Anda di halaman 1dari 8

APPENDIX C

INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIRED EQUIPMENT

C.1.0 General. Appendix C governs the installation, DRAFT REGULATOR, BAROMETRIC – A device
testing, or repair of oil or liquid fuel burners, oil-or built into a fuel-burning appliance or made part of a
liquid-fuel burning systems, oil-or liquid-fuel- chimney connector or vent connector that functions
burning equipment, and the oil-or-liquid fuel piping to reduce excessive draft through an appliance to a
systems used in connection with buildings or desired value by admitting ambient air into the
structures and equipment within the property lines appliance chimney, chimney connector, vent, or vent
of the premises. connector.
FUEL – Natural, manufactured, or liquefied
Definitions. petroleum gas, or a mixture of these gases; all grades
of fuel oil; wood; or any other combustible or
flammable material or any mixture of combustible or
ANTI-FLOODING DEVICE – A primary safety flammable materials.
control that causes the flow of oil or fuel to be shut
FUEL BURNER – A device used to convey the
off after a rise in oil or fuel level, or after receiving
appropriate fuel into the combustion chamber zone
excess oil or fuel, and that operates before the
in close proximity to its primary and secondary air
hazardous discharge of oil or fuel can occur. supply to permit a stable controlled heat release
BURNER, AUTOMATICALLY IGNITED – A burner compatible with the burner design, listing, and
equipped so that main burner fuel may be turned on applicable approvals in a boiler, furnace, device or
and ignited automatically. appliance. It includes, but is not limited to, burning
BURNER, MANUALLY IGNITED – A burner oil or liquid fuel.
equipped so that main burner fuel is turned on only FUEL BURNER SYSTEM – The fuel burner and any
by hand and ignited under supervision. conveyance system or piping system for the purpose
BURNER, MECHANICAL DRAFT TYPE – A burner of introducing the appropriate fuel into the
combustion chamber zone.
that includes a power-driven fan, blower, or other
mechanism as the primary means for supplying the FUEL-BURNING EQUIPMENT/APPLIANCE – An
air for combustion. oil or fuel burner of any type including all oil or
liquid fuel burners, oil, or liquid-fuel-fired-units,
BURNER, NATURAL DRAFT TYPE – A burner that
dual, or multifuel burners and heating and cooking
depends primarily on the natural draft created in the appliances with their fuel burner system and with
chimney or venting system to induce air required for their tank or fuel storage system, piping system, vent
combustion into the burner. connectors, vent flues, fans, blowers, valves, control
CONSTANT LEVEL VALVE – A device for devices, combustion air, wiring, controls, and related
maintaining within a reservoir a constant level of oil devices including all accessories and appurtenances
or fuel for delivery to a burner. for safe and proper operation of the appliance.
CONTROL LIMIT – An automatic safety control that FUEL OIL – Any hydrocarbon oil as specified by
is responsive to changes in fluid flow or level, ASTM D396, or the Canadian Government
pressure, or temperature, and that is normally set Specification Board, 3-GP-28, and having a
beyond the operating range for limiting the flashpoint of not less than 100°F (38°C).
operation of the controlled equipment by shutting FUEL-PIPING SYSTEM – Any method of conveying
off the energy supply. liquid, vapor, steam, gases, or slurry from one point
CONTROL SAFETY – Automatic interlock controls, to another, including accessories, appurtenances,
including relays, switches, and other auxiliary and equipment necessary for its proper operation.
equipment used in conjunction with them, to form a INDIRECT-FIRED APPLIANCE – An oil- or fuel-
safety control system that is intended to prevent burning appliance in which products of combustion
unsafe operation of the controlled equipment. (flue gasses) are not mixed in the appliance with the
DRAFT BOOSTER – A power-operated fan, blower, air or other medium being heated.
or other device installed in the chimney connector to LABELED – Having attached a label, symbol, or
increase the natural draft developed in the other identifying mark of an organization acceptable
connected chimney. to the Building Official and concerned with product

