Division 04 Masonry
ODAC
GENERAL SPECIFICATIONS
FOR
BUILDING CONSTRUCTION
DIVISION 04 : MASONRY
1
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Foreword
General Requirements
Division 02:
Site work
Division 03:
Concrete
Division 04:
Masonry
Division 05:
Metals
Division 06:
Division 07:
Division 08:
Division 09:
Finishes
Division 14:
Conveying Systems
Division 15:
Mechanical
Division 16:
Electrical
Each Division comprises a number of related Sections. For example: Division 08 includes eight sections.
They are:
08100
08200
08300
Special Doors
08400
08500
Metal Windows
08600
08700
Hardware
08800
Glazing
General: This is mainly concerned with the references, quality control, submittals, programs,
and maintenance.
2
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
Part 2:
ODAC
Products: This gives a breakdown of material used in addition to their properties and place of
installation.
Part 3:
Execution: The most significant items in this Part are the execution and installation of the works,
field quality control, as well as cleaning and protection methods.
Part 4:
Methods of Measurement: This indicates the measurement units and the measuring methods
that shall be used for the Bills of Quantities.
Part 5:
Basis of Payment: This indicates the work that shall be completed for each item of the Bills of
Quantities. It also indicates the ancillary works to be included in the unit rate.
Part 6:
3
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
DIVISION 04
MASONRY
INDEX
Division 01: General Requirements
4
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Unit Masonry
5
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Division
04 - Masonry
Section
Part 1: General
1 01 Summary
The work covered by this Section consists of providing all plant, labor and materials
and performing all operations in connection with Masonry Work.
These requirements shall apply to brick-, block- and stonework, methods of fixing
walls, wall ties, anchors, damp-proof courses and joints.
1 01 01
1 01 04
Section includes
01.0
02.0
03.0
04.0
05.0
06.0
07.0
08.0
09.0
10.0
Components
Accessories
Refractory Masonry
Chemical Resistant Masonry
Simulated masonry
Mortar and Masonry Grout
Masonry Restoration and Cleaning
Related Sections
02500 Paving and Surfacing
03200 Concrete Reinforcement
03300 Cast-In-Place Concrete
05810 Expansion Joint Cover Assemblies
07150 Dampproofing
07200 Insulation
07900 Joint Sealers
09300 Tile
09400 Terrazzo and Natural Stone Flooring
1 02 References
1 02 01
Applicable Standards
1 02 01 03
International Standards
1 02 01 04
USA Standards
1 02 01 04 01
ASTM C 62: 97
1
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
ASTM C 73: 97
ASTM C 90: 97
ASTM C 91: 96
ASTM C 141: 96
ASTM C 150: 97
ASTM C 216: 97
ASTM C 315: 96
ASTM C 952: 91
E1-1993 R (1993)
ASTM C1142: 95 Standard Specification for Extended Life Mortar for Unit Masonry
ASTM D1056: 98 Standard Specification for Flexible Cellular Materials - Sponge
or Expanded Rubber
ASTM D1667: 97 Standard Specification for Flexible Cellular Materials - Vinyl
Chloride Polymers and Copolymers (Closed Cell Foam)
ASTM D1751: 83 Standard Specification for Preformed Expansion Joint Filler for
Concrete Paving and Structural Construction (Nonextruding and
Resilient Bituminous Types)
ASTM D1752: 84 Standard Specification for Preformed Sponge Rubber and Cork
Expansion Joint Fillers for Concrete Paving and Structural
Construction
ASTM E 119: 95 Standard Test Methods for Fire Tests of Building
Construction and Materials
ASTM E 447 : 97 Standard Test Methods for Compressive Strength of Laboratory
Constructed Masonry Prisms.
1 02 01 04 02
2
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ACI 530.1: 95
1 02 01 05
ODAC
Section: 04200 Unit Masonry
European Standards
DIN EN 771
DIN EN 771-1: 92
DIN EN 771-2: 92
DIN EN 771-3: 92
DIN EN 771-4: 92
DIN EN 771-5: 92
DIN EN 771-6: 92
BS EN 772
BS EN 772-2: 98
BS EN 772-3: 98
BS EN 772-7: 98
BS EN 772-9: 98
1 02 01 06
British Standards
BS 12: 96
BS 146: 96
Portland Cement
Portland Blast furnace Cements
BS
BS
BS
BS
BS
187: 78
493: 95
743: 70
882: 92
890: 95
BS 1014: 75
BS 1181: 89
BS 1200: 76
BS 1217: 97
BS 1243: 78
BS 3056
BS 3921: 85
BS 4027: 96
BS 4721: 81
BS 4729: 90
BS 4887
BS 4887-1: 86
BS 4887-2: 87
BS 5224: 95
BS 5642
BS 5642-1: 78
3
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
1 02 01 07
BS 6398: 83
BS 6477: 92
BS 6515: 84
BS 6649: 85
BS 8000
German Standards
DIN 105
DIN 105-1: 89
DIN 105-2: 89
DIN 105-3: 84
DIN 105-4: 84
DIN 105-5: 84
Clay bricks
Solid bricks and vertically perforated bricks
Lightweight vertically perforated bricks
High strength bricks and high strength engineering bricks
Ceramic engineering bricks
Lightweight horizontally perforated bricks and
lightweight horizontally perforated brick panels
DIN 106
Sandlime bricks and blocks
DIN 106-1: 89 Solid bricks, perforated bricks, solid blocks, hollow blocks
DIN 106-2 : 80 Facing bricks and hard-burnt facing bricks
DIN 1053
Masonry
DIN 1053-1: 96 Design and Construction
DIN 1053-2: 96 Masonry Strength classes on the basis of suitability tests
DIN 1053-3: 90 Reinforced masonry, design and construction
DIN 1053-4: 78 Building of Prefabricated Brickwork Components
DIN 4243: 79
Hollow glass blocks; requirements and testing
1 02 02
Codes
ACI 530: 95
ASCE 5: 92
1 02 03
ENV 1996: 95
BS 5390: 76
BS 5628
BS 5628-1: 92
BS 5628-2: 95
BS 5628-3: 85
BS 8000-3: 89
BS 8215: 91
Other References
01.0 Masonry Designers Guide based on Building Code Requirements for Masonry
Structures (ACI 530:92) and Specifications for Masonry Structures (ACI
530.1:92).
