Indicadores luminosos
A
B
C
D
E
Pulsadores de mando
1 y 2.
3. ESC/MENU:
4. ENTER:
Manejo de la central
En condiciones normales de operacin la central muestra la pantalla principal, visualizando la
concentracin de CO en cada zona y el estado de la lnea de deteccin y los rels de
ventilacin y alarma.
Estado de la zona
ZONA 1
ZONA 2
ZONA 3
ZONA 4
Anulada
Sin Sensores
Anulada
Anulada
Z1:
Z2:
Z3:
Z4:
100
250
065
300
Vent. Man. H
Vent. Man. F
Niv. V. :050
Vent. Autom.
Concentracin de CO (ppm)
Nmero de zona
-2-
Pulsando la tecla men se accede a las pantallas de men. Existen 5 pantallas de men a las
que se puede acceder a travs de las teclas
o :
Ventilacin (Activacin Manual/Modo Ventilacin, ver figura 1).
Servicio (Zonas On/Off, ver figura 2).
Programacin de Ventilacin (Nivel y Retardo, ver figura 3).
Programacin de Retardo de Alarmas
(figura 4).
Recuperar Datos de Origen (figura 5).
Los datos de origen son los siguientes:
Retardo
Alarma
[CO]
Parmetro
Valor
Nivel de Ventilacin:
Retardo Ventilacin:
Retardo Postventilacin:
Nivel de Alarma:
Retardo Alarma:
Margen
Nivel de
Alarma
50 ppm
4 min
4 min
300 ppm
15 min
Retardo
Postventilacin
Ventilacin
Retardo
Parada
Ventilacin
Alarma
Parada
Alarma
Activada
Nivel de
Ventilacin
Ventilacin
Activada
Ventilacin
Activada
Tiempo
Instalacin
La figura muestra el esquema general de conexionado de los diferentes elementos con la
central.
Se pueden conectar un mximo de 22 detectores por zona.
2
Se recomienda el uso de cable con una seccin mnima de 1.5 mm y la longitud mxima del
mismo por zona no debe exceder los 400m, en una distribucin lineal de detectores.
Estructura por Zona
ALAR.
- +
- +
Alarma
VENT.
ZONA
- +
Ventilacin
-3-
A / VENT.
MANUAL
M : A / VENTILACION
Activar Manual
zona
zona
zona
zona
1
2
3
4
fija
A / ZONA 1
MODO VENT 1 hora
Seleccin de zona +
ENTER
stop +
ENTER
ENTER
ZONA 1 Ventilacion
Conectada
fija
fija +
A / ZONA 1
start
VENT. MAN. F stop
ENTER
ZONA 1 Ventilacion
Manual Parada
start +
ENTER
stop +
ENTER
ZONA 1 Ventilacion
Conectada 1 hora
1 hora +
A / ZONA 1
start
VENT. MAN. H stop
ENTER
ZONA 1 Ventilacion
Manual Parada
start +
ENTER
B / SERV.
ON_OFF
M : B / SERVICIO
On / Off Zonas
ENTER
zona
zona
zona
zona
1
2
3
4
Seleccin de zona +
ZONA 1 Queda
Servicio
on +
B / ZONA 1
SERVICIO
on
off
ENTER
en
ENTER
ZONA 1
Queda
Anulada
off +
ENTER
-4-
C / PROG. zona
NIVEL
zona
RETARDO zona
zona
M : C / PROGRAMACION
VENT: NIvel / Ret
1
2
3
4
C / PROG.
ZONA 1
Seleccin de zona +
ENTER
ENTER
ESC
nivel +
ENTER
nivel
retardo
C / PROG.
ZONA 1
nivel
retardo
C / GRABAR NIVEL
NO: esc SI: enter
C / PROG.
ZONA 1
Nivel: 050 ppm
Seleccin de nivel +
Zona 1 Grabandose
Nivel de ventilacion ... OK
ENTER
ENTER
ESC
C / PROG.
ZONA 1
retardo +
ENTER
C / PROG.
