PCL
Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
GENERIC INFORMATION
It is a standard information which can be configured at any level.
Examples :
- Module xPS, Bay xPS, VoltageLevel xPS, Substation xPS (x=S,D,M)
Long Name :
appears in viewers + printers
Detection Mode :
permanent : DI remains ON as far as signal is ON
Time tagging :
done at starting/end of signal filtering
Persistence filtering :
LHMI display :
Forcing Management :
if FSS enabled, auto/manual force
Schneider Electric - CS&P Datapoints Configuration E01
V4.7
Wired on : DI Channel
SPS acquired by DIU/CCU board
Schneider Electric - CS&P Datapoints Configuration E01
Long Name :
appears in viewers + printers
Time tagging :
done at starting/end of motion
LHMI display :
Forcing Management :
if FSS enabled, auto/manual force
Schneider Electric - CS&P Datapoints Configuration E01
Short Name :
SCE Key + appears in C264 local SOE
Long Name :
appears in viewers + printers
LHMI display :
yes = MPS in state list (MSC)
Forcing Management :
if FSS enabled, auto/manual force
10
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
11
12
Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
13
Long Name :
appears in viewers + printers
Analogue Type :
Analogue (AI,CT/VT,IED)
or Digital Measurement
Forcing Management :
if FSS enabled, automatic force to a given value
LHMI display :
yes = MV in measurements
list (MSC)
MV transmission :
SBUS, LHMI
14
Thresholds definition :
scaled values for LLL, LL, L, H, HH, HHH
thresholds + hysteresis
15
Scaling Low :
Linear / Quadratic
Up to 20 segments
Additional segments :
A2, B2 - A3, B3 - ...
Schneider Electric - CS&P Datapoints Configuration E01
- if transducer 0/10 mA :
min=0, max=10*
- if transducer 4/20 mA :
min=0, max=16*
- if voltage of CT/VT with nominal ph-N = 57.7 V
min=0, max=57.7*
- if IED (T103 : min=0, max=1; Modbus : cf. IED
documentation)
Wired on AI Channel :
Channel to be configured (cf. next slide)
Schneider Electric - CS&P Datapoints Configuration E01
17
18
Execution timeout :
Time allowed for Tap Changing
19
TPI type :
- Analogue Tap Position acquired by
AIU or IED,
- Coded Digital Measurement (1/N,
decimal, gray, BCD) acquired by DIU
20
Thresholds definition :
scaled values for LLL, LL, L, H, HH, HHH
thresholds
21
22
Wired on DI Channels :
Digital TPI acquired by a maximum of 64 channels
on DIU/CCU boards
Wired on AI Channel :
Channel to be configured
23
Long Name :
appears in viewers + printers
Counter Type :
Standard (standard DI counting)
Energy import / Energy export
Counter Acquisition :
validation => min pulse length to be counted
invalidity => for double, non complementarity
LHMI display :
yes = Counter in
measurements list (MSC)
Schneider Electric - CS&P Datapoints Configuration E01
Counter Management :
cf. next slide
24
25
integrate :
Counter computed by MV integration (example : P)
Counter type is not Standard but Energy import
or Energy export
Integration of P or Q :
In case the scale and unit is to big ((MVarh
MVarh for ex.), if
energy is changing of less than 1MVarh in 10 minutes,
the value is not sent (counter is integer so 0.2 value is
equal to 0).
26
Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
27
GENERIC CONTROL
It is a standard control which can be configured at any level.
Examples :
- Module xPC, Bay xPC, VoltageLevel xPC, Substation xPC (x=S,D)
28
Long Name :
appears in viewers + printers
Activation Mode :
- transient => configure pulse duration
- permanent
- permanent until feedback
LHMI display :
yes = SPC in control list
(MSC)
29
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in
Remote
Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed,
from SCADA forbidden
Note : This is internal automation existing and configurable for all xPC.
30
Auto/Manu dependency :
blocks the operator control if an automation is in
progress => connect to SPS/DPS giving
automation status
Feedback definition :
Wired on : DO Channel
31
Long Name :
appears in viewers + printers
Activation Mode :
- transient => configure pulse duration (2
channels open / close)
- permanent
- permanent until feedback
LHMI display :
yes = DPC in control list
(MSC)
32
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in
Remote
Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed,
from SCADA forbidden
Note : This is internal automation existing and configurable for all xPC.
33
Auto/Manu dependency :
blocks the operator control if an automation is in
progress => connect to SPS/DPS giving
automation status
Feedback definition :
Wired on : DO Channel
34
35
Long Name :
appears in viewers + printers
SetPoint type :
increment value
pulse duration
36
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in
Remote
Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed,
from SCADA forbidden
Note : This is internal automation existing and configurable for all
Setpoints.
37
Auto/Manu dependency :
blocks the operator control if an automation is in
progress => connect to SPS/DPS giving
automation status
AO Channels :
C264 will set AO channel
38
Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
39
SPS Status
SPS STATUS
MEANING
RESET
Electric status 0
SET
Electric status 1
TOGGLING
UNKNOWN
FORCED SET *
SUBSTITUTED SET *
SUPPRESSED
40
DPS Status
DPS STATUS
MEANING
OPEN
Electric status 01
CLOSED
Electric status 10
JAMMED
Electric status 00
UNDEFINED
Electric status 11
TOGGLING
UNKNOWN
FORCED OPEN *
SUBSTITUTED OPEN *
SUPPRESSED
41
MPS Status
MPS STATUS
MEANING
UNDEFINED
TOGGLING
UNKNOWN
FORCED STATE N *
SUBSTITUTED STATE N *
SUPPRESSED
42
MV Status
MV STATUS
MEANING
VALID
UNDEFINED
TOGGLING
UNKNOWN
FORCED
SUBSTITUTED STATE N *
SUPPRESSED
OVERRANGE
OPEN CIRCUIT
OVERSHOOT [1,2,3]
UNDERSHOOT [1,2,3]
43