AKF
AFV-8U
AFV-8G
AFH-1
SUPPLY CEILINGS
DSS
DPS
LN-2
FR
Filter class:
Filter class EN 779
G3
G4
F5
F6
F7
F8
F9
Efficiency (%)
80-90
90
Efficiency (%)
H 10
H 11
H 12
H 13
H 14
U 15
U 16
U 17
85
95
99,5
99,95
99,995
99,9995
99,99995
99,999995
> 0,3 m
> 0,12 m
900
Detail A
Installation:
Basic frames are being fitted into the KPF
units via the side opening. The procedure requires
1000 mm of free space (fig. 2).
KPF housing is fitted into the duct network
via the self-locking flange.
A
3
Fig. 2
1. Angle
2. Gasket
3. Gasket
4. Filter
5. Connecting part
6. Filter frame
Component parts:
1. Housing
2. Cover plate
3. Frame
4. Bag filter
1000
Table 1
1A
1B
1C
1D
1E
2A
2B
2C
2D
2E
3A
3B
3C
3D
3E
412
Flow
(m3/h)
Weight
(kg)
H
(mm)
B
(mm)
3400
5100
6800
8500
10200
5100
7650
10200
12750
15300
6800
10200
13600
17000
20400
40
52
63
75
82
53
68
82
91
110
63
81
93
110
123
618
618
618
618
618
925
925
925
925
925
1232
1232
1232
1232
1232
618
925
1232
1539
1846
618
925
1232
1539
1846
618
925
1232
1539
1846
1/ 595
1
1
1
2
2
3
1
1
2
2
3
2
2
4
4
6
2
3
4
5
6
Table 2
Pre-filter dimensions
Lenght (mm)
Effective outlet area (m2)
No. of pockets
Weight
Average rate of synthetic dust filtering (%)
Average rate of atmospheric dust filtering (%)
Dust quantity (g)
Flow (m3/h)
Initial pressure drop (Pa)
Final pressure drop (Pa)
Outlet side designated according
to DIN 24 185 2nd part
Inflammability according to DIN 53438
Temperature resistance (K)
Technical data:
1/ 595
1
x 595
1/
2
290 x 595
1/
4
290 x 290
630
5,40
6
2,90
98
60
960
3400
68
350
630
2,70
3
1,45
98
60
480
1700
68
350
630
1,35
3
0,72
98
60
240
850
68
350
F5 to F7
F5 to F7
F5 to F7
F1
343
F1
343
F1
343
Filter lifetime:
Manometer:
Mark II 0-500 Pa
Magnehelic 0-500 Pa
Ordering example:
It is recommended that a separate manometer is used for each filter unit. Upon customer's request we:
- fix it on the filter housing
- prepare a bracket for fixing
- send a manometer without the bracket
Designation:
Size:
Air flow volume:
Pcs:
KPF - 2B
B x H = 1232 x 618
7650 m3/h
2
413
AKF-I
Application:
Duct Hepa filter unit AKF is being used in the
network of inlet and outlet ducts used to supply or
extract air from the rooms with highest demands
regarding air cleanness. Hepa filters of H10 to H14
class prevent the intake or exhaust of particles
larger than 0,3 m . They can be installed as
follows:
air supply and extract in laboratories
air supply and extract in operation rooms,
infection- and sterile departments
air supply in electronics, precision mechanics,
chemistry, pharmaceutics and food industry
air supply in film and audio tape industry
air supply and extract in nuclear technology etc.
Description:
AKF unit is made of filter housing, connection
flanges (fig. 3) and Hepa filter. Filter is fitted with
washer of a rectangular cross-section. Filter
housing is made oh sheet metal air-tight welded
according to DIN 1946 and coloured in RAL 9010.
Two pressure gauge attachments for measuring of
a pressure drop are incorporated into the housing.
