Anda di halaman 1dari 9

ETL 41 TEST REPORT

5HYN600485-TA

CLIENT

____________________________________

ABB ORDER NO.

____________________________________

STATION

____________________________________

DIRECTION

____________________________________

FREQUENCY

____________________________________

CABINET NO.

____________________________________

EQPT. SR. NO.

____________________________________

TESTED BY : ________________

Edition: 05
July 2010

DATE : ______________

1 of 9

ETL 41 TEST REPORT

5HYN600485-TA

SAFETY INSTRUCTIONS
Electrical Safety
WARNING

Energy hazard

The 48 V d.c. supply or any voltage converter can deliver high currents.
The DC supply can deliver high currents. Remove all rings, watches and other metal
jewellery before removing cover. Do not bridge connectors with tools, etc.

CAUTION

Static sensitive devices

The cards contain static sensitive devices. These devices are sensitive to static
electricity and must be protected by special handling and packaging.

2 of 9

ETL 41 TEST REPORT

5HYN600485-TA

Designations and abbreviations used:


B5LA
P4LA(P15-P18)

module type
test point designations on the frontplate,
test point 15 with respect to 18

[ ]
[X]
[ -]

space for entering the test result


test O.K.
test not applicable

Test
No.

ETL test procedure

Test point

Permissible
value

Units

Test
result

GENERAL

1.

POWER SUPPLY P7LA

1.1
1.2
1.3

Battery 48 V DC
Battery 60 V DC
Main supply 230 V AC

B5LA(BAT-0V)
B5LB(BAT-0V)
B5LC(UR-0V)

-46 to -50
-58 to -62
-49 to -55

V DC
V DC
V DC

[ ]
[ ]
[ ]

2.

POWER SUPPLY P7LB

2.1
2.2
2.3

Stabilised voltage +12.8 V


Stabilised voltage -12.8 V
Stabilised voltage +5.1 V

P4LA(P15-P18)
P4LA(P16-P18)
P4LA(P14-P18)

12.5 to 13.1
-12.5 to -13.1
4.9 to 5.4

V DC
V DC
V DC

[ ]
[ ]
[ ]

2.4
2.5
2.6

Ripple on +12.8 V
Ripple on -12.8 V
Ripple on +5.1 V

P4LA(P15-P18)
P4LA(P16-P18)
P4LA(P14-P18)

< 15
< 15
< 50

mV rms
mV rms
mV rms

[ ]
[ ]
[ ]

3.

FREQUENCY GENERATION, CHANNEL 1

3.1
3.2
3.3

System clock 7.68 MHz


Sync. Volt. Rx sync (SLAVE only)
Tx carrier frequency Txfc
Tx VCO voltage
Rx carrier frequency Rxfc
Rx VCO voltage
Pilot frequency channel
Space frequency
Mark: Connect M-P28 to O4LB/C 1)

3.4
3.5

NOTE:

1)

P4LG(P22-P18)
P4LG(P16-P18)
P4LG(P2-P18)
P4LG(P4-P18)
P4LG(P30-P18)
P4LG(P32-P18)
P4LA(P23-P18)
P4LA(P23-P18)

25
Hz
6.0 2
V DC
Txfc+624kHz 4 Hz
1.6 to 2.0
V DC
Rxfc+624KHz 4 Hz
1.6 to 2.0
V DC
3780
Hz
3750 2
Hz
3810 2
Hz

[
[
[
[
[
[

]
]
]
]
]
]

[ ]
[ ]

Only if O4LB or O4LC in use.

3 of 9

ETL 41 TEST REPORT


Test
No.

ETL test procedure

CHANNEL TESTING

4.

TRANSMITTER

4.1

AF aux. signal level:


Pilot
Press test tone button
1000 Hz test tone

4.2

4.3

5HYN600485-TA

Test point

Permissible
value

Units

Test
result

P4LA(P23-P18)
P4LA
P4LA(P25-P18)

-16.0 0.5

dBu

[ ]

-10.0 0.5

dBu

[ ]

P4LF(switch S1)
P4LB(P15-P18)

_________
-10.0 0.5

dBu

[ ]
[ ]

Adjustment of the RF test tone


level with potentiometer on P4LF
T(RF)

P4LF(P13)
P3LA/B(P11-P13)

____ 1.0

dBu

[ ]

Tx RF level check:
Pilot = T(RF)-6 dB

P3LA/B(P11-P13)

____ 1.0

dBu

[ ]

Test tone POWER T=________dBm


Voltage level at COAX::
POWER T -9 dB across 75
POWER T -6.8 dB across 125
POWER T -6.0 dB across 150

COAX
COAX
COAX

____ 1.0

dBu

[ ]

Output power check:


Inject AF test tone of 800 Hz
at X305 1a/1b
with level = 20 log S dB = ________
AF level = 20 log S - 10 dB
RF level = T(RF) + 20 log S

P4LB(P15-P18)
P3LA/B(P11-P13)

____ 0.5
____ 1.0

dBu
dBu

[ ]
[ ]

P3LA/B(P11-P13)

____ 1.0

dBu

[ ]

P3LA/B(P3)
P4LA(P7)

Tx alarm LED ON
Tx alarm LED ON

[ ]
[ ]

P3LA/B(P3)
P4LA(P7)

Tx alarm LED OFF


Tx alarm LED OFF

[ ]
[ ]

Tx RF level setting:
Setting for S
Inject AF test tone of 800 Hz, 0 dBm0
at O4LA (V9LA-X305 1a/1b)

Note:
For values of S and T(RF) refer to
pt. 4.2
4.4

4.5

Tx alarm threshold:
Set Tx alarm using potmeter R116
on P1LA at the rear side for
a pilot drop of -12 dBm0
Tx alarm indication:
Pilot level < threshold (4.4)
Pilot level > threshold (4.4)

4 of 9

ETL 41 TEST REPORT


Test
No.

