Anda di halaman 1dari 16

PRODUCT: GVR

02

PROVIDING GLOBAL SWITCHGEAR


SOLUTIONS
The names of Whipp & Bourne, Brush and South Wales Switchgear are synonymous with
circuit breaker technology around the globe. All companies have a history which can be
traced back over 125 years and its a background which cannot be ignored even though the
demands of todays industrial and power distribution sectors are vastly different and more
complex. Today they form part of Hawker Siddeley Switchgear Ltd. - part of Melrose plc.
As a major national and international manufacturer of a range of distribution switchgear,
Hawker Siddeley Switchgear Ltd serves not only electrical utilities worldwide but also a vast
array of industrial and transit sectors where the need for safe and reliable power supplies is
paramount.
With a highly-skilled workforce and manufacturing facilities both in the UK and Australia, a
technology centre based in the UK and sales offices around the globe, we have maintained
a global reach - building on a clear and unrivalled reputation for innovation. The success
of the original companies was rooted in an ability to pioneer ground-breaking technologies,
introducing state of the art developments which still lead the way in the switchgear sector.
Hawker Siddeley Switchgear Ltd remains committed to innovation, striving to provide what
our customers could have - not just what they want.

04

GVR RECLOSER: FOR POLE


MOUNTING AND SUBSTATION
APPLICATIONS

The father of modern switchgear, Hawker Siddeley Switchgear Ltds world renowned GVR
Recloser was the first in a range of equipment utilising one of the most advanced operating
mechanisms available on the market today Hawker Siddeley Switchgears Fit & Forget
Technology, featuring the award winning magnetic actuator.
The GVR provides intelligent control and protection on power distribution networks, whilst
offering a lifetime of trouble-free service.
The GVR automatic recloser is now available as a tank only option for those customers
who wish to connect their own protection and control cubicles. Alternatively, customers
looking for a ground-mounted solution can select our epoxy separable bushings for cable
connected networks.



06

KEY FEATURES

Superior, proven Fit & Forget technology with minimal maintenance


The patented, single coil magnetic actuator mechanism allows the GVR to operate


independently of the MV supply
Environmentally friendly vacuum interruption produces no by-products
The lightweight corrosion resistant aluminium tank makes the GVR easier to transport
and install
The EPDM or silicone bushings are tested for tracking and erosion to IEC 61109 and
are resistant to damage from vandalism or mishandling
Endurance tested to 10,000 operations
Pole mounted or substation mounted, the GVR can be integrated into the most
advanced distribution automation schemes, or can operate as a stand-alone recloser
By using the advanced control and protection functions of the Panacea, the GVR can
also be used in applications where reclosers have not traditionally been used such as
closed rings and underfrequency load shedding schemes
The 3-in-1 Recloser the GVR can be configured to function as a Switch, Sectionaliser
or Recloser by using one of the specially pre-engineered protection and control
cubicles

08

APPLICATIONS

The GVR has a wide range of applications:

Pole mounted applications


Substation applications
Wind Farm applications
Switch applications (Auto-reclosing)
Sectionaliser applications

With over 25,000 GVR auto-reclosers in service, the father


of modern switchgear has proved its worth time and time
again as a stellar product.
A product that was at the forefront of technology 20 years
ago still holds its own today, in a very competitive market.

10

RATINGS
GVR15

GVR27

GVR38

MAXIMUM SYSTEM VOLTAGE

15.5kV

27kV

38kV

CONTINUOUS CURRENT

630A

630A

630A

INTERRUPTING CURRENT

12.5/16kA

12.5kA

10kA

IMPULSE VOLTAGE WITHSTAND

110
125/150
kV peak
kV peak

150 (internal)
170 (external)
kV peak

POWER FREQUENCY WITHSTAND


DRY

50kV

60kV

70kV

POWER FREQUENCY WITHSTAND


WET

50kV 1 min

50kV 1 min

60kV 1 min

RATED GAS PRESSURE FOR ABOVE

Atmospheric

Atmospheric
/0.3bar*

0.3bar
(gauge)

NUMBER OF OPERATIONS WITH NO


MAINTENANCE

10,000

10,000

10,000

* Ratings for 150kV impulse version

STANDARDS
ANSI C37.60, IEC 801, IEC 255

Manual Trip/Lock Out


(Hook stick)

Electronic Control Unit

Battery Power Pack

12

Low Voltage Umbilical Lead

DIMENSIONS

All dimensions in mm
Dimensions for a standard GVR Recloser
VOLTAGE CREEPAGE
Up to 27kV
830

38kV 1178

(A) (B) (C) (D)


369 286 571 298
469 312 623 272

(E) 434 (F) 620 (G) 280 (H) 175

TYPICAL WEIGHTS
* Ratings for 150kV impulse version

145 / 155* kg

14

GVR ENGINEERING DETAIL

1 Single piece, aluminium or copper-cored EPDM or silicone rubber bushings, with


grooves to take optional wildlife guards/MV boots. Epoxy separable bushings also
available.

2 Current transformers are mounted within the tanks controlled environment, while

optional capacitive voltage dividers provide voltage signals for use by the Panacea or an
RTU.
3 Aluminium housing with lightweight, moulded baseplate, secured by stainless steel bolts
and incorporating rubber O ring seals.
4 Pressure-relief disc, to comply with IEC 60298, offering the highest levels of safety.
5 Mechanical ON/OFF position indication visible through clear viewing window from
ground level.

6 Hook stick-operated manual trip and lockout control.

7 A single moulding supports the three phase vacuum interrupter assembly, magnetic
actuator mechanism and one-piece drive beam.

8 The patented, single coil magnetic actuator is based on a solenoid plunger, held in the
tripped or closed position by a permanent magnet.

HAWKER SIDDELEY
SWITCHGEAR LTD
UNIT 3 BLACKWOOD BUSINESS
PARK,
NEWPORT ROAD,
BLACKWOOD, SOUTH WALES,
NP12 2XH. UNITED KINGDOM
T +44 (0) 1495 223001
T 00800 42426666 (24HR)
F +44 (0) 1495 225674
E SALES@HSS-LTD.COM
WWW.HSS-LTD.COM
BRUSH GROUP HQ
NOTTINGHAM ROAD,
LOUGHBOROUGH,
LEICESTERSHIRE,
LE11 1EX, UNITED KINGDOM
T + 44 (0) 1509 611511
F + 44 (0) 1509 612009
E SALESUK@HSS-LTD.COM
WWW.BRUSH.EU

HAWKER SIDDELEY
SWITCHGEAR PTY AUSTRALIA
PO BOX 36, KALLANGUR, QLD
4503, AUSTRALIA
T +61 (0) 7 3888 2333
F +61 (0) 7 3888 3241
E HSSAUS@HSS-LTD.COM
HAWKER SIDDELEY
SWITCHGEAR SOUTH
AMERICA, CARRERA 21
NO 86A-31 OF 101,
BOGOTA, COLOMBIA
T +57 (0) 1 256 4617
F +57 (0) 1 655 8915
E SALES@HSS-LTD.COM

Issue 01/14. The design and manufacture of our products are subject to constant review, therefore slight variations may occur between the details given and the equipment supplied