AKF-II
AKF-I
775
695
a1/b1
Components:
1
5
414
H1
4
2
1. Housing
2. Hepa filter (with semicircular gasket)
3. Filter assembly levers
4. Cover
5. Cover fixing bolt
6. DOP test connection
7. p connection
695
Components:
a1/b1
1
5
9
132
158
4
H1
9
7
1. Housing
2. Pre-filter
3. Hepa filter
4. Filter assembly levers
5. Pre-filter cover
6. Hepa filter cover
7. Screws for cover fixing
8. DOP test connection
9. p connection
AKF-II
Fig. 2
775
L
65
a1
700
Components:
b1
132
p +
t
H1
158
A
C
p t
p +
t
DOP
p t
b1
DOP
750
450
520
623
693
Connection flanges
Fig. 3: Connection flange dimensions
82,5
82,5
B1
a1
A2
b1+60
A1
b1
10
B2
30
a1+60
415
Table 1
Designation
No. of filters
Flow (m3/h)
AKF-I
1
Lenght
Flange
Hepa filter size
610x610x150
Hepa filter
610x610x292
1200
2400
/
530
545
328
/
373
198
470
/
515
340
618
/
663
198
760
/
805
340
610x610x150
610x610x292
L
a1
b1
A
B
C
H1
A
B
C
H1
A
B
C
H1
A
B
C
H1
Pre-filter
610x610x60
Hepa filter
610x610x150
Pre-filter
610x610x60
Hepa filter
610x610x292
AKF-II/1, 2, 3, 4
2
3
1200
2400
733
2400
4800
1524
200
328
833
300
328
1033
2D
3600
7200
2315
4800
9600
3106
2400
4800
733
400
500
200
1233
1433
833
615
4800
9600
1524
7200
14400
2315
1260
300
400
1033
373
198
470
975
1175
1375
1575
975
1175
515
340
618
1123
1323
1523
1465
500
1233
1433
1375
1575
1523
1723
1665
1865
515
340
618
1723
1123
1323
663
198
760
1265
9600
19200
3106
373
198
470
663
198
760
1665
1865
1265
1465
805
340
805
340
Table 2
Housing Hepa
size
filter
H1
H2
Initial
pressure (Pa)
Flow
(m3/h)
Air velocity
(m/s)
Max. temp.
(C)
Humidity
(%)
250
250
1200
2400
1.1
2.4
70
70
100
100
Pre-filter
H3
610 x 610 x 50
160
400
2
(610 x 610 x 292)
300
250
200
100
500
1000
1500
2000
2500
3000
3500
Q (m3/h)
416
Fig. 4
Ordering key
AKF-II/1/H1/A1/bag in-out
safe filter replacement
A1 Connection flange position
A2
B1
B2
H1 Filter size 610 x 610 x 150
H2 Filter size 610 x 610 x 292
1 Nominal size (Number of filters)
2
3
4
2D
4D
6D
8D
AKF-I Duct Hepa filter unit size
AKF-II
In case of replacement of filters using bags (bagin, bag-out system), the procedure is the same
with the exception of a bag attached to the
extension. The waste filter is removed into a bag,
which has been attached to the extension since the
last replacement. The bag is then hermetically
closed so that after the separation of the part of the
bag with the filter, a part of the bag remains on the
extension, hermetically closed as well. A new filter
is put in a bag and then placed over the remaining
part closing the duct. Upon the placement of the
new bag, the remaining part of the old bag is first
removed into the new bag. A new filter is installed
from the new bag. The bags are attached to the
extension by means of a rubber collar.
Ordering example:
Designation:
No. of filters:
Filter:
Air flow volume:
Connection type:
Pcs:
AKF-II/2/H2/A1
2
H2 = 610 x 610 x 292
H13 class (99,95 %)
4800 m3/h
A1
1
417
Table 1
AFH - 1/1
AFH - 1/3
Sit-tightness test
Class
1.
Ho
Detail A
Application:
Wall Hepa filter unit AFH-1 is being used in the network of inlet and outlet
ducts used to supply or extract air from the rooms with highest demands
regarding air cleanness. Hepa filters of H10 to H14 class
prevent the intake or exhaust of particles larger than 0,3 m. Hepa filter is fitted with a washer of a rectangular cross section. With the AFH1/3 version, the
seal may also be semi-circular. They can be installed as follows:
air supply and extract in laboratories
air supply and extract in operating rooms, infection- and sterile
departments
air supply in electronics, precision mechanics, chemistry, pharmaceutics
and food industry
air supply in film and audio tape industry
air supply and extract in nuclear technology etc.
Description:
AFH-1 unit is made of filter housing, two-row steel grille JR-5 and Hepa filter.
Filter housing made of sheet steel is air tight welded according to DIN 1946
and coloured in RAL 9010. Grille is made of cold-drawn strip steel and
coloured in RAL 9010. Grille is fastened to the housing via the nuts which can
be tightened or unscrewed manually. AFH-1 unit is fitted with special sealing
frame for sit-tightness test.
Component parts:
1. Housing
2. Hepa filter (with flat gasket)
3. Grille
1
A
2
AFH 1/1
726 x 421
2.
Detail A
Installation:
AFH-1 unit is designed for installation in the walls of the clean rooms.
**
AFH 1/3
3.
752x452
732x427
744x439
Detail B
* Sit-tightness test
** Pressure drop test
686
Connection flange
656
100
100
321
351
381
100
100
626
418
Design variations:
The type of sealing frame determines three filter unit types and two Hepa
filter sizes (AFH-1/1 and AFH-1/3, size 1 and 2).
