Ref
: DNSTW_FIRE_CAL_002
Fire Protection Systems Hydraulic Analysis
The plant is provided with a dedicated hydrant system served by fire pumps located in the process area.
This is shown on dwg no. K654_402_02_0011 & 0013 and schematically in Figure 3, 4 & 5.
The fire pumps provided have the flow characteristics
The hydrant network provides fire fighting water for the Workers Accommodation sprinkler system.
The hydraulic calculation was done in DNSTW_FIRE_CAL_001
(which is submitted on previous
submission Permit ID 16421)
Hydrant Network
The most remote point of the hydrant network is the Workers Accommodation.
The building requires 3 hydrants.
The flow rate for these are as follows.
Most remote Hydrant
500 gpm 1893 Lpm
2nd Hydrant
250 gpm 946 Lpm
rd
3 Hydrant
250 gpm 946 Lpm
Total flow
1000 gpm 3785 Lpm
The minimum pressure available at the most remote hydrant is 350 kPa (50 psi) as required by the codes
The flow characteristics required from the fire pumps considering the friction losses in the hydrant
network piping are calculated in DNSTW_FIRE_CAL_001 as 3785 L/min @ 551 kPa
Sprinkler Network @ Workers Accommodation
By observation the most remote 139m2 area of operation is located under the atrium ceiling (the highest point).
See drawing no: K654_406_02_4029
The actual area of operation is 145 m2.
The number of sprinklers in the area of operation is 16.
The minimum flow rate from each sprinkler, q is (4.1Lpm/m2 x 145m2)/16 spks = 37.16Lpm )
Using quick response sprinklers with K-factor of 8.06 Lpm/kPa, the minimum pressure required at the most
remote sprinkler = (37.16/8.0)2 = 21.24kPa
Based on this minimum pressure requirement at the most remote sprinkler and their elevation at 9.26m,
the pipe friction losses are calculated in DNSTW_FIRE_CAL_001 up to the connection point on the
hydrant network.
The minimum required at connection to hydrant network for the sprinkler system is 897L/min @ 288kPa.
The flow and pressure available at the connection is 1,893L/min @ 386kPa.
Conclusion
After series of hydraulic calculation, it is observed that high demand and high pressure loss required
at Dried Sludge Storage Building no. 14,
Therefore, the fire pump flow characteristics should be
5568.64 L/min @ 641.07 kPa
05-Feb-11
Hydraulic Calculation
REV
DATE
DESCRIPTION
TT
PREPARED
HK
CHECKED
GEK
APPROVED
CLIENT'S APPROVED
TABLE 3
Hydraulic Calculation
Hydraulic Calculation for Sprinkler System at Dried Sludge Storage Building No. 14
Flow
Pipe
Size
Qty
=
=
=
=
=
=
=
=
=
=
=
#2
q
Q
q
DN32
m2
(NFPA13, Table 16.2.1.3.2 & FIGURE 16.2.1.3.2(g))
m2 >186 m2
(See dwg: K654_406_02_2306 )
m2
nos.
(NFPA13, Table 16.2.1.3.2 & FIGURE 16.2.1.3.2(g))
mm/min
