PACiS System Devices

Configuration
PACiS Configuration Training
CS&P Support Team

PCL

Content

 PACiS OI Server Configuration


 PACiS OI Client Configuration
 C264 Configuration
 PACiS Gateway Configuration
 Labels in Datapoint profiles
 Devices Redundancy

Schneider Electric - CS&P System Devices Configuration E01

Content

 PACiS OI Server Configuration


 PACiS OI Client Configuration
 C264 Configuration
 PACiS Gateway Configuration
 Labels in Datapoint profiles
 Devices Redundancy

Schneider Electric - CS&P System Devices Configuration E01

Add / Configure PACiS OI Server


 Under SCS/Ethernet Network
Add from Object Entry window

Note : use OI configured in starting database

 PACiS OI Server Attributes


Follow Good Practice for
addressing
MV computation period
Network name (Never HMI) + IP@
Periodic SQL Historian DB backup
15
5
Good Practice
Schneider Electric - CS&P System Devices Configuration E01

Max number of presence


days for event/value in SQL
Historian database
4

PACiS OI Server Sons


 Basic = System Infos + IEC Mapping

List of System Information :


Operating Mode,
Synchronisation Status, ...
Note : use OI configured in starting
database, all system information are
already configured

IEC 61850 Mapping


Schneider Electric - CS&P System Devices Configuration E01

PACiS OI Server Sons


 Possible sons
Klaxon for audible alarm

Serial Printer
Printer
Sequence of Events / System
Log Book
Printer Name as installed on the
PC (spool name)
for main and backup
Used during ordering
process of dated events

Schneider Electric - CS&P System Devices Configuration E01

Used when main printer breaks down


during starting of backup printer

PACiS OI Server Sons


Klaxon

Klaxon action (immediate/defer) and


acknowledgement (auto/manu).

Klaxon can be executed on one SPC in


one C264 (horn).
If not configured => PACiS OI Server PC
uses the buzzer
Note : Relation warns audibly (gives an audible warning) to determine which
alarms are triggering the klaxon
Note 2 : The SPC must be direct execute, without dependency, without
interlock, with on and off orders possibility.

Schneider Electric - CS&P System Devices Configuration E01

Content

 PACiS OI Server Configuration


 PACiS OI Client Configuration
 C264 Configuration
 PACiS Gateway Configuration
 Labels in Datapoint profiles
 Devices Redundancy

Schneider Electric - CS&P System Devices Configuration E01

Add / Configure PACiS OI Client


 Under SCS/Ethernet Network
Add from Object Entry window

 PACiS OI Client Attributes


Follow Good Practice for
addressing

Network name + IP@


same if installed on same PC as
OI Server

Schneider Electric - CS&P System Devices Configuration E01

PACiS OI Client Sons and Relations


 Basic = System Infos + Relation to OI Server + Relation to graphic part

Link Status :
Status of the Link between OI Client and
OI server

Link to OI Server

Link to graphic part

- all clients are linked with PACiS


OI Server Main or Backup.
- At least 1 OI Client has to be
connected on each OI Server.

the client will show the views


configured under the chosen
workspace

Schneider Electric - CS&P System Devices Configuration E01

10

Content

 PACiS OI Server Configuration


 PACiS OI Client Configuration
 C264 Configuration
 PACiS Gateway Configuration
 Labels in Datapoint profiles
 Devices Redundancy

Schneider Electric - CS&P System Devices Configuration E01

11

Add / Configure MiCOM C264


 Under SCS/Ethernet Network
Add from Object Entry window

Note1 : use C264 configured in starting database


Note2 : create new C264 by copy/paste of existing one

Schneider Electric - CS&P System Devices Configuration E01

12

MiCOM C264 Attributes


 General Tab

Computer Name
80TE=C264 / 40TE=C264C

IRIG-B signal or not


Network name + IP@
Follow Good Practice for
addressing

Schneider Electric - CS&P System Devices Configuration E01

13

MiCOM C264 Attributes


 BI Filtering Tab

Debouncing / Filtering => signal


validation
Toggling parameters
Note : used for SPS, DPS and MPS acquisition on DI board

Debouncing / Filtering => signal


validation
Timetag => t0 or t2 (configurable)

F ilte r in g tim e
D e b o u c in g
tim e
t0

t1

t2

Toggling applied on validated signal

Schneider Electric - CS&P System Devices Configuration E01

14

MiCOM C264 Attributes


 Measurements Tab

Debouncing / Filtering => signal


validation for Digital Measurements
AI board acquisition cycle
CT/VT board acquisition frequency
(neighbourhood of 0)
MV transmission cycle on SBUS and
LHMI
Long period = N x short period
Note 1 : Transmission periods are used if MV is declared as periodic
Note 2 : too small transmission periods values has strong impact on SQL
Historian database filling => default values are too small

Schneider Electric - CS&P System Devices Configuration E01

15

MiCOM C264 Attributes


 Counter Tab

Debouncing / Filtering => signal


validation for counted Digital Input
Note : Applicable for single or double counters

 Miscellaneous Tab

Avoid endless C264 reboot on fault


detection, define a number of faults
acceptable during a period.

