a danger of unit falling
It may result in death, serious injury, or product failure.
Only use components that are approved by the manufacturer and do not repair or modify them.
Failure to do so may result in electric shock, effect on product performance or product failure.
Only use the refrigerant specified on the air conditioner label. Failure to do so may result in explosion
or fire.
enter
SAFETY INSTRUCTIONS
ON OFF
When there is a gas leak, before using air conditioner again contact authorized service person for
verification and repair. Failure to do so may result in explosion or fire.
Do not block the inlet or outlet of air flow. It may effect product performance.
or serious injury.
or health complications.
For inner cleaning, contact an Authorized Service Center or a dealer. Do not use harsh detergent that
causes corrosion or damage on the unit. Harsh detergent that causes failure or product, fire or
electronic shock
not cause
neighbours.
,
Dos & Don'ts
SAFETY INSTRUCTIONS
remote
Prior to Operation
Preparing for Operation
1. Contact an installation specialist for
installation.
2. Plug in the power plug properly.
3. Use a dedicated circuit breaker.
4. Do not use an extension cord.
5. Do not start/stop operation by plugging/
unplugging the power cord.
6. If the cord/plug is damaged, replace it with
only an authorized replacement part.
Usage
1. Being exposed to direct airflow for a long
time may be hazardous to your health. Do
not expose occupants, pets, or plants to
direct airflow for a long time.
2. Due to the possibility of oxygen deficiency,
ventilate the room when using the
appliance together with stoves or other
heating devices.
3. Do not use this air conditioner for nonspecified special purpose (e.g. preserving
precision devices, food, pets, plants, or art
objects). Such use may damage your
properties.
Service
For repair and maintenance, contact your
authorized service dealer.
Components
Symbols used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that may cause harm to the
air conditioner.
This symbol indicates special notes.
Features
WARNING
This appliance should be installed in accordance with national wiring regulations. This guide acts as a
guide to help to explain product features.
Indoor unit
Air Inlet
Signal Receiver
Air Filter
Front Panel
Outdoor unit
Air Intake Vents
Connecting
Wires
Piping
Drain Hose
Electrical Safety
WARNING
This appliance must be properly grounded.
To minimize the risk of electric shock, you must always plug into a grounded outlet.
Do not cut or remove the grounding.
Attaching the adapter ground terminal to the wall receptacle cover screw does not ground the
appliance unless the cover screw is metal and not insulated, and the wall receptacle is grounded
through the house wiring.
If you have any doubt whether the air conditioner is properly grounded, check the wall receptacle
and circuit checked by a qualified electrician.
Air Circulation button Used to circulate the room air without cooling or
heating.
Mosquito Away operation button Used to
start or stop Mosquito Away operation
Sets the
sleep mode auto operation.
Display
Screen
2
FAN
MSOON
Control
Panel
fan speed.
HCOOL
LIGHT
M
MSOON
Signal Transmitter
HCOOL
Display
Screen
2
AM
ON
OFF
MSOON
A/CLEAN
Control
Panel
HCOOL
LIGHT
remote
LIGHT
12 BASIC FUNCTIONS
BASIC FUNCTIONS
Cooling your room
(Cooling operation)
(Monsoon operation)
1 Press
2 Press
operation.
- is displayed on the display screen.
1 Press
2 Press
-
3 Press
or
temperature.
- The temperature range is 18C 30C
2 Press
operation.
is displayed on the display screen.
-
3 Press
or
to set the desired temperature.
- The temperature range is 16C 30C
NOTE
NOTE
13
circulation operation.
is displayed on the display screen.
3 Press
NOTE
Adjusting the air flow direction horizontally may not be supported, depending
on the model.
Adjusting the air deflector arbitrarily may
cause product failure.
If you restart the air conditioner, it starts
to operate with the previously set direction of air flow, so the air deflector may
not match the icon displayed on the remote control. When this occurs, press
to adjust the direction of
or
the air flow again.
14
2 Press
3 Press
or
to finish.
or
to select the timer setting
to cancel.
2 Press
- To cancel all timer settings, press
(The timer lamp on the air conditioner and
the display will go off.)
1 Press
2 Press
or
time.
times.
to select desired
2 Press
3 Press
to finish.
4 When setting the timer, current time and
3 Press
4 Press
or
(up to 7 hours).
to finish.
is displayed on the display screen in
sleep mode.
2 Press
or
times.
to select the
desired
time.
3 Press
to finish.
4 When setting the timer, current time and
OFF icon are displayed on the display
screen indicating that the OFF TIMER is
set.
ADVANCED FUNCTIONS 15
ADVANCED FUNCTIONS
The air conditioner offers some additional advanced functions.