(as per NFPA13, Table 16.2.1.3.4.3)
mm/min
1/2
gpm/(psi)1/2 =
11.52 L/min/(kPa)
(NFPA 13 , clause 14.4.2.4.3)
Friction
loss / m
90 Std Elbow
1L
F
T
L
89.2
91.38 DN32
(kPa/m)
C = 120
10.7758 Pf
Pt
180.58
112.44 DN32
3 C = 120
4 6 in-rack
sprinkler
T
DN40
R/ Tee
1F
1.22
4.22
349.42 DN100
Q
q
Q
350.06 DN100
353.14 DN100
1867.29
Pe
521.65
1514.15
26.3858 Pf
Pt
3 C = 120
9.8071 Pf
Pt
3 C = 120
Pe
q
qir
1L
293.02
642.44
Notes
0.2789 Pf
Pt
3 C = 120
Pe
1.3624 Pf
Pt
3 C = 120
Pe
(kPa)
59.96 Q = 9.35 x 15.9 = 89.2
p = ( 89.2 / 11.52 )
= 59.96
2.96
62.92 q =11.52 x 62.92 = 91.38
32.33
95.25 q =11.52 x 95.25 = 112.44
Pe
90 Std Elbow
293.02
Pt
Pe
1.01
1.01
2.9227 Pf
Pt
3 C = 120
Pe
F
2
Pressure
Summary
(m)
F
#3
186
186.9
9.35
20
15.9
9.54
8
Q/ p
(Q/K)2
K p
Eqv. Pipe
Length
(L/min)
1 #1
IV
2.0078 Pf
79.16
174.41 Kc = 293.02 /
15 Kc = 23
41.39
174.41
34.3
235.73 q =23 x 235.73 = 353.14
6.03
Page 4 of 15
6 6 in-rack
sprinkler
q
qir
Q
q
Q
8 2 in-rack
sprinkler
9 hose
533.32
Pe
2758.23
366.68 DN150
demand
183.03
F
T
1892.5 DN150
5568.64
T
DN200
5568.64
DN200
90 Std Elbow
4L
Gate Valve
1F
1T
90 Std Elbow
1L
F
5568.64
T
DN200
L
F
-ground
pipe
13 Under
5568.64
T
DN250
-ground
pipe
Q
15 Pump
1L
1F
T
DN250
90 Std Elbow
5568.64
q
Q
90 Std Elbow
5568.64
14
0.7013 Pf
Pt
DN200
5568.64
3L
0.9471 Pf
Pt
68 C = 120
Gate Valve
1T
5568.64 L/min
1471.24 gpm
2.85
(As per NFPA13, Table 16.2.1.3.5 )
51.54
Pe
70
113.5
0.5328 Pf
Pt
528.49
Pe
15
18.6
0.4006 Pf
Pt
155.5 C = 140
Pe
550.95
12.5 C = 140
6.1
0.4006 Pf
Pt
234.5 C = 140
Pe
22.86
257.4
0.1210 Pf
155.5
17 C = 120
Pt
1892.5 L/min
60.5
7.46
62.3
613.25
-15
31.13
629.38
-25
0.1609 Pf
Pt
1.5 C = 120
Pe
27.14
28.64
0.5328 Pf
6.42
500 gpm =
397.99
Pe
39.86
1F
= 368.2
62 C = 120
T
1L
2.11
256.27 q =23 x 256.27
2.0421 Pf
Pt
68
22.86
12.4
254.16 q =23 x 254.16 = 366.68
Pe
F
R/ Tee
Pe
-ground
pipe
3 C = 120
3676.14
12 Under
Q
q
368.2 DN150
11 Under
q
qir
stream
10
4.1319 Pf
Pt
3 C = 120
Pe
3124.91
3 C = 120
Pt
357.62 DN100
610.8
15
15.27
641.07
641.07 kPa
64.11 mH2O
92.96 psi
Page 5 of 15
K=
p=
Q=
Nozzle
Ident. &
Location
Flow
Pipe
Size
Qty
#b
90 Std Elbow
1.01
1.01
82.04
83.04 DN32
L
F
#c
q
Q
90 Std Elbow
256.3
1.22
1.52
521.65
T
L
F
521.65
521.65
Pe
7.6553 Pf
Pt
1.6 C = 120
Pe
6.2650 Pf
Pt
8.8 C = 120
Pe
1.6
6.2650 Pf
Pt
1.5 C = 120
Pe
1.5
T
DN65
20.5966 Pf
Pt
0.3 C = 120
T
L
2.4
F
265.35 DN50
DN50
2.5036 Pf
Pt
2.4 C = 120
Pe
2.4
Pt
T
1L
F
f
Notes
(kPa)
103.5 Q =8.064x 103.5 = 82.04
Pe
256.3
DN40
Pressure
Summary
9.1273 Pf
Pt
2.4 C = 120
Pe
91.22 DN32
q
Q
165.08
(kPa/m)
C = 120
1L
Friction
loss / m
(m)
DN32
Eqv. Pipe
Length
(L/min)
#a
14
15
103.5
5.6
8.8
1.9760 Pf
Pt
2.53
106.03 q =8.064 x 106.03 = 83.04
21.91