Schneider Electric - CS&P System Devices Configuration E01

16

MiCOM C264 Sons


 Basic = System Infos + 3 boards (CPU,BIU,GHU) + IEC Mapping

I/O Boards :
Naming Good Practice :
Slot#_<board type>_<board nb>

IEC 61850 Mapping


Created by Automatic Addressing
function

PLC Object
C264 Automations

Schneider Electric - CS&P System Devices Configuration E01

17

MiCOM C264 Sons


 Basic = System Infos + 3 boards (CPU,BIU,GHU) + IEC Mapping

List of System Information :


Operating Mode,
Synchronisation Status, ...
Note : use C264 configured in starting
database, all system information are
already configured

Schneider Electric - CS&P System Devices Configuration E01

18

MiCOM C264 Sons


 Possible sons = Object Entry Window

Hardware
LBUS per protocol
TBUS
Local C264 printer
 Add / Configure I/O board
Note : another method is to copy/paste existing board

Physical Board Number


Schneider Electric - CS&P System Devices Configuration E01

Relation made by automatic @


(to remove when duplication)

19

Content

 PACiS OI Server Configuration


 PACiS OI Client Configuration
 C264 Configuration
 PACiS Gateway Configuration
 Labels in Datapoint profiles
 Devices Redundancy

Schneider Electric - CS&P System Devices Configuration E01

20

Add / Configure PACiS Gateway


 Under SCS/Ethernet Network
Add from Object Entry window

Note1 : use GTW configured in starting database

 PACiS GTW Attributes

Follow Good Practice for


addressing
Network name + IP@

Schneider Electric - CS&P System Devices Configuration E01

21

PACiS Gateway Sons


 Basic = System Infos + 8 serial ports + IEC Mapping
8 serial communication ports

1 to 4 protocols with the


relevant SCADA mapping

List of System Information :


Operating Mode,
Synchronisation Status, ...

IEC 61850 Mapping


Schneider Electric - CS&P System Devices Configuration E01

Note : use GTW configured in starting


database, all system information are
already configured
22

Content

 PACiS OI Server Configuration


 PACiS OI Client Configuration
 C264 Configuration
 PACiS Gateway Configuration
 Labels in Datapoint profiles
 Devices Redundancy

Schneider Electric - CS&P System Devices Configuration E01

23

System Information Labels in Profiles


 All Devices Operating Mode (OI, C264, GTW) => MPS

Note 1 : TEST Mode N/A for OI and GTW


Note 2 : Useful for graphical animation

 MiCOM C264 Boards status => MPS


Note 1 : Applicable for all kind of boards
Note 2 : Special status
Missing = in configuration not in rack
Too Many = in rack not in configuration
OK Empty = used at SMT only

Schneider Electric - CS&P System Devices Configuration E01

24

System Information Labels in Profiles


 ISaGRAF Status => MPS (under C264/PLC)
Note :
Not Activated = No ISaGRAF configured
Cycle too long = cycle > 2s
Queue Overflow = ISaGRAF overflow

 PACiS OI Printer Status (parallel or LAN) (SOE/SLB) => MPS


Note 2 : N/A for C264 printer
Parallel :

Schneider Electric - CS&P System Devices Configuration E01

LAN :

25

System Information Labels in Profiles


 Central Archive => MPS (under OIS)

 PACiS OI Redundancy Status => MPS (under OIS)

Schneider Electric - CS&P System Devices Configuration E01

26

Content

 PACiS OI Server Configuration


 PACiS OI Client Configuration
 C264 Configuration
 PACiS Gateway Configuration
 Labels in Datapoint profiles
 Devices Redundancy

Schneider Electric - CS&P System Devices Configuration E01

27

Redundant MiCOM C264


 Create Redundant C264
Select C264 and Create Backup

Redundant C264 parameters

Schneider Electric - CS&P System Devices Configuration E01

28

Redundant PACiS OI Server


 Create Redundant OI Server
Select OI Server and Create Backup

Redundant OI Server parameters

Schneider Electric - CS&P System Devices Configuration E01

29

Hot Redundancy in PACiS OI Server


 On PACiS 4.6.0, Hot redundancy principle :
OI Client is connected to preferred OI Server. If server not available
it will immediately try connect to the other one.
Client A

Client B

Client C

Server 1

Server 2

SQL database

SQL database

IEC 61850 Station Bus

Both OI server perform DP acquisition simultaneously. There is a


consolidating mechanism insuring all data are the same on both.

