SUBMITTAL
Tag:
All dimensions are in inches.
7 Ton
Split System Cooling
Single Compressor
TTA090A
RECOMMENDED SERVICE
Table 1
Unit Wiring
Unit
Minimum Circuit
Maximum Fuse Size or
Unit
Operating
Ampacity
Maximum Circuit Breaker2
Model No.
Voltage Range
TTA090A3
187-253
37.0
60
TTA090A4
414-506
19.7
25
TTA090AW
518-632
15.6
20
Note:
1. Electrical characteristics reflect nameplate values and are calculated in accordance with UL and ARI
specifications. Values are system rated.
2. HACR type circuit breaker per NEC.
Net
Maximum
326
1
105
Corner Weights
2
3
4
83
61
77
Net
2
12
1
8
23
1
Table 4
General Data
Table 5
7 Ton
Single Compressor
TTA090A3, A4,AW
Cooling Performance
Gross Cooling Capacity
Matched Air Handler
92,000
92,000
Condensing Unit Only2
89,000
ARI Net Cooling Capacity3
EER 4
Matched Air Handler
10.3
Condensing Unit Only
11.6
5
8.8
System Data7
No. Refrigerant Circuits
Suction Line (in.) OD
Liquid Line (in.) OD
1
1 3/8
1/2
Plate Fin
.375
19.25
2/18
Propeller
1/26
Direct/1
5,670
1/.50
Motor RPM
Outdoor
Temperature
in Degrees (F)
Head press PSIG
65
Cap. Btuh/1000
Unit KW
Head press PSIG
75
Cap. Btuh/1000
Unit KW
Head press PSIG
85
Cap. Btuh/1000
Unit KW
Head press PSIG
95
Cap. Btuh/1000
Unit KW
Head press PSIG
105
Cap. Btuh/1000
Unit KW
Head press PSIG
115
Cap. Btuh/1000
Unit KW
30
166
82.0
5.45
190
78.4
5.97
217
74.4
6.60
247
70.1
7.35
279
65.4
8.21
313
60.5
9.17
55
195
125.4
6.29
221
119.5
6.86
250
113.5
7.54
281
107.3
8.31
315
100.9
9.17
351
94.3
10.12
Performance data calculated at 15 F subcooling and 15 F superheat and does not include capacity loss due to
refrigerant lines.
Table 6
1,100
16.0
NOTES:
1. Cooling Performance is rated at 95F ambient, 80F
entering dry bulb, 67F entering wet bulb. Gross
capacity does not include the effect of fan motor
heat. ARI capacity is net and includes the effect of
fan motor heat. Certified in accordance with the
Unitary Large Equipment certification program, which
is based on ARI Standard 340/360-93.
2. Condensing Unit Only Gross Cooling Capacity rated
at 45F saturated suction temperature and at 95F
ambient.
3. ARI Net Cooling Capacity is calculated with matched
blower coil and 25 ft. of 1 3/8", " OD interconnecting tubing.
4. EER is rated at ARI conditions and in accordance
with DOE test procedures.
5. Integrated Part Load Value is based on ARI
Standard 210. Units are rated at 80F ambient, 80F
entering dry bulb, and 67F entering wet bulb at ARI
rated cfm.
6. Sound shown is tested in accordance with ARI
Standard 270.
7. System Data based on maximum linear length 80 ft.
Maximum lift: suction 60 ft., liquid 60 ft. For greater
lengths, refer to refrigerant piping applications
manual.
8. Refrigerant (operating) charge is for condensing unit
(all circuits) with matching blower coils and 25 ft. of
interconnecting refrigerant lines. All units are
shipped with a small holding charge only.
Table 7
Unit
Model No.
7
No.
TTA090A3
TTA090A4
TTA090AW
Volts
1
1
1
208-230
460
575
Phase
3
3
3
27.1
14.5
11.5
Amps
LRA(ea)
172.0
90.0
62.3
No.
1
1
1
Volts
Phase
208-230
460
575
NOTE:
1. Electrical characteristics reflect nameplate values and are calculated in accordance with UL and ARI specifications. Values are system rated.