329
C.1.0 – C.6.0 UNIFORM MECHANICAL CODE

evaluation that maintains periodic inspection of C.3.0 Approval of Equipment. Oil-or liquid-fuel-
production of labeled equipment or materials and by burning equipment must be approved.
whose labeling the manufacturer indicates
compliance with appropriate standards or C.4.0 Placing Equipment in Operation. After
performance in a specified manner. completion of all installations, the installer shall test
PREMIXING – A power burner in which all or nearly all safety and operating controls and venting before
all of the air for combustion is mixed with the gas as placing the burner in service. The correct input of
primary air. liquid fuel must be determined and the fuel-to-air
PUMP, OIL OR FUEL TRANSFER – An oil or fuel ratio set. Each oil or liquid fuel burner must be
pump, automatically or manually operated, that adjusted to its proper input according to the
transfers oil or fuel through continuous piping from manufacturer's instructions. Overrating the burners
a supply tank to an oil or fuel-burning appliance or or the appliance is prohibited. The input range must
to an auxiliary tank, and that is not designed to stop be appropriate to the appliance.
pumping automatically in case of total breakage of (1) For conversion burners installed in hot
the oil or fuel supply line between the pump and the water (liquid) boilers or warm-air furnaces,
appliance. the rate of flow of the oil or liquid fuel in
TANK, AUXILIARY – A tank having a capacity of btu/h must be adjusted to within plus or
not over sixty (60) gallons listed for installation in the minus 5 percent of the design load, not to
supply piping between a burner and its main fuel exceed the design rate of the appliance.
supply tank. It may be included as an integral part of (2) For conversion burners installed in steam
an automatic pump or a transfer pump, or it may be boilers, the oil or liquid fuel hourly input
a separate tank. demand must be adjusted to meet the steam
TANK, GRAVITY – A supply tank from which the oil load requirements. The oil or liquid fuel
or fuel is delivered directly to the burner by gravity. input demand necessitated by an oversized
TANK, INTEGRAL – A tank that is furnished by the boiler must be established and added to
manufacturer as an integral part of an oil- or fuel- total input demand.
burning appliance.
TANK STORAGE – A separate tank that is not C.5.0 Pilot Operation. Igniter or pilot flames
connected to the oil- or fuel-burning appliance. must be effective to ignite the oil or liquid fuel at the
TANK SUPPLY – A separate tank connected directly main burner or burners and must be adequately
or by a pump to the oil- or fuel-burning appliance. protected from drafts. Pilot flames must not become
TANK, VACUUM OR BAROMETRIC – A tank not extinguished during the pilot cycle when the main
exceeding five (5) gallons capacity that maintains a burner or burners are turned on or off in a normal
definite level of oil or fuel in a sump or similar manner either manually or by automatic controls.
receptacle by barometric feed. Fuel is delivered from
the sump to the burner by gravity.
C.6.0 Burner Operation. In making tests to
VALVE, MANUAL OIL, GAS, OR FUEL SHUTOFF determine compliance with the requirements of this
– A manually operated valve in a fuel line for the section, care must be exercised to prevent the
purpose of turning on or completely shutting off the accumulation of unburned liquid fuel in the
fuel supply to the burner. appliance that might result in an explosion or fire.
VALVE, OIL, GAS, OR FUEL CONTROL – An (1) The flames from the burner must freely
automatically or manually operated device ignite the liquid fuel when operating at the
consisting essentially of a fuel valve for controlling lowest firing position.
the fuel supply to a burner.
(2) Burner flames must not flash back when the
liquid fuel is turned on or off by an
C.2.0 Standards and Accepted Practices. The automatic control mechanism.
installation, testing, and repair of oil- or liquid-fuel-
(3) Main burner flames must ignite freely from
burning equipment systems must comply with this
the pilot when the pilot flame is reduced to
section, the appropriate standards listed in Chapter
a minimum point that will actuate the pilot
17, and other information outlined in the UMC such
safety device.
as, but not limited to, combustion air, flue and
breeching requirements, room clearances and (4) When ignition is made in a normal manner,
dimensions, and control requirements. the flame will not flash outside the appliance.