Technical data:
Table 2
Nominal size
1
2
Hepa filter
Ho
H1
Grille JR-5
338
480
150
292
725 x 425
725 x 425
Table 3
Filter
Hepa
unit size filter
1
2
Initial
pressure (Pa)
Flow
(m3/h)
Air velocity
(m/s)
Max. temp.
(C)
Humidity
(%)
250
250
850
1700
0.90
2.20
70
70
100
100
300
200
150
100
50
200
600
1000
1600
Q (m3/h)
Magnehelic 0-750 Pa
Mark II 0-700 Pa
Fig. 4
Fig. 5
It is recommended that a separate manometer is used for each filter unit. Upon customer's request we:
- fix it on the filter housing
- prepare a bracket for fixing
- send a manometer without the bracket
Ordering key
AFH-1/1 Size 1
Hepa filter
units size
AFH-1/1 JR-5
1-with filter 305 x 610 x 150
H13 class (99,95 %)
Air flow volume: 600 m3/h
Grille:
JR-5
Pcs:
12
On request it is possible to produce also AFH-1
units for other sizes of Hepa filters.
Manometers have to be ordered separately.
Example of manometer order:
Manometer Magnehelic 0-750 Pa, fitted on the
housing.
419
3
* Sit tightness test
** Pressure drop test
Description:
Ceiling Hepa filter unit AFV-8 is made of filter housing, standard diffusers
KD-1, AKD-1, KD-6, OD-8 or OD-9 and Hepa filter. Filter is fitted with
washer of a rectangular cross-section. Housing of sheet steel is air tight
welded according to DIN 1946 and coloured in RAL 7001. Two pressure
gauge attachments for measuring of a pressure drop are incorporated into the
housing. Diffusers made of sheet steel are coloured in white (RAL 9010).
AFV-8 housing has a special sealing frame designed to perform sit tightness
test.
Component parts:
1. Housing
2. Hepa filter (with flat gasket)
3. Diffuser
Installation:
AFV-8 unit is constructed to fit into suspended ceilings.
Types:
The following Hepa filter units AFV-8 are possible:
with circular side entry spigot (AFV-8 RS) (fig. 1, table 1)
with circular top entry spigot (AFV-8 RV) (fig. 2, table 1)
with rectangular side entry spigot (AFV-8 KS) (fig. 3, table 3).
*
Detail A
A
77.5
Application:
On the ceiling Hepa filter unit AFV-8 a shut-off damper ZL-2 is installed in the
housing connection. The shut-off damper ZL-2 conforms to the DIN 1946/4
standard requirements.
The advantage of such a combination of an Hepa filter housing and a shut-off
damper is the ability to close the shut-off damper during the filter exchange and
thereby to prevent room air pollution. Upon the completion of the filter
exchange, the shut-off damper is reopened. Such a filter exchange procedure
eliminates the need to disinfect the room, which is mandatory in the case of
exchanging the filter without shutting-off the inlet of non-filtered air.
40
Description:
On the connection of the standard ceiling Hepa filter unit AFV-8, a galvanised
sheet steel shut-off damper is mounted by means of four screws. The damper
may be controlled either manually or by means of an electric motor.
Components:
1. AFV-8/RS, RV
2. ZL-2
3. electric motor (with spring)
420
Table 1
B1 x B1
**
H1
Ho
60
H3
50
Size
Hepa filter
Bo
B1
H0
H1
H3
1
2A
2B
3
4
5
148
198
198
198
298
348
355
507
507
660
660
660
348
500
500
653
653
653
319
471
471
624
624
624
324
476
476
629
629
629
450
428
500
428
600
792
270
198
270
198
270
412
178
230
230
230
330
378
J
Bo
A
Table 2
B1 x B1
D
Size
Hepa filter
Bo
B1
Ho
H1
1
2A
2B
3
4
5
148
198
198
198
298
348
355
507
507
660
660
660
348
500
500
653
653
653
319
471
471
624
624
624
324
476
629
629
629
629
350
278
350
278
350
492
270
198
270
198
270
412
H1
Ho
**
80
60
50
J
Bo
A
B1 x B 1
60
50
H1
H2
Size
HEPA filter
Bo
B1
H1
H2
a1
b1
a2
b2
1
2A
2B
3
4
5
355
507
507
660
660
660
348
500
500
653
653
653
319
471
471
624
624
624
324
476
476
629
629
629
270
198
270
198
270
412
400
328
400
328
460
642
250
400
400
500
560
560
100
100
100
100
160
200
285
435
435
535
595
595
136
131
136
136
196
236
a2
15
a1
82.5
Bo
11
b2
b1
Fig. 3
15
421
KD-1
KD-6
Diffuser types:
OD-9K
OD-8K
Technical data:
Possible combinations of diffuser size regarding
the size of housing and Hepa filter is specified in
table 4. Mounting dimensions of diffusers to be
installed in AFV-8 are specified in tables 1, 2 and
3 and in column A.
