Anda di halaman 1dari 6

Cable-glands for armoured and non armoured cables

Explosion Proof - Boxes, accesories and components

code:

EXPA / EXPN

GENERAL INFORMATION
Ex d IIC and Ex e II according to IEC 79.1 and 79.7
Ex DIP A 21 T6 (for zone 21) according to IEC 1241-1-1.
IP 65.
APPLICATIONS
Designed for electrical installations in classified
areas, to use outdoors, where dust or any
other external agent is present. Used with armoured and
non-armoured cables, with frames like helical of galvanized
steel wire, braid of galvanized steel wire and helical of
galvanized steel band: used in entries of command boxes,
control stations, lighting fixtures, pannels, engines, etc.
In the armoured cable model, the press of armour is made
by a double cone which is compressed inside by the
pieces that provides the continuity of mass fixing the
wire mechanically
It has a double hermetic seal: one flame-proof and another
weather-proof to prevent the entry of water, dust, etc.

FEATURES
Manufacture:
Metal body of brass, acrylonitrile gasket, watertightness
washer of polyamide.
On request: Metal body of nickel brass.

Accesories:
Brass nut: Limited to e protection boxes with thin
walls and through hole.
On request: Nickel brass.

Thread Type: (see table of Threaded Entries)


- 1/2" to 2 in N.P.T.
- M20 to M63 in Metric 1,5.
On request:
- 1/2" to 2 in BSPT
- PG 11 to PG 48.

Brass terminals: To provide internal and / or external


earth in boxes with non-continuity of mass or when using
non-armoured cables is required earth.
On request: Nickel brass.

CODES AND DIMENSIONS


Cableglands depending on threaded entry and armoured cable to use.
Basic size

1-2

66 - DELGA S.A.

Cable diameter
Under armor
External

Cableglands code for armoured cable


NPT OPTION THREAD

from

to

from

to

1/2" IIB*

1/2"

3/4"

3.0

7.0

9.0

12.0

EXPAB 1S017

EXPA 2S017

EXPA 2S027

EXPAB 1M017 EXPA 2M017 EXPA 2M027

1"

1 1/4"

1 1/2"

2"

6.5

12.8

10.5

16.0

11.0

14.3

13.0

21.0

11.0

15.0

14.0

18.0

EXPA 3S027

14.0

20.0

17.0

24.0

EXPA 3M027 EXPA 3M037

17.0

21.0

23.0

28.0

EXPA 4S037 EXPA 4S047

20.0

24.0

27.0

32.0

EXPA 4M037 EXPA 4M047

23.0

27.0

31.0

36.0

EXPA 4L037 EXPA 4L047

22.0

26.0

26.0

32.0

EXPA 5S047 EXPA 5S057

25.0

29.0

31.0

37.0

EXPA 5M047 EXPA 5M057

28.0

32.0

36.0

42.0

EXPA 5L047 EXPA 5L057

29.0

34.0

35.0

41.0

EXPA 6S067

34.0

39.0

41.0

47.0

EXPA 6M067

39.0

44.0

47.0

52.0

EXPA 6L067

EXPA 2L017

EXPA 2L027
EXPA 3S037

w w w. d e l g a . c o m
Basic
size

1-2

3
4

Cable diameter
Under armor

Cableglands code for armoured cable


METRIC THREAD x 1,5

External

from
3.0
6.5
11.0
11.0
14.0
17.0
20.0
23.0
22.0
25.0
28.0
29.0
34.0

to
7.0
12.8
14.3
15.0
20.0
21.0
24.0
27.0
26.0
29.0
32.0
34.0
39.0

from
9.0
10.5
13.0
14.0
17.0
23.0
27.0
31.0
26.0
31.0
36.0
35.0
41.0

to
12.0
16.0
21.0
18.0
24.0
28.0
32.0
36.0
32.0
37.0
42.0
41.0
47.0

M 20 IIB*
M 20
M 25
M 32
M 40
M 50
EXPAB 1SM20 EXPA 2SM20 EXPA 2SM25
EXPAB 1MM20 EXPA 2MM20 EXPA 2MM25
EXPA 2LM20 EXPA 2LM25
EXPA 3SM25 EXPA 3SM32
EXPA 3MM25 EXPA 3MM32
EXPA 4SM32 EXPA 4SM40
EXPA 4MM32 EXPA 4MM40
EXPA 4LM32 EXPA 4LM40
EXPA 5SM40 EXPA 5SM50
EXPA 5MM40 EXPA 5MM50
EXPA 5LM40 EXPA 5LM50
EXPA 6SM50
EXPA 6MM50

39.0

44.0

47.0

52.0

EXPA 6LM50

M 63

* Only for IIB or IIC groups with less volume than 2000 cm3. For IIC with more volume than 2000 cm3 can use the 3 3 EXPA 2#017 version.