ETL test procedure

5.

RECEIVER

5.1

Standard AGC setting using


potmeter on P3LA/B

5.2

AF Rx level setting:
Adjust AF testtone level with
Potmeter on P4LB(P34)
Opposite station feed 800Hz or
press CALL button.

5.3

5.4

5.5

5HYN600485-TA

Test point

Permissible
value

Units

Test
result

P4LA(AGC)

26 1

dB

[ ]

P4LB(P23-P18)

-10.0 0.5

dBu

[ ]

AGC test
Opposite station feed 800Hz or
press CALL button.
Set 26 - 20 dB
26 +10 dB

P4LB(P23-P18)
P4LB(P23-P18)

-10.0 0.5
-10.0 0.5

dBu
dBu

[ ]
[ ]

Remote loop check:


Inject 800 Hz
Check at 800 Hz

P4LB(P4-P5)
P4LB(P23-P18)

0.0
-10 0.5

dBm
dBu

[ ]

Rx alarm indication:
Interrupt RF line,
after delay

P4LA(P8)

Rx alarm LED ON

[ ]

Reconnect RF line,
after delay

P4LA(P8)

Rx alarm LED OFF

[ ]

5 of 9

ETL 41 TEST REPORT

5HYN600485-TA

Test
No.

ETL test procedure

Test point

Permissible
value

6.

TELEPHONY
2/4 WIRE PAX INTERFACE

O4LC

Slot

Units

Test
result

N______

Refer Annexure for Jumper Settings for O4LC with option USIC
6.1

Tx level check:
4W In, join
input_______dBm, 800 Hz
at X306 2a/2b

O4LC(SC-P28)
O4LC(P13-P18)

-10.0 0.5

dBu

[ ]

O4LC(HY-P28)
O4LC(P13-P18)

-10.0 0.5

dBu

[ ]

Rx level check:
Opposite station: feed signal
as for 6.1, connect
Check 4W Out across 600

O4LC(SC-P28)
O4LC(4W-OUT)

____ 0.5

dBm

[ ]

Opposite station: feed signal


as for 6.1, connect
Check 2W Out across 600

O4LC(HY-P28)
O4LC(2W-OUT)

____ 0.5

dBm

[ ]

2W In, join
input_______dBm, 800 Hz
at X306 1a/1b
6.2

6.3

Dialing channel:

Figure - 1
M-wire input open at
opposite station, check: E-wire
as per figure - 1
Close M-wire input in the
opposite station i.e. join
Measure E-wire as per figure - 1

O4LC(X306 10a/10b)

23

V DC

[ ]

O4LC(M-P28)
O4LC(X306 10a/10b)

2.5

V DC

[ ]

6 of 9

ETL 41 TEST REPORT


Test
No.

ETL test procedure

6.4

Service telephone check:


Press CALL button at opposite
station
Rx: after 3 sec.
At depressed CALL button:
1 kHz tone at
Distortion factor:
Feed 400 Hz at -6 dBm0 (-9.5dBm)
in the opposite station. Join
Rx output across 600

6.5

6.6

Frequency response:
Feed signal at -6 dBm0 (-9.5dBm) in
the remote station and measure
frequency response across 600
frequency range

Speech 2.0 kHz


0.2 kHz
0.2 to 0.3 kHz
0.3 to 0.4 kHz
0.4 to 0.6 kHz
0.6 to 1.2 kHz
1.2 to 1.6 kHz
1.6 to 2.0 kHz
2.0 to 2.2 kHz
2.2 kHz

Speech 2.2 kHz


0.2 kHz
0.2 to 0.3 kHz
0.3 to 0.4 kHz
0.4 to 0.6 kHz
0.6 to 1.4 kHz
1.4 to 1.8 kHz
1.8 to 2.2 kHz
2.2 to 2.4 kHz
2.4 kHz

5HYN600485-TA

Test point

Permissible
value

O4LC

Buzzer sounds

[ ]

telephone receiver

audible

[ ]

O4LC(SC-P28)
O4LC(4W-OUT)

k1

O4LC(4W-OUT)

-9.5 0.5

dBm

Speech 2.4 kHz


0.2 kHz
0.2 to 0.3 kHz
0.3 to 0.4 kHz
0.4 to 0.6 kHz
0.6 to 1.6 kHz
1.6 to 2.0 kHz
2.0 to 2.4 kHz
2.4 to 2.6 kHz
2.6 kHz