Table 4
Filter
Hepa
unit size filter
1
2A
2B
3
4
5
D i f f u s e r
KD-1
KD-6
A*
355 x 355
507 x 507
507 x 507
660 x 660
660 x 660
660 x 660
1,2,3
3,4
3,4
5,6,7,8
7,8
7,8
s i z e **
OD-8K
OD-9K
400
500,600,625
500/16
500,600,625
500/16
600,625 600/24, 625/54
600,625 600/24, 625/54
600,625 600/24, 625/54
400
500
500
600
600
600
Filter
Hepa
unit size filter
1
2A
2B
3
4
5
Initial
pressure (Pa)
Flow
(m3/h)
Air velocity
(m/s)
Max. temp.
(C)
Humidity
(%)
250
250
250
250
250
250
290
660
660
1200
1200
2400
1,0
1,1
1,1
1,1
1,1
2,4
70
70
70
70
70
70
100
100
100
100
100
100
3, 4
300
250
200
100
500
1000
1500
2000
2500
3000
3500
Q (m3/h)
1
2A
2B
3
4
5
422
Hepa filter
ZL-2
size
305x305x150
457x457x78
457x547x150
610x610x78
610x610x150
610x610x292
148
198
198
198
298
348
150
200
200
200
300
350
115
190
190
190
190
220
1
2A
2B
3
4
5
Filter size
305 x 305 x 150
457 x 457 x 78
457 x 457 x 150
610 x 610 x 78
610 x 610 x 150
610 x 610 x 292
Mark II 0-700 Pa
Fig. 4
Fig. 5
It is recommended that a separate manometer is used for each filter unit. Upon customer's request we:
- fix it on the filter housing
- prepare a bracket for fixing
- send a manometer without the bracket
Table 6
Filter
Hepa
unit size filter
Flow
(m3/h)
Allowed.
permeability (%)
1
2A
2B
3
4
5
290
660
660
1200
1200
2400
2,9
6,6
6,6
12,0
12,0
30,0
Ordering key
Ordering example:
Designation:
AFV-8/RS3/OD-9 RAL 9010
Connection type: circular side entry
spigot RS
Size:
3-with filter 610 x 610 x 78
H13 class (99,95 %)
Air flow volume: 1200 m3/h
Diffuser:
OD-9 RAL 9010
Pcs:
12
On request it is possible to produce also AFV-8
units for other sizes of HEPA filters.
Manometers have to be ordered separately.
Example of manometer order:
Manometer Magnehelic 0-750 Pa, fitted on the
housing.
Shut-off
damper ZL-2
Hepa
filter
unit
size
Connection
1
2A
2B
3
4
5
* The AFV-8 version with the shut-off damper ZL-2 is only availible with the
RS and RV versions.
Hepa filter: Size and filter class is to be specified independently.
423
Component parts:
1. Plenum box
2. Hepa filter housing
3. Filter (version K - duct in the gasket or version P - semicircular gasket)
4. Mask
5. DOP test connection
6. +p connection
3
2
4
424
Installation:
Housing is adapted for suspended ceiling installation
60-70
Installation T (traverse)
35-70
Installation O (hangers)
Filter:
Version K - filter with the duct in the gasket (enabling of airtightness testing)
Version P - filter with the semicircular gasket (airtightness testing not possible)
425
Dimensions:
AFV-8U/RS with circular side entry spigot
60
H1
H0
H3
B2
Size
Hepa filter
1
2
3A
3B
3C
4
5
305x305x80
457x457x80
610x610x80
610x610x150
305x610x80
610x915x80
610x1220x80
B0
B1
B2
158
415
409,5
380
265
198
567
561,5
532
417
248
720
714,5
685
570
313
720
714,5
685
570
198 415x720 409,5x714,5 380x685 265x570
313 720x1025 714,5x1019,5 685x990 570x875
348 720x1330 714,5x1324,5 685x1295 570x1180
H0
H1
H3
343
383
433
568
383
498
533
133
133
133
203
133
133
133
210
250
300
365
250
365
400
B1
B0
H1
H0
100
60
B1
B0
Size
Hepa filter
1
2
3A
3B
3C
4
5
305x305x80
457x457x80
610x610x80
