2000 Amps
Cable
Cable

@ +24VDC & 80 Amps @ -48VDC

162 Power System

Front View
Rear View

100 Amp Switchmode Rectifiers


Up to 20 can be equipped per bay, for a total of 2000 Amps of
+24VDC power
10 Amp Converters
Converts the +24VDC supplied by the rectifiers into -48VDC.
Up to eight can be equipped for a total of 80 Amps at -48VDC
Four Circuit Breaker Configurations for Distribution of +24VDC
Option 1 - (80) 0 to 100 Amp
Option 2 - (24) 0 to 100 Amp, (5) 125 to 250 Amp, and
(4) 300 to 450 Amp
Option 3 - (48) 2 to 100 Amp and (6) 125 to 250 Amp
Option 4 - (36) 2 to 100 Amp and (8) 125 to 250 Amp
Two -48VDC Configurations for Distribution
Option 1 - (3) circuit breakers 2 to 60 Amps
Option 2 - (20) GMT fuses 0.18 to 7.5 Amps
Meter, Monitor, and Control Panel
Easy to navigate, pushbutton controller has two lines
of text to facilitate plant monitoring and control
Small Footprint
23.62" by 23.62" (600mm by 600mm)
Front Accessible
All installation, operation, and general maintenance
is from the front of the unit

Product Description
The 162 Power and Distribution System supplies 100 to 2000 Amps of +24VDC power in increments of 100 Amps.
The system is self-contained, providing power, distribution, alarms, and monitoring within one bay. To create the
flexible power needed by the 162, up to twenty switchmode rectifiers can be used. Up to eight optional +24VDC
to -48VDC converters can be installed, for a total output current of 80 Amps at -48VDC. The 162 was designed
for ease of installation, incorporating all customer connections for loads, controls, alarms, and monitoring from the
front of the bay.
Users may choose one of four distribution options for +24VDC, and one of two options for -48VDC. All +24VDC
distribution options feature A & B sections. The 162 system may be accessed, monitored, and controlled from
one entry point via the meter, monitor, and control (MMC) panel, which is easy to use and provided as standard
equipment.
The system is equipped with eight relays for extending alarms and status remotely, and 22 LEDs for immediate
visual notification of alarms and operating status. A & B low voltage load disconnects (LVLD) are optional.
162/1-03/a

Specifications are subject to change without notice. Please visit our website for the latest revision.

2000 Amps @ +24VDC & 80 Amps @ -48VDC


162 Power System

162 Power System Specifications


Input - 220VAC
Voltage Range
Frequency Range
Current

176 - 264VAC, single phase


47 - 63Hz
18 Amps (220VAC input and 100A output)

Output
Float Voltage Range
Current

23.5 - 28.5VDC. Factory set @ 27.2VDC


Maximum of 2000 Amps at + 24VDC per bay (from rectifiers)
Maximum of 80 Amps at - 48VDC per bay (from converters)

Environmental
Storage Ambient
Operating Ambient (NEBS)
Humidity

-40F to +85F (-40C to +85C )


23F to 122F (-5C to +50C)
< 95% non-condensing (maximum)

Mechanical
Height
Width
Depth
Weight
Mounting
Cooling

84.0" (2133.6 mm)


23.62" (600 mm)
23.62" (600 mm)
1,000 lbs. (453.6kg) when equipped with 20 rectifiers and 8 converters
Floor
Front-to-rear fans in rectifiers and converters

Documentation
Product Manual
System Layout Drawing

4380211PD
J-438162P

Visual Indicators
MMC Front Panel:

LED Description
Power Major
Power Minor
Rectifier Major
Rectifier Minor
Battery Monitor
Distribution Fuse
Distribution Current
MMC OK
Low Low Voltage
Low Voltage
High Voltage

Color
Red
Amber
Red
Amber
Amber
Red
Amber
Green
Red
Amber
Red

LED Description
Battery Fuse
Battery Distribution
Battery Discharge
Load Disconnect
Total Current
AC Fail
Temp High/Low
Float Mode
Equalize Mode
BTC Active

Color
Red
Red
Amber
Red
Amber
Amber
Amber
Green
Amber
Amber

Specifications are subject to change without notice. Please visit our website for the latest revision.

162/1-03/a

2000 Amps @ +24VDC & 80 Amps @ -48VDC


162 Power System

Options
List #
1
5
6
7
8
20
22
25
27
30
31
32
33
40
41

Description
PECO II Part Number
Basic +24VDC @ 2,000 Amp bay including frame, controller,
distribution bus bar and rectifier shelves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6070836P
OPTION 1: (80) 2-100 Amp plug-in circuit breaker positions, including output terminator
bus & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180602P
OPTION 2: (24) 2-100 Amp, (5) 125 - 250 Amp, (4) 300 - 450 Amp circuit breaker positions
including output termination bus bar & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180603P
OPTION 3: (48) 2 - 100 Amp, (6) 125 - 250 Amp circuit breaker positions
including output termination bus bar & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180606P
OPTION 4: (36) 2 - 100 Amp, (8) 125 - 250 Amp circuit breaker positions
including output termination bus bar & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180608P
+24 VDC @ 100 Amp rectifier module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SM100F24-UP
Rectifier blank for unused rectifier positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4361154P
-48 VDC @ 10 Amp DC/DC converter module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SM48P10A-D
DC/DC converter blank for unused converter positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4361159P
-48 VDC @ 40 Amp initial converter plant consisting of (1) 40 Amp converter shelf and wiring,
add up to (4) list 25 converters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420552P
-48 VDC @ 40 Amp supplemental converter plant consisting of
(1) 40 Amp converter shelf and wiring, add up to (4) list 25 converters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420552P-1
Converter distribution: (3) 2 - 60A circuit breaker positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420556P
Converter distribution: (20) 0.18 - 7.5A GMT fuse positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420556P-1
Load A/B disconnects for +24VDC distribution options, list 5-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420554P
Load C disconnect for -48VDC DC/DC converter plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420553P

Distribution Circuit Breakers


Plug-in Type
Description
PECO II Part Number
2 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-2
5 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-5
7 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-7
8 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-8
10 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-10
15 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-15
20 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-20
25 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-25
30 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-30
35 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-35
40 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-40
45 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-45
50 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-50
60 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-60
70 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-70
80 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-80
90 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-90
100 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-100
162/1-03/a

Bolt-on Type
Description
PECO II Part Number
125 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-125
150 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-150
175 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-175
200 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-200
225 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-225
250 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-250
300 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-300
350 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-350
400 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-400
450 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-450

Notes: distribution options list 6, 7, 8


One 300-450A breaker can be installed in any two adjacent
125-250A positions

Specifications are subject to change without notice. Please visit our website for the latest revision.

2000 Amps @ +24VDC & 80 Amps @ -48VDC


162 Power System

Line Drawing
162 Power System is shown
Option 1

Option 2

Option 3

Option 4

Certifications: