Datapoints Configuration

PACiS Technical Training Level 2


CS&P Support Team

PCL

Content
 SPS, DPS, MPS
 MV, TPI, Counters
 SPC, DPC, SetPoints
 Datapoints Quality

Schneider Electric - CS&P Datapoints Configuration E01

Content
 SPS, DPS, MPS
 MV, TPI, Counters
 SPC, DPC, SetPoints
 Datapoints Quality

Schneider Electric - CS&P Datapoints Configuration E01

Typed / Generic xPS


 TYPED DIGITAL INFORMATION
It is an information which is representing a special input regarding the
MiCOM C264 inner automations.
Examples :
- Switchgear Position DPS, Locking device status SPS, Bay
Local/Remote DPS

 GENERIC INFORMATION
It is a standard information which can be configured at any level.
Examples :
- Module xPS, Bay xPS, VoltageLevel xPS, Substation xPS (x=S,D,M)

Schneider Electric - CS&P Datapoints Configuration E01

Typed / Generic xPS


 Mapping SPS
It is an input which is produced by mapping to another DP. Each state of
this DP is mapped and corresponds to a state of the mapping SPS.

 Day cyclic SPS


It is a transient SPS which is triggered every day at fixed time. (accuracy of
+/- 1 minute)(8 max per C264).

Schneider Electric - CS&P Datapoints Configuration E01

Add / Configure a SPS (1)


1) SPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy. Some SPS are System Info.
2) SPS attributes
Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

Detection Mode :
permanent : DI remains ON as far as signal is ON

Time tagging :
done at starting/end of signal filtering

Persistence filtering :
LHMI display :

SPS should remain valid Set or Reset during


the configured timer

yes = SPS in state list (MSC)

Forcing Management :
if FSS enabled, auto/manual force
Schneider Electric - CS&P Datapoints Configuration E01

Add / Configure a SPS (2)


3) SPS can be acquired by DIU/CCU board, IED. Some SPS are computed by
C264 application (C264 automation, )
=> Relations under a SPS

Has for IED address :


SPS acquired by IED

V4.7

Wired on : DI Channel
SPS acquired by DIU/CCU board
Schneider Electric - CS&P Datapoints Configuration E01

Add / Configure a DPS (1)


1) DPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy. Some DPS are System Info.
2) DPS attributes
Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

Time tagging :
done at starting/end of motion

Motion & Persistence filtering :

LHMI display :

Motion : eliminate transients 00 and/or 11 motion


states
Persistence : DPS should remain valid Open or
Closed during the configured timer

yes = DPS in state list (MSC)

Forcing Management :
if FSS enabled, auto/manual force
Schneider Electric - CS&P Datapoints Configuration E01

Add / Configure a DPS (2)


3) DPS can be acquired by DIU/CCU board, IED. Some DPS are computed by
C264 application (C264 automation, )
=> Relations under a DPS
Wired on :
DPS acquired by 2 channels (open and
closed) on DIU/CCU board

DPS computed from 2 SPS :


DPS acquired using 2 SPS, 1 for open and 1 for
closed

Has for IED address :


DPS acquired by IED

Schneider Electric - CS&P Datapoints Configuration E01

Add / Configure a MPS (1)


1) MPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy. Some MPS are System Info.
A MPS can have a maximum 16 valid states.
2) MPS attributes

Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

Motion & Persistence filtering :


Motion : inhibition (cf. next slide)
Persistence : MPS should remain in one valid
state during the configured timer

LHMI display :
yes = MPS in state list (MSC)

Forcing Management :
if FSS enabled, auto/manual force

Schneider Electric - CS&P Datapoints Configuration E01

10

Add / Configure a MPS (2)


Example : Change State with Filtering all DI =0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16

Before change state

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16

During change all DI =0

0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16

End of change state

Example : Change State with Filtering all DI =1


0
0
0
0
0
0
0
1
1
0
0
0
0
0
0
0
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
Schneider Electric - CS&P Datapoints Configuration E01

During change all DI =1

11

Add / Configure a MPS (3)


3) MPS can be acquired by DIU/CCU board, IED. Some MPS are computed by
C264 application (C264 automation, )
=> Relations under a MPS
Wired on :
MPS acquired by a maximum of 16 channels on
DIU/CCU boards

Has for IED address :


MPS acquired by IED
Schneider Electric - CS&P Datapoints Configuration E01

12

Content
 SPS, DPS, MPS
 MV, TPI, Counters
 SPC, DPC, SetPoints
 Datapoints Quality

Schneider Electric - CS&P Datapoints Configuration E01

13

Add / Configure a MV (1)


1) MV can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy. Some MV are System Info.
2) MV attributes in General Tab
Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

Analogue Type :
Analogue (AI,CT/VT,IED)
or Digital Measurement

Forcing Management :
if FSS enabled, automatic force to a given value

LHMI display :
yes = MV in measurements
list (MSC)

Schneider Electric - CS&P Datapoints Configuration E01

MV transmission :
SBUS, LHMI

14

Add / Configure a MV (2)


3) MV attributes in Value Features Tab

Minimum / Maximum Value :


scaled values for SCADA and OI display + Full
Scale definition

Thresholds definition :
scaled values for LLL, LL, L, H, HH, HHH
thresholds + hysteresis

Schneider Electric - CS&P Datapoints Configuration E01

15

Add / Configure a MV (3)


4) MV attributes in Scaling Tab

Scaling Low :
Linear / Quadratic

Minimum / Maximum acquisition values :


Scaling coefficients :
scaled value = A1 x acq. Value + B1

Up to 20 segments

Additional segments :
A2, B2 - A3, B3 - ...
Schneider Electric - CS&P Datapoints Configuration E01

- if transducer 0/10 mA :
min=0, max=10*
- if transducer 4/20 mA :
min=0, max=16*
- if voltage of CT/VT with nominal ph-N = 57.7 V
min=0, max=57.7*
- if IED (T103 : min=0, max=1; Modbus : cf. IED
documentation)

* schedule a max value = 120% of expected max


max=12, max=20, max=70 ... (transducers can
measure more and display overflow and
undershoot measurements).
16

Add / Configure a MV (4)


5) MV can be acquired by AIU/TMU/DIU/CCU board, IED. Some MV are
computed by C264 application (C264 automation, )
=> Relations under a MV
Wired on DI Channels :
Digital Measurements acquired by a maximum of
64 channels on DIU/CCU boards

Has for IED address :


MV acquired by IED

Computed by CT/VT board :


relation to be configured

Wired on AI Channel :
Channel to be configured (cf. next slide)
Schneider Electric - CS&P Datapoints Configuration E01

17

Add / Configure a MV (5)


6) AI Board channel configuration
Transducer range :

Scanning acquisition period :


cf. C264 configuration, Measurements tab

Schneider Electric - CS&P Datapoints Configuration E01

18

Add / Configure a TPI (1)


1) TPI can ONLY be added under a Tap Changer object belonging to a
Transformer module.
=> Add / Configure a Tap Changer object :
Built-in function :
Tap Changer

Min TAP, Max TAP

Execution timeout :
Time allowed for Tap Changing

Schneider Electric - CS&P Datapoints Configuration E01

19

Add / Configure a TPI (2)


2) TPI attributes :
2.1) General Tab

TPI type :
- Analogue Tap Position acquired by
AIU or IED,
- Coded Digital Measurement (1/N,
decimal, gray, BCD) acquired by DIU

Note : Tabs are not the same


- Value Features is common to Analogue and Digital TPI
- Scaling & Tap Position for Analogue
- Tap Position for Digital
Schneider Electric - CS&P Datapoints Configuration E01

20

Add / Configure a TPI (3)


2) TPI attributes :
2.2) Value Features Tab

Minimum / Maximum Value :


Should comply with Tap Changer object
configuration

Thresholds definition :
scaled values for LLL, LL, L, H, HH, HHH
thresholds

Schneider Electric - CS&P Datapoints Configuration E01

21

Add / Configure a TPI (4)


2) TPI attributes :
2.3) Scaling Tab (for Analogue TPI only)
Minimum / Maximum Acquisition Value :
Same as for a MV

2.4) Tap Position Tab


For Analogue TPI :
filtering => transient intertap filtering
current valid range => gives validity DC input
range for each tap

For Digital TPI :


filtering => signal validation
inhibition => transient intertap filtering

Schneider Electric - CS&P Datapoints Configuration E01

22

Add / Configure a TPI (5)


3) TPI can be acquired by AIU/DIU/CCU board, IED.
=> Relations under a TPI

Wired on DI Channels :
Digital TPI acquired by a maximum of 64 channels
on DIU/CCU boards

Has for IED address :


TPI acquired by IED

Wired on AI Channel :
Channel to be configured

Schneider Electric - CS&P Datapoints Configuration E01

23

Add / Configure a Counter (1)


1) Counter can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy.
2) Counter attributes in General Tab
Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

Counter Type :
Standard (standard DI counting)
Energy import / Energy export

Counter Acquisition :
validation => min pulse length to be counted
invalidity => for double, non complementarity

LHMI display :
yes = Counter in
measurements list (MSC)
Schneider Electric - CS&P Datapoints Configuration E01

Counter Management :
cf. next slide

24

Add / Configure a Counter (2)


2) Counter attributes in General Tab

Counter Total for IED counters :


Yes => IED is sending real counter
value
No => IED is sending non-scaled
value

Counter cumulative period :


