www.elsevier.com/locate/ijepes
a,*
, Vishal Verma
b,1
Department of Electrical Engineering, Indian Institute of Technology, Delhi, Hauz Khas, New Delhi 110016, India
b
Department of Electrical Engineering, Delhi College of Engineering, Delhi 110042, India
Received 1 June 2004; received in revised form 29 March 2006; accepted 19 July 2006
Abstract
This paper presents a topology of an Improved Hybrid Filter System (IHF) with self supporting DC bus, to eliminate harmonics in
supply current and voltage at the point of common coupling (PCC), created due to nonlinear load, typically rectier load. The compensation principle and ltering characteristics of the system are discussed in detail. A PI controller over average DC bus voltage of hybrid
combination of active lters is used for the control of IHF. Operation of IHF is investigated under dynamic change of loading conditions. The eectiveness of the scheme to protect overloading of passive lters is demonstrated under distorted supply conditions along
with harmonic compensation.
2006 Elsevier Ltd. All rights reserved.
Keywords: Series active lter; Hybrid lter; Harmonic compensation; Harmonic isolation; Voltage distortion; Resonance
1. Introduction
The increased use of solid state converters, produces
harmonics in the supply current and voltage waveforms.
Nonlinear loads, including adjustable speed drives, UPS,
switch mode power converters, microprocessor controls,
robotics, fax machines and laser printers create harmonics
[122]. These devices also tend to be the most sensitive to
malfunction from harmonic distortion. The harmonic currents generated by these non-linear loads do not only cause
additional heating of power system components, but at the
same time they ow through the system impedance and
current harmonics create voltage drops at their respective
harmonic frequencies distorting the voltage waveform.
Electronic loads are sensitive to distortion of their supply
*
313
314
a
b
c
isa
iLa
isb
iLb
isc
Cdc
iLc
Cr
if a
Lr
VDC
Lr
if c
Rectifier Load
Cr
5:1
CDC
3 Phase VSI
if b
3 Phase VSI
5th 7th
HPF
Passive Filters
Table 1
System parameters for present study
Line impedance
Load impedance
Tuned passive lter
Tuned passive lter
High pass lter
Ripple lter
DC bus capacitance
Gains for PI controller
Gains of Se.AF and Sh.AF
Zs
Is
Ifh
Vch*
IL
VL
Vch#
Vs
Passive
Filters
Vf
Zs1
Is1
If
+
Passive
Filters
V s1
Ish
L
O
A
D
Zsh
V
+
Vsh
*
ch
Ifh
=K1Ish
ILh
+VLh
Vch# = -K2Vfh
315
Passive
Filters
Vfh
Fig. 3. Single phase equivalent circuit of IHF (a) at fundamental Frequency (b) at harmonic frequencies.
V ch K 1 I sh
4. Control scheme
The control scheme of IHF system is shown in Fig. 4.
The main objective of IHF is to control the series active
lter to present zero impedance for the fundamental frequency and high impedance at harmonic frequencies,
and shunt active lter to provide zero impedance for harmonic frequency and high impedance at fundamental frequency. This forces the entire harmonics load current at
harmonic frequency to ow into passive lter decoupling
the supply and load at harmonic frequencies and provides
the voltage appearing at PCC near sinusoidal. In order to
nd the reference output voltages of the series active lter
(vch ) and active lter in shunt (v#
ch ), harmonic component
of the supply current (ish), and voltage drop across the
where
Zeq = {Zsh + K1 + (1 K2)Zfh}Zlh + {(Zsh + K1)
(1 K2)Zfh}. For K1 to be very large, much greater than
Zs, and Zf, and K2 1, the supply current becomes near
sinusoidal (Ish 0). The rst term of Eq. (2) indicates the
operation of hybrid lter acting as a attenuator at harmonic
frequency, eliminating the possibility of parallel resonance,
and, second term reects the capability of series lter to act
as a blocking resistance to harmonic current from supply
side to ow into the passive lter. Hence the desired output
voltage of the series active lter is given as
K2
v fha
SRF
Isolator
vch
PWM
Generation
Voltage at PCC
is a
AF of PHF
vch*
isa1
SRF
Isolator
Supply Current
V DC
Ref.
Voltage
v fa
PI
Controller
K1
+
X
isa*
Hys.
