TCE CONSULTING ENGINEERS LIMITED

30421007-3CL00007-P0B

SHEET i OF i
CT & PT CALCULATION FOR 480V SWITCHGEAR
SIZING REPORT

SAUDI ELECTRICITY COMPANY


EASTERN OPERATING AREA
Dammam, Saudi Arabia
GENERATION EXPANSION OF ARAR POWER PLANT
(CONTRACT NO : 30421007/00)

DESIGN BASIS
FOR
CT & PT CALCULATION FOR 480V SWITCHGEAR

DOCUMENT NO : 30421007-3CL-0000-P0B
APRIL 2005

ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST.MARK'S ROAD
BANGALORE 560001
INDIA

CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O.BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL.00966-1-14633660 : FAX.00966-1-4631150

P0B
03.05.2005

DG

SJH

REV NO. DATE

PREPARED BY

CHECKED BY

276447609.xls
SECTION :cover sheet

CLEARED BY

APPROVED BY

SHEET 1 OF 9

By

TCE CONSULTING ENGINEERS LIMITED

DG

Date
Chd.
Date

7/14/2015

Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH
7/14/2015

Project : Generation expansion at ARAR P/P

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

Rev. No.

CALCULATIONS FOR CT & PT PARAMETERS IN ARAR GENERATION EXPANSION PROJECT


REFERENCE DATA
1) Short Cicruit Study
2) General Site Layout - Dwg No KA-667182
3) SEC -EOA's Specification : PTS-1022
4) Main One line diagram(480V Swgr) dwg no KA667484
5) 480V Aux One line Diagram KT-808221

2 of 9

P0B

By

TCE CONSULTING ENGINEERS LIMITED

DG

Date
Chd.
Date

7/14/2015

Project : Generation expansion at ARAR P/P


Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

7/14/2015

Rev. No.

480V Switchgear Incomer CT sizing


1) Calculation of parameters for SAT Neutral side CT used for Earth Fault 51G protection.
BCT-HY.C1
Station Auxiliary Transformer Rating

3 MVA , ONAN
4.16/0.480kV, Dyn11, Z=8% at ONAN rating

Therefore full load currrent on 480V Side

=
=
=

(MVAx 1000)/(1.732 x kV)


3
x
1000
/ 1.732 x
3608.55
Amps

CT ratio chosen

0.48

4000/1 A

Relay Used : SPAJ110C


Knee Point Voltage Formulae
The rated knee point voltage

Ek

Kx (Rct+Rb) x Isn

( IEC 60044-1 Amend, Page 17)

where
Kx
Rct
Isn
Rb

= Dimensioning facor
= Maximum resistance of secondary winding
= Rated secondary current
= Rated resistive burden
= Rrelay + 2Rl
Rl
= Cable resistance between CT & Relay
Knee Point Voltage calculation
The actual fault as per short cirucit study is 45.7kA. Considering 20% margin it is
Kx
= 54.84/ 2000
=

27.42

Rct

14

Rb

54.84 KA

Rrelay + 2Rl

The CT burdens of numerical relays are below 0.1VA and can therefore be neglected
Considering 6 sq.mm copper conductor cable between CT and relay, resistance of
6 sq.mm copper cable
=
3.5
Ohms / km
Maximum cable length
=
50
Cable Lead Resistance for the loop Rl

Rb

0.350

0.350

M
=

(from site plan)


2

3.5

Ohms

Knee point voltage Ek

=
27 x (14 + 0.35)
=
393
Considering a margin of 20% on Ek as per PTS-1022, Appendix-V, Page 20 of 46
=
472
Ek

CT Class =
Therefore CT chosen
CT RATIO
Knee Point Voltage
CT Wdg. Res. Rct
CT Class
CT Cable to be used

475

PX

>=
=

4000/1 A
475 V
14 ohms
PX
6 sq.mm copper cable

2) Calculation of CT parameters for ( 51& 51N) on LV side of SAT


CT-101F.C1

3 of 9

0.05

P0B

By

TCE CONSULTING ENGINEERS LIMITED

DG

Date
Chd.
Date

7/14/2015

Project : Generation expansion at ARAR P/P


Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

7/14/2015

Rev. No.

CT Ratio Selection :
SAT Rating

Full Load current on 0.48kV side

=
=

CT ratio selected on 480V side is

3.0

MVA

(MVAx 1000)/(1.732 x kV)


3608.44 A
=

4000 /1 Amp

Relay Used : SPAJ140C


Knee Point Voltage Formulae
The rated knee point voltage

Ek

Kx (Rct+Rb) x Isn

( IEC 60044-1 Amend, Page 17)

where
Kx
Rct
Isn
Rb

= Dimensioning facor
= Maximum resistance of secondary winding
= Rated secondary current
= Rated resistive burden
= Rrelay + 2Rl
Rl
= Cable resistance between CT & Relay
Knee Point Voltage calculation
The actual fault as per short cirucit study is 45.7KA. Considering 20% margin it is
Kx
= 54.84/ 2000
=