Retardo:
nivel
retardo
C / GRABAR RETARDO
NO: esc SI: enter
ZONA 1
4 min
Seleccin de retardo +
Zona 1 Grabandose
retardo de ventilacion ... OK
ENTER
ENTER
ESC
M : D/ PROG. ALARMAS
Retardo: 10 min
M : D/ PROG. ALARMAS
Retardo: 10 min
D / GRABA RETARDO
NO: esc SI: enter
Seleccin de retardo +
Zona 1 Retardo
Alarma grabandose ... OK
ENTER
ENTER
ESC
M : E/ RECUPERAR
DATOS DE ORIGEN
M : E/ RECUPERAR
DATOS DE ORIGEN
-5-
+
BAT
Bateras
J1
- +
Alar
Ve nt
- +
Zona1
Vent1 Z1
Q2
U3
U4
1
Q4
D2
U2
1
Q3
D1
K2
D4
K1
Alarma Z1
Vent1 Z2
Alarma Z2
Alarma Z3(*Z1)
Vent1 Z3(*Z1)
Vent1 Z4(*Z2)
Alarma Z4(*Z2)
Q1
D3
Q5
D5
K5
- +
Zo na2
K4
Vent
Z1
Z2
Z3
Z4
AL
GND CPU
- +
Alar
K3
- +
Zo na1
R5
Vent
R4
- +
Alar
R3
- +
Zona2
R1
Ve nt
R2
- +
Alar
J4
U1
1
U5
1
Vent2 Z2
Vent2 Z3
Vent2 Z4
Vent2 Z1
Valor
Nivel de Ventilacin 1:
50 ppm
Retardo Ventilacin 1:
4 min
Retardo Postventilacin 1:
4 min
Nivel de Ventilacin 2:
200 ppm
Retardo Ventilacin 2:
10 min
Retardo Postventilacin:
Nivel de Alarma:
Retardo Alarma:
4 min
300 ppm
15 min
Margen
Programable
(20 150 ppm)
Programable
(1 9 min)
Fijo
Programable
(20 300 ppm) y
Nivel ventilacin 1
Programable
(1 30 min) y
Retardo ventilacin 1
Fijo
Fijo
Programable
(10 30 min)
Retardo
Alarma
[CO]
Nivel de
Alarma
Retardo
Postventilacin
Ventilacin
Retardo
2
Ventilacin 2
Nivel de
Ventilacin 2
Retardo
Postventilacin 1
Ventilacin 1
Retardo
Parada
Ventilacin 1
Ventilacin
2
Alarma
Parada
Alarma
Activada
Ventilacin
2
Nivel de
Ventilacin 1
Ventilacin
1
Ventilacin
1
Tiempo
Bateras:
12V
12V
-6-
CCO110 / CCO115
CASTELLANO
Indicadores luminosos
A
B
C
D
E
F
G
H
Pulsadores de mando
1. Seleccin Display:
2 y 3.
4. ON/OFF Ventilacin
-7-
CCO110 / CCO115
CASTELLANO
Manejo de la central
La central permite la programacin del Nivel de Ventilacin y del Retardo de Ventilacin
mediante las teclas
y SELECCION DISPLAY.
La tecla ON/OFF VENTILACION MANUAL permite activar/desactivar manualmente la
ventilacin en cualquier momento.
Los datos de origen son los siguientes:
Parmetro
Valor
Nivel de Ventilacin:
50 ppm
Retardo Ventilacin:
4 min
Retardo Postventilacin:
Nivel de Alarma:
Retardo Alarma:
4 min
300 ppm
0 min
Retardo
Alarma
[CO]
Margen
Nivel de
Alarma
Retardo
Postventilacin
Ventilacin
Retardo
Parada
Ventilacin
Alarma
Parada
Alarma
Activada
Nivel de
Ventilacin
Ventilacin
Activada
Ventilacin
Activada
Tiempo
Instalacin
La figura muestra el esquema general de conexionado de los diferentes elementos con la
central.
Se pueden conectar un mximo de 10 detectores por zona en la central CCO110 y 15 en
la central CCO115.
2
Se recomienda el uso de cable con una seccin mnima de 1,5mm y la longitud mxima del
mismo por zona no debe exceder los 400m, en una distribucin lineal de detectores.
Estructura por Zona
VENT.
ZONA
- +
ALAR.