610x610x150
305x610x80
610x915x80
610x1220x80
B0
B1
B2
158
415
409,5
380
265
198
567
561,5
532
417
248
720
714,5
685
570
313
720
714,5
685
570
198 415x720 409,5x714,5 380x685 265x570
313 720x1025 714,5x1019,5 685x990 570x875
348 720x1330 714,5x1324,5 685x1295 570x1180
H0
H1
233
233
233
303
233
233
233
133
133
133
203
133
133
133
Diffusers types:
KD-1
426
KD-6
OD-9K
Size
1
2
3A
3B
3C
4
5
Hepa
filter
External diffuser
dimension
A
KD-1
KD-6
Aef (m )
OD-9
Aef (m )
305 x 305 x 80
457 x 457 x 80
610 x 610 x 80
610 x 610 x 150
305 x 610 x 80
610 x 915 x 80
610 x 1220 x 80
415 x 415
567 x 567
720 x 720
720 x 720
415 x 720
720 x 1025
720 x 1330
1,2,3
2,3,4
5,6,7,8
5,6,7,8
-
0,0342
0,0743
0,1368
0,1368
0,0684
0,198
0,2664
0,0189
0,0414
0,0651
0,0651
0,0288
0,1088
0,1348
KD-1
2
1
2
3
4
5
6
7
8
Aef (m2)
0.0104
0.0185
0.0279
0.0440
0.0628
0.0728
0.1175
0.1280
The table indicates possible combinations of diffuser sizes according to housing and Hepa filter size.
Size
Hepa
filter
1
2
3A
3B
3C
4
5
305 x 305 x 80
457 x 457 x 80
610 x 610 x 80
610 x 610 x 150
305 x 610 x 80
610 x 915 x 80
610 x 1220 x 80
H13
Initial pressure
(Pa)
H14
250
250
250
250
250
250
250
Flow
(m3/h)
Initial pressure
(Pa)
Flow
(m3/h)
Max. temp
(C)
Humidity
(%)
300
740
1400
1530
640
2150
2900
125
125
125
125
125
125
150
340
600
300
900
1200
80
80
80
80
80
80
80
100
100
100
100
100
100
100
Ordering key
1
2
3A
3B
3C
4
5
427
Description:
Ceiling Hepa filter unit with gel gasket AFV-8G is made filter housing, standard diffusers KD-1, AKD-1, KD-6, OD-8 or OD-9 and Hepa filter. Housing of
sheet steel is air tight welded according to DIN 1946 and coloured in RAL
7001. Diffusers are made of sheet steel and coloured in white (RAL 9010).
AFV-8G housing has a special sealing frame designed to fit gasket filters.
A
**
Component parts:
1. Housing
2. Hepa filter (with gel gasket)
3. Diffuser
Installation:
Detail A
Detail C
Spring
claw
fastener
Types:
The following ceiling Hepa filter units with gel gasket are possible:
with circular side entry spigot (AFV-8G RS) (fig. 1, table 1)
with circular top entry spigot (AFV-8G RV) (fig. 2, table 1)
with rectangular side entry spigot (AFV-8G KS) (fig. 3, table 3).
Application:
On the Ceiling Hepa filter units with gel gasket AFV-8G a shut-off damper ZL-2
is installed in the housing connection. The shut-off damper ZL-2 conforms to
the DIN 1946/4 standard requirements.
The advantage of such a combination of an Hepa filter housing and a shut-off
damper is the ability to close the shut-off damper during the filter exchange and
thereby to prevent room air pollution. Upon the completion of the filter
exchange, the shut-off damper is reopened. Such a filter exchange procedure
eliminates the need to disinfect the room, which is mandatory in the case of
exchanging the filter without shutting-off the inlet of non-filtered air.
77.5
428
40
Description:
On the connection of the standard AFV-8G unit, a galvanised sheet steel shutoff damper is mounted by means of four screws. The damper may be controlled
either manually or by means of an electric motor.