27.42

Rct

14

Rb

54.84 KA

Rrelay + 2Rl

The CT burdens of numerical relays are below 0.1VA and can therefore be neglected
Considering 6 sq.mm copper conductor cable between CT and relay, resistance of
6 sq.mm copper cable
=
3.5
Ohms / km
Maximum cable length
=
50
Cable Lead Resistance for the loop Rl

Rb

0.350

0.350

M
=

(from site plan)


2

3.5

0.05

Ohms

Knee point voltage Ek

=
27 x (14 + 0.35)
=
393
Considering a margin of 20% on Ek as per PTS-1022, Appendix-V, Page 20 of 46
=
472
Ek

CT Class =
Therefore CT chosen

475

PX

CT RATIO
Knee Point Voltage
CT Wdg. Res. Rct
CT Class
CT Cable to be used

>=
=

4000 /1 Amp
475 V
14 ohms
PX
6 sq.mm copper cable

3) SAT LV side metering CT


CT-101F.C1
Meters

0.05
0.05

Total
CT VA burden selected is

As per ION metering catalogue

30VA

Voltage developed across CT at rated current(1A) =

1 x (Rct + 30) V

4 of 9

P0B

By

TCE CONSULTING ENGINEERS LIMITED

DG

Date
Chd.
Date

7/14/2015

Project : Generation expansion at ARAR P/P


Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

7/14/2015

Rev. No.

=
=

1 x (14 + 30)
44V

Isf selected is 5
Therefore during fault voltage across CT = 5 x (Rct + 30) V
=
185 V
When the connected burden is 0.05 the voltage developed is
=
y x (14 + 0.05)
y

Where y is magnified Isf)

13

Therefore CT chosen

4000 /1 A.
30 VA
CL.0.5
ISF <5.

4) Calculation of parameters for 480V VT on LV side of SAT & Bus VT


VT ratio chosen

480/ 3 /115/ 3

VT will be with dual accuracy

0.5 / 3P class

Equipment

VA Burdens
0.05 As per ION catalogue
0.5
ABB catalogue

Meters

27-1 & 2
Total

0.55
Therefore PT chosen =

480/ 3 /115/ 3
0.5 / 3P class
100 VA

Unit Switchgear Incomer


5) Calculation of parameters for UAT Neutral side CT used for 51G protection.
BCT-HY.C1
Refer CT calculation for GT and UAT bay
6) Calculation of CT parameters for ( 50/51& 51N) on LV side of UAT & Incomer from Station Swgr
CT-201F.C1 & CT-202F.C1
UAT Rating

Full Load current on 0.48kV side

=
=

CT ratio selected on 480V side is

1.25

MVA

(MVAx 1000)/(1.732 x kV)


1503.52 A
=

2000 /1 Amp

Knee Point Voltage Formulae


Knee Point Voltage Formulae
The rated knee point voltage

Ek

Kx (Rct+Rb) x Isn

( IEC 60044-1 Amend, Page 17)

where
Kx
Rct
Isn
Rb

= Dimensioning facor
= Maximum resistance of secondary winding
= Rated secondary current
= Rated resistive burden
= Rrelay + 2Rl
Rl
= Cable resistance between CT & Relay
Knee Point Voltage calculation
The actual fault as per short cirucit study is 44kA. Considering 20% margin it is
Kx
= 52.8/ 2000

5 of 9

52.8 KA

P0B

By

TCE CONSULTING ENGINEERS LIMITED

DG

Date
Chd.
Date

7/14/2015

Project : Generation expansion at ARAR P/P


Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

7/14/2015

26.4

Rct

Rb

Rev. No.

Rrelay + 2Rl

The CT burdens of numerical relays are below 0.1VA and can therefore be neglected
Considering 6 sq.mm copper conductor cable between CT and relay, resistance of
6 sq.mm copper cable
=
3.5
Ohms / km
Maximum cable length
=
50
Cable Lead Resistance for the loop Rl

Rb

M
=

0.350

0.350

(from site plan)


2

3.5

0.05

Ohms

Knee point voltage Ek

=
26 x (7 + 0.35)
=
194
Considering a margin of 20% on Ek as per PTS-1022, Appendix-V, Page 20 of 46
=
233
Ek

250

CT Class =

PX

Therefore CT chosen
CT RATIO
Knee Point Voltage
CT Wdg. Res. Rct
CT Class
CT Cable to be used

>=
=

2000 /1 Amp
250 V
7 ohms
PX
6 sq.mm copper cable

7) Calculation of parameters for UAT LV side Overall Unit Differential Protection 87OA.
CT-201F.C3
Refer CT calculation for GT and UAT bay
8) Calculation of parameters for 480V VT for Incomers & Bus VT
PT201
Refer Calculation for GT and UAT bay
9) Incomer metering CT
CT-201F.C2 & CT-202F.C2
Refer Calculation for GT and UAT bay
Station Switchgear & Unit Switchgear Outgoing feeders
10) 800A Feeder(Typ)- 50/51, 50N/51N
CT ratio selected

800 /1 Amp

Knee Point Voltage Formulae


The rated knee point voltage

Ek

Kx (Rct+Rb) x Isn

( IEC 60044-1 Amend, Page 17)

where
Kx
Rct
Isn
Rb

= Dimensioning facor
= Maximum resistance of secondary winding
= Rated secondary current
= Rated resistive burden
= Rrelay + 2Rl
Rl
= Cable resistance between CT & Relay
Knee Point Voltage calculation

6 of 9

P0B

By

TCE CONSULTING ENGINEERS LIMITED

DG

Date
Chd.
Date

7/14/2015

Project : Generation expansion at ARAR P/P


Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

7/14/2015

Kx

20

Rct

Rev. No.