330
INSTALLATION AND TESTING OF OIL (LIQUID) C.6.0 – C.7.0
FUEL- FIRED EQUIPMENT
(5) Burners must not expel liquid fuel through (d) Carbon dioxide concentration between
air openings when operating at prevailing 8 percent and 13 percent.
pressure. (e) Oxygen concentration between 4 percent
(6) Burners must have a proper liquid fuel air and 10 percent.
mixture to ensure smooth ignition of the (f) Smoke test no higher than #2 for light
main burner.
oils, or #4 for oils heavier than #4.
(g) Draft must be in accordance with
C.7.0 Method of Test. the burner manufacturer's specifications.
(1) The flue gas, venting, safety, and operating Note:
controls of the appliance must be checked
Induced draft- and fan-assisted types of
by the installer to ensure their proper and
safe operation. appliances may require a sample be taken after
the induced-draft fan that may cause oxygen
(2) Method of test – atmospheric, induced draft,
figures in excess of the limits stated. In such
or fan assisted types.
cases, safe liquid fuel combustion ratios must be
The appliance must be allowed to operate maintained and be consistent with approvals and
until the stack temperature becomes listings of the appliance.
stabilized, after which a sample of the
undiluted flue products must be taken from
the appliance flue outlet. The sample taken (5) Method of test––power type
must be analyzed for carbon monoxide, The appliance must be allowed to operate
carbon dioxide, and oxygen. Stack until the stack temperature becomes
temperature must be noted. stabilized; after that, a sample of the
Note: undiluted flue products must be taken from
Appliance designs incorporating induced-draft the appliance flue outlet. The sample must
assemblies may require a flue gas sample to be taken be analyzed for carbon monoxide, carbon
ahead of the draft regulator or induced draft fan. dioxide, and oxygen. Stack temperature
(3) Performance standards for atmospheric must be noted.
type must meet: (6) Performance standards for power type
(a) Minimum of 75 percent efficiency as (a) Minimum of 80 percent efficiency as
determined by flue gas analysis method determined by flue gas analysis method
at appliance flue outlet. at the appliance flue outlet.
(b) Carbon monoxide concentration in flue (b) Carbon monoxide concentration in the
gas not greater than 0.04 percent. flue gas not greater than 0.04 percent.
(c) Stack temperature not greater than (c) Stack temperature not greater than
700°F (371°C), plus ambient. 700°F (371°C) plus ambient.
(d) Carbon dioxide concentration between (d) Carbon dioxide concentration between
8 percent and 13 percent. 8 percent and 13 percent.
(e) Oxygen concentration between 4 percent (e) Oxygen concentration between 4 percent
and 10 percent. and 10 percent.
(f) Smoke test no higher than #2 for light (f) Smoke test no higher than #2 for light
oils or #4 for oils heavier than #4. oils or #4 for oils heavier than #4.
(g) Draft must be in accordance with the
(g) Draft must be in accordance with the
burner manufacturer's specifications.
burner manufacturer's specifications.
(4) Performance standards for induced-draft or
(7) After completion of the test of newly
fan-assisted types:
installed oil- or liquid-fuel-burner equipment
(a) Minimum of 75 percent efficiency, as as provided in this section, the installer shall
determined by flue gas analysis method file with the Authority Having Jurisdiction
at appliance flue outlet. complete records of the test on a form
(b) Carbon monoxide concentration in flue approved by the Authority Having Jurisdiction.
gas not greater than 0.04 percent. The tag stating the date of the test and the
(c) Stack temperature not greater than name of the installer must be attached to the
700°F (371°C), plus ambient appliance at the main valve.