- If you turn off the power, the fan operates for 30 minutes and cleans the inside
of the indoor unit.
NOTE
Press
HCOOL
This mode minimizes power consumption during cooling and increases the set temperature
to the optimal level for a more comfortable environment.
The temperature automatically sets at
22C if ambient temperature is below 22C.
The temperature maintains if ambient temperature is above 22C
1 Press
2 Press
operation.
3 Press
-
1 Press
2 Press
is displayed on the display screen.
NOTE
16 ADVANCED FUNCTIONS
1 Press
2 Press
3 Press
or
Auto Changeover
(Optional)
1 Press
2 Press
AI
Code
2
1
0
Description
Cool
Cool slightly
Maintain
room
temperature
-1 Heat slightly
-2 Heat
NOTE
AI
3 Press
or
to set the desired
temperature.
- The temperature range is 18C - 30C
4 Press
NOTE
Dimmer (Optional)
In Dimmer Mode Unit Display will be turned OFF
completely but system will be in running state.
1 Press
- To start Mosquito Away function.
function.
2 Press
again to finish
NOTE
ADVANCED FUNCTIONS 17
(Forced Operation)
ON/OFF
restart (Optional)
8
Open the front
panel upward
ON/OFF
button
Open the front
panel upward
ON/OFF
button
Cooling Model
Operating mode
Cooling
High
High
High
High
Setting Temperature
22C
22C
23C
24C
NOTE
18 MAINTENANCE
OFF
consumption.
MAINTENANCE 19
Caution :
Do not press
the mesh
20 MAINTENANCE
,
- Do not wash the Micro Protection Filter
with water because the filter can be
damaged.
Outdoor Unit
The heat exchanger coils and panel vents of the outdoor unit
should be checked regularly. If clogged with dirt or soot, the
heat exchanger and panel vents may be professionally steam
cleaned.
(Rear)
Air intake
vents
(Side)
Piping
Drain Hose
Air outlet
vents
TROUBLESHOOTING 21
call
call
call
call
22 TROUBLESHOOTING
Operation ranges
For Heat & Cool model, heating operation range follows the below table.
Heating
Operation range
Outdoor temperature
0~24C
* When the outdoor temperature drops below 0C, heating capacity may drop slightly depending on the
operation condition.
When the air conditioner is not going to be used for a long time.
When air conditioner is not going to be
used for a long time.
CAUTION
Turn off the circuit breaker when the air conditioner
is not going to be used for a long time.
Dirt may collect and may cause a fire.
Remove the batteries from the remote
control.
DISCLAIMER 23
DISCLAIMER
IMPORTANT: Long term effect not tested and mosquitoes may become resistant. Mosquito species used in
the test below may differ from the mosquito species of your region. This product is one of the ways to manage
mosquitoes and not intended to replace other protective devices against mosquitoes.
Test Details:
A:
Tested by International Institute of Biotechnology and Toxicology (IIBAT), India, According to LG internal
testing method.
Test conducted, three times at temperature of 272C and humidity of 6010%
Test used two chambers size 3.5m x 2.6m x 2.2m, the chamber with the LG air conditioner assumed to
be inside (inside chamber) and the chamber without the LG conditioner assumed to be outside
(outside chamber).
Cages (25cm3) are placed inside each chamber, connected using netted sleeves to enable the movement
of the mosquitoes from one cage to another.
One person is placed inside the chamber to attract mosquitoes
For each test, 50 lab cultured 3-5 days old mosquitoes were placed in the cage in outside chamber; number
of mosquitoes coming into the cage in inside chamber was counted every 10 minutes for 90 minutes under
2 settings:
Control setting (low fan ON + mosquito repelling ultrasonic OFF)
Treatment setting (low fan ON + mosquito repelling ultrasonic ON)
Test Result:
Found to repel on average 81.1% of Aedes aegypti mosquitoes. Repel rate shows percentage of mosquitoes
prevented from entering the inside chamber after 90 minutes of Treatment setting compared to Control setting.
Represented average of 81.1% derived from 76.9%, 84.6%, 81.8%.
B:
Test Result:
Found to repel on average 72.5% of Aedes aegypti mosquitoes. Repel rate shows percentage of mosquitoes
prevented from entering the inside chamber after 90 minutes of Treatment setting compared to Control setting.
Represented average of 72.5% derived from 73.1%, 64.3%, 80.0%.
Results may vary in other settings, including but not limited to temperature, humidity, location, space, mosquito
species, number of mosquitoes, number of persons, and operation time.
INSTALLATION 21
20 INSTALLATION
TEST RUNNING
1. Check that all tubing and wiring have been
properly connected.
2. Check that the gas and liquid side service valves
are fully open.