127.94 q =8.064 x 127.94 = 91.22
49.44
177.38 Kir = 256.3 /
Kir = 19.3
11.64
177.38
Page 6 of 15
ISOMETRIC SKETCH_ FORM DRIED SLUDGE STORAGE BLDG (NO. 14)TO FIRE PUMPS
FIGURE 3
Page 7 of 15
TABLE 4
Hydraulic Calculation
Hydraulic Calculation for Sprinkler System at Thermal Drying Plant
Classification of Occupancies
Area of Sprinkler Operation
Actual Area of Sprinkler Operation
Coverage per sprinkler, a
No. of sprinkler calculated
Design density, D
Sprinkler discharge characteristics, K
=
=
=
=
=
=
=
K=
p=
Q=
Nozzle
Ident. &
Location
Flow
Pipe
Size
Qty
#b
q
Q
q
DN32
#c
q
Q
#d
q
Q
#e
90 Std Elbow
F
T
L
74.68
75.61 DN32
150.29
92.13 DN40
104.1 DN40
F
T
T
DN50
R/ Tee
6.5314 Pf
Pt
3 C = 120
Pe
431.45
Pe
1.01
1.01
2.1040 Pf
Pt
3 C = 120
Pe
F
L
327.35
1L
12.0379 Pf
Pt
3 C = 120
Pe
431.45
20.0632 Pf
Pt
4.5 C = 120
Pe
F
Q
Pt
235.22
Pressure
Summary
7.6724 Pf
Pt
3 C = 120
Pe
84.93 DN40
(kPa/m)
C = 120
1L
F
Q
Friction
loss / m
Notes
(m)
F
Q
Eqv. Pipe
Length
(L/min)
1 #a
4.5
4.4095 Pf
(kPa)
85.77 Q = 9.22 x 8.1 = 74.68
2
p = ( 74.68 / 8.064 )
= 85.77
2.13
87.9 q =8.064 x 87.9 = 75.61
23.02
110.92 q =8.064 x 110.92 = 84.93
19.6
130.52 q =8.064 x 130.52 = 92.13
36.12
166.64 q =8.064 x 166.64 = 104.1
60.19
226.83 K = 431.45 /
226.83
10 K = 29
19.85
Page 8 of 15
464.62 DN100
3 C = 120
896.07
466.02 DN100
3 C = 120
1362.09
q
q1
Q
DN100
Pe
3
1.1201 Pf
Pt
3 C = 120
Pe
130.5
1492.59
DN100
L
F
Q
q
Q
8 Under
1492.59
946.25 DN150
2438.84
DN150
90 Std Elbow
9L
Gate Valve
1F
1T
90 Std Elbow
2L
-ground
pipe
9 Under
2438.84
DN200
R/ Tee
10 Under
2438.84
-ground
pipe
11
Q
12 Pump
1L
3F
90 Std Elbow
3L
2438.84
q
Q
4L
DN200
2438.84
Pt
1.55
258.23 q =29 x 258.23 = 466.02
3.37
261.6
q1 = 8.064 x 261.6 = 130.5
3.99
265.59
15.93
281.52 +250gpm for inside hose stream demand
200 (As per NFPA13, Table 11.2.3.1.2 )
87.94
Pe
15
5.09
0.0870 Pf
Pt
429.5 C = 140
Pe
76.2
505.7
0.0263 Pf
90
17 C = 120
7.83
597.38
-15
13.28
595.66
22.86
Pe
-25
0.0349 Pf
Pt
1.5 C = 120
Pe
27.14
28.64
0.1157 Pf
1.4
1L
1F
Gate Valve
1T
946.25 L/min
589.55
Pt
39.86
250 gpm =
569.46
T
R/ Tee
2438.84 L/min
644.35 gpm
0.3333 Pf
Pt
90 C = 140
Pe
9.76
T
DN250
5.5 C = 140
15.26
90 Std Elbow
2438.84
1.3267 Pf
Pt
134 C = 120
Pe
64.35
198.4
0.4433 Pf
12
T
DN250
1.3267 Pf
Pt
12 C = 120
Pe
3
T
F
-ground
pipe
0.5162 Pf
Pt
Q
5
Pt
Pe
572.06
15
3.32
590.38
590.38 kPa
59.04 mH2O
85.61 psi
Page 9 of 15
FIGURE 4
Page 10 of 15
TABLE 5
Hydraulic Calculation
Hydraulic Calculation for Sprinkler System at Thermal Drying Plant (Silo Area)
Classification of Occupancies
Area of Sprinkler Operation
Actual Area of Sprinkler Operation
Coverage per sprinkler, a
No. of sprinkler calculated
Design density, D
Sprinkler discharge characteristics, K