FLA(ea)
1
1
1
3.1
1.6
1.2
Amps
LRA(ea)
8.1
3.7
3.0
Table 8
Gross Cooling Capacities (MBh) 7 Ton TTA090A Condensing Unit with 7 Ton TWE090A Air Handler
AmbientTemperature
85
CFM
Airflow
2700
3000
3300
3600
Enter.
Dry
Bulb
61
(F)
MBH SHC
75
85.0 66.9
80
85.4 77.9
85
87.1 87.1
90
91.5 91.5
75
86.7 69.9
80
87.3 82.0
85
89.9 89.9
90
94.5 94.5
75
88.1 72.7
80
88.9 85.9
85
92.4 92.4
90
97.0 97.0
75
89.2 75.5
80
90.5 89.7
85
94.5 94.5
90
99.3 99.3
67
MBH SHC
93.8 56.6
94.1 64.4
94.2 75.3
94.6 86.4
95.5 54.9
95.7 67.2
95.9 79.0
96.6 91.2
96.9 56.6
97.0 69.7
97.3 82.6
98.4 95.9
98.0 58.3
98.2 72.2
98.5 86.0
99.3 99.3
95
73
MBH SHC
103.2 38.1
103.2 49.8
103.4 61.2
103.6 72.5
104.9 38.8
104.9 51.4
105.1 63.8
105.2 75.9
106.2 39.5
106.3 52.9
106.5 66.3
106.6 79.2
107.4 40.0
107.5 54.3
107.7 68.6
107.8 82.4
61
MBH SHC
81.8 65.3
82.3 76.4
84.5 84.5
88.8 88.8
83.3 68.3
84.1 80.4
87.2 87.2
91.6 91.6
84.6 71.1
85.7 84.3
89.5 89.5
94.0 94.0
85.8 73.8
86.8 86.8
91.5 91.5
96.2 96.2
67
MBH SHC
90.3 55.2
90.5 62.9
90.7 73.7
91.3 84.9
91.9 53.3
92.0 65.5
92.2 77.4
93.1 89.7
93.1 55.1
93.3 68.1
93.6 81.0
94.9 94.3
94.2 56.7
94.4 70.5
94.8 84.4
96.3 96.3
105
Entering Wet Bulb
73
61
MBH SHC MBH SHC
99.3 36.8 78.3 63.5
99.4 48.3 78.9 74.7
99.6 59.7 81.6 81.6
99.6 70.9 85.8 85.8
100.9 37.5 79.7 66.5
100.9 49.9 80.6 78.7
101.1 62.3 84.1 84.1
101.2 74.3 88.4 88.4
102.1 38.0 80.9 69.3
102.2 51.4 81.8 81.8
102.4 64.8 86.3 86.3
102.6 77.6 90.8 90.8
103.2 38.5 82.0 72.0
103.3 52.8 83.6 83.6
103.5 67.2 88.2 88.2
103.7 80.8 92.8 92.8
MBH
86.4
86.7
86.8
87.6
87.9
88.0
88.3
89.4
89.1
89.2
89.6
90.8
90.1
90.3
90.8
92.9
67
SHC
53.6
61.2
72.0
83.2
51.7
63.8
75.7
88.0
53.4
66.3
79.3
90.8
55.1
68.8
82.7
92.9
115
MBH
95.2
95.2
95.4
95.5
96.6
96.7
96.9
97.0
97.7
97.9
98.1
98.2
98.7
98.9
99.0
99.3
73
SHC
35.3
46.8
58.2
69.3
35.9
48.3
60.8
72.7
36.4
49.8
63.2
75.9
36.9
51.2
65.3
79.1
MBH
74.5
75.3
78.4
82.5
75.8
77.0
80.8
85.0
76.9
78.4
82.8
87.2
77.9
80.1
84.6
89.2
61
SHC
61.7
72.8
78.4
82.5
64.6
76.9
80.8
85.0
67.4
78.4
82.8
87.2
70.0
80.1
84.6
89.2
MBH
82.3
82.5
82.7
83.7
83.6
83.8
84.2
85.1
84.7
84.9
85.4
87.3
85.6
85.9
86.5
89.2
67
SHC
52.0
59.3
70.2
81.5
49.9
61.9
73.9
85.1
51.7
64.5
77.4
87.3
53.3
66.9
80.8
89.2
73
MBH SHC
90.7 33.8
90.8 45.1
91.0 56.5
91.1 67.5
92.0 34.3
92.1 46.7
92.4 59.1
92.5 70.9
93.0 34.7
93.2 48.2
93.3 61.3
93.6 74.2
93.9 35.2
94.2 49.6
94.3 63.5
94.6 77.3
Equal MBH and SHC values constitute dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat
Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
MBH = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table 8
Gross Cooling Capacities (MBh) 7 Ton TTA090A Condensing Unit with 10 Ton TWE120A Air Handler
AmbientTemperature
85
CFM
Airflow
3100
3400
3700
4000
95
105
Enter.