Components:
1. AFV-8G/RS, RV
2. ZL-2
3. electric motor (with spring)
CEILING HEPA FILTER UNITS WITH GEL GASKET AFV-8G TECHNICAL DATA
B1 x B1
50
50
H1
H0
80 (128)
H3
60
B0
A
Table 1
Hepa filter
unit size
Hepa
filter
Bo
B1
Ho
H1
H3
ZL-2
Ho
H3
1
2
3A
3B
3C
4
5
6
305 x 305 x 80
457 x 457 x 80
610 x 610 x 80
610 x 610 x 128
305 x 610 x 80
610 x 915 x 80
610 x 1220 x 80
545 x 545 x 80
158
198
198
248
198
313
353
198
355
507
660
660
355 x 660
660 x 965
660 x 1270
595
348
500
653
653
348 x 653
653 x 958
653 x 1263
588
319
471
624
624
319 x 624
624 x 929
624 x 1234
559
395
435
435
535
435
550
590
435
200
200
200
250
200
200
200
200
195
235
235
285
235
350
390
235
163
203
203
253
203
318
358
203
400
440
440
540
440
555
595
440
200
240
240
290
240
355
395
240
B1 x B1
D
H0
60
50
H1
80 (128)
50
B0
A
Table 2
Hepa filter
unit size
Hepa
filter
Bo
B1
Ho
H1
ZL-2
D
1
2
3A
3B
3C
4
5
6
305 x 305 x 80
457 x 457 x 80
610 x 610 x 80
610 x 610 x 128
305 x 610 x 80
610 x 915 x 80
610 x 1220 x 80
545 x 545 x 80
158
198
198
248
198
313
353
198
355
507
660
660
355 x 660
660 x 965
660 x 1270
595
348
500
653
653
348 x 653
653 x 958
653 x 1263
588
319
471
624
624
319 x 624
624 x 929
624 x 1234
559
280
280
280
330
280
280
280
280
200
200
200
250
200
200
200
200
163
203
203
253
203
318
358
203
429
CEILING HEPA FILTER UNITS WITH GEL GASKET AFV-8G TECHNICAL DATA
B1 x B1
60
50
50
15
a2
a1
H1
b2
11
b1
H0
80 (128)
82.5
B0
A
Table 3
Hepa filter
unit size
Hepa
filter
Bo
B1
Ho
H1
a1
b1
a2
b2
1
2
3A
3B
3C
4
5
6
305 x 305 x 80
457 x 457 x 80
610 x 610 x 80
610 x 610 x 128
305 x 610 x 80
610 x 915 x 80
610 x 1220 x 80
545 x 545 x 80
158
198
198
248
198
313
353
198
355
507
660
660
355 x 660
660 x 965
660 x 1270
595
348
500
653
653
348 x 653
653 x 958
653 x 1263
588
319
471
624
624
319 x 624
624 x 929
624 x 1234
559
314
314
314
414
314
314
314
314
200
200
200
250
200
200
200
200
250
400
500
500
500
800
1000
400
100
100
100
150
100
100
100
100
285
435
535
535
535
835
1035
435
135
135
135
185
135
135
135
135
KD-1
KD-6
Diffuser types:
OD-9K
OD-8K
Technical data:
Table 4
Hepa filter
unit size
1
2
3A
3B
3C
4
5
6
Hepa
filter
A*
KD-1
KD-6
OD-8K
OD-9K
305 x 305 x 80
457 x 457 x 80
610 x 610 x 80
610 x 610 x 128
305 x 610 x 80
610 x 915 x 80
610 x 1220 x 80
545 x 545 x 80
355 x 355
507 x 507
660 x 660
660 x 660
660 x 355
660 x 965
660 x 1270
595 x 595
1,2,3
2,3,4
5,6,7,8
5,6,7,8
3,4,5,6
Aef (m2)
Filter unit size
KD-6
OD-8
OD-9
KD-1
1
2
3A
3B
3C
4
5
6
0.0342
0.0743
0.1368
0.1368
0.0684
0.1980
0.2664
0.1095
0.0300
0.0450
0.0639
0.0450
0.0189
0.0414
0.0651
0.0651
0.0288
0.1088
0.1348
0.0509
1
2
3
4
5
6
7
8
430
Aef (m2)
0.0104
0.0185
0.0279
0.0440
0.0628
0.0728
0.1175
0.1280
CEILING HEPA FILTER UNITS WITH GEL GASKET AFV-8G TECHNICAL DATA
Mask OD-8
Hepa filter unit size 3A
660
507
660
507
660
660
Mask OD-9
Hepa filter unit size 3A,B
Hepa filter unit size 6
Hepa filter unit size 2
660
595
355
507
355
507
595
660
660
355
660
965
660
1270
Table 5
Hepa filter
unit size
1
2
3A
3B
3C
4
5
6
Hepa
filter
Initial
pressure (Pa)
Flow
(m3/h)
Air velocity
(m/s)
Max. temp.
(C)
Humidity
(%)
305 x 305 x 80
457 x 457 x 80
610 x 610 x 80
610 x 610 x 128
305 x 610 x 80
610 x 915 x 80
610 x 1220 x 80
545 x 545 x 80
125
125
125
125
125
125
125
125
150
340
600
900
300
900
1200
500
0,45
0,45
0,45
0,45
0,45
0,45
0,45
0,45
80
80
80
80
80
80
80
80
100
100
100
100
100
100
100
100
3C
300
3A
250
p (Pa)
200
3B,4
150
100
50
150
300
450
600
750
900
1050
1200
1350
Q (m3/h)
Hepa
filter
1
2
3A
3B
3C
4
5
6
305x305x80
457x457x80
610x610x80
610x610x128
305x610x80
610x915x80
610x1220x80
545x545x80
ZL-2
size A
160
200
200
250
200
315
355
200
115
190
190
190
190
190
220
190
431
CEILING HEPA FILTER UNITS WITH GEL GASKET AFV-8G TECHNICAL DATA
Magnehelic 0-750 Pa
Mark II 0-700 Pa
Fig. 4
It is recommended that a separate manometer is used for each filter unit. Upon customer's request we:
- fix it on the filter housing
- prepare a bracket for fixing
- send a manometer without the bracket
Ordering key
Damper R manual
control B electric motor
Shut-off
damper ZL-2
Hepa filter
unit size
1
2A
3A
3B
3C
4
5
Connection
* The AFV-8G version with the shut-off damper ZL-2 is only availible with
the RS and RV versions.
Hepa filter: Size and filter class is to be specified independently.
432
Ordering example:
Designation:
AFV-8G/RS3A/OD-9 RAL 9010
Connection type: circular side entry
spigot RS
Size:
3A with filter 610 x 610 x 83
H14 class (99,995 %)
Air flow volume: 600 m3/h
Diffuser:
OD-9 RAL 9010
Pcs:
12
On request it is possible to produce also AFV-8
units for other sizes of HEPA filters.
Fixation of the perforated plates is on the one hand carried out with the help of
hinges and on the other hand with the help of locks.
The ceiling is fitted with the hepa filters 610x305x292, which belong to the class
H13 or H14 and have been tested according to the DIN 24 185, which means that
parts in diameter of 0.3m are removed 99,95% and 99,995% respectively. They
are fitted into the side connection on the longer side of the ceiling. The dimensions
of the connection duct and the number of filters are given in the table. The inside
of the ceiling is fitted with the filter pressure drop measurement connections (the
difference between the pressure in front of and behind the filter, which serves to
control the dirtiness of the filter) and with the DOP or PAO test connection.
Fig. 1
With the nominal flow rate of air, given in the table, the initial pressure drop
is 250 Pa. At a filter load with larger or smaller flow rates than the nominal
the pressure drop increases and decreases respectively, which is shown
in the diagram. Leak-tightness of hepa filter at the sealing frame is
in accordance with the DIN 1946 standard, Chapter 4. When changing filters
one has to check the leak-tightness of the hinges.
The ceiling, filter body, filters, PPI-20 foam and the assembly material are
delivered separately.
The assembly of ceilings to the concrete ceiling is carried out with the
threaded bars and inners for the concrete.
Hepa filter replacement:
During the operation the permeability of the Hepa filter is decreased and the
differential pressure increases. The permeability-loss rate is measured with
differential manometer via the tubes fitted in front and after the filter. When the
pressure drop has reached double its initial value, it is recommended to
replace the Hepa filter. When replacing absolute filters, the first row of face
plates has to be removed.
433
301
Component parts:
1. Plenum box
2. Filter housing with connection flanges
3. Filter with semicircular gasket
4. Perforated plate
5. Transition for the connection of lights
321
321
150
5
4
B
25
PAO (DOP)
405
170
59
315
170
25
connection flange
Ceiling dimensions:
B
Q (m3/h)
vef (m/s)
2000
2400
2400
2400
2400
3000
3000
3000
3000
1000
1200
1400
1500
1800
1800
1800
2400
3000
3
4
4
4
4
5
5
5
5
2
2
2
2
3
3
3
4
5
1000
1600
1800
2000
2400
2000
3000
4000
4000
0,15
0,15
0,15
0,15
0,15
0,15
0,15
0,15
0,15
no.of
filters
1
2
2
2
3
2
3
4
4
Initial
Connection
pressure p
flange
230
678x315
190
1302x315
200
1302x315
230
1302x315
180
1915x315
230
1302x315
230
1915x315
230
two connections 1302x315
230
two connections 1302x315
Ordering example:
3 filtri
4 filtri
2 filtra
500
400
p (Pa) 300
250
200
100
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Q (m3/h)
434
435
322
322
4
5
25
connecting
flange
priklju~na prirobnica
25
170
135
PAO (DOP)
135
135
405
315
59
170
322
322
priklju~na prirobnica
connecting
flange
330
3
2
271.5
1
4
BxH
436
Dimensions:
Dimensions
BxH
2400 x 1400
2400 x 1800
3000 x 1800
2400 x 2400
3000 x 2400
3000 x 3000
Flow
m3/g
2000
3000
4000
4200
5000
6000
Number of
filters
2
3
4
4
6
6
500
3 filtri
filters
400
4 filtri
filters
p (Pa)
300
250
200
6 filtrov
filters
100
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
Q (m /h)
Installation:
30
30
25
Ordering key:
DSS/2400x1400/L/S/Z
Z installation with angle
X installation without angle
S connection from side
V connection from top
opening for lamp
BxH
Unstandard dimensions and any other required air flow on customer's request.