331
C.7.0 – C.9.0 UNIFORM MECHANICAL CODE

(8) (a) The concentration of oxygen in the (11) The complete control diagram of the
undiluted flue products of oil or liquid- installation and suitable operating
fuel burners must in no case be less than 3 instructions must be supplied and posted by
percent nor more than 10 percent and shall the installer of the appliance.
be in conformance with applicable
performance standards and shall be
consistent with the listing and approval of C.8.0 (Reserved)
the equipment.
(b) The allowable limit of carbon monoxide C.9.0 Special Requirements Based on Btu/h
must not exceed 0.04 percent. Input.
(c) The flue gas temperature of an oil (A) Zero to 400,000 Btu/h per burner (0 to 2.8
appliance, as taken on the appliance gallons per hour):
side of the draft regulator, must not exceed
(1) One (1) approved manual shutoff valve
applicable performance standards and
shall be consistent with the listing and lever handle.
approvals of the equipment. (2) One (1) approved fuel oil filter, installed
(9) The oxygen figures may not apply when on the supply piping.
there is an approved oxygen trim system on (3) Approved automatic safety shutoff
the burner that is designed for that use, valve to provide 100 percent shutoff of
including a low oxygen interlock when all oil.
approved by the Authority Having Jurisdiction. (4) A flame safeguard control capable of
(10) (a) Supervised startup may be required to providing 100 percent shutoff in the
verify the safe operation of an oil or liquid- fuel event of flame failure. Flame failure
burner and to provide documentation that response timing shall not exceed the
operation is consistent with this code, control manufacturer's specifications.
listing, and approval. Supervised startup
(5) Two (2) controls, one operating and one
shall be required for all liquid fuel burners
in categories 9(B), 9(C), and 9(D). high limit, activated by temperature or
Supervised startup requires that the liquid pressure, as appropriate.
fuel burner must be tested in the presence of (6) All burners relying on mechanical
the mechanical official in a manner set forth means to provide air for combustion must
by the Authority Having Jurisdiction before have actual proof-of-air interlock
the installation is approved. Testing must device.
include safety and operating controls, input, (7) Installations with dampered com-
flue gas analysis, and venting. Flue gas must bustion air openings must prove
be tested at high, medium, and low fires. damper open position before trial for
Provisions must be made in the system to burner ignition.
allow a firing test in warm weather. After
completion of the test of newly installed oil- (8) Vent dampers and flue dampers must
or liquid-fuel burner equipment, as be properly interlocked to prevent
provided in this section, the installer shall burner ignition unless safely open.
file with the Authority Having Jurisdiction (B) 400,001 to 999,999 Btu/h per burner
complete records of the test on a form (more than 2.8 to 7.0 gallons per hour)
approved by the Authority Having (1) One (1) approved manual shutoff valve
Jurisdiction. The tag stating the date of the
lever handle.
test and the name of the tester must be
attached to the appliance at the main valve. (2) One (1) approved fuel-oil filter, installed
on the supply piping.
(b) Oil and liquid fuel burners of 1,000,000
Btu/h input or more require a (3) Two (2) safety shutoff valves in series,
supervised startup as in 10(A). maximum five seconds closing time.
(c) Installation of oxygen trim systems, (4) One (1) electronic flame safeguard pilot
modulating dampers, or other draft control providing a separately
control or combustion devices require a supervised and proven pilot, 100
supervised startup as in 10(A). percent shutoff manual reset. Flame
(d) All direct-fired heaters require a failure response time shall not exceed
supervised startup as in 10(A). the control manufacturer's specifications.