Discharge air
Discharge
temperature
kgf/cm2
2
kgf/cm
PUMP DOWN
This is performed when the unit is to be
relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the
outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the
unit cooling mode.
Bolt
Tubing connection
INSTALLATION 19
AIR PURGING
Soap water method
(1) Remove the caps from the 2-way and 3-way
valves.
(2) Remove the service-port cap from the 3-way
valves.
(3) To open the 2-way valve turn the valve stem
counterclockwise approximately 90, wait for
about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent
on the indoor unit connection or outdoor unit
connections by a soft brush to check for
leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Gas side
Liquid side
3-way valve
(Close)
2-way valve
(Open)
Cap
Hexagonal wrench
C Evacuation
Connect the charge hose end described in the
preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.
Indoor unit
Outdoor unit
Manifold valve
Pressure
gauge
Lo
Hi
Open
Close
Vacuum pump
18 INSTALLATION
AIR PURGING
Air purging
Air and moisture remaining in the refrigerant
system have undesirable effects as indicated
below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may
freeze and block capillary tubing.
Water may lead to corrosion of parts in the
refrigeration system.
Therefore, the indoor unit and tubing between
the indoor and outdoor unit must be leak tested
and evacuated to remove any noncondensables
and moisture from the system.
Indoor unit
B Leak test
Outdoor unit
Manifold valve
Pressure
gauge
Lo
Hi
CAUTION
Be sure to use a manifold valve for air
purging. If it is not available, use a stop valve
for this purpose. The 3-way valve must always
be kept close.
CAUTION
To avoid nitrogen entering the refrigerant system in a
liquid state, the top of the cylinder must be higher than its
bottom when you pressurize the system. Usually, the
cylinder is used in a vertical standing position.
Nitrogen gas
cylinder(in vertical
standing position)
CAUTION
There is a risk of fire and explosion.
- Inert gas (nitrogen) should be used when you
check plumbing leaks, cleaning or repairs of
pipes etc.
If you are using combustible gases including
oxygen, product may have the risk of fires and
explosions.
INSTALLATION 17
A unit cabinet.
Taping
Drain
hose
Pipings
Connecting
cable
C Drain piping
The drain hose should point downward for
easy drain flow.
Downward slope
Trap
Accumulated
drain water
Air
Do not raise
Water
leakage
Water
leakage
Waving
Less than
50mm gap
Ditch
Trap
16 INSTALLATION
Outdoor Unit
Terminal block
Connecting cable 1
Connecting cable 2
Over 5mm
Cover Control
control
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for
the method of wiring, be guided by the circuit diagram posted on the inside of control
cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come
loose from vibrations to which the unit is subjected during the course of
transportation. Check them and make sure that they are all tightly fastened. (If they
are loose, it may cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capability is sufficient.
5) The starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 15))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the
normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed
wiring and have an air gap contact separation of at least 3mm in each active(phase)
conductors.
INSTALLATION 15
CAUTION
The power cord connected to the indoor unit should
be compiled with the following specifications
Capacity
(Btu/h)
no
Cooling model (9K,12K)
(Optional)
NORMAL CROSS
-SECTIONAL AREA
1.5mm2
18K
1.0mm2
9K, 12K
24K
2.5mm2
Capacity
(Btu/h)
NORMAL CROSS
-SECTIONAL AREA
2.5 mm2
18K,(2,3 Star)
24K
1.5 mm2
18K,(4,5 Star)
1.0mm2
9K, 12K
NORMAL
CROSS-SECTIONAL
AREA 0.75mm 2
CAUTION
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Main power source
Air
Conditioner
Circuit Breaker
Use a circuit
breaker or time
delay fuse.
14 INSTALLATION
Connection of the
piping-Outdoor
Align the center of the pipings and
Wrap with
vinyl tape(wide)
Piping for
passage through
piping hole
kgf.cm
180~250
340~420
550~660
630~820
990~1210
N.m
17.6~24.5
33.3~41.2
53.9~64.7
61.7~80.4
97~118.6
Tubing holder
1 Hook
Outdoor unit
Gas side piping
(Bigger diameter)
2 Push
Liquid side
piping
(Smaller
diameter)
Connecting
cable
Drain hose
Torque wrench
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
INSTALLATION 13
kgf.cm
180~250
340~420
550~660
630~820
990~1210
N.m
17.6~24.5
33.3~41.2
53.9~64.7
61.7~80.4
97~118.6
Drain pipe
Adhesive
Vinyl tape(narrow)
Indoor unit
Spacer
Installation plate
8cm
Connection
pipe
Vinyl tape
(wide)
Indoor unit tubing
Flare nut
Pipings
Pipe
Connecting cable
Flare nut
Connection pipe
Torque wrench
Indoor unit tubing
12 INSTALLATION
Spanner (fixed)
Flare nut
Indoor
unit pipe
Wrap with vinyl tape
Connection pipe
Torque wrench
Connecting cable
kgf.cm
180~250
340~420
550~660
630~820
990~1210
N.m
17.6~24.5
33.3~41.2
53.9~64.7
61.7~80.4
97~118.6
Vinyl tape(narrow)
Drain pipe
Vinyl tape(wide)
Drain hose
Indoor unit drain hose
Adhesive
Vinyl tape(narrow)
Connecting cable
Drain pipe
INSTALLATION
11
Loop
Tubing holder
To remove the holder,
press the bottom of
chassis near the holder
upward and pull the tab
out of its hole.