- configure a period at the end of which the counter value is transmitted (SBUS,
LHMI)
- possible values : 10mn, 15mn, 30mn, 1h, 2h, 3h, 24h
-at the end of this period, counter value can be reset (C264 re-start counting from
0)

Schneider Electric - CS&P Datapoints Configuration E01

25

Add / Configure a Counter (3)


3) Counter can be acquired by DIU/CCU board, IED. Some Counters are
computed by C264 application (C264 automation, )
=> Relations under a Counter
Wired on :
Single counter => 1 DI Channel
Double counter => 2 DI Channels

Has for IED address :


Counter acquired by IED

integrate :
Counter computed by MV integration (example : P)
Counter type is not Standard but Energy import
or Energy export

Schneider Electric - CS&P Datapoints Configuration E01

Integration of P or Q :
In case the scale and unit is to big ((MVarh
MVarh for ex.), if
energy is changing of less than 1MVarh in 10 minutes,
the value is not sent (counter is integer so 0.2 value is
equal to 0).
26

Content
 SPS, DPS, MPS
 MV, TPI, Counters
 SPC, DPC, SetPoints
 Datapoints Quality

Schneider Electric - CS&P Datapoints Configuration E01

27

Typed / Generic xPC


 TYPED CONTROL
It is an information which is representing a special functionality regarding
the MiCOM C264 inner automations.
Examples :
- Switch Ctrl DPC, Locking device status SPC, Bay Local/Remote DPC,
Sync CB Close

 GENERIC CONTROL
It is a standard control which can be configured at any level.
Examples :
- Module xPC, Bay xPC, VoltageLevel xPC, Substation xPC (x=S,D)

Schneider Electric - CS&P Datapoints Configuration E01

28

Add / Configure a SPC (1)


1) SPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy. Some SPC are System Info.
2) SPC attributes General Tab
Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

Activation Mode :
- transient => configure pulse duration
- permanent
- permanent until feedback

LHMI display :
yes = SPC in control list
(MSC)

Schneider Electric - CS&P Datapoints Configuration E01

Inter Control timeout :


no possibility to execute 2 consecutive orders
during this timer

29

Add / Configure a SPC (2)


3) SPC execution may be dependant on Local/Remote status of
Substation/Bay, on SBMC and/or on control uniqueness
=> SPC attributes Dependencies tab
Bay Local/Remote :
Bay Local => control from LHMI
allowed, from OI & SCADA not
allowed

SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in
Remote

Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed,
from SCADA forbidden
Note : This is internal automation existing and configurable for all xPC.

Schneider Electric - CS&P Datapoints Configuration E01

30

Add / Configure a SPC (3)


4) SPC can be executed on DOU/CCU board, IED. Some SPC are computed
by C264 application (C264 automation, )
=> Relations under a SPC
Interlock SPS :
holds a logic allowing/blocking the control

Associated DO channel status SPS :


for hardwired SPC only

Auto/Manu dependency :
blocks the operator control if an automation is in
progress => connect to SPS/DPS giving
automation status

Feedback definition :
Wired on : DO Channel

for C264 acknowledgement


cf. slide 3.4

SPC executed on DOU/CCU board

Has for IED address :


SPC executed by IED
Schneider Electric - CS&P Datapoints Configuration E01

31

Add / Configure a DPC (1)


1) DPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy. Some DPC are System Info.
2) DPC attributes
Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

Activation Mode :
- transient => configure pulse duration (2
channels open / close)
- permanent
- permanent until feedback

LHMI display :
yes = DPC in control list
(MSC)

Schneider Electric - CS&P Datapoints Configuration E01

Inter Control timeout :


no possibility to execute 2 consecutive orders
during this timer

32

Add / Configure a DPC (2)


3) DPC execution is dependant on one hand from Local/Remote status of
Substation/Bay and on the other hand from control uniqueness
=> DPC attributes Dependencies tab
Bay Local/Remote :
Bay Local => control from LHMI
allowed, from OI & SCADA not
allowed

SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in
Remote

Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed,
from SCADA forbidden
Note : This is internal automation existing and configurable for all xPC.