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
90.8 73.8 99.9 61.9 109.7 40.7 87.4 72.1 96.2 60.4 105.6 39.3 83.4 70.2
80
91.4 86.7 100.2 70.8 109.7 54.0 88.1 85.1 96.4 69.3 105.7 52.5 84.4 83.3
85
94.5 94.5 100.3 83.5 109.9 67.2 91.6 91.6 96.6 81.9 105.9 65.7 88.4 88.4
90
99.2 99.2 101.0 96.5 110.1 80.3 96.2 96.2 97.5 95.0 106.0 78.6 92.9 92.9
75
92.2 76.8 101.4 59.5 111.1 41.3 88.7 75.1 97.6 58.0 106.9 39.8 84.7 73.2
80
93.1 90.9 101.6 73.7 111.2 55.6 89.7 89.3 97.7 71.9 107.1 54.1 85.9 85.9
85
97.0 97.0 101.7 87.3 111.4 69.8 94.0 94.0 98.0 85.7 107.2 68.3 90.7 90.7
90
101.8 101.8 102.8 101.5 111.4 83.6 98.8 98.8 98.9 98.9 107.3 82.1 95.4 95.4
75
93.4 79.8 102.6 61.3 112.2 41.8 89.8 78.0 98.7 59.7 108.0 40.3 85.8 76.1
80
94.2 94.2 102.7 76.2 112.4 57.1 91.2 91.2 98.8 74.5 108.2 55.6 87.8 87.8
85
99.2 99.2 103.0 91.0 112.6 72.3 96.1 96.1 99.2 89.4 108.4 70.8 92.7 92.7
90
104.2 104.2 104.3 104.3 112.7 87.0 101.0 101.0 101.1 101.1 108.5 85.4 97.6 97.6
75
94.5 82.6 103.6 63.0 113.2 42.3 90.8 80.8 99.7 61.4 108.9 40.7 86.8 78.9
80
96.1 96.1 103.8 78.7 113.4 58.5 93.0 93.0 99.8 77.1 109.1 57.0 89.5 89.5
85
101.2 101.2 104.2 94.5 113.6 74.8 98.0 98.0 100.4 92.9 109.2 73.0 94.5 94.5
90
106.3 106.3 106.4 106.4 113.7 90.3 103.0 103.0 103.1 103.1 109.4 88.7 99.5 99.5
MBH
92.1
92.3
92.5
93.6
93.4
93.5
93.9
95.5
94.4
94.6
95.1
97.6
95.3
95.5
96.2
99.6
67
SHC
58.8
67.4
80.1
93.3
56.3
70.1
83.9
95.5
58.0
72.7
87.6
97.6
59.7
75.3
91.1
99.6
115
73
MBH SHC
101.2 37.8
101.4 50.9
101.6 64.1
101.7 76.9
102.4 38.2
102.6 52.5
102.9 66.7
103.0 80.4
103.4 38.7
103.7 54.0
103.9 69.3
104.0 83.8
104.2 39.2
104.6 55.5
104.7 71.3
105.0 87.0
61
MBH SHC
79.2 68.2
80.3 80.3
84.9 84.9
89.4 89.4
80.4 71.2
82.3 82.3
87.1 87.1
91.8 91.8
81.5 74.1
84.2 84.2
89.0 89.0
93.8 93.8
82.5 76.9
85.8 85.8
90.7 90.7
95.6 95.6
Equal MBH and SHC values constitute dry coil condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat
Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
MBH = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
67
MBH SHC
87.7 57.1
87.9 65.5
88.2 78.3
89.6 89.6
88.9 54.5
89.1 68.2
89.5 82.0
91.9 91.9
89.9 56.2
90.1 70.8
90.7 85.7
93.9 93.9
90.7 57.9
90.9 73.3
91.8 89.3
95.7 95.7
73
MBH SHC
96.5 36.2
96.7 49.2
97.0 62.4
97.1 75.1
97.6 36.5
97.9 50.8
98.1 65.1
98.3 78.6
98.5 37.0
98.9 52.3
99.0 67.2
99.3 82.0
99.3 37.5
99.7 53.8
99.9 69.5
100.2 85.3
Mechanical
Specifications
General
Units shall be assembled on heavy
gauge steel mounting/lifting rails and
shall be weather proofed. Units shall
include hermetic scroll compressors,
plate fin condenser coils, fans and
motors, controls and holding charge of
nitrogen. Operating range shall be
between 115F and 50F in cooling as
standard from the factory. Units shall be
UL 1995 listed, certified and rated in
accordance with ARI Standard 340/360
or 365.