- +
Ventilacin
+
Alarma
Detectores CO
-
(max. 15 en CCO115)
+
-8-
CCO110 / CCO115
CASTELLANO
Alarm
OFF
Parmetro
Nivel de Ventilacin 1:
Retardo Ventilacin 1:
Valor
Margen
50 ppm
1 min
Fijo
Programable
(1 9 min)
Fijo
Fijo
Fijo
Fijo
Fijo
Fijo
Retardo Postventilacin 1:
4 min
Nivel de Ventilacin 2:
100 ppm
Retardo Ventilacin 2:
0 min
Retardo Postventilacin:
0 min
Nivel de Alarma:
200 ppm
Retardo Alarma:
0 min
Retardo
Alarma
[CO]
Nivel de
Alarma
Retardo
Postventilacin
Ventilacin
Retardo
2
Ventilacin 2
Nivel de
Ventilacin 2
Retardo
Postventilacin 1
Ventilacin 1
Retardo
Parada
Ventilacin 1
Ventilacin
2
Alarma
Parada
Alarma
Activada
Ventilacin
2
Nivel de
Ventilacin 1
Ventilacin
1
Ventilacin
1
Tiempo
Bateras:
Las bateras se deben conectar a la entrada de bateras del circuito situada en la parte
derecha del circuito fuente de alimentacin, esta salida est identificada.
Conexin de las dos bateras de 12 V en serie:
+
-
12V
12V
-9-
Light Indicators
A
B
C
D
E
External Controls
1 & 2.
3. ESC/MENU:
4. ENTER:
ZONE 1
ZONE 2
ZONE 3
ZONE 4
Disabled
No Sensors
Disabled
Disabled
Z1:
Z2:
Z3:
Z4:
100
250
065
300
Man.Vent.H
Man.Vent.F
V.Lev.:050
Autom.Vent.
CO Concentration (ppm)
N of zone
- 10 -
To accede into menu displays, press MENU pushbutton. There are 5 different menu displays.
or
to move forward different menus:
Using cursors
Parameter
Value
Margins
Ventilation Levels:
50 ppm
Ventilation Delay:
Post-ventilation delay:
Alarm Level:
Alarm Delay:
4 min
4 min
300 ppm
15 min
Alarm
Delay
[CO]
Alarm
level
Post-ventilation
Delay
Postventilacin
Ventilation
Ventilation
OFF
Delay
Alarm
ON
Ventilation
level
Ventilation
ON
Ventilation
ON
Time
Cursors and which appears in some displays of menu, indicates that there are previous
and next displays, respectively, than the current one.
Installation
Below picture shows the general connection outline of different components.
It is possible to connect up to 22 sensors per zone.
2
Wiring: it is recommended to use cable with 1.5 mm of minimum section. Maximum length of
cable per zone must not exceed 400m, in a lineal distribution of sensors.
- 11 -
A / VENT.
MANUAL
M: A / VENTILATION
Activate Manual
zone 1
zone 2
zone 3
zone 4
A / ZONE 1
VENT. MODE
Zone selection +
ENTER
stop +
fixed
1 hour
ENTER
ENTER
ZONE 1
Ventilation
Connected fixed
fixed +
ENTER
A / ZONE 1
MAN.VENT
start
stop
ZONE 1
Ventilation
Manual Stopped
start +
ENTER
stop +
ENTER
ZONE 1
Ventilation
Connected 1 hour
1 hour +
A / ZONE 1
MAN.VENT
ENTER
start
stop
ZONE 1
Ventilation
Manual Stopped
start +
ENTER
B / OPER.
ON_OFF
M : B / OPERATION
On / Off Zones
ENTER
zone 1
zone 2
zone 3
zone 4
zone selection +
B / ZONE 1
OPERATION
on
off
ENTER
ZONE 1 is
operating
on +
ENTER
ZONE 1 is
disabled
off +
ENTER
- 12 -
C / PROG. zone 1
LEVEL
zone 2
DELAY
zone 3
zone 4
M : C / PROGRAMMING
VENT: Level / Del
C / PROG.
ZONE 1
zone selection +
ENTER
level
delay
ENTER
ESC
level +
ENTER
C / PROG.
ZONE 1
level
delay
C / SAVE LEVEL
NO: esc YES: enter
C / PROG. ZONE 1
Level: 050 ppm
Seleccin de nivel +
Zone 1 Saving
Ventilation level ..... OK
ENTER
ENTER
ESC
C / PROG.
ZONE 1
retardo +
ENTER
level
delay
C / SAVE DELAY
NO: esc YES: enter
C / PROG.