Speech 3.4 kHz


0.2 kHz
0.2 to 0.3 kHz
0.3 to 0.4 kHz
0.4 to 0.6 kHz
0.6 to 2.4 kHz
2.4 to 3.0 kHz
3.0 to 3.4 kHz
3.4 to 3.6 kHz
3.6 kHz

-0.0 / +
-0.9 / +
-0.9 / +3.0
-0.9 / +1.7
-0.9 / +0.9
-0.9 / +1.7
-0.9 / +3.0
-0.0 / +
-0.0 / +

Units

dB
dB
dB
dB
dB
dB
dB
dB
dB

Test
result

[ ]

[ ]

AnnexureNormal O4LC Operation 1. Remove U-Lugs from the front plate of O4LC module.
2. Put jumpers- J, JO, CX, TA
O4LC with USIC Board (Optional)
1. Put the U-Lugs back on the front plate of the O4LC module.
2. Put the jumpers at JU, TB, CF and remove the jumper J.
3. Put the jumpers as mentioned in the following table-

Voice Service
FXO End
(EPAX End)

Jumper
USIC
O4LC
PA, PB, PC, PD, PE,
JU,TB,CF
PF, PG, PH, PJ
Remove jumper J

FXS End
(Remote Subscriber End)

SA, SB, SC, SD, SE,


SF, SG, SH, HI, SJ

JU,TB,CF
Remove jumper J

Hotline

SA, SB, SC, SD, SE,


SF, SG, SH, SI, SJ

JU,TB,CF
Remove jumper J

7 of 9

ETL 41 TEST REPORT


Test
No.

ETL test procedure

Test point

7.

TELEOPERATION

O4LA

7.1

Tx level check:
feed at X305 1a/1b
input 1,______dBm, 800 Hz
feed at X305 2a/2b
input 2,______dBm, 800 Hz
feed at X305 3a/3b
input 3,______dBm, 800 Hz
Rx level checks:
Opposite station:
feed in as under 7.1
output 1 800 Hz, across 600
output 2 800 Hz, across 600
output 3 800 Hz, across 600

7.2

7.3

7.4

5HYN600485-TA
Permissible
value

Units

Test
result

Location

________

O4LA(P14-P18)

-10.0 0.5

dBu

[ ]

O4LA(P15-P18)

-10.0 0.5

dBu

[ ]

O4LA(P16-P18)

-10.0 0.5

dBu

[ ]

O4LA(OUTPUT 1)
O4LA(OUTPUT 2)
O4LA(OUTPUT 3)

____ 0.5
____ 0.5
____ 0.5

dBm
dBm
dBm

[ ]
[ ]
[ ]

-6.0 0.5
-0.0 / +
-0.9 / +
-0.9 / +1.7
-0.9 / +0.9

dBm
dB
dB
dB
dB

[ ]

-6.0 0.5

dBm

-0.9 / +1.7
-0.9 / +0.9

dB
dB

Wideband frequency response :


Opposite station, Tx input O4LA or
P4LB, feed signal -6 dBm0, 100-3600 Hz
Frequency response across 600
O4LA(OUTPUT____)
200 Hz
200 Hz to 300 Hz
300 Hz to 400 Hz
400 Hz to 3600 Hz
Frequency response, transit via E1LA:
opposite station, Tx input O4LA or
P4LB feed signal -6 dBm0
100-3600 Hz
Frequency response across 600
O4LA(OUTPUT ____)
Passband of E1LA only
from ________ to ________ Hz
300 Hz to 600 Hz
600 Hz to 3600 Hz

[ ]

8 of 9

ETL 41 TEST REPORT


Test
No.

ETL test procedure

Test point

8.

AF AUX INPUT/OUTPUT

P4LB

5HYN600485-TA
Permissible
value

Units

Test
result

-10 0.5

dBu

[ ]

_________

dB

If Aux. input/output used


8.1

8.2

8.3

8.4

AF AUX I/P:
Feed in, 0 dBm0, 800 Hz
via P4LB X308 A6/C6
Check

P4LB(P15-P18)

AF AUX input boost level:


Boost ratio BR
Feed in as under 8.1
Provide boosting with
Check boosted level

P4LB(X308 8a/8b)
P4LB(P15-P18)

closed
BR-10 0.5

dBu

[ ]

AF AUX output:
Feed in at opposite station as
under 8.1, check level across 600

P4LB(X308 3a/3b)

____ 0.5

dBm

[ ]

Frequency response transit via 3.6 kHz low-pass filter:


(if not checked with O4LA)
Feed in at opposite station as
under 8.1, -6 dBm0, 100-3600Hz
Frequency response across 600
P4LB(X308 3a/3b)
200 Hz
200 Hz to 300 Hz
300 Hz to 400 Hz
400 Hz to 3400 Hz
3400 Hz to 3600 Hz
3600 Hz

_________
-0.0 / +
-0.9 / +
-0.9 / +1.7
-0.9 / +0.9
-0.9 / +1.7
-0.0 / +

dB
dB
dB
dB
dB
dB

[ ]

9 of 9

Anda mungkin juga menyukai