Casing
Unit casing shall be constructed of 18
gauge zinc coated heavy gauge,
galvanized steel. Exterior surfaces shall
be cleaned, phosphatized and finished
with a weather-resistant baked enamel
finish. Units surface shall be tested 500
hours in salt spray test. Units shall have
removable end panels which allow
access to all major components and
controls.
Refrigeration System
Units shall have a single refrigeration
circuit. Each refrigeration circuit has an
integral subcooling circuit. A
refrigeration filter drier shall be
provided as standard.The units shall
have both a liquid line and suction gas
line service valve with gauge port.
Units shall have one direct-drive
hermetic scroll compressor with
centrifugal oil pump providing positive
lubrication to moving parts. Motor shall
be suction gas-cooled and shall have a
voltage utilization range of plus or minus
10 percent of unit nameplate voltage.
Crankcase heater, discharge line
thermostat, internal temperature and
current-sensitive motor overloads shall
be included for maximum protection.
Scroll type compressor shall provide
inherently low vibration and noise by
having no suction and discharge valves.
External high and low pressure cutout
Library
Product Section
Product
Model
Literature Type
Sequence
Date
File No.
Supersedes
ACCESSORIES
Low Ambient Head Pressure Control
Shall modulate the RPM of unit outdoor
fan motor in response to outdoor
ambient temperature and discharge line
pressure. Accessory provides unit
cooling operation to outdoor
temperatures of 0F.
Vibration Isolation Packages Shall
reduce transmission of noise and
vibration to building structures,
equipment and adjacent spaces.
Packages shall be available in either
neoprene-in-shear or spring-flex types.
Hot Gas Bypass Kit Shall be
available to provide capacity
modulation.
Time Delay Relay Shall prevent
compressors in dual compressor unit
from coming on line simultaneously.
Timer shall be 24-volt, 60 cycle, with
four minute timing period.
Anti-Short-Cycle Timer Shall prevent
rapid on-off compressor cycling in light
load conditions by not allowing
compressor to operate for
5-7 minutes upon shutdown. Shall
consist of a solid state timing device, 24volt, 60 cycle with either 5 or 7 minute
fixed-off timing period.
Condenser Coil Guard Metal grille
with PVC coating shall be provided to
alleviate coil damage.
FACTORY INSTALLED ACCESSORIES
Black Epoxy Coated Condenser Coil
This option is designed to provide
corrosion protection of air cooled
condenser coils for seacoast application.
The black epoxy coil protection is a
factory applied thermoset vinyl coating,
bonded to normal aluminum fin stock.
The uniform thickness of the bonded
vinyl layer exhibits excellent corrosion
protection in salt spray tests performed
in accordance with ASTM B177.
Product Literature
Unitary
Split System Cooling
TTA090A 7-1/2 Ton
Submittal
206.09
September 2001
PL-UN-S/S-TTA090-SQ-206.09 9/01
TTA090-SQ-206.08