ZONE 1
Delay: 4 min
Delay selection +
Zone 1 Saving
ventilation delay ..... OK
ENTER
ENTER
M : D/ PROG. ALARMS
Delay: 10 min
M : D/ PROG. ALARMS
Delay: 10 min
D / SAVE DELAY
NO: esc
YES: enter
Delay selection +
Zone 1 saving
Alarm delay ..... OK
ENTER
ENTER
ESC
M : E/ RESTORE
FACTORY SETTINGS
M : E/ RESTORE
FACTORY SETTINGS
- 13 -
+
BAT
Bateras
J1
Vent1 Z1
Q2
D1
K2
U3
U4
1
U2
1
Q3
D4
K1
Alarma Z1
Vent1 Z2
Alarma Z2
Alarma Z3(*Z1)
Vent1 Z3(*Z1)
Vent1 Z4(*Z2)
Alarma Z4(*Z2)
Q1
D3
Q4
Q5
D2
D5
K5
Vent
Z1
Z2
Z3
Z4
AL
GND CPU
- +
Zona1
K4
- +
Alar
K3
Ve nt
- +
Zona2
R5
- +
Alar
R4
Vent
- +
Zona1
R3
- +
Alar
R1
Ve nt
- +
Zona2
R2
- +
Alar
J4
U1
U5
Vent2 Z1
Vent2 Z2
Vent2 Z3
Vent2 Z4
Parameter
Value
Margins
Alarm
Delay
[CO]
Ventilation 1 Level:
50 ppm
Ventilation 1 Delay:
4 min
Post-ventilation 1 delay:
4 min
200 ppm
Ventilation 2 Level:
Ventilation 2 Delay:
10 min
4 min
Post-ventilation 2 delay:
Alarm Level:
300 ppm
Alarm Delay:
15 min
Alarm
level
Programmable
(20 150 ppm)
Programmable
(1 9 min)
Fixed
Programable
(20 300 ppm) and
Ventilation 1 level
Programable
(1 30 min) and
Ventilation 1 delay
Fixed
Fixed
Programmable
(10 30 min)
Post-ventilation 2
Delay
Ventilation 2
Ventilation 2
OFF
Delay
Ventilation 2
level
Post-ventilation 1
Delay
Ventilation 1 Ventilation 1
OFF
Delay
Ventilation 2
ON
Alarm
OFF
Alarm
ON
Ventilation 2
ON
Ventilation 1
level
Ventilation 1
ON
Ventilation 1
ON
Tiempo
Batteries:
Batteries must be wired to the to the battery output
on the board on the right side of the panel, this
output is labelled.
Two 12V-batteries series-connected:
+
-
12V
12V
- 14 -
CCO110 / CCO115
ENGLISH
Light Indicators
A
B
C
D
E
F
G
H
External Controls
1. Seleccin Display:
2 & 3.
:
4. ON/OFF Ventilation
- 15 -
CCO110 / CCO115
ENGLISH
Value
Ventilation Level:
50 ppm
Ventilation Delay:
4 min
Post-ventilation Delay:
Alarm Level:
Alarm Delay:
4 min
300 ppm
0 min
Alarm
Delay
[CO]
Margin
Programmable (20 150 ppm,
on a 10 ppm increase rate)
Programmable (1 9 min, on a
1 min increase)
Fixed
Fixed
Fixed
Alarm
level
Post-ventilation
Delay
Postventilacin
Ventilation
Ventilation
OFF
Delay
Alarm
OFF
Alarm
ON
Ventilation
level
Ventilation
ON
Ventilation
ON
Time
Installation
Below picture shows the general connection outline of different components.
It is possible to connect up to 10 sensors per zone in CCO110 panel and up to 15 sensors
in CCO115 panel.
2
Wiring: it is recommended to use cable with 1.5 mm of minimum section. Maximum length of
cable per zone must not exceed 400m, in a lineal distribution of sensors.
Estructure per Zone
VENT.
ZONE
- +
ALAR.