Schneider Electric - CS&P System Devices Configuration E01

30

Hot Redundancy in PACiS OI Server


Each OI server is managing its own system DP. These are not
consolidating because each server is aware of status of the other one.
Master OI can :
- acquire DP from IEC servers.
- be connected to OI Client.
- perform archives (Historian) and manage alarms.
- accept and manage controls from any OI Client (directly
connected to itself or connected to OI Slave).
- print events on SOE printers
Slave OI can :
- acquire DP from IEC servers.
- be connected to OI Client.
- perform archives (Historian) and manage alarms.
- propagate controls from its OI Client (directly connected to
itself) to OI Master which will manage the controls.

Schneider Electric - CS&P System Devices Configuration E01

31

Hot Redundancy in PACiS OI Server


Standalone OI can :
- acquire DP from IEC servers.
- be connected to OI Client.
- perform archives (Historian) and manage alarms.
- accept and manage controls from its OI Client (directly
connected to itself) as the other Standalone OI; but in that case Control
Uniqueness is done at C264 level.
- print events on connected SOE printers
Performances (typical switching time):
OI server failure

OI Client switching time

PC power off

Less than 20s

Application stop

Less than 20s

Ethernet disconnection

Less than 60s

Schneider Electric - CS&P System Devices Configuration E01

32

Hot Redundancy in PACiS OI Server


Both OI are connected on Ethernet and visible.

OI Master shuts down then restarts

Server 1

Server 2

Server 1

Server 2

START-UP

START-UP

MASTER

SLAVE

STANDALONE

WAIT

MASTER

PC halted
GOING TO
STANDALONE

SLAVE

STANDALONE
PC start-up
START-UP

SLAVE

MASTER

OI is proceeding consolidating messages before


going to Standalone.

Schneider Electric - CS&P System Devices Configuration E01

33

Hot Redundancy in PACiS OI Server


One OI is not connected and reconnects.

One OI is not connected and reconnects.


Server 1

Server 2

START-UP

START-UP

STANDALONE

STANDALONE

Server 2

Server 1
START-UP

START-UP

STANDALONE

STANDALONE

Ethernet connexion
Ethernet connexion

Case 2 : OI server 2 with less OI clients connected than OI server 1 (means


that the number of OI clients connected is exchanged between OI servers)

Case 1 : no OI client connected on OI server 1

SHUTDOWN
SHUTDOWN

START-UP
START-UP

MASTER
SLAVE

SLAVE

MASTER

Schneider Electric - CS&P System Devices Configuration E01

34

Hot Redundancy in PACiS OI Server


 Fault Tolerance automation : principle of MASTER/SLAVE election
1.
2.

The 1st server that starts is MASTER


In case of Ethernet reconnection, the criteria for MASTER election
are, from highest priority to lowest :
a. There is a control in progress on one server
b. The quantity of connected clients
c. The first one configured in SCE

The client connection to preferred server principle and the


MASTER/SLAVE election have no correlation

Schneider Electric - CS&P System Devices Configuration E01

35

Hot Redundancy in PACiS OI Server


 SQL consolidation
Objective : ensure both OI servers Historian database are in line
How :
At SQL level only
Every 2 minutes (based on clock time : 8h00, 8h02, 8h04, ) :

Compare both databases

Fix discrepancies (if any)

Tag every consolidated event

Next consolidation starts from 1st event not tagged

Schneider Electric - CS&P System Devices Configuration E01

36

Hot Redundancy in PACiS OI Server


 On PACiS 4.6.0, Hot redundancy configuration :
1. Preferred server of OI Client is chosen using relation Has for HMI
server
2. Good Practice is to select at least 1 OI Client per OI Server.
3. Files servers.dat are automatically created by SCE during
generation. There is no need to manually install it after DB switch.

Schneider Electric - CS&P System Devices Configuration E01

37

Buffered Reports for PACiS OI Server


 Buffered reports is used to retrieve max 1000 events stored in C264 in
case of C264 disconnection from OI Server (PACiS GTW DOES NOT
support buffered reports)
 Add relation under SCS : Has for buffered report client : <OI server>
 Functionality can be tested on OI event viewer (printer is depending on
its own buffer)
A Buffer overflow DP is reached in that case.

Schneider Electric - CS&P System Devices Configuration E01

38