02.0 Standard Method of Measurement (SMM) issued by the British 'Royal
Institution of Chartered Surveyors and the National British Federation of Building
Trade Employers'
03.0 Civil Engineering Standard Method of Measurement issued by the Institution of
Civil Engineers (Thomas Telford, London 1985)
04.0 NCMA TEK 45 issued by: National Concrete Masonry Association (NCMA)
Herndon, VA 22071-3406 (USA)
4
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
05.0 ILI Handbook issued by: Indiana Limestone Institute of America, Inc. (ILIA)
Bedford, IN 47421 (USA)
1 03 Definitions
1 03 01
Technical Terms
For technical terms and definitions not listed below see: BS 6100: Part 5 Masonry.
Actual dimension - see: work size.
Additions - finely ground substances (e. g. pozzolana or pigments for producing
colored mortar) added to modify certain properties of the mortar, the volumes of
which are to be taken into account when designing the mix.
additives - this term is sometimes used for additions.
admixtures - substances added to the mortar and which, by chemical or physical
action or by both, modify such properties of the mortar as its workability, hardening,
setting, etc. They are added in negligible quantities.
autoclaving - steam curing at high pressure.
bed joint mortar layer upon which masonry units are set
block - a masonry unit exceeding the length or width or height specified for bricks.
brick - a masonry unit with defined nominal dimensions acc. to the relevant
standard.
brick earth - a mixture of clay and shale particularly suitable for brick or block
making
cast stone - cast stone is manufactured from cement and natural aggregate for
use in a manner similar to, and for the same purpose as, natural stone
cellular - unit with a defined volume of holes as per relevant standard which do
not
effectively pass through the unit.
characteristic strength of masonry the value of the strength of masonry below,
which the probability of test results falling is not more than 5 %.
closer - portion of a masonry unit used to maintain masonry bond, either specially
manufactured or cut.
collar joint continuous vertical joint parallel to the face of the wall
common brick - a brick, which is suitable for general building work but which, has
no special claim to give an attractive appearance.
compressive strength - the average value of the crushing strength of a specified
number of masonry units.
coping - unit or assemblage placed at the head of a wall and designed to shed
rainwater from the top of the wall clear of all exposed faces of the walling it is
intended to protect.
co-ordinating size - the size of a co-ordinating space to a masonry unit,
including allowances for joints and tolerances.
cross joint joint, other than a bed joint, at right angles to the face of a wall
facing brick - bricks, which are specially made or selected to give an attractive
appearance when, used without rendering or plaster or other surface treatment of
the wall.
fixing unit - a masonry unit of the same dimensions as a brick, which permits the
easy driving of, and provides a good purchase for nails or screws.
5
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
1 03 02
Bill of Quantities
Quality Control
1 04 System Description
1 04 01 01
General
The design shall be in accordance with:
01.1
Masonry Designers Guide based on Building Code
Requirements for Masonry Structures and Specifications for
Masonry Structures (ACI 530.1:92)
01.2
1 05 Submittals
In compliance with conditions of contract and provisions of section 01300, the
following shall be submitted within forty five (45) days before masonry works to
commence
6
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
1 05 01
ODAC
Section: 04200 Unit Masonry
Product Data
The product data for each different masonry unit, accessory and other
manufactured product indicated.
1 05 02
Shop Drawings
Shop drawings shall include :
01.0 complete layout and sections of unit masonry.
02.0 bending and placement of masonry reinforcing bars.
03.0 trim units, copings, fixing units and the like.
04.0 all accessories embedded in the masonry.
1 05 03
Samples
Unless otherwise approved, sample panels shall not be part of the finished
construction but shall be retained at the job site until all work has been accepted.
01.0
02.
1 05 04
01.2
02.2
weep holes/vents
02.3
02.0
03.0
04.0
05.0
06.0
07.0
1 05 05 02
1 05 05 02 01
7
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
1 05 06
ODAC
Section: 04200 Unit Masonry
Other Submittals
01.0
02.0
1 06 Quality Assurance
Sampling, testing and checking shall be recorded on a daily basis
(i.e. indicating day, month, year) including corrective actions taken by the
Contractor if necessary.
Reports and records shall be available for assessment to the Engineer not later
than three (3) days after testing and checking.
Reports and records shall be established in a manner to ensure traceability
between records, test results and locations of placed masonry units.
Arrangements shall be made in Contractors work schedule and time allowed for
testing and checking as indicated.
The Contractor shall permit and facilitate access of the Engineers representatives
to the construction site and assist the performance of all activities for quality
assurance.
1 06 01
Qualifications
Site supervisor shall have knowledge of referenced standards and at least
five (5) years of documented experience in masonry works. He shall have had
successfully completed masonry works similar in material, design, and extent to
that work indicated for the Project .
Masons shall be familiar with all materials and installation procedures and shall be
skilled and trained.
1 06 03
Certifications
Certificates of Compliance issued by an independent agency/laboratory (approved
by the Engineer), and not more than 12 months old, indicating that any material
proposed by the Contractor meets or exceeds the requirements of the referenced
standards, shall be submitted by the Contractor prior to execution of any work, in
particular for masonry units, grout, mortar and accessories.
1 06 04
Quality Control
1 06 04 01
8
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
1 06 04 02
ODAC
Section: 04200 Unit Masonry
1 06 04 03
1 07 02
Environmental Requirements
01.0
Dust Control
Dust caused by contractors operations on and near
work shall be controlled by use of all means necessary.
02.0
Pollution Prevention
Necessary precautions shall be taken to prevent
pollution of ground with fuel, oil, chemicals or other
harmful materials.
9
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Part 2: Products
2 01 Manufactured Unit Masonry
2 01 01
Clay Units
Clay units shall be made of clay, shale or loam with brick earth, subsequently made
durable by firing to high temperatures. The density may be reduced by additives.
Clay units shall be tested in accordance with SASO 184.
2 01 01 01
Clay Bricks
The permissible variations in dimensions of individual units shall not exceed the
actual dimension by more than +/-3 % unless otherwise stated.
Bricks shall be regularly shaped units with flat, level and true faces.
Dimensions and other properties shall be as indicated in the Project B.o.Q.
Following supplementary standard(s) shall apply:
01.1 DIN EN 771-1
01.2 BS 3921, 4729, and 6649
01.3 DIN 105
01.4 ASTM C34, C56, C62, C126, C212 and C216
2 01 01 02
Clay Blocks
The permissible variations in dimensions of individual units shall not exceed the
specified dimension by more than +/-4 % unless otherwise stated.
Blocks shall be regularly shaped units with flat, level and true faces.