=
=
=
=
=
=
=
K=
p=
Q=
Nozzle
Ident. &
Location
Flow
Pipe
Size
Qty
#b
q
Q
q
DN32
#c
q
Q
#d
90 Std Elbow
F
T
L
71.02
71.91 DN32
142.93
98.29 DN40
322.06
R/ Tee
16.0230 Pf
Pt
3 C = 120
Pe
11.6805 Pf
Pt
0.75 C = 120
Pe
0.75
T
DN40
Pe
1.01
1.01
1.9172 Pf
Pt
3 C = 120
Pe
F
L
322.06
Pt
223.77
Pressure
Summary
6.9918 Pf
Pt
3 C = 120
Pe
80.84 DN32
(kPa/m)
C = 120
1L
F
Q
Friction
loss / m
Notes
(m)
F
Q
Eqv. Pipe
Length
(L/min)
1 #a
1L
11.6805 Pf
(kPa)
77.57 Q = 8.77 x 8.1 = 71.02
2
p = ( 71.02 / 8.064 )
= 77.57
1.94
79.51 q =8.064 x 79.51 = 71.91
20.98
100.49 q =8.064 x 100.49 = 80.84
48.07
148.56 q =8.064 x 148.56 = 98.29
35.05
183.61 K = 322.06 /
183.61
10 K = 24
8.77
Page 11 of 15
341.43 DN100
3 C = 120
663.49
342.18 DN100
3 C = 120
1005.67
343.79 DN100
Pe
3
0.6390 Pf
Pt
3 C = 120
Pe
L
F
1349.46
T
DN100
L
F
Q
q
Q
8 Under
1349.46
946.25 DN150
2295.71
DN150
90 Std Elbow
8L
Gate Valve
1F
1T
90 Std Elbow
2L
-ground
pipe
9 Under
2295.71
DN200
R/ Tee
10 Under
2295.71
-ground
pipe
11
Q
12 Pump
1L
3F
90 Std Elbow
3L
2295.71
q
Q
4L
DN200
2295.71
Pt
0.89
203.27 q =24 x 203.27 = 342.18
1.92
205.19 q =24 x 205.19 = 343.79
3.31
208.5
18.72
227.22 +250gpm for inside hose stream demand
275 (As per NFPA13, Table 11.2.3.1.2 )
44.39
Pe
15
4.55
0.0778 Pf
Pt
429.5 C = 140
Pe
76.2
505.7
0.0235 Pf
90
17 C = 120
Pt
7
573.16
-15
11.88
570.04
22.86
Pe
-25
0.0312 Pf
Pt
1.5 C = 120
Pe
27.14
28.64
0.1034 Pf
1.25
1L
1F
Gate Valve
1T
946.25 L/min
566.16
39.86
250 gpm =
546.61
T
R/ Tee
2295.71 L/min
606.53 gpm
0.2980 Pf
Pt
90 C = 140
Pe
9.76
T
DN250
5.5 C = 140
15.26
90 Std Elbow
2295.71
1.1010 Pf
Pt
52.5 C = 120
Pe
59.47
112
0.3964 Pf
17
T
DN250
1.1010 Pf
Pt
17 C = 120
Pe
3
T
F
-ground
pipe
0.2961 Pf
Pt
Q
5
Pt
Pe
546.29
15
2.97
564.26
564.26 kPa
56.43 mH2O
81.82 psi
Page 12 of 15
ISOMETRIC SKETCH_ FORM THERMAL DRYING PLANT (Silo Area) TO FIRE PUMPS
FIGURE 5
Page 13 of 15
Hydraulic Calculation
For Non-Process Buildings
Fire Pump Curve
As per NFPA 20, the pump's shutoff head will range from a minimum of 101 percent to a maximum of 140 percent of
rated head. At 150 percent of rated capacity, head will range from a minimum of 65 percent to maximum of just below
rated head.
Overall requirement
100% of rated capacity =
100% of rated head =
150% of rated capacity =
65% of rated head =
140% of rated head =
1471.2
92.96
2206.86
60.4
130.1
gpm
psi
gpm
psi
psi
Remarks:
The fire sprinkler pumps shall be UL listed and FM aprroved.
Hydraulic Calculation
for Non-Process Buildings
Fire Water Tank Sizing
Required flow rate =
Required pressure =
Type of Fire Fighting Pump
Type of Driven
=
=
1471.24
79.96
gpm
psi
Horizontal Centrifugal
Electric Motor Driven & Diesel Engine Driven