Liquid side
piping
Drain hose
Gas side
piping
Connecting
cable
CAUTION
When install, make sure
that the remaining parts
must be removed clearly
so as not to damage the
piping and drain hose,
especially power cord
and connecting cable.
Connecting
cable
Drain hose
Flare nut
Pipings
10 INSTALLATION
D Flaring work
Carry out flaring work using flaring tool as shown
below.
Outside diameter
mm
inch
6.35
90
1/4"
A
mm
1.1~1.3
1.9~2.1
3/4"
19.05
1.6~1.8
5/8"
15.88
1.6~1.8
1/2"
12.7
1.5~1.7
3/8"
9.52
Thickness
mm
0.7
0.8
0.8
1.0
1.0
Bar
Copper
pipe
"A"
Bar
Yoke
Cone
Copper pipe
Clamp handle
B Burrs removal
Completely remove all burrs from the cut E
cross section of pipe/tube.
Put the end of the copper tube/pipe in a
downward direction as you remove burrs in
order to avoid dropping burrs into the tubing.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared
section and do flaring work again.
Smooth all round
Pipe
Reamer
= Improper flaring =
Point down
Inclined Surface Cracked Uneven
damaged
thickness
Even length
all round
C Putting nut on
Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after flaring
work)
Flare nut
Copper tube
INSTALLATION
Outdoor
5-7mm
(0.2~0.3")
CAUTION
Make sure that the drilled hole in the wall is
properly sealed (using a proper sealant, for
example cement, plaster of paris etc.) after
passing the installation pipe, drainage pipe
and the inter connecting cable.
Type A Screw
B
Hole center
70mm
Drain Pan
Drain Pipe
INSTALLATION
Rooftop Installation
If the outdoor unit is installed on a roof structure, be
sure to level the unit. Ensure the roof structure and
anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
Pipe Size
GAS LIQUID
3/8"
1/4"
9K, 12K,
18K (2,3 star) 1/2" 1/4"
18K Heat Pump
18K (5 star)
24K Cooling
5/8" 1/4"
24K, 26K
Cooling & Heat Pump 5/8" 3/8"
Max.
length
20
3 to 5
20
3 to 5
A (m)
Standard
Length
(m)
3 to 5
3 to 5
20
20
Additional
Refrigerant
(g/m)
20
20
30
30
Outdoor unit
More than 2300mm
CAUTION
Indoor unit
B Outdoor Unit
Outdoor unit
Oil trap
Indoor unit
CAUTION
Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
INSTALLATION PARTS
Installation Tools
S.No.
Required Tools
Gas-Leak Detector
Hexagonal Wrench
Electric Drill
Screw Driver
Level Gauge
Thermometer
12
Gauge Manifold
11
Vacuum Pump
10
INSTALLATION PARTS
INSTALLATION PARTS
Installation parts provided with the unit
Name
Quantity
Type B Screw
Installation Plate
Type A Screw
Shape
Others
Owners Manual
Installation Manual
Shape
Others
Sleeve
Installationpartsyou
mustpurchase
Bushing Sleeve
Installation plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealant)
Owners
Manual
Installation
Manual
Air filter
Vinyl tape (Wide)
Vinyl tape
Vinyl tape
Connecting cable: Cooling & Heat pump: 2EA
Cooling only: 1EA
Saddle
SAFETY INSTRUCTIONS
Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product or may effect product performance.
to neighbours.
not cause
neighbours.
SAFETY INSTRUCTIONS
INSTALLATION PARTS
INSTALLATION
INSTALLATION MANUAL
ROOM AIR
CONDITIONER
Please read this installation manual completely before
installing the product and retain it for future reference.
TYPE : WALL MOUNTED
For Split AC Domestic Models
P/No. MFL39754865_V3
MFL39754865
Regd. Office: LG Electronics India Pvt. Ltd., A Wing (3rd Floor), D-3, District Center, Saket, New Delhi - 110017