Using Vectors to Approximate the Neutral Current in a Three Phase Power System

Part 1: Using Vectors to Approximate the Neutral Current in a Three


Phase Power System
for three phase 60 hertz systems with unity power factor and resistive loads
by Gerald Newton
November 3, 1999

The diagrams below show just how simple three phase power can be. American electricians are fortunate
that power frequencies are established at 60 hertz and take the form of the common sine wave.
Engineers, on the other hand, are quite unfortunate since they must learn electrical theory for any
frequency and wave form, and for power factors other than unity. But this article is not for engineers, it
is for the American electrician so calculus is not going to be included in this discussion. However,
electricians are expected to know geometry, trigonometry, algebra and arithmetic. The diagrams below
are an attempt to provide a simple understanding of three phase power systems such as seen with
208/120 volt and 480/277 volt three phase, 4 wire systems. We already know by common electrical
knowledge that the neutral current in a balanced three phase system is 0 amperes for resistive loads such
as incandescent lighting and heaters where the power factor is approximately 1.0. We also know that in a
balanced three phase system the neutral current is approximately equal to the line current for electric
discharge lighting loads such as high pressure sodium lights or fluorescent lights because of third
harmonics.
For systems where the line currents are not equal there is a simple method for finding the neutral current.
We can convert A phase, B phase and C phase into polar coordinates where the amperes are represented
by vectors then add the three vectors to find the approximate neutral current and phase angle. This is
called geometric vector addition.
Mathematically, we can precisely add the three vectors for the line currents by converting vectors into
their horizontal and vertical components by using trigonometry. We can add the horizontal components,
then add the vertical components, then convert this to polar coordinates to find the sum of the vectors.
This is called algebraic vector addition.
We will do the geometric addition using the root mean square values of the sine wave. The second part
of this discussion will cover algebraic addition.
First let us convert cartesian coordinates or the familiar X Y type graph to a Polar graph as demonstrated
below.

http://www.electrician2.com/electa1/electa3htm.htm[7/2/2015 5:28:34 PM]

Using Vectors to Approximate the Neutral Current in a Three Phase Power System

http://www.electrician2.com/electa1/electa3htm.htm[7/2/2015 5:28:34 PM]

Using Vectors to Approximate the Neutral Current in a Three Phase Power System

So what about B Phase? Well here it is!

http://www.electrician2.com/electa1/electa3htm.htm[7/2/2015 5:28:34 PM]

Using Vectors to Approximate the Neutral Current in a Three Phase Power System

Combining A phase, B phase, and C Phase.....

That looks easy enough and is. We have all learned a little about vectors, I am sure. A Vector is a line that represents
magnitude (its length) and has direction. The direction is referenced to zero degrees and that is usually a horizontal
line that parallels this sentence.

For example below is the phase vectors representing a line current of 30 amperes for each phase.

http://www.electrician2.com/electa1/electa3htm.htm[7/2/2015 5:28:34 PM]

Using Vectors to Approximate the Neutral Current in a Three Phase Power System

Our next step is to add the vectors. The neutral current is the sum of the A phase, B phase, and C phase vectors. So
how do we add vectors? Actually, there is a very simple, easy, and fast method that gives a good approximation.
Simply place each vector on the end of the preceding vector, then draw a line from the center point where the
magnitude value is zero to the end of the final vector. It is done like this:

http://www.electrician2.com/electa1/electa3htm.htm[7/2/2015 5:28:34 PM]

Using Vectors to Approximate the Neutral Current in a Three Phase Power System

The approximate value of the Sum is 20 plus something and the direction is about 260 degrees. We could get much
better results using polar graph paper and a ruler to scale the values.
We can do the same thing with the three phase vectors that represent current as shown below.
In this example the vectors represent equal line currents of 30 amperes. The neutral current should be zero and sure
enough, the sum of the phase currents add up to a vector of zero magnitude. The direction is irrelevant. Remember,
the neutral current is the sum of the three vectors that represent the phase line currents.

Now let us try this approximation method to add three phase line currents that are not equal.
http://www.electrician2.com/electa1/electa3htm.htm[7/2/2015 5:28:34 PM]

Using Vectors to Approximate the Neutral Current in a Three Phase Power System

Click the mouse button


to place several vectors
on the screen. Then
click on action to sum
them up. The vector is
the sum is the white
vector from the origin
to the head of the last
vector.

http://www.electrician2.com/electa1/electa3htm.htm[7/2/2015 5:28:34 PM]

Using Vectors to Approximate the Neutral Current in a Three Phase Power System

Use the mouse button


to lay down up to ten
vectors. Click on the
Action button to sum
the up.

To go to Part 2 using algebra to add vectors click here.


Return to electrician2.com
Last updated: 10/26/106