TEMPERATURE INSTRUMENTS (FILLED SYSTEM)


ITEM N

QUANTITY

OFF

SHEET

PROJECT REFERENCE
N

SPECIFICATION REFERENCES
I.S.A S
PDVSAK

GENERAL 1.

Tag N
Function

Record

Indicate

Control

4.

Mounting

Flush

Surface

Yoke

5.

Enclosure

Safe area

Classified

Class

DATE

T1

110 V 60 Hz

24 Volts d.c.

Circular

9. Scale Range

T2

Range

Temp. Switch

Group

Div.

Intr. safe

Temp. Class

7. Chart

Trans

Ex. proof

Weatherproof

Power Supply

REVISED

Service

2.

6.

By

OF

STD

T3

T4

Spring

DriveElec
2

T6

Speed

XMTR

10. Transmitter

420 mA

Other

CONTR

11. Control Modes

12. Automan

MFR.STD switch

13. Set Point Adj.

Manual

Remote

14. Output

420 mA

21103 kPa (315 psig)

17. Fill

SAMA Class

18. Process Data

Temp.: Min.

315 psig
PI

T5

Reversible Action

Other

PID

Manual Regulator

Other

ELEMENT

19. Range

To

Max.

Max. Press

Overrange

Protection to

20. Bulb

Type

Mtl.

Extension: Length

21. Capillary
22. Thermowell

Length
Mtl.

Mtl.
Insertion

Armor
Lag. Ext.

Const:

Drilled

Process Conn.

ALARMS 23. Switches

Function on meas.

OPTIONS 24. Options

FiltReg.

MFR

Full compensation

High and low

No. of alarms

Type

Form: DPDT /amp. @ 24 v.d.c.

Charts

26. Model N

Notes: 1. All items shall be corrosion resistant to marine atmosphere and tropicalised.
2. Alarm contact shall be normally closed and open on alarm condition

20.11a

PDVSA
ITEM N

QUANTITY

TEMPERATURE INSTRUMENTS (FILLED SYSTEM)


OFF

SPECIFICATION REFERENCES
I.S.A S
PDVSAK

Item
N5

Tag. N5

SHEET

PROJECT REFERENCE

Range

Thermowell
Process Conn.

Insertion
Length

Lagging
Ext.

By

OF
REVISED

Capillary
Length

DATE

Notes

Notes:

20.11b

ENGINEERING SPECIFICATION

PDVSA

INSTRUCTIONS TO FILL FORMS


20.11A AND 20.11B

PDVSA doc.20.11
REVISION

DATE

AUG.94

Page
Men Principal

Indice manual

Indice volumen

Indice norma

TEMPERATURE INSTRUMENTS (FILLED SYSTEMS)


1. To be used for a single item. Use secondary sheet for multiple listing.
2. Check as many as apply.
3. Nominal size refers to approximate front of case dimensions; width x height.
4. Yoke refers to a bracket designed for mounting the instrument on a pipe stand.
5. Enclosure class refers to composite instrument. If electrical contacts are in the
case, they must meet this classification inherently or by reason of enclosure.
Use NEMA identification or ISA identification RP8.1.
6. Specify electrical power to the entire instrument from an external source.
7. Specify chart size, range and number applicable.
8. Chart drive mechanism assumed to be synchronous motor operating in 117V
60 Hz and suitable for ENCLOSURE CLASS specified on line 5. If the chart
drive is pneumatic so state identify pneumatic pulser under options. Note
deviations from standard (MFR) under notes i.e., dual speed or special speeds.
9. The scale type may be SEGMENTAL VERTICAL, HORIZONTAL, DIAL
(CIRCULAR) or other. Ranges 1, 2, 3 and 4 are used for multiple inputs. The
first listed (No. 1) is assumed to be the controller input, if a controller is used.
10. Specify transmitter output if applicable.
11. See explanation of terminology given on specification sheet. For further
definition refer to American National Standard C85.11963, Terminology for
Automatic Control. Specific ranges of control modes can be listed after
OTHER, if, required.
12. For multiple items specify on second sheet.
13. If standard automanual switching is not known or not adequate, specify
particular requirements, such as BUMPLESS, PROCEDURELESS,
4POSITION, or as required.
14. Remote set point adjustement assumes full adjustment range. Specify limits
required.
15. Specify if applicable.
16. Specify if applicable.
17. Filled thermal systems can be of the following SAMA classification:

ENGINEERING SPECIFICATION

PDVSA

INSTRUCTIONS TO FILL FORMS


20.11A AND 20.11B

PDVSA doc.20.11
REVISION

DATE

AUG.94

Page
Men Principal

Class 1A:
Class IB:
Class IIA:
Class IIB:
Class IIC:
Class IIIA:
Class IIIB:
Class VA:
Class B:

Indice manual

Indice volumen

Indice norma

Liquid filled, uniform scale, fully compensated.


Liquid filled, uniform scale, case compensated only.
Vapor pressure, nonlinear scale with measured temperature
above case and tubing temperature.
Vapor pressure, nonlinear scale with measured temperature
below case and tubing temperautre.
Vapor pressure, nonlinear scale with measured temperature
above and below case and tubing temperature.
Gas filled, uniform scale, fully compensated.
Gas filled, uniform scale, case compensated only.
Mercury filled, uniform scale, fully compensated.
Mercury filled, uniform scale, case compensated only.

18. Range refers to process input span for which an output is desired.
Adjustable range means that the unit can give its normal output over a
range of inputs.
19. Bulb type can be plain, averaging, rigid, adjustable union connections, fixed
union connection. Capillary extension length can be rigid or flexible, etc.
20. Capillary tube specifications.
21. Well specifications.
22. Form may be SPST, SPDT, DPDT, etc. Rating is electrical rating of switch
in volt amps.
23. Check if alarm is to be actuated by measured variable or by deviation from
controller set piont. Give contact action if single throw from.