Dimensions shall be as indicated in the Project B.o.Q.
Following supplementary standard(s) shall apply:
01.1 DIN EN 771-1
01.2 DIN 105
01.3 ASTM C652
2 01 02
Concrete Units
2 01 02 01
Concrete Bricks
The permissible variations in actual dimensions in the mean shall not exceed:
length: +4, -2 mm, width: -2 mm, height: +/-2 mm, unless otherwise stated.
Bricks shall be regularly shaped units with flat, level and true faces.
Dimensions and other properties shall be as indicated in the Project B.o.Q.
Following supplementary standard(s) shall apply:
01.1 DIN EN 771-3, 771-4
01.2 BS 6073
01.3 ASTM C55
2 01 02 02
Concrete Blocks
The permissible variations in dimensions in the mean shall not exceed +/-4 mm
unless otherwise stated in accordance with the relevant standard.
10
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Blocks generally shall be regularly shaped units with flat, level and true faces.
Dimensions and other properties shall be as indicated in the Project B.o.Q.
Following supplementary standard(s) shall apply:
01.1 DIN EN 771-3, 771-4
01.2 BS 6073
01.3 ASTM C145
2 01 03
2 01 03 01
2 01 03 02
2 02 01
11
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
03.0 metamorphic
04.0 as indicated in the Project B.O.Q. or in the Drawings
2 02 02
2 02 03
Embedded Items
Metal dowels and fixings shall comply with BS 5390 (9.1) and shall be noncorrodible non-ferrous metal and / or stainless steel and / or galvanized steel
2 03 Glass Blocks
Glass blocks shall be of soda-lime silicon and shall comply with DIN 4243.
Glass blocks shall be hermetically sealed.
The permissible variations in dimensions in the mean shall not exceed:
length: +/ -2 mm, unless otherwise stated.
Dimensions and other properties shall be as indicated in the Project B.o.Q.
Thermal resistance value in (m2 * k) / W and maximum allowed sound
transmission shall be as indicated.
The following material specifications and properties shall be as indicated in the
Project B.o.Q.:
01.0
block type
02.0
solar reflection
03.0
transparency
04.0
texture
2 04 Components
2 04 01
Air Bricks
Air bricks shall comply with BS 493, class 1 units: Airbricks for external use.
Air bricks shall be units having apertures to allow for the passage of air and shall
be built into external walls. They shall be, as stated in BS 493, constructed of clay,
concrete, fireclay, terra-cotta, cast iron, copper, aluminum or stainless steel as
indicated.
The strength shall be as indicated and shall be adequate for the location where it is
to be used.
2 04 02
2 04 03
2 04 04
Coping Units
Coping units shall comply with BS 5642 : Part 2.
Coping units shall be made of
01.0
clay
12
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
02.0
precast concrete
03.0
cast stone
04.0
natural stone
05.0
slate
06.0
2 05 Accessories
2 05 01
Joint Reinforcement
Joint reinforcement shall consist of metal rods, hoops or mesh reinforcement
complying with
2 05 02
01.0
ACI 530/530.1
02.0
BS 5628 : Part 2
Anchors
Anchors for masonry and stonework shall be of stainless steel, to sizes, shapes
and thicknesses suitable for the function to be fulfilled.
Anchors shall comply with
2 05 03
01.0
ACI 530/530.1
02.0
BS 5628
Ties
Wall ties shall be manufactured from stainless steel wire or strip of strength and
thickness as indicated and shown in Fig. 2.3 (see Part 6: Annex) unless otherwise
approved by the Engineer.
Wall ties shall comply with
2 05 04
01.0
ACI 530/530.1
02.0
BS 1243
Premoulded closed-cell cellular rubber expansion jointmaterial shall comply with ASTM D 1056.
02.0
03.0
2 06 Refractory Masonry
2 06 01
BS 1181
02.0
ASTM C 315
13
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
2 06 02
ODAC
Section: 04200 Unit Masonry
Fireclay Refractories
Bricks shall be true to form and have sharp edges and shall be free from
deleterious cracks, laminations, cavities and black core.
Fireclay refractories shall comply with
01.0
BS 3056
02.0
ASTM C 315
Acid-resistant Bricks
Bricks shall be true to form and be free from deleterious substances.
Acid-resistant bricks shall comply with ASTM C 279.
2 08 Simulated Masonry
2 08 01
General
Definitions and terms see: BS 6100: Part 5: Section 5.2.
Simulated masonry may be of mineral, epoxy, or fiberglass type.
The ingredients of the stone shall be mixed and poured into moulds in order to
produce the type, the size and face finish as indicated.
2 08 02
Cast Stone
01.0 Cast stone shall comply with
01.1
DIN EN 771-5
01.2
BS 1217
2 08 03
Reconstructed Stone
01.0 Reconstructed stone shall comply with
01.1
DIN EN 771-5
01.2
BS 1217
Mortar
Masonry mortar ingredients shall be of uniform quality and colour to be obtained
from one source or one manufacturer.
Calcium chloride is not allowed in mortar or grout.
Mortar shall be of the type and colour as indicated and shall conform to
01.0
ASTM C 270
14
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
02.0
2 09 01 01
Aggregates
2 09 01 01 01
Natural Aggregates
2 09 01 01 02
Manufactured Aggregates
Manufactured sand shall be graded in accordance with ASTM C 144
2 09 01 01 03
Lightweight Aggregates
Lightweight aggregates shall comply with:
01.0 BS 877 : Part 2
02.0 BS 3797 : Part 2
2 09 01 01 04
2 09 01 02
Binder
2 09 01 02 01
Cement
For cement in general see: Section 03300 Cast-In-Place Concrete.
Cement shall conform to standard(s)
01.0 BS 12
02.0 BS 146
03.0 BS 4027
04.0 BS 5224
05.0 ASTM C 91
06.0 ASTM C 150
2 09 01 02 02
Lime
Lime shall only be used in conjunction with cement. For mix proportions see:
Clause
2 09 01 05 Mixes.
Lime shall comply with
01.0 ASTM C 207 Hydrated lime for masonry purposes
02.0 ASTM C141 Hydraulic hydrated lime for structural purposes
03.0 BS 890
2 09 01 02 03
Epoxy resin
Epoxy resin shall be a proprietary product, to be used strictly in accordance with
the instructions of the manufacturer.
15
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
2 09 01 03
ODAC
Section: 04200 Unit Masonry
Water
Water for mortar mixing shall be potable unless otherwise indicated and approved.