332
INSTALLATION AND TESTING OF OIL (LIQUID) C.9.0
FUEL- FIRED EQUIPMENT
Direct-spark ignition is allowed only reset lockout, 100 percent shutoff (both
when approved by the Authority pilot and main burner), and a separately
Having Jurisdiction and then only when supervised and proven pilot.
used on number 2 or lighter oil. Note:
(5) Two (2) controls, one operating and one Flame-sensing systems utilizing a UV scanner must
high limit, activated by temperature or prove pilot and interrupt ignition spark prior to
pressure, as appropriate. main burner valves being energized.
(6) All burners relying on mechanical (5) Two (2) controls, one operating and one
means to provide air for combustion high limit, activated by temperature or
must have actual proof-of-air interlock pressure, as appropriate.
device.
(6) All burners relying on mechanical
(7) Power burners must include proven means to provide air for combustion
prepurge of at least sixty (60) seconds at must have actual proof-of-air interlock
high-fire damper settings. This prepurge device.
must occur before every burner cycle,
regard- less of reason. (7) Power burners must include proven
prepurge of at least sixty (60) seconds at
(8) Installations with dampered combustion
high fire damper settings. This
air openings must prove damper open
prepurge must occur before every
position before trial for burner ignition.
burner cycle, regardless of reason.
(9) Vent dampers and flue dampers must
(8) Installations with dampered
be properly interlocked to prevent
combustion air openings must prove
burner ignition unless safely open.
damper open position before trial for
(10) One (1) high-oil or liquid-fuel pressure burner ignition.
interlock, reset from flame safeguard or
manually. (9) Vent dampers and flue dampers must
be properly interlocked to prevent
(11) If hot water or steam, one (1) low water burner ignition unless safely open.
cutoff.
(10) One (1) high-oil or liquid-fuel pressure
(12) An atomizing medium proving switch.
interlock, reset from flame safeguard or
(13) A low-oil-temperature switch for oil or manually.
liquid fuel requiring preheating.
(11) If hot water or steam, two (2) low water
(14) A high-oil-temperature interlock for oil cutoffs.
or liquid fuel requiring preheating.
(12) An atomizing medium proving switch.
(15) The burner oil pump must
automatically not operate or rotate (13) A low-oil-temperature switch for oil or
while the alternate fuel is firing. liquid fuel requiring preheating.
(16) A pressure-relief valve must be (14) A high-oil-temperature interlock for oil
provided between safety shutoff valves or liquid fuel requiring preheating.
and between pump and safety valves if (15) The burner oil pump must auto-
an integral valve is used with a pump. matically not operate or rotate while the
(17) A separate relief device is required on alternate fuel is firing.
each transfer pump. (16) A pressure-relief valve must be
(C) 1,000,000 to 2,499,999 Btu/h input per burner provided between safety shutoff valves
(more than 7.0 to 17.5 gallons per hour) and between pump and safety valves if
(1) One (1) approved manual shutoff an integral valve is used with a pump.
valve lever handle. (17) A separate relief device is required
(2) One (1) approved fuel oil filter, on each transfer pump.
installed on the supply piping. (18) One (1) low-oil or liquid-fuel pressure
(3) Two (2) safety shutoff valves in series interlock, reset from flame safeguard or
with a combined flame failure response manually.
and valve closing time not to exceed five (19) Burners with automatic controls,
(5) seconds with strainer directly before prepurge, proof-of-closure, modulation,
the valves. or postpurge shall not use relays
(4) Programmed electronic flame safeguard external to the flame safeguard to
including proven low fire start, manual accomplish these functions.