437
B
B1
H1
Dimensions:
Nominal
dimension
B
H
325
225
425
525
425
325
525
625
Free
area
B1
285
385
485
385
485
585
H1
185
285
Recom.
flow rate
Q
270
380
500
600
750
900
10
LN-1
30
10
LN-1/G4,F5
Free
area
BxH
282 x 182
382 x 182
482 x 182
382 x 282
482 x 282
582 x 282
Recom.
flow rate
Q
270
380
500
600
750
900
80
10
LN-1/F
Installation:
The grille may be mounted flush with the wall face
(Figure 1).
Filter Insert Cleaning and Replacement:
Due to dirt, which collects on the grille, it needs to
be removed and cleaned from time to time. Due to
the build-up of impurities, the grille must be
removed and cleaned. Loosen the grille face screw
and simply withdraw the grille face from the
installation frame. With the LN-1/Filter variant,
withdraw the filter insert from the frame and
replace it by a new insert.
Installation:
Figure 1
B/H
Ordering key:
LN-1 / G4
BxH
G4 filter quality (G4 or F5)
F adjustment insert
438
B2
B1
Free
area
B1
H1
285 185
385 185
485 185
385 285
485 285
585 285
B2
377
477
577
477
577
677
Recom.
flow rate
H2
Q
277 270
277 380
277 500
377 600
377 750
377 900
Nominal
dimension
B
H
325
225
425
225
525
225
425
325
525
325
625
325
Filter
dimension
BxH
282 x 182
382 x 182
482 x 182
382 x 282
482 x 282
582 x 282
Recom.
flow rate
Q
270
380
500
600
750
900
LN-2
H2
H1
16
16
LN-2/G4,F5
36
29
16
LN-2/F
Installation:
LN-2/S
Ordering key:
LN-2 / V / G4 BxH
B/H
B+5 / H+5
439
FILTER GRILLE FR
35,5
Filter grille
Application:
Grilles with a filter are intended to be built in the
walls of rooms which require cleaner air (computer
Inox centres, libraries, clean rooms, etc,). Primarily used
RAL
for exhaust air from the room.
B2/H2
F
...
9010
Description:
Grilles are made of stainless (polish) sheet metal.
The installed filter is of G2, G3, G4 or of F5
quality.
32
H1
Dimensions:
33
33
B1
33
33
225
325
425
525
625
325
425
525
625
425
525
625
525
625
625
225
325
425
525
625
Installation:
1. by screws (designation V)
B2
222
322
422
522
622
322
422
522
622
422
522
622
522
622
622
H1
H2
Dimensions:
Standard dimensions of louvres are 225 x 75 mm
to 1125 x 525. The depth of the grilles is 35 mm.
198
222
Installation:
298
322
398
422
498
522
598
622
32
B/H
33
B1
198
298
398
498
598
298
398
498
598
398
498
598
498
598
598
B1/H1
Filter
dimension
BxH
283 x 183
383 x 183
483 x 183
383 x 283
483 x 283
583 x 283
A
0.05178
0.07009
0.08839
0.10839
0.13669
0.16499
Recom.
flow rate
Q
450
650
800
1000
1200
1500
32
Ordering key:
FR / V / F5
BxH
440
B1/H1
80
initial pressure drop p (Pa)
50
G4
60
G3
40
G2
40
30
20
20
10
0
2000
4000
6000
1000
8000
Q 0(m3/h.m2)
2000
3000
4000
Q0(m3/h.m2)
H1
A (m2)
198
298
398
498
598
298
398
498
598
398
498
598
498
598
598
198
198
198
198
198
298
298
298
298
398
398
398
498
498
598
0,02744
0,04130
0,05516
0,06902
0,08288
0,06216
0,08302
0,10388
0,12474
0,11088
0,13874
0,16660
0,17360
0,20846
0,25032
Example:
Q=200 m3/h
Filter G4
FR/298x198
Calculation of air flow per m2 of filter:
1. Q (m3/h.m2 ) =
Q
200 m3/h
= 4843 m3/h.m2
=
A
0,0413 m2
441