2 09 01 04
2 09 01 04 01
Admixtures
Any mortar with admixtures shall first stand a suitability test and has to be
approved by the Engineer.
2 09 01 04 02
Additions
The additions shall in no way adversely affect the mortar strength or contain
chemicals which may be harmful to other building materials.
It is strictly forbidden to add gypsum to the cement or mortar.
2 09 01 05
Mixes
The basic materials for mortar (aggregates, binder, water, etc.) shall be mixed for
at least three (3) minutes with the minimum amount of water to produce a correctly
mixed workable consistency in a mechanical batch mixer.
Mortar shall be mixed by volume in approved gauge boxes.
For small jobs only, hand mixing shall be permitted on condition of approval by the
Engineer or his Representative.
The mortar strength shall not exceed the strength of the materials to be bond
together.
Mortars shall be mixed in batches which can be used within a period before the
setting process commences. Once a mix begins to go off it shall be discarded, no
ingredients shall be added to it once the setting process begun.
Mortar for refractories or acid-resisting brickwork shall be a type suitable for the
particular application.
2 09 01 05 01
2 09 01 05 02
2 09 01 05 03
16
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
2 09 01 05 04
ODAC
Section: 04200 Unit Masonry
2 09 01 05 05
Colored Mortar
01.0 Colored mortar shall obtain its colour from pigments complying with BS
1014 and the pigments shall not exceed 10 % by weight of the cement in the
mortar.
02.0 The colour shall be approved as part of a mock-up sample.
2 09 01 05 06
Ready-Mixed Mortar
Ready-mixed mortar shall be equivalent to the mortar specified above and shall
only be used with the approval by the Engineer.
Ready-mixed mortar shall comply with
01.0 BS 4721
02.0 ASTM C 1142
2 09 02
Grout
2 09 02 01
General
Masonry grout shall comply with ASTM C476
Masonry Cleaner
Masonry cleaner shall be a job-mixed detergent solution, a job-mixed acidic
solution or a propriatory acidic solution to be proposed by the Contractor subject
to the approval of the Engineer.
2 10 02
Masonry Coating
Water repellent shall comply with BS 6477 and shall be of class as indicated.
17
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Part 3: Execution
3 01 General Examination
3 01 01
Verification Of Conditions
Prior to the start of masonry construction, the Contractor shall verify that
foundations are constructed within the following tolerances:
Actual width or length shall be at the most 10 mm smaller than the specified
dimensions.
Variation in alignment: +/- 5 mm in 3 m.
Variation from specified elevations: +/- 10 mm.
Variation from level or specified slope: +/- 5 mm in 3 m.
The Contractor shall verify that the reinforcing dowels are positioned as specified
in the standards and indicated in the drawings.
In the event the conditions above are not met, the Engineer shall be advised and
remedial directions requested.
3 02 General Preparation
Set out building relative to securely marked or pegged reference lines and datum
levels, check squareness, securely fix datum and profile marks, leave datum
level points in positions so that a gauge rod can be used for coursing other
heights.
Set out starting course anticipating the positions of openings etc. to avoid
unnecessary cutting.
When materials and components are distributed to the work position ensure that
neither construction nor scaffolding is overloaded and that their protection is
maintained to prevent any damage or deterioration before use.
Construction procedure must be planned in advance to ensure the necessary
safety of personnel engaged in formwork and concrete placement and the
integrity of the finished structure.
3 03 Installation
3 03 01
3 03 01 01
18
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
3 03 01 02
3 03 01 02 01
Laying:
Bricks shall be laid on a full bed of mortar and all cross joints and collar joints
should be filled. Immediately after the brick is laid, excess mortar should be
struck off the external face of the work and off the internal face of leaves of cavity
walls.
Solid and cellular blocks shall normally be laid on a full bed of mortar and cross
joints and collar joints should be filled.
All beds of mortar shall be level and straight and vertical joints formed so as to
present a uniform pattern of bond.
Units shall be adjusted in position only while the mortar is still soft and plastic.
Any unit disturbed after mortar has begun to set shall be removed, cleaned and
re-laid with fresh mortar. Damaged units shall not be re-used. No portion of
masonry shall be built up more than 1 m high at a time. Work which is stopped
and later resumed shall not be toothed and bonded together, but the work shall
be racked back in preparation for re-commencement. All masonry to receive
plaster, stucco or any other such applied finish shall have sufficiently roughkeyed surfaces and/or joints.
Exposed masonry shall be of uniform texture and colour or a uniform blend within
the ranges accepted for these characteristics and shall be obtained from one
source or manufacturer. No section of the work shall be constructed with a
mixture of units from differing sources. Batches from the same manufacturer or
source shall be mixed to ensure that no patchiness results from allowable natural
manufacturing variations in colour.
Units erected, when the ambient air has a temperature of more than 42 deg C in
the shade and a relative humidity of less than 50 %, shall be protected from
direct exposure to wind and sun for 48 hours after construction. The absorption
rates of masonry units shall be adjusted by previously wetting to ensure a good
solid bond with the mortar.
3 03 01 02 02
Bonding:
All masonry for half-brick thick walls or single thickness blockwork and stonework
shall be laid in stretcher bond (i.e. the vertical joint between units in one course
shall be offset by at least one-quarter of the length of the unit to the vertical joints
in the course above and below) (see 6: Annex, Fig.1).
Brick walls over a half-brick wide and block walls of more than one block
thickness shall be either tied together with wall ties or bonded to give stability to
the wall.
3 03 01 02 03
Joint Reinforcement:
Joint Reinforcement shall be laid in mortar beds as indicated and shall not be
visible on any exposed face.
3 03 01 02 04
Built-in Items:
Anchors, ties, pipe sleeves, flashings, lintels and the like indicated to be built into
the work shall be inserted and executed as the work proceeds.
Wall ties cast in with concrete shall be bent down after the removal of formwork
and securely jointed into the mortar beds of walling.
3 03 01 02 05
19
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Chases and holes shall be cut neatly and without damaging the walls. The
restrictions
of BS 8000 : Part 3; (3.7.9) shall apply.
3 03 01 02 06
3 03 01 02 07
Damp-Proof Courses:
In general, Section 07150 Dampproofing shall apply:.
Damp-proof course shall be laid on even mortar bed, free from projections which
may puncture the material. Where a damp-proof course is to be stepped only
flexible membranes shall be used.
3 03 01 02 08
Insulation:
In general, Section 07200 Insulation shall apply:
Insulation to be inserted into the cavities or applied to faces of brickwork or
blockwork shall be executed in accordance with the manufacturers instructions.
Where foam insulation is to be inserted into cavities, holes and openings shall be
sealed prior to injection to prevent seepage of the foam.
Loose fill insulation shall be poured into cavities from the top of each wall section
completed, where indicated or directed, and shall be allowed to form its natural
density and shall not be tamped.
3 03 01 02 09
Expansion Joints:
Expansion joints shall be built into walls as indicated.
Structural expansion joints within the building structure shall be carried through
the entire wall thickness.
All faces of units abutting expansion joints shall be square and true and
thoroughly cleaned.
For expansion joint cover see Section 05810and for joint sealers see Section
07900.
3 03 01 03
3 03 01 03 01
Embedded Items
Materials for anchorages, dowels and fixings shall comply with
BS 5628 : Part 3; Section 2.
Unless otherwise directed, joint reinforcement, ties, and anchors - if not made of
stainless steel - shall be galvanized in accordance with ACI 530.1 (3.2.1.4).
3 03 01 04
Tolerances
Masonry shall be erected within the tolerances specified in ACI 530.1 (2.3.3.2)
unless otherwise indicated or directed.
The permissible variation of walls shall not exceed 15 mm above and below the
plumb, and horizontal lines, and the specified dimensions.
Mortar beds and vertical joints shall be 12 mm thick.
20
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
The reinforcement shall be laid to every fourth course or within 500 mm at the
most, with a minimum of 150 mm laps at overlaps and junctions.
Walls or partitions abutting concrete columns or walls shall be securely anchored
and tied with metal anchors or ties at not more than 450 mm vertical centers.
For pointing, masonry joints shall be raked out to a depth of 20 mm and left clean
and ready for pointing.
3 03 01 05
Cavity Walls
Cavity walls shall consist of both an outer and inner skin, each of which may be
either brickwork, blockwork or stone as indicated.
3 03 01 05 01
Weep holes shall be provided as indicated. The cavity side of weep holes shall be covered with cotton or
plastic insect screen cloth before placing any loose fill insulation into cavities (see
6 Annex: Fig. 2.1/2.2).
For damp-proof courses see Section 07150 Dampproofing.
3 03 01 06
Masonry Facings
3 03 01 06 01
3 03 01 07
Curved Walls
Curved walls shall be built as indicated from either rectangular shaped units with
tapering joints or from special curved units with standard thickness joints .
The mortar beds and joints shall be of regular thicknesses to present an even
appearance. The wall shall be well-supported to prevent any movement
especially in arches and the like, prior to setting.
All curved walls shall be built to an even radius with no unit being built out of line.
3 03 01 08
Coping Units
Copings shall be set with faces plumb and true in a full bed of mortar. Upon
completion of the walls the remainder of the bed joint shall be filled solidly with
mortar front and back and the exterior face of the mortar tooled smooth.
21
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
3 03 01 09
ODAC
Section: 04200 Unit Masonry
3 03 01 10
Glass Blockwork
Glass blocks are not intended to carry superimposed loads and are to be built in
panels free of the main structure. They carry their own weight up to 6 m height of
panel and resist lateral pressure if individual panels do not exceed 11 m2 in area.
Panels exceeding 1.8 m in width shall be reinforced with approved gauge
expanded metal strips in every fourth course, the ends being built at least 150
mm into adjoining masonry unless the glass blocks are retained within rebates in
the brickwork. Panels exceeding 6 m in width shall be vertically reinforced unless
otherwise indicated or directed.
Mortar joints shall be 6 mm for external and 5 mm for internal work..
The bottom course of a panel should be bedded in bitumen or similar material to
allow for slight movement, and there should be a clearance of 12 mm on the
other three sides, filled with mastic or fiberglass to allow for expansion.
The jointing and horizontal surfaces shall be coated so as to provide a
satisfactory bond between the glass and the mortar. The recommendations of the
manufacturer shall be observed
3 03 02
3 03 02 01
3 03 02 02
3 03 02 02 01
Laying:
Natural stone units in walls shall be laid on their natural bed . The natural bed is
the plane of stratification in a sedimentary rock. The natural bed of voussoirs
shall be parallel to their mortar joint. The natural bed of cornices shall be vertical.
No angled mitered joints shall be allowed in any part of the work.
All work such as mortises for dowels, cramps and the like shall be performed by
a qualified stonemason and all dowels, cramps and other methods of fixing
correctly inserted, and bedded and grouted into the unit as indicated.
The type of walling shall be as indicated in the Project B.o.Q.
or the Project drawings.
3 03 02 02 02
Bonding
If any bond other than stretcher bond is indicated in the Drawings, the Contractor shall
provide the necessary shop drawings.
3 03 02 02 03
22
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Units used at edges and corners of exposed work shall not detract from the aesthetic
appearance of the wall.
3 03 02 03
3 03 02 03 01
Embedded Items
By all means, the Contractor shall co-ordinate with the stone supplier to avoid the
cutting of holes and chases in stone on Site. Where these are required they
should be cut by an experienced stone mason upon approval by the Engineer.
Fixing of metal with stone shall comply with BS 5390.
3 03 02 04
Tolerances
3 03 02 04 01
Ashlar Walling
Ashlared stone shall be finely square dressed blocks as approved by the Engineer.
The tolerances of the dimensions of the units shall be so as to produce beds and
joints of not greater than 5 mm in thickness.
3 03 02 04 02
Rubble Walling
Refractory Masonry
3 03 03 01
General
During construction of flues with flue linings of proprietary flue blocks or refractory
bricks the following must be observed:
01.0 all joints shall be filled with jointing and caulking
materials in accordance with the manufacturers sitework
instructions.
02.0 at the joints of socketed flue liners, the inner
surface of the lining shall be smooth
03.0 the void between brick chimney and flue liners shall
be filled with lightweight concrete or weak mortar.
04.0 no cracked or broken liner sections and no cut
lengths to form bends shall be used.
3 03 03 02
3 03 03 03
23
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
3 03 04
ODAC
Section: 04200 Unit Masonry
3 03 05
Simulated Masonry
For installation see: 3 03 01 Manufactured Unit Masonry.
3 03 06
3 03 06 01
Mortar
For handling and preparation of mixes see: 2 09 01 05.
For jointing and pointing see: 3 03 01 02 06.
Placing of mortar shall comply with ACI 530.1 (2.3.3.3).
3 03 06 02
Grout
For handling and preparation of mixes see: 2 09 02.
Spaces to be grouted shall be free of mortar dropping, debris, loose aggregates,
and any material deleterious to masonry grout.
Placing of grout shall comply with ACI 530.1 (4.3).
3 03 07
General
Inspection and quality control testing shall conform to the requirements of Clause
1 06 Quality Assurance and ACI 530.1 (1.5).
In addition, the testing agency, designated and approved by the Engineer, will
have specific duties as mentioned under Clauses 3 04 02 and 3 04 03.
3 04 02
Testing Frequency
Tests and evaluations listed below will be performed during construction for each
150 m2 of wall area or as indicated.
3 04 03
Testing Methods
3 04 03 01
3 04 03 02
Mortar Properties
Mortar properties shall be tested according to ASTM C 270.
3 04 03 03
Mortar Composition
Mortar composition shall be tested according to ASTM C 780.
24
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
3 04 03 04
ODAC
Section: 04200 Unit Masonry
3 04 03 05
Adjusting
Remove and replace masonry units that are loose, chipped, broken, stained, or
otherwise damaged or if units do not match adjoining units. Install new units to
match adjoining units and in fresh mortar or grout, point to eliminate evidence of
replacement.
When pointing joints, enlarge any voids or holes, except weep holes, and
completely fill with mortar.
3 05 02
Cleaning
3 05 02 01
General
Masonry shall be free of stains, efflorescence, mortar or grout droppings, and
debris.
After mortar is thoroughly set and cured, clean exposed masonry as follows:
Unless otherwise indicated or directed masonry shall be cleaned with cleaners in
accordance with Clause 2 10 01.
Test cleaning methods on sample wall panel: leave 1/2 panel uncleaned for
comparison purposes. Obtain Engineers approval of sample cleaning before
proceeding with cleaning of masonry.
01.0 Remove large mortar particles by hand with
wooden paddles and non-metallic scrape hoes or
chisels.
02.0 Adjacent stone and non-masonry surfaces shall
be protected from contact with cleaner by covering them
with liquid strippable masking agent, polyethylene film or
waterproof masking tape subject to the approval of the
Engineer.
03.0 Wall surfaces shall be wetted with water prior to
application of cleaners: remove cleaners promptly by
rinsing thoroughly with clear water.
3 05 02 02
Clay Masonry
Clay masonry shall be cleaned by means of bucket and brush hand-cleaning
method. The masonry cleaner: as indicated (see Clause 2 06).
3 05 02 03
Concrete Masonry
Concrete masonry shall be cleaned by means of method indicated in NCMA TEK
45 applicable to type of stain present on exposed surfaces.
3 05 02 04
Glass Masonry
Clean glass unit masonry after mortar has attained final set before it has dried on
block surfaces by use of scrub brush with stiff fiber bristles and damp cloth.
Do not use abrasive cleaners, steel wool or wire brush.
25
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
3 05 02 05
ODAC
Section: 04200 Unit Masonry
Limestone Masonry
Limestone masonry shall be cleaned acc. to the recommendations in ILI
Handbook of Indiana Limestone Institute of America, Inc.
3 07 Protection
Protect the top of newly built brick- and blockwork from rain and at all times when
work is not proceeding.
Care shall be taken in particular with open textured units, that no mortar
encroaches upon the face of the units.
Provide protection and maintain conditions, in a manner acceptable to the
Engineer, to ensure that unit masonry is without damage and deterioration at
time of Preliminary Hand-Over.
26
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
General
The quantities to be paid for will be measured in place or determined from
drawings.
No deductions will be made for openings not exceeding 0.50 m2 of a wall area.
4 02
Units Of Measurement
Walls generally will be measured by area (m2), giving the type and thickness.
Walls are measured on the centre line of the material. No deduction is made for
voids not exceeding 0.10 m2. No deduction is made for lintels, sills, and the like.
Walls built against other constructions will be measured by area (m2) giving the
type and thickness of the wall and nature of the adjoining construction.
2
Isolated piers will be measured by area (m ) giving the type and thickness.
Air bricks or the like and special bricks will be enumerated (no.).
27
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Part 5:
Basis of Payment
5 01
General
Payments will be made for complete work including, but limited to furnishing all
materials, equipment, tools, scaffolding, storage facilities, water, power, labour,
samples and mock-ups, coordinating work with other trades, checking,
examination, testing, quality assurance, cleaning and protecting.
5 02
Sills, lintels, copings, bearing bars, steps, timbers, steel sections and the like, oversealing courses, or the
like
Expansion joints or the like
Mortar for bedding and jointing,
Type of bond and method of pointing,
Raking out joints or leaving rough joints to form key,
Extra materials for curved work,
Building overhand,
Bonding ends of walls to other work including providing ties or other fixings and extra material in bonding,
Reveals, angles and intersections,
Rough and fair cutting,
Grooves, throats, mortices, chases, rebates, holes, stops, miters and the like,
Weather fillets, angle fillets and the like and pointing in flashings including cutting grooves or chases,
Labours in returns, ends and angles,
Building in or cutting and pinning ends of lintels, sills, bearing bars, steps, timbers, steel sections and the
like,
Templates for forming openings and temporary support and protection to built-in frames.
28
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
365
300
240
2
1.4
1.0
Thickness of
load-bearing wall
to be braced
mm
Bracing Wall
Storey height
Spacing
m
Thickness
mm
=< 4.50
=< 3.25
=< 6.00
=< 3.50
=< 8.00
>= 300
=< 5.00
>= 115
29
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
Table 3:
ODAC
Section: 04200 Unit Masonry
Wall
thickness
mm
Wherein:
8 20 m
20 100 m
x = 1.0
x > 2.0
X = 1.0
x > 2.0
x =1.0
x > 2.0
115
12
175
20
14
13
240
36
25
23
16
16
12
>=300
50
33
35
23
25
17
x: is the ratio of the larger to the smaller side of the panel wall area.
At lateral ratios of 1.0 > x > 2.0 the admissible maximum values of the
panel areas can be interpolated in a straight line.
30
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
6 02
ODAC
Section: 04200 Unit Masonry
Figures
31
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
32
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
33
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
34
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
35
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
7 02 Performance Requirements
The system strength requirement for unit masonry and its characteristic
compressive strength shall be indicated if required in accordance with the Project
documents and complying with the related standards.
7 03 Masonry Units
Options and alternatives for detailed material properties - subject to the standards
specified are to be selected and indicated in the Project Specification and /or the
Project B.o.Q
7 03 01
Clay Units
7 03 01 01
Clay bricks
01.0 load bearing class:
Non-load bearing
Load bearing, class...
Facing
36
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
7 03 01 02
Clay Blocks
01.0 load bearing class:
Non-loadbearing
loadbearing, class.........
02.0 minimum mean compressive strength:
2.5 MPa
7.5 MPa
15MPa
03.0 water absorption shall not exceed:
25 %
20 %
17 %
no limit
04.0 clay blocks shall be:
frost resistant
moderately frost resistant
non frost resistant
05.0 soluble salt content:
low (L)
normal (N)
06.0 efflorescence:
nil
slight
moderate
heavy
07.0 block type:
solid
cellular
hollow
frogged
7 03 02
Concrete Units
Dense aggregate concrete units shall be made from a mixture of selected
aggregate and cement and other approved materials in a rigid form under pressure
and/or vibration.
37
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
Lightweight aggregate concrete units shall be made from a mixture with a low
density principal aggregate, e.g. expanded slag, expanded clay or pumice etc., and
cement and other approved materials in a rigid form under pressure and/or
vibration.
Autoclaved aerated concrete units shall be made from a mixture of fine siliceous
aggregate, cement, lime and an appropriate aeration agent and cured in the
autoclaving process.
7 03 02 01
Concrete Bricks
01.0 aggregates shall comply with BS 882 and shall be:
dense
lightweight
autoclaved aerated
02.0 loadbearing class
non-loadbearing
loadbearing, class.........
03.0 minimum mean compressive strength:
3 MPa
7MPa
7.5 MPa
17.3 MPa
24.1 MPa
04.0 water absorption shall not exceed in average:
15 %
no limit
05.0 brick type:
solid
cellular
hollow
perforated
06.0 concrete bricks shall be:
Grade N: for use as architectural veneer and facing units
in exterior
walls; high strength; resistance to moisture penetration;
severe frost action.
Grade S: for general use, moderate strength and
resistance to moisture penetration and frost action.
07.0 The average value of drying shrinkage shall not exceed:
0.06 %
not to be tested
7 03 02 02
Concrete Blocks
01.0 aggregates shall comply with BS 882 and shall be:
dense
lightweight
autoclaved aerated
02.0 loadbearing, class:
non-loadbearing
loadbearing class.........
03.0 minimum mean compressive strength:
2.5 MPa
5 MPa
7.5 MPa
04.0 water absorption shall not exceed in average:
20 %
no limit
38
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
7 03 03
7 03 03 01
7 03 03 02
39
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
is not requested
7 03 04
Glass Blocks
Glass blocks shall not be used externally in areas that are exposed to sand storms
or direct sun.
The thickness of the glass provides significant noise insulation. Therefore the
indication of the sound transmission factor in the Project B.o.Q. is recommended:
The sound transmission shall be in maximum ................................
01.0 block type:
solid
hollow
02.0 solar reflection:
regular
solar reflective
03.0 transparency:
frosted
transparent
translucent
04.0 texture shall be:
clear
weavy
ribbed
crossribbed
squared
7 04 Mortar
Mortar is an artificial stone made from a mixture of binder (cement, lime), fine
aggregate and water, sometimes also containing admixtures and additions.
The mortar designation and type shall be specified taking into account the type of
masonry unit, type of construction, position in the building, degree of exposure.
7 04 01
Grading of Aggregates
7 04 01 01
Natural Aggregates
Table 1:
40
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
7 04 01 02
Table 2:
ODAC
Section: 04200 Unit Masonry
Manufactured Aggregates
Grading for Manufactured Sand according to ASTM C 144.
Sieve size
mm
4.75
2.36
1.18
0.60
0.30
0.15
0.075
7 04 01 03
Sieve size
mm
12.5
9.5
4.75
2.36
1.18
0.60
0.30
7 04 02
ASTM C 404.
Admixtures
Admixtures are used to improve particular properties of the mortar, but there is a risk
that the same admixtures will have an adverse effect on other important properties
like strength and adhesion.
In view of the above mentioned facts, any mortar to include admixtures shall first
undergo a suitability test.
7 04 03
Mixes
Usually, the mix proportion of mortar is specified by volume.
If the mix proportion shall be measured by weight, the figures are different to those
measured by volume and must be indicated,
7 05 Stone Masonry
The choice of natural stone is influenced by the design of the building and its
situation and may involve aesthetic as well as technical considerations.
41
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
7 05 01
ODAC
Section: 04200 Unit Masonry
7 06 Execution
7 06 01
Expansion Joints:
Thermal expansion joints shall be built into walls to allow thermal expansion of
units. The spacing of joints shall be at centers close enough to allow areas to
expand and contract without damage to the units, mortar beds, and joints.
Structural expansion joints within the building structure shall be carried through the
walls to prevent possibility of differential movement.
All faces of units abutting expansion joints shall be square and true and thoroughly
cleaned to ensure a good connection with any materials used for the formation of
the expansion joint. Expansion joints exposed externally shall be faced with a
sealer to ensure a watertight joint:
7 06 02
Cavity Walls
The two skins separated by a cavity shall be tied together with ties or cramps
correctly bedded in the mortar beds and joints at centers to ensure a stable and
rigid structure and ties shall be placed at staggered centers.
All cavity walls shall be solidly closed at jambs and openings to exclude wind and
rain and a damp-proof course shall be built into the closure to form a moisture
barrier.
The cavity must be kept free from mortar droppings, rubbish and other deleterious
matter, which may facilitate the passage of moisture to the inner skin.
Cavity tray damp-proof courses shall be provided with slope towards the outer skin
where lintels or any other solid objects bridge the cavity to direct water away from
the inner skin . In such positions weep holes shall be provided to allow any water
accumulating in the cavity to escape from the building. The cavity side of weep
holes shall be covered with cotton or plastic insect screen cloth before placing any
loose fill insulation in cavities.
7 06 03
42
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Division 04 Masonry
ODAC
Section: 04200 Unit Masonry
If chimneys pass through fire resisting elements then they shall be constructed to
achieve a fire resistance at least equal to the minimum fire resistance required of
the element through which they pass. Also horizontal branches to chimneys
passing through fire resisting elements shall meet the same requirements or shall
incorporate fire dampers at junctions with fire resisting elements, which will seal the
branch in case of fire.
Exit air chimneys shall only be used for achieving ventilation to internal spaces
Exit air chimneys for ventilation purposes shall be constructed from bricks, blocks
or rigid sheet materials and shall be as indicated in the Drawings:
square in section
rectangular in section
circular in section
specially shaped
7 06 04
Refractories
The refractory bricks and blocks used for flue linings are of a special nature and the
manufacturers sitework instructions shall be carefully followed. The Quality of the
workmanship is important, as any such flue will have to function correctly in
containing large quantities of very hot gases.
43
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
F10
F10
ODAC
BRICK/ BLOCK WALLING
TYPES OF WALLING
310
-
350
-
351
-
352
-
AL FATEH UNIVERSITY
F10
380
-
ODAC
BRICK/ BLOCK WALLING
WORKMANSHIP GENERALLY
431
-
440
-
460
-
MORTAR GROUPS
Mix proportions: For a specified group select a mix design from the following:
_________________________________________________________________
Group
1
2
3
4
_________________________________________________________________
PC*:lime:sand with or without air entraining additive
1:0-0.25:3 1:0.5-4.5
1:1:5-6
1:2:8-9
_________________________________________________________________
Masonry cement:sand containing PC* and lime in approx ratio 1:1, and an air
entraining additive
1:3
1:3.5-4
1:4.5
_________________________________________________________________
Masonry cement:sand containing PC* and inorganic materials other than lime
and air entraining additive
1:2.5-3.5
1:4-5
1:5.5-6.5
_________________________________________________________________
PC*:sand and air entraining additive
1:3
1:3-4
1:5-6
1:7-8
_________________________________________________________________
PC* = Portland cement
Batching: Mix proportions by volume.
Mortar type: Continuous throughout any one type of masonry work.
2
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
F10
ODAC
BRICK/ BLOCK WALLING
500
-
LAYING GENERALLY
Mortar joints: Fill vertical joints. Lay bricks, solid and cellular blocks on a full bed.
Bond where not specified: Half lap stretcher.
Vertical joints in facework: Even widths. Plumb at every fifth cross joint.
510
-
OVERHAND LAYING
Must not be used without approval.
520
-
ACCURACY
Courses: Level and true to line.
Faces, angles and features: Plumb.
Permissible deviations:
- Position in plan of any point in
relation to the specified building
reference line and/ or point at
the same level
10 mm.
- Straightness in any 5 m length 5 mm.
- Verticality up to 3 m height
10 mm.
- Verticality up to 7 m height
14 mm.
- Overall thickness of walls
10 mm.
- Level of bed joints up to 5 m
(brick masonry)
11 mm.
- Level of bed joints up to 5 m
(block masonry)
13 mm.
535
540
-
545
580
-
585
-
AL FATEH UNIVERSITY
F10
ODAC
BRICK/ BLOCK WALLING
635
-
JOINTING
Profile: Consistent in appearance.
645
-
665
-
POINTING
Joint preparation: Remove debris. Dampen surface.
Mortar: As section Z21.
671
-
FIRE STOPPING
Avoidance of fire and smoke penetration: Fit tightly between cavity barriers and
masonry. Leave no gaps.
690
-
ADVERSE WEATHER
General: Do not use frozen materials or lay on frozen surfaces.
Air temperature requirements: Do not lay bricks/ blocks:
- In cement gauged mortars when at or below 3C and falling or unless it is at
least 1C and rising.
- In hydraulic lime:sand mortars when at or below 5C and falling or below 3C
and rising.
- In thin joint mortar glue when outside the limits set by the mortar manufacturer.
Temperature of walling during curing: Above freezing until hardened.
Newly erected walling: Protect at all times from:
- Rain and snow.
- Drying out too rapidly in hot conditions and in drying winds.
760
-
APPEARANCE
Brick/ block selection: Do not use units with damaged faces or arrises.
Cut masonry units: Where cut faces or edges are exposed cut with table masonry
saw.
Quality control: Lay masonry units to match relevant reference panels.
- Setting out: To produce satisfactory junctions and joints with built-in elements
and components.
- Coursing: Evenly spaced using gauge rods.
Lifts: Complete in one operation.
780
-
GROUND LEVEL
Commencement of facework: Not less than 150 mm below finished level of
adjoining ground or external works level.
790
-
PUTLOG SCAFFOLDING
Use: Not permitted in facework.
4
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
F10
ODAC
BRICK/ BLOCK WALLING
800
-
TOOTHED BOND
New and existing facework in same plane: Bonded together at every course to
achieve continuity of bond and coursing.
830
-
CLEANLINESS
Facework: Keep clean.
Mortar on facework: Allow to dry before removing with stiff bristled brush.
Removal of marks and stains: Rubbing not permitted.
5
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
F30
F30
ODAC
ACCESSORIES/ SUNDRY ITEMS FOR BRICK/ BLOCK/ STONE WALLING
217
-
241
-
270
-
281
-
310
-
320
-
380
-
415
425
-
HORIZONTAL DPCS
Placement: In continuous lengths on full even bed of fresh mortar, with 100 mm
laps at joints and full laps at angles.
Width: At least full width of leaf unless otherwise specified. Edges of dpc not
covered with mortar or projecting into cavity.
Overlying construction: Immediately cover with full even bed of mortar to recieve
next masonry course.
Overall finished joint thickness: As close to normal as practicable.
GROUND LEVEL DPCS
Joint with damp proof membrane: Continuous and effectively sealed.
1
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
F30
560
-
ODAC
ACCESSORIES/ SUNDRY ITEMS FOR BRICK/ BLOCK/ STONE WALLING
590
-
610
-
615
-
616
-
630
-
650
POINTING IN FLASHINGS
2
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
F30
655
660
-
ODAC
ACCESSORIES/ SUNDRY ITEMS FOR BRICK/ BLOCK/ STONE WALLING
730
-
750
-
830
-
BUILDING IN FRAMES
Preparation: Remove horns and provide support.
Fixing cramps: Fully bed in mortar.
840
-
3
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Z21
Z21
ODAC
MORTARS
MORTARS
To be read in conjunction with General Requirements.
CEMENT GAUGED MORTARS
110
120
-
131
-
160
171
175
WATER FOR MORTAR: Clean and uncontaminated. Obtain approval for other
than mains supply. Test to BS EN 1008:2002 if instructed.
1
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV
AL FATEH UNIVERSITY
Z21
ODAC
MORTARS
180
200
-
210
-
360
-
2
Al LABINA / AL MANAR
in partnership with Hamza/ ECH/ LCE JV