333
C.9.0 UNIFORM MECHANICAL CODE

(D) 2,500,000 to 12,499,999 Btu/h per burner (16) The burner oil pump must
(17.5 to 87.5 gallons per hour) automatically not operate or rotate
(1) One (1) approved manual shut-off valve while the alternate fuel is firing.
lever handle. (17) A pressure-relief valve must be
(2) One (1) approved fuel oil filter, provided between safety shutoff valves
installed on the supply piping. and between pump and safety valves if
an integral valve is used with a pump.
(3) Two (2) safety shutoff valves in
series, with a combined flame (18) A separate relief device is required on
failure response and valve closing each transfer pump.
time not to exceed five (5) seconds (19) One (1) low-oil or liquid-fuel pressure
with strainer directly before the interlock reset from flame safeguard or
valves. manually.
(4) Programmed electronic flame (20) Burners with automatic controls,
safeguard including proven low prepurge, proof-of-closure, modulation,
fire start, manual reset lockout, 100 or postpurge shall not use relays
percent shutoff (both pilot and main external to the flame safeguard to
burner), and a separately supervised and accomplish these functions.
proven pilot. (E) 12,500,000 and greater Btu/h per burner
Note: inputs – these burners must conform with
Flame-sensing systems utilizing a UV scanner must the requirements of the appropriate
standards listed in Chapter 17 and the
prove pilot and interrupt ignition spark prior to
following (greater than 87.5 gallons per
main burner valves being energized.
hour):
(5) Two (2) controls, one (1) operating and
(1) One (1) approved manual shut-off
one (1) high limit, activated by
valve lever handle.
temperature or pressure, as appropriate.
(2) One (1) approved fuel oil filter,
(6) All burners relying on mechanical
installed on the supply piping.
means to provide air for combustion
must have actual proof-of-air interlock (3) Two safety shutoff valves in series, one
device. with proof of closure, with a combined
flame failure response and valve closing
(7) Power burners must include proven
time not to exceed two (2) seconds with
prepurge of at least sixty (60) seconds at
strainer directly before the valves.
high fire damper settings. This
prepurge must occur before every burner (4) Programmed electronic flame safeguard
cycle, regardless of reason. including proven low fire start, manual
reset lockout, 100 percent shutoff (both
(8) Installations with dampered com-
pilot and main burner), and a separately
bustion air openings must prove
supervised and proven pilot.
damper open position before trial for
burner ignition. Note:
(9) Vent dampers and flue dampers must Flame-sensing systems utilizing a UV scanner must
be properly interlocked to prevent prove pilot and interrupt ignition spark prior to
burner ignition unless safely open. main burner valves being energized.
(10) One (1) high oil or liquid fuel pressure (5) Two (2) controls, one (1) operating and
interlock, reset from flame safeguard or one (1) high limit, activated by
manually. temperature or pressure, as appropriate.
(11) If hot water or steam, two (2) low water (6) All burners relying on mechanical
cutoffs. means to provide air for combustion
must have actual proof-of-air interlock
(12) An atomizing medium proving switch. device.
(13) A low-oil-temperature switch for oil or (7) Power burners must include proven
liquid fuel requiring preheating. prepurge of at least sixty (60) seconds at
(14) A high-oil-temperature interlock for oil high fire damper settings. This
or liquid fuel requiring preheating. prepurge must occur before every
(15) A separate firing rate control valve. burner cycle, regardless of reason.

334
INSTALLATION AND TESTING OF OIL (LIQUID) C.9.0
FUEL- FIRED EQUIPMENT
(8) Installations with dampered com-
bustion air openings must prove
damper open position before trial for
burner ignition.
(9) Vent dampers and flue dampers must
be properly interlocked to prevent
burner ignition unless safely open.
(10) One (1) high-oil or liquid-fuel pressure
interlock; reset from flame safeguard or
manually.
(11) A manual firing cock.
(12) If hot water or steam, two (2) low water
cut-offs.
(13) An atomizing medium proving switch.
(14) A low-oil-temperature switch for oil or
liquid fuel requiring preheating.
(15) A high-oil-temperature interlock for oil
or liquid fuel requiring pre-heating.
(16) A separate firing rate control valve.
(17) The burner oil pump must automatically
not operate or rotate while the alternate
fuel is firing.
(18) A pressure-relief valve must be
provided between safety shutoff valves
and between pump and safety valves if
an integral valve is used with a pump.
(19) A separate relief device is required on
each transfer pump.
(20) One (1) low-oil or liquid-fuel pressure
interlock, reset from flame safeguard or
manually.
(21) Burners with automatic controls,
prepurge, proof-of-closure, modulation,
or postpurge shall not use relays
external to the flame safeguard to
accomplish these functions.
(F) Shutoff Valve. All oil or liquid-fuel burner
installations must include a non-electric
shutoff valve that is held open by a fusible
link designed to close at 165°F (79°C),
installed near the burner in the same room
as the burner. This must prevent the flow of
oil or liquid fuel to the burner through the
supply pipe. A check valve is required in the
return line if the tank is higher than the
burner.

335
UNIFORM MECHANICAL CODE

336

Anda mungkin juga menyukai