Rb
= Rrelay + 2Rl
The CT burdens of numerical relays are below 0.1VA and can therefore be neglected
Rl is neglible as they are internally wired.
Knee point voltage Ek

=
20 x
3
=
60
Considering a margin of 20% on Ek as per PTS-1022, Appendix-V, Page 20 of 46
=
72
Ek

100

CT Class =
Therefore CT chosen

PX

CT RATIO
Knee Point Voltage
CT Wdg. Res. Rct
CT Class

>=
=

800 /1 Amp
100 V
3 ohms
PX

11) 1000A Feeder(Typ)- 50/51, 50N/51N


CT ratio selected

1000 /1 Amp

Knee Point Voltage Formulae


The rated knee point voltage

Ek

Kx (Rct+Rb) x Isn

( IEC 60044-1 Amend, Page 17)

where
Kx
Rct
Isn
Rb

= Dimensioning facor
= Maximum resistance of secondary winding
= Rated secondary current
= Rated resistive burden
= Rrelay + 2Rl
Rl
= Cable resistance between CT & Relay
Knee Point Voltage calculation
Kx

20

Rct

3.5

Rb
= Rrelay + 2Rl
The CT burdens of numerical relays are below 0.1VA and can therefore be neglected
Rl is neglible as they are internally wired.
Knee point voltage Ek

=
20 x
3.50
=
70
Considering a margin of 20% on Ek as per PTS-1022, Appendix-V, Page 20 of 46
=
84
Ek

CT Class =
Therefore CT chosen
CT RATIO
Knee Point Voltage
CT Wdg. Res. Rct
CT Class

100

PX

>=
=

1000 /1 Amp
100 V
3.5 ohms
PX

7 of 9

P0B

By

TCE CONSULTING ENGINEERS LIMITED

DG

Date
Chd.
Date

7/14/2015

Project : Generation expansion at ARAR P/P


Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

7/14/2015

Rev. No.

12) 2000A Feeder(Typ)- 50/51, 50N/51N


CT ratio selected

2000 /1 Amp

Knee Point Voltage Formulae


The rated knee point voltage

Ek

Kx (Rct+Rb) x Isn

( IEC 60044-1 Amend, Page 17)

where
Kx
Rct
Isn
Rb

= Dimensioning facor
= Maximum resistance of secondary winding
= Rated secondary current
= Rated resistive burden
= Rrelay + 2Rl
Rl
= Cable resistance between CT & Relay
Knee Point Voltage calculation
Kx

20

Rct

Rb
= Rrelay + 2Rl
The CT burdens of numerical relays are below 0.1VA and can therefore be neglected
Rl is neglible as they are internally wired.
Knee point voltage Ek

=
20 x
7
=
140
Considering a margin of 20% on Ek as per PTS-1022, Appendix-V, Page 20 of 46
=
168
Ek

175

CT Class =
Therefore CT chosen

PX

CT RATIO
Knee Point Voltage
CT Wdg. Res. Rct
CT Class

>=
=

2000 /1 Amp
175 V
7 ohms
PX

13 ) CT parameters for Station switchgear Bus coupler protection , 51


CT1.1
CT ratio selected

4000 /1 Amp

Knee Point Voltage Formulae


The rated knee point voltage

Ek

Kx (Rct+Rb) x Isn

( IEC 60044-1 Amend, Page 17)

where
Kx
Rct
Isn
Rb

= Dimensioning facor
= Maximum resistance of secondary winding
= Rated secondary current
= Rated resistive burden
= Rrelay + 2Rl
Rl
= Cable resistance between CT & Relay
Knee Point Voltage calculation
Kx

20

Rct

14

Rb
= Rrelay + 2Rl
The CT burdens of numerical relays are below 0.1VA and can therefore be neglected

8 of 9

P0B

By
Date
Chd.
Date

TCE CONSULTING ENGINEERS LIMITED

DG
7/14/2015

Doc. No.30421007-3CL-00007

Client : Saudi Electricity Company

SJH
7/14/2015

Project : Generation expansion at ARAR P/P

Subject : CT & PT Calculation for 480V Swgr


Contract No.- 30421007

Rev. No.

Rl is neglible as they are internally wired.


Knee point voltage Ek

=
20 x
14
=
280
Considering a margin of 20% on Ek as per PTS-1022, Appendix-V, Page 20 of 46
=
336
Ek

CT Class =
Therefore CT chosen
CT RATIO
Knee Point Voltage
CT Wdg. Res. Rct
CT Class

350

PX

>=
=

4000 /1 Amp
350 V
14 ohms
PX

9 of 9

P0B