Basic
size
1
2
3
4
5
6

Dimensional (mm.)
e/c A
25.4
31.75
38.1
50.8
57.2
76.2

turn
27.5
34.5
42.0
55.0
62.0
83.0

C
80
85
90
100
100
105

F
10
25
25
25
25
25

Min. Packing
(unit)
25
15
10
5
5
2

Packing weight
unit (kg)

4,10
4,22
3,44
3,31
5,20
3,30

Dimensions and weights are approximated.

Cable glands depending on threaded entry and non-armoured cable to use.


Basic
size
1-2
3
4

Basic
size
1-2
3
4

Cable diameter

Cableglands code for Non armoured cable

External
from
to
3.1
7.0
6.5
12.8
11.0
14.3
11.0
15.0
14.0
20.0
17.0
21.0
20.0
24.0
23.0
27.0
22.0
26.0
25.0
29.0
28.0
32.0
29.0
34.0
34.0
39.0
39.0
44.0

NPT OPTION THREAD


1/2" IIB*
3/4"
1"
1 1/4"
1 1/2"
1/2"
EXPNB 1S017 EXPN 2S017 EXPN 2S027
EXPNB 1M017 EXPN 2M017 EXPN 2M027
EXPN 2L017 EXPN 2L027
EXPN 3S027 EXPN 3S037
EXPN 3M027 EXPN 3M037
EXPN 4S037 EXPN 4S047
EXPN 4M037 EXPN 4M047
EXPN 4L037 EXPN 4L047
EXPN 5S047 EXPN 5S057
EXPN 5M047 EXPN 5M057
EXPN 5L047 EXPN 5L057

Cable diameter
External
from
to
3.1
7.0
6.5
12.8
11.0
14.3
11.0
15.0
14.0
20.0
17.0
21.0
20.0
24.0
23.0
27.0
22.0
26.0
25.0
29.0
28.0
32.0
29.0
34.0
34.0
39.0
39.0
44.0
-

Cableglands code for Non armoured cable


METRIC THREAD x 1,5
M 20 IIB*
M 20
M 25
M 32
M 40
M 50
EXPNB 1SM20 EXPN 2SM20 EXPN 2SM25
EXPNB 1MM20 EXPN 2MM20 EXPN 2MM25
EXPN 2LM20 EXPN 2LM25
EXPN 3SM25 EXPN 3SM32
EXPN 3MM25 EXPN 3MM32
EXPN 4SM32 EXPN 4SM40
EXPN 4MM32 EXPN 4MM40
EXPN 4LM32 EXPN 4LM40
EXPN 5SM40 EXPN 5SM50
EXPN 5MM40 EXPN 5MM50
EXPN 5LM40 EXPN 5LM50
EXPN 6SM50
EXPN 6MM50
EXPN 6LM50

2"

EXPN 6S067
EXPN 6M067
EXPN 6L067

M 63

* Only for IIB or IIC groups with less volumen than 2000 cm3. For IIC with more volumen than 2000 cm3 can use the EXPAN 2#017 version.

Basic
size
1
2
3
4
5
6

e/c A
25.4
31.75
38.1
50.8
57.2
76.2

Dimensional
Turn
27.5
34.5
42.0
55.0
62.0
83.0

(mm.)
C
52
60
63
67
68
70

F
10
25
25
25
25
25

Min. Packing Packing weight


unit (kg)
(unit)
25
2,71
15
2,85
10
2,10
5
1,96
5
3,12
2
1,80

Dimensions and weights are approximated.

DELGA S.A. - 67

15

Cable-glands for armoured and non armoured cables


Explosion Proof - Boxes, accesories and components

code:

EXPA / EXPN

Order example

EXPA 2 S 017 LN

EXPN 2 S 017 LN
Nickel brass (material on request).
1/2 NPT (size and thread type).
Small (cable size).

Nickel brass (material on request).


1/2 NPT (size and thread type).
Small (cable size).

2 (Basic size).
Cablegland for armoured cable

2 (Basic size).
Cablegland for non-armoured cable

CABLE GLAND FOR ARMOURED CABLE


Unarmed

8 - Watertightness
washer

7 - Body
gland

6 - Flame-proof
gasket

4 - Adjusting

2 - Watertight

O ring

gasket

5 - Adjusting

3 - Union body

Cone

1 - Tighten
nut

Assembled method
1.0 - Grease all the threads. (Industrial vaseline or oily lithium)

5 - Adjusting cone

1
1.1 - Peel the end of the cable, considering that the length "X" until the wiring position
must include the body length between threads.
1.2 - Cut the metal mesh leaving an useful length as long as the conic zone of the
clamping and earthing cone (5) plus 1or 2 mm.

