Anda di halaman 1dari 2

or

f
t
r
o
Supp /400
AS Series

9910 Uninterruptible Power Systems


660VA to 1.3kVA

Intelligent Communications
An AS/400 interface port, an interface cable, along
with a keypad and front display panel offer convenient
local unit communication and monitoring of 14 system
parameters. Fortress also has RS-232 external communications through optional Best Power CheckUPS
power monitoring, management and control software. A
Best Power SNMP Adapter enables remote network
operations.
Advanced Power Integrity and Management for
AS/400 Midrange Computing
A True UPS

Reliable, on-line, no-break power to AS/400


applications can be user programmed to protect against
disturbances as low as 27 percent below nominal
voltage. Fortress for AS/400 is the newest member of
the Fortress family, which recently scored over 300,000
hours Mean Time Between Failure (MTBF) in an
independent field research study.
Expandable and Upgradeable

Adding modular battery packs allows extended


runtimes. Fortress B63 and B64 are upgradeable to B67
or B68 (respectively).

Order with New or Installed AS/400s

You can order Fortress classic black UPS models with


AS/400 9402/04 models: 200 Series or 400 Series.
Order for installed AS/400 models through the MES
upgrade path in the AS/400 configurator.
A Perfect Match for AS/400s

Fortress matches the raven black color of the AS/400. It


is extremely compact and designed for office environments.

(U.S.A. and Canada)

Fortress

P.O. Box 280, N9246 Highway 80 S., Necedah, WI 54646 U.S.A. 1-608-565-7200/1-800-356-5794

ced nd 400
n
a
v
d
0 aproducts
Best answersAin powerlsprotection
0
2
Mode

Fax:1-608-565-2221 Fax-On-Demand: 1-800-487-6813 Web Site: www.bestpower.com

UNINTERRUPTIBLE
POWER SYSTEMS

Fortress

9910 Uninterruptible Power Systems


660VA to 1.3kVA
Optional Battery Packs
IBM Model Number (9910)

B24

Best Model

B63

LI660BW5

Capacity (VA/Watts)

675/400

(inches) 6.5/5.25/15.5
(mm) 165/135/395

Weight

B64

750/750

1100/940

B68

B70

6610

6611

LI750DWM

LI1.3KDWN

LIEBP2W

LIEBPW

675/400

750/750

10.75/5.25/17.25

17.25/8/20

Same as

1300/940

Same as

Same as

10/8/19.5
260/205/495

275/135/440

440/205/510

B63/B67

B69

B63

(lbs)

28

47

122*

Same as

Same as

Same as

68

(kg)

12.7

21.3

55.3*

B63/B67

B69

B63

30.8

Output (AC) Receptacles Quantity/Type


Output Connector (DC)

B69

LI675BWM LI750BWM LI1.3KBWN LI675DWM

660/400

Dimensions H x W x D

B67

4 ea 5-15R

6 ea 5-15R

4 ea C13

None

None

1 ea. Anderson

Input Connector

C14

Equipment cords Quantity/Type

Anderson

1 ea. C13 to 5-15P

1 ea. C13 to C14

each 6/1.8 m long


Runtimes

N/A

(Full Load)

6.5m

13m

5m

*18m

13m

5m

*18m

(Half Load)

18m

35m

15m

42m

35m

15m

42m

N/A

Operation
Nominal Input Voltage

110/115/120 VAC

Input Range of On-line Operation

For input range voltage of 92-136 VAC, output

220/230/240 VAC

N/A

For input voltage of 176-254 VAC,

voltage will be 105-136 VAC

output voltage will be 196-254 VAC

105-136 VAC

200-254 VAC

On-Battery Voltage

On-Battery Frequency

50/60 Hz 1 Hz, autosensing

On-Battery Waveform

Sine-wave

Same as input on line

On-line Voltage
Output Protection
Lightning and Surge Protection
Normal Mode Surge Let-Through Voltage

Automatic current and overvoltage protection

Passed ANSI/IEEE C62.41 Categories A and B. IEC - 801/5

0.7% of peak

0.3% of peak (max)

0.6% of peak (max)

When Subjected to IEEE 587 Cat A 6kV Test


Noise (RF) Isolation

5-45 dB common-mode, 28-80db normal mode

5-60 dB common-mode, 28-80 db normal mode

Input Protection

Fuse

Transfer Time
Recharge Time to 85% Capacity

0 ms

Temperature compensated charger provides typical recharge time of 3-12 hours

Battery Type

Sealed, maintenance-free UL 924 recognized

Battery

24 volts

Efficiency
User-Selectable Functions

95% on line

Silence Alarm 1; Silence Alarm 2; Low Battery Time Warning Set Point; Auto Restart; Startup

Test; Communications Mode; Low Voltage Set Point; High Voltage Set Point
Alarms

Overload; High Ambient Temperature; Overcurrent Shutdown; Replace Battery; Inverter

Failure; High Battery Low Battery; Fan Alarm (some alarms are model-dependent)
Safety Compliance

UL, cUL or CSA-Certified

EMI Compliance

FCC Class B

FCC Class A

TUV/GS

Same as UPS

VDE 0871 or VFG 243/46 1992 Level B

Same as UPS

Environmental
Operating Temperature

0 to 40 C (32 to 104 F)

Storage Temperature

0 to 40 C (32 to 104 F)

Humidity

0 to 95%, RH

Audible Noise On-line at One Meter

38 - 44 db depending on model

Extended Runtimes with optional External Battery Packs (Full Load)


UPS

One (1) 9910-6610

Two (2) 9910-6610

Three (3) 9910-6610

One (1) 9910-6611

Two (2) 9910-6611

Three (3) 9910-6611

(LIEBP2W)

(LIEBP2W)

(LIEBP2W)

LIEBPW)

(LIEBPW)

(LIEBPW)

B63, B64

1 hour

2 hours

3 hours

N/A

N/A

N/A

B67, B68

25 minutes

55 minutes

80 minutes

N/A

N/A

N/A

B69, B70

N/A

N/A

N/A

50 minutes

75 minutes

100 minutes

MLP-0236A 9/97
1997, Best Power
All rights reserved.