HOJA DE DATOS

CLIENTE:
PROYECTO:

REA:
TTULO:

PEB / STO

E-FD-7020.18-1210-800-IPK-001
HOJA:

PETROBRAS BOLIVIA S.A.


1
ING. BSICA DUCTO Y FACILIDADES
MDULO III + SBL-6
CAMPO DE SABALO 11
ELEMENTO DE MEDICION DE FLUJO POR DISPERSIN
TERMICA

ARCHIVO :

E-FD-7020.18-1210-800-IPK-001=0.XLS

CONTRATO :

PEB-AJUR 301-2013

de

NDICE DE REVISIONES
REV.

DESCRIPCIN Y/U HOJAS AFECTADAS

EMISIN ORIGINAL

REV. 0
FECHA

REV. A

REV. B

REV. C

REV. D

REV. E

REV. F

REV. G

07/04/2014

PROYECT

IPE

EJECUCIN

D. DELGADILLO

VERIFICACIN

G. MONTAO

APROBACIN

W. CHAVEZ

LAS INFORMACIONES DE ESTE DOCUMENTO SON PROPIEDAD DE PETROBRAS BOLIVIA S.A., SIENDO PROHIBIDA SU UTILIZACIN FUERA DE SU FINALIDAD.
PE-5I3-00004 - ANEXO A PADRONIZADO POR LA NORMA PETROBRAS N-381 REV. G.

REV. H

HOJA DE DATOS
PROYECTO:

TTULO:

GENERAL

PROCESS
CONDITIONS

FLOW ELEMENT
(PROBE)

TRANSMITTER

PURCHASE

ING. BSICA DUCTO Y FACILIDADES


MDULO III + SBL-6

de

ELEMENTO DE MEDICION DE FLUJO POR DISPERSIN


TERMICA

Tag Number

40-FQIT-91131

Service

Medidor de Caudal de Gas al Flare

P&ID

E-DE-7020.11-1210-944-BSQ-002

Line

4-92095-FL-6"-CB10-B

Location

Pluma de Venteo 4-FL-1001

Pipe Diameter

8" (inch)

Pipe Material

API - 5L Gr.B

Schedule

20

Function

Indicacin Continua de Caudal

10

Type

Thermal Dispersion

11

Mounting

Local

12

System

Process System - DeltaV PCS (Panel 4-PCS-01)

13

Area Classification

Class 1, Zone 2, Group C/D

14

Fluid

15

Flow Oper. (MSCFD)

Flow Max. (MSCFD)

4000

4400

16

Pressure Oper. (Psig)

Pressure Max. (Psig)

10

58.10

17

Temperature Oper. (F)

Temperature Max. (F)

71,58

18

Oper. Density (lb/ft3)

0.04283

19

Molecular Weigth

21.08

20

Compressibility Factor Z

0.9974

21

Style or Type

Insertion Probe, with Retractable packing glands

22

Probe Material

AISI 316 SS

23

Process Connection

Flange RF

24

Flange Size

2 RF - ANSI #150

25

Probe position related to pipe

Vertical Pipe, Flow up

26

Process Temperature Range

-50 F to 200 F

27

Calibration System

VeriCal system for in situ calibration

28

Insertion U-Length

9"

29

Flange of Top distance

6" cara superior de la brida

30

Additional Fitting

Retractable packing glands

31

Material Housing

Aliminum

32

Enclosure

Explossion Proof

33

Transmitter Electronics

Mounted on a separated cabinet

34

Material Housing

Aluminum

35

Electrical conection

2 x 1" NPT-F

36

Keypad

Include

37

Indicator Display

Include

38

Output Signal

Analog 4 - 20 mA

39

Digital Signal

RS-232C (EIA-232)

40

Protection Grade

IP 66 - Explosion Proof - resists of weather and corrosion

41

Dual Alarm

High / Low Temperature

42

Power Supply

24 VDC

43

Agency Approval

ATEX, EExd IIC T4

44

Number of Contacts

45

Type of Relays

SPDT

46

Manufacturer

FCI

47

Model

GF90-CA-4DDVABMHE0090D-G5-A3

48

Serial Number

Natural Gas

1. Calculating Insertion Length - Probe:


L = OC + PD/2 + N + V
L = 1 + (8/2) +1.5 + 2.5
L = 9"
L = Injection length
OC = Over Center (1"inch in accordance by manufacturer)
PD = Pipe Diameter (8" inch)
N = Length Flange (1.5" inch)
V = Length of VeriCal Fitting (2.5" inch)
2. Mount the flow element at least 20 diameters downstream and 10 diameters upstream from any bends or interference
LAS INFORMACIONES DE ESTE DOCUMENTO SON PROPIEDAD DE PETROBRAS BOLIVIA S.A., SIENDO PROHIBIDA SU UTILIZACIN FUERA DE SU FINALIDAD.
PE-5I3-00004 - ANEXO A PADRONIZADO POR LA NORMA PETROBRAS N-381 REV. G.

HOJA:

NOTES

Where:

REV.

E-FD-7020.18-1210-800-IPK-001