2.1 - Thread the tighten nut with the weather proof gasket inside (1), the reduction body (3), the clanping
and earthing ring so that the main side cone remains at the cut end of cable.

2
1 - Nut (with watertight
gasket)
4 - Adjusting ring

3.1 - Open the metal mesh in such a way that it "copies" the adjustment cone. Thread it.

3
5 - Adjusting cone

68 - DELGA S.A.

3 - Union body

w w w. d e l g a . c o m

4.1 - Thread the body gland, with watertightness washer to the other cableglands side.
4.2 - Thread the body gland at the entry with the appropriate wrench until it has been adjusted definitively.

4.3 - Then thread the union body (3) and the lock nut (1) with a considerable adjustment (with the appropriate wrench).

7 - Body gland

5.1 - In case of cableglands for "e mode" protection or weather proof, add the watertightness washer (8).

5
8 - Watertightness
washer

CABLE GLAND FOR NON ARMOURED CABLE


Unarmed

4 - Body
gland

3 - Flame proof
gasket

5 - Watertightness washer
(to be used in e version)

1 - Tighten
nut

2 - Adjustment
bushing

Assembled method
1.0 - Grease all the threads. (Industrial vaseline or oily lithium grease)
4 - 3.- Body gland with
flame-proof gasket

2 - Adjustment
bushing

1 - Tighten
nut

1.1 - Thread in the cable, the tighten nut (1), the adjustment bushing (2) and body gland (4)
with the flameproof gasket (3) toward of the side of the other part of the cablegland.
1.2 - Thread the body gland at the entry with the appropriate wrench until it has been adjusted definitively.
1.3 - Thread all the parts with a considerable adjustment (with the appropriate wrench).
2.1 - In cases of cableglands for e protection or weather proof, add the watertightness washer.

2
5 - Watertightness
washer

DELGA S.A. - 69

Cable-glands for armoured and non armoured cables


Explosion Proof - Boxes, accesories and components

code:

EXPA / EXPN

RECOMENDATIONS
The choice of the right system
1 - Set the classified area for the installation.
2 - Define the type of cable to use (armoured or non armoured).
3 - Determine the entries of the element you want to enter (diameter and thread type):
If it is possible use NPT threads. Remember that Delga s cable-glands and standard accesories are
manufactured in this type of thread, so you will obtain a quick delivery and reposition of parts.
4 - Define the diameters under armor and external (if corresponds) of the cable to use.
5 - According to the cable s diameter, choose the exact cable-gland.
6 - Order the chosen option by its code. Otherwise, detail their characteristics
(cable`s diameter and thread type).

Recommendations for use


1 - Verify that the peeled length of the cable is just what you re needing.
2 - Grease all the threads before assembling.
3 - Be sure that cable is strongly pressed by the corresponding gasket.
4 - In the case of using an armoured cable, select the adjustment ring that better adapts to the armour type of cable s:
- big ring (with external slot) for helical armour of steel tape or wire.
- small ring (without external slot) for helical armour of wire or braid.
5 - Cut the armour in a way that can enclose the shape of the cone.
6 - When using the "e" version with conic threads (NPT) the hole where it will be applied must be adjust
by the corresponding nut.
7 - In the "e" version, the watertightness washer must be placed and adjust so much as it is possible
without deforming it, but bear in mind that it must support and exert a considerable pressure.
8 - Use just the right accesories.

ACCESORIES
Brass nut
NPT Threads
A
H
Turn
Code
Min. Packing (unit)

Dimensions (mm.)
Threads size
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
25.4
31.8
38.1
50.8
57.2
76.2
3.5
3.5
3.5
3.5
5.0
5.0
27.5
34.5
42.0
55.0
62.0
83.0
EXPT 1017 EXPT 2027 EXPT 3037 EXPT 4047 EXPT 5057 EXPT 6067
50
30
20
10
10
10

Weight packaging unit (kg)

Dimensions (mm.)
Threads size
Metric Thread x 1,5
M 20
M 25
M 32
M 40
M 50
M 63
A
25.4
31.8
38.1
50.8
63.5
76.2
H
3.5
3.5
3.5
3.5
5.0
5.0
Turn
27.5
34.5
42.0
55.0
73.2
83.0
Code
EXPT 1M20 EXPT 2M25 EXPT 3M32 EXPT 4M40 EXPT 5M50 EXPT 6M63
50
30
20
10
10
10
Min. Packing (unit)
Weight packaging unit (kg)

Dimensions and weights are approximated.

Order example

EXPT 1 017
1/2" NPT (size and thread type).
1 (Basic size).
Brass nut.
70 - DELGA S.A.

