Anda di halaman 1dari 13

TCE CONSULTING ENGINEERS LIMITED

SHEET i OF i

30421007-3CL00011-P0B

33 kV MV CABLE
SIZING REPORT

SAUDI ELECTRICITY COMPANY


EASTERN OPERATING AREA
Dammam, Saudi Arabia
GENERATION EXPANSION OF ARAR POWER PLANT
(CONTRACT NO : 30421007/00)

DESIGN BASIS
FOR
33kV MV CABLE SIZING

DOCUMENT NO : 30421007-3CL-00011-P0B
AUGUST 2004

ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST.MARK'S ROAD
BANGALORE 560001
INDIA

CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O.BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL.00966-1-4633660 : FAX.00966-1-4631150
P0B
30.10.2004

MP

SR

P0A
28.08.2004

MP

SR

REV NO. DATE

PREPARED BY

CHECKED BY

277755671.xls
SECTION :cover sheeet

CLEARED BY

APPROVED BY

SHEET 1 OF 13

REV NO. DATE

277755671.xls
SECTION :cover sheeet

PREPARED BY

CHECKED BY

CLEARED BY

APPROVED BY

SHEET 2 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)

ARAR 33kV CABLE SIZING REPORT

DOCUMENT NO. 30421007-3CL-00011-P0B

CONTENTS

SECTION

DESCRIPTION

1.0

SCOPE

2.0

STANDARDS & REFERENCES

3.0

GENERAL PARAMETERS

4.0

SIZING CRITERIA

5.0

CONCLUSION

6.0

CABLE SIZING REPORT SUMMARY

277755671.xls
SECTION :Index

SHEET 3 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)

277755671.xls
SECTION :Index

SHEET 4 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)
ARAR 33kV CABLE SIZING REPORT
1.0

DOCUMENT NO. 30421007-3CL-00011-P0B

SCOPE
Scope of this report is to calculate the 33kV Cable size (18/30kV Grade) from Existing Switchgear to Station
Transformer T401 or T402.

2.0

STANDARDS & REFERENCES

2.1

IEC 60986-short circuit sizing.

2.2

IEC 60364-5-523 Selection and erection of electrical equipment-Current Carrying capacities in wiring system.

2.3

SES-P-104.03 - Cable Selection -Engineering standards.

2.4

Key One Line Diagram for Arar Plant Drawing No:KA667481, REV P0D

2.5

SAUDI CABLE COMPANY - Medium Voltage Cables Catalogues

3.0

GENERAL PARAMETERS
- Depth of Burried Cables
- Ground Temperature at a depth of 1 meter
- Average Thermal Soil resistivity
- Ambient air Temperature
- Short Circuit current

4.0

=
=
=
=
=

1 meter
35 Deg C
2 Deg C-m/w
50 Deg C
31.5 kA for 1 second

SIZING CRITERIA
The Power Cable size shall be selected on the basis of :
- Short circuit Rating.
- Current Carrying Capacity.
- Permissible Voltage Drop.

4.1

SHORT CIRCUIT SIZING.


According to SES-P-104.03 Engineering standards Cl No:4.9.6 the minimum cable cross section may be
calculated with the formula:
142 x S
I =
t
Where,
I = Maximum Allowable conductor Short Circuit Current in Amps
t = Duration of Short circuits in seconds
S = Cross Sectional Area of Current Carrying conductor in Sqmm
K = Temperature co-efficient of conductor resistance. = 142 for copper XLPE
therefore,
Ix t
S =
142

31500 x 1
142
221.831

Sqmm

Minimum nearest cable size is 240 Sqmm (Refer SAUDI CABLE COMPANY)

277755671.xls
SECTION :Notes and Sizing Cal

SHEET 5 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)
ARAR 33kV CABLE SIZING REPORT

DOCUMENT NO. 30421007-3CL-00011-P0B

However, as per the Cl.No. 3.03-12 of PTS-1022, page 40 of 336 the size for 33kV (18/30kV grade) cable
to Station Transformers is selected as 1C x 630 Sqmm/Phase Cu, XLPE Unarmoured cable.
4.2

CURRENT CARRYING CAPACITY


The total load current to be
carried by 33kV cable to
Station Transformer T401 or
T402

7.5 MVA
=

3 x 33 kV

= 131.21Amps

According to SAUDI CABLE COMPANY Catalogues for Medium Voltage Cable System,the nominal
current carrying capacities are,
Laying Conditions(in duct)
Laid directly in ground or duct ways, Ground
temp.in flat formation 30 DegC and Thermal
resistivity of soil = 1.2K m/W, depth of laying =
0.8m

Current Carrying capacity


in Amps for 1C x 630
Sqmm
670

Laid directly in ground or duct ways, Ground


temp.in trefoil formation 30 DegC and Thermal
resistivity of soil = 1.2K m/W, depth of laying =
0.8m

730

Current Carrying capacity


in Amps for 1C x 630
Sqmm

Laying Conditions (in Air)


Laid in Air (tray),in flat formation Ambient
Temperature 40 Deg C

990

Laid in Air (Tray), in trefoil formation Ambient


Temperature 40 Deg C

975

The following Derating factors have been considered as per SAUDI CABLE COMPANY Catalogues
for the site conditions specified:
Derating factor Kd for Cable Laid in Duct ways :(for both Flat/trefoil formation)
-

Ground Temperature 35 DegC


K1
=
0.95
Thermal Resistivity of soil 2.0DegC m/W K2
=
0.84
Depth of Laying 1m
K3
=
0.98
Group Rating Factor
K4
=
0.80
-according to:
- installation system = spacing between two adjacent (center linre to center line) ducts equl 0.3m
- No of ducts in ground = 3