- +
Ventilation
+
Alarm
CO Detectors
-
(CCO115 up to 15)
+
- 16 -
CCO110 / CCO115
ENGLISH
Parameter
Value
Margins
Alarm
Delay
[CO]
Ventilation 1 Level:
Ventilation 1 Delay:
50 ppm
1 min
Post-ventilation 1 delay:
4 min
100 ppm
Ventilation 2 Level:
0 min
Ventilation 2 Delay:
0 min
Post-ventilation 2 delay:
Alarm Level:
200 ppm
Alarm Delay:
0 min
Alarm
level
Fixed
Programmable
(1 9 min)
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Post-ventilation 2
Delay
Ventilation 2
Ventilation 2
OFF
Delay
Ventilation 2
level
Post-ventilation 1
Delay
Ventilation 1 Ventilation 1
OFF
Delay
Ventilation 2
ON
Alarm
OFF
Alarm
ON
Ventilation 2
ON
Ventilation 1
level
Ventilation 1
ON
Ventilation 1
ON
Tiempo
Batteries:
Batteries must be wired to the to the battery output on the board on the right side of the panel,
this output is labelled.
Two 12V-batteries series-connected
+
-
12V
12V
- 17 -
Indicadores luminosos
A
B
C
D
E
1 e 2.
3. ESC/MENU:
4. ENTER:
- 18 -
Premindo a tecla menu acede-se aos ecrs de menu. Existem 5 ecrs de menu aos quais se pode aceder
atravs das teclas
ou :
* Ventilao (Activao Manual/Modo Ventilao, ver figura 1).
* Servio (Zonas On/Off, ver figura 2).
* Programao de Ventilao (Nvel e Atraso, ver figura 3).
* Programao de Atraso de Alarmes (figura 4).
* Recuperar Dados de Origem (figura 5).
Parmetro
Valor
Nvel de Ventilao:
Atraso Ventilao:
Atraso Ps-ventilao:
Nivel de Alarme:
Atraso Alarme:
50 ppm
4 min
4 min
300 ppm
15 min
Atraso
Alarme
[CO]
Nivel
Alarme
Margem
Programvel (20 150 ppm)
Programvel (1 9 min)
Fixo
Fixo
Programvel (10 30 min)
Atraso
Ps-ventilaco
Ventilaco
Atraso
OFF
Ventilaco
Alarme
OFF
Alarme
ON
Nivel
Ventilaco
Ventilaco
ON
Ventilaco
ON
Tempo
As flechas e que aparecem em alguns ecrs de menu, indicam a existncia de ecrs anteriores e
posteriores, respectivamente, ao ecr actual.
Instalao
A figura mostra o esquema geral de ligao dos diferentes elementos com a central.
Pode ligar-se um mximo de 22 detectores por zona.
Recomenda-se o uso de cabo com uma seco mnima de 1.5 mm2 e a longitude mxima do mesmo por
zona no deve exceder os 400m, numa distribuio linear de detectores.
Estructura
Estructurapor
porZona
zona
ALAR.
- +
- +
Alarme
Alarma
VENT.
ZONA
- +
Ventilao
Ventilacin
-
- 19 -
- 20 -
- 21 -
+
BAT
Bateras
J1
Vent1 Z1
Q2
D1
K2
U3
U4
1
U2
1
Q3
D4
K1
Alarma Z1
Vent1 Z2
Alarma Z2
Alarma Z3(*Z1)
Vent1 Z3(*Z1)
Vent1 Z4(*Z2)
Alarma Z4(*Z2)
Q1
D3
Q4
Q5
D2
D5
K5
Vent
Z1
Z2
Z3
Z4
AL
GND CPU
- +
Zona1
K4
- +
Alar
K3
Ve nt
- +
Zona2
R5
- +
Alar
R4
Vent
- +
Zona1
R3
- +
Alar
R2
Ve nt
- +
Zona2
R1
- +
Alar
J4
U1
1
U5
1
Vent2 Z1
Vent2 Z2
Vent2 Z3
Vent2 Z4
Valor
Nvel de Ventilao 1:
50 ppm
Atraso Ventilao 1:
4 min
4 min
Atraso Ps-ventilao 1:
Nvel de Ventilao 2:
120 ppm
Atraso Ventilao 2:
Atraso Ps-ventilao 2:
Nivel de Alarme:
Atraso Alarme:
10 min
4 min
200 ppm
0 min
Margem
Programvel
(20 150 ppm)
Programvel
(0 9 min)
Fixo
Programvel
(20 200 ppm) e
Nivel ventilaco 1
Programvel
(0 30 min) e
Atraso ventilaco 1
Fixo
Fixo
Programvel
(0 30 min)
Atraso
Alarme
[CO]
Nivel
Alarme
Atraso
Post-ventilaco 2
Ventilaco 2
Atraso
OFF
Ventilaco 2
Nivel
Ventilaco 2
Atraso
Post-ventilaco 1
Ventilaco1
Atraso
OFF
Ventilaco 1
Ventilaco 2
ON
Alarme
OFF
Alarme
ON
Ventilaco 2
ON
Nivel
Ventilaco 1
Ventilaco 1
ON
Ventilaco1
ON
Tempo
Baterias:
+
-
12V
12V
- 22 -
CCO110 / CCO115
PORTUGUS
A
B
C
D
E
F
G
H
Botes de comando
1. Seleco Display:
2 e 3.
4. ON/OFF Ventilao:
- 23 -
CCO110 / CCO115
PORTUGUS
Manobra da central
A central permite a programao do Nvel de Ventilao e do Atraso de Ventilao a travs das teclas
, e SELECO DISPLAY.
A tecla ON/OFF VENTILAO MANUAL permite activar/desactivar manualmente a ventilao a
qualquer momento.
Os dados de origen so os seguintes:
Atraso
Alarme
[CO]
Parmetro
Valor
Nvel de Ventilao:
Atraso Ventilao:
Atraso Ps-ventilao:
Nivel de Alarme:
Atraso Alarme:
Margem
Nivel
Alarme
50 ppm
4 min
4 min
300 ppm
0 min
Atraso
Ps-ventilaco
Ventilaco
Atraso
OFF
Ventilaco
Alarme
OFF
Alarme
ON
Nivel
Ventilaco
Ventilaco
ON
Ventilaco
ON
Tempo
Instalao
A figura mostra o esquema geral de ligao dos diferentes elementos com a central.
Pode ligar-se um mximo de 10 detectores por zona.
Recomenda-se o uso de cabo com uma seco mnima de 1.5 mm2 e a longitude mxima do mesmo por
zona no debe exceder os 400m, numa distribuio linear de detectores.
Estructura por Zona
ALAR.
VENT.
ZONA
- +
- +
ventilao
Alarme
Detectores CO
-
- 24 -
CCO110 / CCO115
PORTUGUS
Valor
Nvel de Ventilao 1:
Atraso Ventilao 1:
50 ppm
1 min
4 min
Atraso Ps-ventilao 1:
Nvel de Ventilao 2:
100 ppm
Atraso Ventilao 2:
0 min
Atraso Ps-ventilao 2:
0 min
200 ppm
Nivel de Alarme:
0 min
Atraso Alarme:
Margem
Fixo
Programvel
(1 9 min)
Fixo
Fixo
Fixo
Fixo
Fixo
Fixo
Atraso
Alarme
[CO]
Nivel
Alarme
Atraso
Post-ventilaco 2
Ventilaco 2
Atraso
OFF
Ventilaco 2
Nivel
Ventilaco 2
Atraso
Post-ventilaco 1
Ventilaco1
Atraso
OFF
Ventilaco 1
Ventilaco 2
ON
Alarme
OFF
Alarme
ON
Ventilaco 2
ON
Nivel
Ventilaco 1
Ventilaco 1
ON
Ventilaco1
ON
Tempo
Baterias:
As baterias devem ligar-se entrada de baterias do circuito situada na parte direita
do circuito fonte de alimentao, esta sada est identificada.
Ligao das duas baterias de 12 V em srie:
+
-
12V
12V
- 25 -
NOTAS/NOTES/NOTAS
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
.............................................................................................................
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS FIRE PROTECTION MANUFACTURER - FABRICANTE DE PRODUCTOS DE INCNDIO
Ctra. de Molins de Rei a Rub, Km. 8,4 - 08191 RUB (Barcelona) ESPAA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
- 26 -
cofem@cofem.com
comercial@cofem.com
marketing@cofem.com
tecnic@cofem.com
compras@cofem.com
export@cofem.com
Ventas
Sales
Marketing
Marketing
S.A.T.
T.A.S.
Compras
Purchase
Export
Export
Fax pedidos
Orders Fax
Fax general
Fax
ABCDEF
[Escriba una
cita del
18
documento
o