Material
Brass
Nickel brass
Aluminium

Code
std. (*)
LN
AL

(*) std. material not mentioned


On request
On request

w w w. d e l g a . c o m

Earth terminal
Dimensions (mm.)
Thread size
1
2
3
4
5
6
A
21.5
26.5
33.0
43.0
50.0
63.0
B
29.0
34.0
41.0
53.0
62.0
78.0
E
6.0
6.0
7.0
8.0
8.0
8.0
G
12.0
12.0
14.0
16.0
16.0
16.0
Code
EXPM 1 EXPM 2 EXPM 3 EXPM 4 EXPM 5 EXPM 6
50
50
50
1
1
1
Min. Packing (unit)

Metric Thread x 1,5

Weight packaging unit (kg)

Instructions for use

Thickness 0,8 mm of brass plate

Dimensions and weights are approximated.

Order example

EXPM 1
Basic size.
Earth terminal.
Basic size
1

CABLEGLANDS
FOR ARMOURED CABLE
EXPAB 1S017
EXPAB 1M017
EXPAB 1SM20
EXPAB 1MM20
EXPA 2S017
EXPA 2M017
EXPA 2L017
EXPA 2SM20
EXPA 2MM20
EXPA 2LM20
EXPA 2S027
EXPA 2L027
EXPA 2SM25
EXPA 2SM25
EXPA 2MM25
EXPA 2LM25
EXPA 3S027
EXPA 3M027
EXPA 3SM25
EXPA 3MM25
EXPA 3S037
EXPA 3M037
EXPA 3SM32
EXPA 3MM32
EXPA 4S037
EXPA 4M037
EXPA 4L037
EXPA 4SM32
EXPA 4MM32
EXPA 4LM32
EXPA 4S047
EXPA 4M047
EXPA 4L047
EXPA 4SM40
EXPA 4MM40
EXPA 4LM40
EXPA 5S047
EXPA 5M047
EXPA 5L047
EXPA 5SM40
EXPA 5MM40
EXPA 5LM40
EXPA 5S057
EXPA 5M057
EXPA 5L057
EXPA 5SM50
EXPA 5MM50
EXPA 5LM50
EXPA 6S067
EXPA 6M067
EXPA 6L067
EXPA 6SM50
EXPA 6MM50
EXPA 6LM50

ACCESORIES
FOR NON ARMOURED CABLE
EXPNB 1S017
EXPNB 1M017
EXPNB 1SM20
EXPNB 1MM20
EXPN 2S017
EXPN 2M017
EXPN 2L017
EXPN 2SM20
EXPN 2MM20
EXPN 2LM20
EXPN 2S027
EXPN 2L027
EXPN 2SM25
EXPN 2SM25
EXPN 2MM25
EXPN 2LM25
EXPN 3S027
EXPN 3M027
EXPN 3SM25
EXPN 3MM25
EXPN 3S037
EXPN 3M037
EXPN 3SM32
EXPN 3MM32
EXPN 4S037
EXPN 4M037
EXPN 4L037
EXPN 4SM32
EXPN 4MM32
EXPN 4LM32
EXPN 4S047
EXPN 4M047
EXPN 4L047
EXPN 4SM40
EXPN 4MM40
EXPN 4LM40
EXPN 5S047
EXPN 5M047
EXPN 5L047
EXPN 5SM40
EXPN 5MM40
EXPN 5LM40
EXPN 5S057
EXPN 5M057
EXPN 5L057
EXPN 5SM50
EXPN 5MM50
EXPN 5LM50
EXPN 6S067
EXPN 6M067
EXPN 6L067
EXPN 6SM50
EXPN 6MM50
EXPN 6LM50

BRASS NUT

BRASS TERMINALS

EXPT 1017
EXPT 1M20
EXPM 1

EXPT 1017

EXPT 1M20

EXPT 2027

EXPT 2M25

EXPM 2

EXPT 2027
EXPT 2M25
EXPT 3037
EXPT 3M32
EXPM 3

EXPT 3037

EXPT 3M32

EXPT 4047

EXPT 4M40
EXPM 4
EXPT 4047

EXPT 4M40

EXPT 5057
EXPM 5
EXPT 5M50

EXPT 6067
EXPM 6
EXPT 5M50

CERTIFICATIONS
EXPA / EXPN Series - IEC 79.1
Area classification

Certifying entity

Certificate Number

Ex d IIC / Ex e II

INTI CITEI

INTI-CITEI 2004D217 + Extens. 2004D217/1

Ex d IIC / Ex e II

INTI CITEI

2002D131 + Extens. 2002D131/2

EXPA / EXPN Series - IEC DIP 21


Area classification
Ex DIP A 21

Certifying entity
INTI CITEI

Certificate Number
INTI-CITEI 2005DIP258

Observations
IP 65

DELGA S.A. - 71

Anda mungkin juga menyukai