Derating Factor Kd
Kd

=
=

K1 x K2 x K3 x K4
0.6256

Derating factor Ka for Cable installed in free air:(for both Flat/trefoil formation)
- ambient Air Temperature 50 DegC
K5
- Laying on Cable Tray(in touching form)
K6
according to:
- installation system in three phase circuits

277755671.xls
SECTION :Notes and Sizing Cal

=
=

0.89
0.86

SHEET 6 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)
ARAR 33kV CABLE SIZING REPORT

DOCUMENT NO. 30421007-3CL-00011-P0B

- No of trays = 3
Derating Factor Ka
Ka

=
=

K5 x K6
0.7654

According to the above, the maximum current carrying capacity of the selected 1C x 630Sqmm/phase
cable is as follows
Maximum current carrying capacity of Cable Laid in Duct ways(after considering derating factor)
Laying cable in flat formation, current
=
Laying cable in trefoil formation, current =

670 x Kd =
730 x Kd =

419.17
456.71

Maximum current carrying capacity of Cable Laid in Air(Cable Tray)


(after considering derating factor)
Laying cable in flat formation, current
Laying cable in trefoil formation, current

=
=

990 x Ka =
975 x Ka =

757.75
746.27

As per above calculation, 1C x 630 Sqmm/Phase cable can carry the required load current of 131.21Amps
under all site conditions.
4.3

VOLTAGE DROP SIZING


The Voltage drop check is calculated as follows :
=
V%
3 x(RCOS + XSIN) x I x L x 100 /Un for three phase system
Where,
=
Power Factor
= 0.8
COS
=
= 0.6
SIN
Full load Current in A =
I
=
131.21
L
=
Length in Km
= 0.35
Un
=
Cable Voltage in V = 33000
R
=
Resistance /Km = 0.0423
X
=
Reactance /Km = 0.11
The Voltage Drop
=
0.024 % Volts
which is < 5% Hence, Voltage drop is within the limits.
V%

5.0

CONCLUSION
From 33kV Switchgear to Station Transformer T 401 or T 402
18/30 kV Grade(33kV), XLPE insulated, Copper Conductor of size 1C x 630 Sqmm/Phase,
Unarmoured cable has been selected based on the above calculations.

277755671.xls
SECTION :Notes and Sizing Cal

SHEET 7 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)
ARAR 33kV CABLE SIZING REPORT

277755671.xls
SECTION :Notes and Sizing Cal

DOCUMENT NO. 30421007-3CL-00011-P0B

SHEET 8 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)

DOCUMENT NO. 30421007-3CL-00011-P0B

Grade) from Existing Switchgear to Station

urrent Carrying capacities in wiring system.

V P0D

as per Cl.No.4.01.1,4.01.2 &


4.01.3 page 70 & 71of 336 of
PTS - 1022

e minimum cable cross section may be

t Circuit Current in Amps

rying conductor in Sqmm


or resistance. = 142 for copper XLPE

277755671.xls
SECTION :Notes and Sizing Cal

SHEET 9 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)

DOCUMENT NO. 30421007-3CL-00011-P0B

the size for 33kV (18/30kV grade) cable


XLPE Unarmoured cable.

Voltage Cable System,the nominal

DI CABLE COMPANY Catalogues

t/trefoil formation)

re to center line) ducts equl 0.3m

t/trefoil formation)

as per IEC 60364-5-523


table 52-E5

277755671.xls
SECTION :Notes and Sizing Cal

SHEET 10 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)

DOCUMENT NO. 30421007-3CL-00011-P0B

the selected 1C x 630Sqmm/phase

ys(after considering derating factor)


Amps
Amps

Amps
Amps

the required load current of 131.21Amps

three phase system

nce, Voltage drop is within the limits.

size 1C x 630 Sqmm/Phase,

277755671.xls
SECTION :Notes and Sizing Cal

SHEET 11 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)

DOCUMENT NO. 30421007-3CL-00011-P0B

277755671.xls
SECTION :Notes and Sizing Cal

SHEET 12 OF 13

GENERATION EXPANSION OF ARAR POWER PLANT


(CONTRACT NO : 30421007/00)
6.0 CABLE SIZING REPORT SUMMARY

ARAR 33kV CABLE SIZING REPORT


SL
NO.

FEEDER DESCRIPTION

DOCUMENT NO. 30421007-3CL-00011-P0B

LOAD

VOLTAGE

kVA

VOLTS

FULL
LOAD
CURRENT CARRYING CAPACITY OF CABLE (SINGLE
CABLE SIZE SELECTED
CURRENT
RUN)
IFL
AMPS

SQ.MM
IN DUCT
BANKS

EXISTING 33kV SWITCH GER TO


STATION TRANSFORMER T401 or
T402

7500

33000

277755671.xls
SECTION :Cable Sizing Report Summary

131.22

IN AIR

1 RUN OF 1 RUN OF
1C X 630
1C X
/Phase
630 /Phase

DERATING FACTOR

CURRENT CARRYING CAPACITY OF


CABLE AFTER DERATING FACTOR (SINGLE RUN)

CABLE LAID IN AIR(CABLE CABLE LAID IN DUCT CABLE LAID IN AIRCABLE LAID IN DUCT
CABLE LAID IN AIR(CABLE
BANKS
CABLE TRAYS
TRAY)
BANKS
TRAY)
(IN BOTH
(IN
FLAT/TREFOIL
BOTH FLAT/TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
FORMATION)
FORMATION)
FORMATION FORMATION FORMATION FORMATION
FORMATION FORMATION FORMATION FORMATION
CABLE LAID IN DUCT
BANKS

670.00

730.00

990.00

975.00

0.6256

0.7654

419.15

456.69

757.75

746.27

LENGTH
OF
CABLE

% VOLTAGE
DROP

KM

0.35

0.024

SHEET 13 OF 13