com/search/label/Electric%20Light%20and
%20Power
http://yourelectrichome.blogspot.com/
Parallel Operation of Two Alternators
We have seen that in case of interconnected systems at power stations number
of alternators are operation in parallel. In fact the electricity demand of a country is
fed by many alternators operating in parallel. There are various advantages of
operating the alternators in parallel. Some of them are listed below.
i) For a given capacity of a generating station, either a single large unit or many
small units may be installed. If there are many small units operating in parallel
instead of single large unit then number of alternators operating at a time can be
changed depending upon electricity requirements or load demands. This will help in
operating the alternator near its full load capacity so that the efficiency will also be
better. Therefore operating cost will be significantly reduced compared to a single
large unit.
ii) A particular unit may be shut down for certain period during the maintenance and
inspection at the power stations. For that period the load can be transferred to other
units if number of units are operating in parallel.
iii) Several power stations are interconnected by a grid which is economical and
advantageous. This will make sure the optimum utility of the alternators.
iv) The continuity and reliability of the supply can be maintained at better level due
to interconnections.
The interconnection of alternators i.e. the process of synchronization is already
discussed in previous sections. Now we will consider how the two alternators will
operate in parallel. What will happen if the driving torque or the excitation or the
excitation for any of the alternator is changed. In practice it is rare to have two
alternators operating in parallel. But the concept of parallel operation of alternators
can be will understood by considering two alternators in parallel.
Consider two identical alternators connected in parallel as shown in the Fig. 1.
Here cylindrical rotor alternators are assumed for simplicity, but the results
obtained are equally applicable to both salient to both salient and nonsalient
machines.
The terminal voltage V is given by,
The maximum power occurs at = 90o . Beyond this point the machine falls
out of step and loses synchronism. The machine can be taken up to P i max only by
gradually increasing the load. This is known as the steady state stability limit of the
machine. The is normally operated at much less than 90o.
Sycnhronizing Current
After proper synchronization of the alternators, they will run in synchronism. A
synchronizing torque will be developed if any of the alternator drops out of
synchronism and will bring it back to the synchronism.
Consider the two alternators shown in the Fig. 1 which are in exact
synchronism. Due to this they are having same terminal p.d. and with reference to
their local circuit they are in exact phase opposition. So there will not be any
circulating current in the local circuit. The e.m.f. E 1 of alternator 1 is in exact phase
opposition to that of alternator E2 .
Fig. 1
With respect to external load, the e.m.f.s of the two alternators are in the same
direction although they are in phase opposition with reference to local circuit. There
will be no resultant voltage in the local circuit.
Now assume that speed of alternator 2 is changed such that its e.m.f. E 2 falls by
an angle . But E1 and E2 are equal in magnitude. The resultant voltage in this case
will cause a current in the local circuit which is called synchronizing current. This
circulating current is given by,
ISY = Er /Zs
where
The phase angle of ISY is given by an angle which can be computed as tan =
Xs/Ra where Xs is synchronous reactance and R a is armature resistance. This angle is
almost 90o.
Fig. 2
Thus ISY lags Er by almost 90o and approximately in phase with E 1. This current is
generating current with respect to alternator 1 since it is in the same direction as
that of e.m.f. of alternator 1 while it will be motoring current for alternator 2 as it is
in the opposite direction as that of e.m.f. of alternator 2. This current I SY will produce
a synchronizing torque which will try to retard alternator 1 whereas accelerate the
alternator 2.
The power output of alternator 1 supplies power input to alternator 2 and
copper losses in the local path formed by armatures of two alternators.
Power output of alternator 1 = E1 ISY cos1
This power is approximately equal to E 1 ISY as 1 is small and is almost in phase
with E1. This power is called synchronizing power. Similarly power input to alternator
2 is E2 ISY cos2 which is equal to E2 ISY as 2 is also small.
E1 ISY = E2 ISY + Cu losses in the local circuit
Let
E1 = E2 = E
Let the magnitude of resultant e.m.f. be Er which is given by,
Er = 2 E (/2) = E
The electrical angle is expressed in radians.
If Ra is not assumed as negligible then will not be so the above expression can
be written in exact form as,
The above expression is valid for two alternators connected in parallel and
operating at no load.
Now let us consider the case of alternator connected to infinite bus bar (the
concept of infinite bus bar is explained later) then the above expression for
synchronizing power is still valid with the changes of reactance of only one
alternators.
...
Er = E
If Ra is neglected,
Now assuming that E2 has advanced in phase shown in the Fig. 2(b). The
synchronizing current ISY in this case will be generating current for machine 2 and
motoring current for machine 1. This will again produce a torque which will try to
accelerate alternator 1 and try to retard alternator 2.
Note : Hence if synchronism between the two machines is lost then synchronizing
current will flow in the local circuit which will produce a synchronizing torque.
This torque will tend to accelerate the lagging machine while will try to retard
the leading machine. In case of machines which are loaded this current is
superimposed on the load current
Synchronization by Sycnhronscope
It can be seen that the previous method is not accurate since it requires correct
sense of judgement of the operator. Hence to avoid the personal judgement, the
machines are synchronized by accurate device known as synchroscope.
It consists of a rotating pointer which indicates the exact moment of closing the
synchronizing switch. If the pointer rotates in anticlockwise direction, it indicates
that incoming machine is running slow whereas clockwise rotation of pointer
indicates that incoming machine is running faster. The rotation of pointer is
proportional to the difference in the two frequencies. The pointer should rotate at a
very low speed in the direction of arrow marked fast as shown in the Fig. 1.
Fig. 1
When the rotating pointer reaches the vertical position at slow speed, the
switch must be closed. The pointer will oscillate about some mean position instead
of rotating if difference in frequencies is large. In such cases the speed of incoming
machine is adjusted properly.
The connections for synchroscope are shown in Fig. 1. Any two bus bars lines
are connected to its terminals while its other terminals are connected to
corresponding lines of incoming machine. The phase sequence from bus bars and
from machine must be same. It can be checked with the help of phase sequence
indicator. The voltmeter is used to check the equality of voltage of bus bars and
incoming machine. The synchronization procedure is already explained before.
Note : The use of lamps and synchroscope together is a best method of
synchronization.
Now a days automatic synchronizing devices are also available which will
perform the entire process of synchronization automatically without the help of shift
engineer. But such schemes are more complicated and may take larger time than
required by a shift engineer.
Fig. 1
The voltages on primary and secondary sides can be represented on the phasor
diagram as shown in the Fig.2.
Fig. 2
Fig. 3
Now
...
Vph2 /Vph1 = K
Vph2 = K Vph1 = K (VL1/3)
Since secondary is connected in delta.
Vph2 = VL2
VL2 = K (VL1/3) = ( K/3) VL1
The primary side is star connected. Hence fewer number of turns are
required. This makes the connection economical for large high voltage step
down power transformers.
2.
3.
Solid Grounding
In this method of earthing, natural is directly connected to earth by a metallic
connection or a wire of negligible resistance and reactance. The charging currents
flows through the system under normal condition similar to ungrounded system.
Because of the connection of system neutral point to earth, it always remains
at earth potential at all operating conditions and under faulty conditions voltage of
healthy phase will not exceed.
The solid grounding us represented in the Fig. 1.
Whenever there is earth fault on any one phase (phase B in this case), the
phase to earth voltage of faulty phase is zero while voltage to earth of the
remaining two healthy phases will be normal phase voltages as neutral in this case
is not shifted. The phasor diagram corresponding to this condition is shown in the
Fig. 2.
Let the capacitive currents flowing in the healthy phases be I R and IY. the
resultant capacitive current is vector sum of I R and IY. The alternator in addition to
capacitive current also provides the fault current. This current flows from fault point
through faulty phase and then return to the alternator through earth and neutral
connection. The resistance of earth fault is negligible. The magnitude of fault
current after the analysis is given by,
i) Due to high value pf fault currents, the system may become unstable and there
will be greater interference to neighbouring circuits. Thus this method is employed
where system impedance is sufficiently large to limit fault current.
ii) With high values of fault currents, circuit breakers are difficult to handle and
heavy contacts are to be provided in the circuit breakers.
The above disadvantages can be overcome by employing high rupturing
capacity and high speed circuit breakers along with fast operating relays.
This method is used in high voltage systems with voltages below 33 kV with
total capacity not exceeding 5000 KVA for the economic reasons.
Reactance Earthing
In this system, instead of resistance, a reactance is connected between neutral
and earth with ratio of reactance more than 3. The system is represented in the Fig.
1. Let the earth fault occurring on phase B.
Fig. 1
In addition to zero sequence impedance of the source and faulty phase upto
point of fault, the fault current is dependent on reactance. By changing the value of
reactance, the fault current can be varied. In practice this method is employed to
give characteristics similar to solidly earth system.
There is drawback of this system. With increase in reactance, there is increase
in transient voltages resulting from arcing. Hence it is not commonly employed
Earthing Transformer
When the transformers or generators are delta connected or if the neutral
points are not accessible then artificially the neutral earthing point can be created
with the use of star connected earthing transformer. Such transformer has no
secondary. Each phase of primary has two equal parts. There are three limbs and
each limb has two windings providing opposite flux during normal condition. Such a
transformer is shown in the Fig.1.
Fig. 1
One set of windings are connected in star providing the neutral point. The other
ends of this set of windings are connected to the second set of windings as shown in
the Fig. 1. The directions of the currents in the two windings on each limb are
opposite to each other. The small exciting current is circulated in the windings
during normal operation. Under faulty condition, the transformer offers a low
impedance path to the flow of zero phase sequence currents. The value of fault
current is limited in some cases by the use of a resistor in series with the neutral
earthing connection. This is necessary in systems with operating voltage between
2.2 KV and 3.3 KV.
The transformers are of short time ratings in the range of 10 seconds to 1
minute. Hence the size of these transformers is small as compared to power
transformers of small rating. If the earthing transformer is not available then a stardelta transformer is used.
type of soil, moisture content, dissolved salt etc. It is also affected by grain size and
its distribution. The temperature and pressure are the other factors which have
influence on soil resistivity.
In practice it is not possible to have homogeneous soil. The apparent resistivity
is hence defined for an equivalent homogeneous soil.
The moisture content in the soil is also a variable factor which changes with
sensors. With increase in moisture content, resistivity of soil reduces. To overcome
this difficulty, the grounding systems may be installed near to the permanent water
level so that the change in resistivity due to change in seasons is minimized.
With decrease in temperature, the soil resistivity increases and the
discontinuity is observed at freezing point. The quantity of salt dissolved in the
moisture reduces the resistivity appreciably. Various salts have different effects on
the soil resistivity. With finer graining, the resistivity of soil reduces while the large
value of pressure decreases soil resistivity.
The variation of soil resistivity with moisture and salt content is shown in the
Fig. 1(a) and (b).
Fig 2
The total resistance in this case can be divided into three parts which are viz.
i) resistance of conductor ii) contact resistance between the surface of electrode
and main body of earth which is negligible iii) resistance of body of earth
surrounding the electrode which is the main part.
Let I be the current dissipated by the electrode. This current spreads out
radically in the earth. At a distance x from the centre of hemispherical the current
density is given by,
The line integral of the field strength e from the surface of sphere of radius R to
the distance x gives the voltage V.
The variation of e, V and i with respect to distance x is shown in the Fig. 2(b).
The voltage between the hemispherical electrode and a point at infinity i.e. x = is
given by,
Total flow of current from the electrode in the outward direction is,
Suppose C is the capacitance of the single electrode with the return electrode
at infinity then R is the resistance of earth for single electrode.
Where C is the electrostatic capacity of the electrode along with its image
above the surface of the earth. The combined electrode is considered as in air.
For the cylindrical rod with hemisphere and the above expression becomes,
From the expression for resistance of driven rods, it can be seen that, the
earthing resistance is inversely proportional to length l .
Generally resistance of single rod is not sufficient. Hence number of rods are
connected in parallel. It is necessary to minimize the overlap among the areas of
influence of the rods. This is possible by keeping large distance between the rods. It
is difficult to achieve this in practice and approximate method is used.
In this method, a rod is replaced by hemispherical electrode having same
resistance. If n rods are connected in parallel then their resistance is greater than
(1/n) of that of a single driven rod due to the mutual screening.
The screening coefficient for n electrodes in parallel is defined as,
Grounding Grids
The low ground resistance in case of high voltage substations can be obtained
with the use of interconnected ground grids. In a typical grounding grid system, a
number of interconnected bare soild copper conductors are buried at a depth of 0.3
to 0.6 m and spaced in a grid pattern. It provides common earth for all devices and
metallic structures in the substation.
At each of the junction point, the conductors are bonded together. This system
is usually suported by a number of vertical rods about 3 m long at some joints.
If a is cross-sectional area of copper, in circular miles, t is the fault duration in
seconds, Tm is the maximum allowable temperature and T a is the ambient
temperature then the size of grid conductors required which prevents fusing under
the fault current is given as,
If the grid depth is less than 0.25 m then the earthing resistance of the grid is
given by,
The effective grounding of the equipment is possible through the grid. Also the
voltage gradient at the surface of the earth can be controlled at safe value for
human contacts with the addition of ground rods, the ground resistance further
reduces when soil resistivity in the upper layer is more than the soil underneath.
Under the fault condition, the potential of earth and its gradient over the
surface out from the electrode is dependent on the ground resistance. The systems
with higher values for maximum ground fault current, it is not possible to have
lower values for ground resistance so as to have rise in grounding system potential
to safe value.
The practical solution for grounding at substation yards is through grid or mat.
The grid consists of a number of meshes and connected to several earth electrodes
driven at intervals.
The total number of electrodes required is determined by using the expression.
Number of electrodes = Maximum Fault Current/ 500
The grounding resistance for a grounding grid or mat is calculated from the
following expression,
Where IF is fault current in amperes while t is time in seconds for the operation
of protective relays including circuit breaker tripping time. C is a constant. Its value
is 70 for steel having temperature rise of 400oC while for copper with temperature
rise of 300oC, its value is 165.
The minimum size required for proper mechanical strength in case of steel is 61
mm . for copper it is 107.2 mm2 while in case of aluminium it is 195 mm2.
2
In case of grounding conductors made up of steel, its size should be checked for
corrosion. If the soil is moderately or severely corrosive then the steel strip of
minimum thickness 6 mm and minimum cross section area should be 200 mm 2.
The earthing grid system is normally extended over the total substation yard
and in few cases, several meters beyond it. The grounding conductors should have
low impedance. They should be able to carry prospetcive fault current without
getting fused or damaged. They must take account the future expansion of
connected power system.
Fig. 2
Fig. 3
Now two supplies are supplying lamp pairs, E RYB i.e. voltage supply of bus bar
while ER'Y'B' i.e. supply generated by alternator B. The switch S 3 is still open.
Let the three bus bar voltages be represented by phasors OR, OY, OB rotating
at angular speed of 1 rad/s. The incoming alternator voltage are represented by
phasors OR', OY', OB' rotating at angular speed of 2 rad/s.
The phasor ERR', joining the tips R and R' is voltage across lamp pair L1.
Similarly EYB , and EBY, are voltages across lamps L2 and L3 respectively.
If there is difference between the two frequencies due to difference in speeds of
the twp alternators, the lamps will become dark and bright in a sequence. This
Fig. 4