Anda di halaman 1dari 5

Mod.

N-312
Rev.01 dd 23/02/2009
Page 1 of 5

New Product Technical Datasheet


Datasheet N:

0003/2008

rev.02 dd 10/05/2011

FLFE series
lighting fixtures
New
product:

FLFE-218

FLFE-236

FLFE-258

Marking
CE 0722:
1

II

2 GD Ex de IIC Ex tD A21 IP66 T6 T70CT80C Ta -20C+45C

10

1.

11

Ta spec. -20C+55C
12

CE mark means "European Conformity": the product fulfils all EU Directives requirements on safety, health,
consumer protection,...
2. Identification number of the notified board (CESI) that supervises production in compliance to 94/9/CE ATEX
Directive
3. Explosion Protection Marking
4. Apparatus Group II (surface equipment)
5. Category 2 (suitable for gas zone 1 and 2, dust zone 21 and 22)
6. Gas and Dust (suitable for both gas and dust zone)
7. Mode of protection (Ex de: explosion proof Ex d- with Ex e junction box; IIC: gas group; Ex tD A21: dust
protection)
8. IP mechanical protection degree
9. Temperature class
10. This is the max temperature that can be reached on the equipment hottest surface, while working
11. Ambient temperature allowed range
12. Extended ambient temperature allowed range (for special executions)

Ex Zone
ZONE 1; ZONE 21; ZONE 2; ZONE 22

ATEX certificate number


CESI 09 ATEX 008

Other available certifications


Will follow upon market demand

Conformity to Standards
EN60079-0, EN60079-1, EN60079-7, EN61241-0, EN61241-1

Compliant to
ATEX 94/9/CE Directive

New Product Technical Datasheet

Mod.N-312
Rev.01 dd 23/02/2009
Page 2 of 5

Applications and use


Cortem FLFE series lighting fixtures are normally used to light uniformly indoor and
outdoor areas requiring limited vertical encumbering, low power consumption (feature of
fluorescent tubes technology), easy installation (see the wide range of mounting kits,
allowing a quick and safe mounting (without need of sealing fittings) and maintenance /
re-lamping operations.
Advantages:
The fixture has been designed with an Ex e terminal junction box which allows
connecting it with an Ex e cable gland (not necessarily Ex d barrier cable gland) and
hence, the equipment installation in both cable and conduit distribution plants.
Easy and fast re-lamping procedure, and hence higher safety and cost savings on
maintenance.
The fixture, in the Emergency execution, is provided with all electric components
internally mounted, reducing encumbering in the installation area.
The fixture is presented with a wide variety of mounting kits, which make it particularly
performing.
NOTE: for further info please refer to the technical dossier on Cortem
General Catalogue

Installation

Chemical, petrochemical and pharmaceutical industries, refineries


Oil & Gas installations (Onshore and offshore), naval equipment
Explosion / fire hazardous areas
Nuclear power plants, thermal power plants
Joineries, sugarhouses, silos in general

Furthermore, due to their high mechanical robustness and to the Cortem exclusive paint
treatment, FLFE series fixtures are also suitable for:

Chemically aggressive and extreme environments


Marine environments with high saline corrosiveness
Sites with presence/occurrence of mechanical shocks, due to vibrations and impacts
Sites with presence of UV
Environments with ambient temperature up to +55C (see tab. A, below)
Ta -20C +45C
Max. Surface Temp.
T70C

Ta -20C +55C
Max. Surface Temp.
T80C

Normal service

Normal service +
emergency

Emergency only
(NP service)

Table A

Ta -20C +50C
Max. Surface Temp.
T75C

New Product Technical Datasheet

Plus

Ex e junction box, complete with 4


or more feed terminals type RN2
(4mm2 section) and Earth screw.

N2 hubs M25 threaded


GAS UNI ISO 7/1
Complete with no.1 PLG2IB plug
and no.1 FL2IBK cable gland (ext
cable dia range 1217mm).

Re-lamping and electric/electronic gears substitution

Unscrewing the cover it is possible


to have direct access to the fixture
internal chamber.

After disconnecting it, it is possible


to take out the internal mounting
plate, making it slide on its own
rails.

Mod.N-312
Rev.01 dd 23/02/2009
Page 3 of 5

Mod.N-312
Rev.01 dd 23/02/2009
Page 4 of 5

New Product Technical Datasheet


Construction features
Protection upon request

Cover
O-ring
Electrical equipment

Frame/reflector
Plug type PLG2IB

Fluorescent tubes

Internal frame guide

Connector
terminals L, N, Pe sez.4 mm

Cable gland type FL2IBK


Sealed bushing
Lampholder type G13

O-ring
Cover

Stainless steel guard upon request

Electrical features
- Suitable for no.2 fluorescent tubes
(18W,36W,58W)
- Nominal voltage 230VAC (110, 240, 277V
upon request)
- Nominal frequency: 50/60Hz
- Direct connection to terminal strip L, N, Pe
section 4mm2
- Bi-pin lamp-holder, type G13
- 4Ah or 7Ah, 6VDC rechargeable batteries
- Electronic Inverter 110/230VAC, 50/60Hz
- Electronic ballast 110/230VAC, 50/60Hz
- Signalling LED installed onto internal
frame, in order to verify batteries charge
current
- Internal wiring in silicone rubber, glass
fibre reinforced, cables.
- Possibility to loop-in / loop-out connection
between multiple installed fixtures (special
execution for FLFE with emergency
service)
- safety switch installed internally for fixture
in emergency service

(certificate extension for loop-in/loop-out connection, for emergency


service fixtures, coming soon)

Accessories

Protection guard + external protection for the electrical part against UV


rays and environment agents.
Fluorescent tubes 2 pin 26 T8
Fixture Mounting Kits (see options ad codes in the sketch)
Bracket for relamping loop-in / loop-out connection between multiple
installed fixtures
Other voltages rating

Fixture mounting kits


(available upon request)

Cod.

M8

T
(Tige)

20

GOF-8
(Eyebolt)

140
10

10

G-244
(Bracket type U)
140
10

10

G-263
(Bracket type V)

10

G-258
(Bracket type D)

45

10

G-0480
(Pole bracket)
1 12"
40

- End-cups in copper-free aluminium, as a


standard RAL7035 epoxy coated
- Borosilicate glass tube, resistant to shocks
and high temperatures
- Internal mounting plate in aluminium, white
painted, performing as a reflector too
(standard)
- Silicone resin between glass tube and
aluminium end cups
- Electric/electronic gears protection against
UV radiation by means of an additional
aluminium white painted reflector and a
stainless steel protection guard (upon
request)
- Nickel plated brass PLG2IB plug and
FL2IBK cable gland (standard)
- Neoprene sealing gaskets, resistant to
acids and hydrocarbons
- Stainless steel screws

100

Mechanical features

M8

New Product Technical Datasheet

Mod.N-312
Rev.01 dd 23/02/2009
Page 5 of 5

Models
Code
FLFE-218
FLFE-236
FLFE-258
FLFE-218EF
FLFE-236EF
FLFE-258EF

Watt
18
36
58
18
36
58

Service

Supply

Normal service
230VAC 50/60Hz
Normal service +
emergency

Market

Industry
o Mechanical and electrical engineering
o Onshore and Offshore Oil & Gas equipment
o Agro-food
o Distilleries
o Natural gas
o Pharmaceutical
o Explosives storage

Engineering and Contractors


o Project Design companies
o Electrical contractors
o Construction companies

Electrical equipment distributors


Shipyards / ports
Plants maintenance companies

Product line description


FLFE lighting fixture series has been designed considering the following market demands:
-

Low surface temperature


Possibility of installation in environments with ambient temperature up to +55C (see also table A
on page 2)
Low power consumption
Possibility to have the electrical/electronic gears inside the fixture body, avoiding the use of added
separate enclosures
Possibility to mount standard (not barrier) cable glands, with related cost savings
Easier maintenance and re-lamping operations
Economical advantage compared with EVF-218/236/258EB and EVF-218/236/258E series

In order to identify the desired model code, please check the General Catalogue, the
short-form Catalogue or Cortem web site.