Schneider Electric - CS&P Datapoints Configuration E01

33

Add / Configure a DPC (2)


4) DPC can be executed on DOU/CCU board, IED. Some DPC are computed
by C264 application (C264 automation, )
=> Relations under a DPC
2 Interlock SPS (open/close):
holds a logic allowing/blocking the controls

2 Associated DO channel status SPS :


for hardwired DPC only

Auto/Manu dependency :
blocks the operator control if an automation is in
progress => connect to SPS/DPS giving
automation status

Feedback definition :
Wired on : DO Channel

for C264 acknowledgement


cf. slide 3.4

DPC executed on DOU/CCU board

Has for IED address :


DPC executed by IED
Schneider Electric - CS&P Datapoints Configuration E01

34

Configure a xPC feedback


1) SPC/DPC can have for feedback a SPS/DPS
=> C264 checks if control success (ex: CB control, feedback CB position)
=> Example given for DPC with DPS feedback
DPC
Relation has for feedback
with 2 attributes :
DPS

Schneider Electric - CS&P Datapoints Configuration E01

- execution timeout : maximum


time allowed to get feedback
- status check : C264 will check
status before performing control

35

Add / Configure a SetPoint (1)


1) SetPoints can be added at Substation, Voltage Level, Bay, Module,
ISaGRAF automation level in Electric hierarchy.
2) SetPoint attributes
Short Name :
SCE Key + appears in C264 local SOE

Long Name :
appears in viewers + printers

SetPoint type :

For Digital SetPoint :


LHMI display :

increment value
pulse duration

yes = SetPoint in control list


(MSC)

Minimum / Maximum value :


raw values for SetPoint validity
Schneider Electric - CS&P Datapoints Configuration E01

36

Add / Configure a SetPoint (2)


3) SetPoint execution is dependant on one hand from Local/Remote status of
Substation/Bay and on the other hand from control uniqueness
=> SetPoint attributes Dependencies tab
Bay Local/Remote :
Bay Local => control from LHMI
allowed, from OI & SCADA not
allowed

SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in
Remote

Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed,
from SCADA forbidden
Note : This is internal automation existing and configurable for all
Setpoints.

Schneider Electric - CS&P Datapoints Configuration E01

37

Add / Configure a SetPoint (3)


4) SetPoints can be executed on DOU/CCU board, IED. Some SetPoints are
computed by C264 application (C264 automation, )
=> Relations under a SetPoints
DO Channels :
C264 will close DO channels using configured
code (BCD, binary, )

Auto/Manu dependency :
blocks the operator control if an automation is in
progress => connect to SPS/DPS giving
automation status

Has for IED address :


SP executed by IED

AO Channels :
C264 will set AO channel

Schneider Electric - CS&P Datapoints Configuration E01

38

Content
 SPS, DPS, MPS
 MV, TPI, Counters
 SPC, DPC, SetPoints
 Datapoints Quality

Schneider Electric - CS&P Datapoints Configuration E01

39

SPS Status
SPS STATUS

MEANING

RESET

Electric status 0

SET

Electric status 1

SELF CHECK FAULTY

Faulty DI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED SET *

SPS is Forced Set by C264 (FSS enable)

SUBSTITUTED SET *

SPS is Substituted Set by Oper. (FSS enable)

SUPPRESSED

SPS is Suppressed by Oper. (FSS enable)

* => Same for RESET


Quality => gives the nature of invalidity

Schneider Electric - CS&P Datapoints Configuration E01

40

DPS Status
DPS STATUS

MEANING

OPEN

Electric status 01

CLOSED

Electric status 10

JAMMED

Electric status 00

UNDEFINED

Electric status 11

SELF CHECK FAULTY

Faulty DI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED OPEN *

DPS is Forced Open by C264 (FSS enable)

SUBSTITUTED OPEN *

DPS is Substituted Open by Op. (FSS enable)

SUPPRESSED

DPS is Suppressed by Oper. (FSS enable)

* => Same for CLOSED


Quality => gives the nature of invalidity
Schneider Electric - CS&P Datapoints Configuration E01

41

MPS Status
MPS STATUS

MEANING

STATE 1 -> STATE 16

Only one channel activated

UNDEFINED

No channel or more than one activated

SELF CHECK FAULTY

Faulty DI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED STATE N *

MPS is Forced St. N by C264 (FSS enable)

SUBSTITUTED STATE N *

MPS is Substituted St. N by Op. (FSS enable)

SUPPRESSED

MPS is Suppressed by Oper. (FSS enable)

Quality => gives the nature of invalidity


Schneider Electric - CS&P Datapoints Configuration E01

42

MV Status
MV STATUS

MEANING

VALID

MV in between min/MAX and/or L/H threshold

UNDEFINED

No DI channel or more than one activated DM

SELF CHECK FAULTY

Faulty DI/AI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED

MV is Forced C264 (FSS enable)

SUBSTITUTED STATE N *

MV is Substituted by Op. (FSS enable)

SUPPRESSED

MV is Suppressed by Oper. (FSS enable)

OVERRANGE

Acquisition out of range

OPEN CIRCUIT

No current on AI channel (mA)

OVERSHOOT [1,2,3]

Over H, HH, HHH Threshold

UNDERSHOOT [1,2,3]

Under L, LL, LLL Threshold

Quality => gives the nature of invalidity


Schneider Electric - CS&P Datapoints Configuration E01