Generation
SAF
isa
VDC
Low Pass
Filter
316
4 isb 5
3
3
3 0
isb
2
2
isc
isd
cosx1 t sinx1 t isa
7
isq
isb
sinx1 t cosx1 t
SRF isolator extracts the DC quantities by low pass lters (LPF) for each isd and isq, realized by moving averager
at 100 Hz. The extracted DC components isdc D and isdc Q are
transformed back into abc coordinates to obtain the fundamental components as shown below
is1 a
isdc D
cosx1 t
sinx1 t
8
is1 b
sinx1 t cosx1 t isdc Q
2
3
2
3
0
r 1
is1 a
p
26 1
3 7 i s1 a
6
7
9
4 is1 b 5
4 2
2 5
p
3
i s1 b
3
1
is1 c
2 2
The phase harmonic currents are as
2
3 2 3 2
3
i s1 a
isa
isha
6
7 6 7 6
7
4 ishb 5 4 isb 5 4 is1 b 5
i s1 c
ishc
isc
3
i s1 a
6 7
6
7
6
7
4 vchb 5 K 1 4 ishb 5 K 3 4 is1 b 5
vchc
i s1 c
ishc
2 # 3
2
3
vfha
vcha
6 # 7
6
7
4 vchb 5 K 2 4 vfhb 5
vfhc
v#
chc
vcha
isha
12
13
The error signal, ve(n) is processed in PI controller and output K3(n) at nth sampling instant is expressed as
K 3n K 3n1 K p fven ven1 g K I fven g
10
11
14
15
where vtri is the instantaneous value of the carrier waveform and sa is the switching logic for the inverter leg corresponding to phase a. Similarly the switching logic of the
other two phases (b and c) of series active lter and
the three phases of shunt lter are formulated.
5.3. State space equations of the active lters
The active lters are connected to line and shunt branch
through the coupling transformers (CT). The CT has a
nominal turns ratio of n1:n2 (1:6) for series active lter
and turns ratio of n1:n2 (1:10) for shunt active lter. As
shown in Fig. 1, the secondaries of the CTs are connected
in star, and across the secondary winding a capacitor Cr is
connected. The output of the active lter is ltered using a
ripple lter (Lr, Cr) to avoid the induction of high frequency ripple voltage generated by the PWM inverter at
the terminals of the secondary winding of the CT. The voltage across the secondary winding of the CT has the same
waveform as the voltage across Cr. The high frequency
components gets dropped across Llr, whereas the low
frequency components, drops across Cr. Thus the voltage
controlled series active lter is modeled by the following
state space equations:
pifa fvfab vfac vcr ab vcr ac g=3 Rr ifa =Lr
16a
16b
16c
17a
pvcr b ifb =C r
17b
pvcr c ifc =C r
17c
where p is the dierential operator (d/dt) and Rr is the eective resistance of the coil (Lr). vfab, vfbc and vfca are the three
phase output line to line voltages of the Voltage Source Inverter (VSI). It may be expressed in terms of instantaneous
DC bus voltage (vdc) and switching functions as
vfab vfa vfb ; vfbc vfb vfc and vfca vfc vfa ;
where
vfa vdc 2sa sb sc =3
18a
18b
18c
vcha, vchb and vchc are the voltage injected in the line by
series lter, this produces high impedance KX at harmonic
frequencies and produces a gain of K3 at fundamental frequency. Their values are given as
vcha vcr a n1 =n2
vchb vcr b n1 =n2
19a
19b
19c
20
where ifa, ifb, ifc are the series active lter currents and i0fa ,
i0fb , i0fc are the shunt active lter currents. Similarly the
switching functions are dened as sa, sb, sc and s0a , s0b , s0c ,
respectively, for series and shunt active lters.
5.4. Modeling of load
A three-phase rectier with lter capacitor feeding resistive load is considered for three-phase, three-wire system.
The system equations are developed in this section. The
317
21
22
ilb
ilc
If vmax vab
If vmax vbc
id
0
id
id
0
id
If vmax vca
id
id
If vmax vba
If vmax vac
id
id
id
0
0
id
If vmax vcb
id
id
23
318
PCC
500
-500
100
-100
50
-50
PF
100
-100
ca(P)
50
-50
ca(S)
100
-100
232
dc
230
228
226
0.02
0.04
0.06
0.08
0.1
0.12
0.14
0.16
0.18
Time (secs.)
Fig. 5. Dynamic performance of IHF for rectier load with an additional load connected at t = 0.02 s, and is withdrawn at t = 0.10 s. Vca(S), Vca(P):
compensating voltage injected by SAF and shunt active lter.
319
25
Load Current
Source Current with Passive Filters alone
Source current with Hybrid Filter
20
15
10
10
15
20
25
Harmonic Index
Fig. 6. Harmonic spectrum of load current,, supply current with passive lter and with IHF, under ideal supply condition.
350
Voltage at PCC with Passive Filter alone
Voltage at PCC with Hybrid Filter
300
250
200
150
100
50
10
15
20
25
Harmonic Index
Fig. 7. Harmonic spectrum of voltage at PCC with Passive Filter and IHF under ideal supply condition.
Table 2
Percentage THD of dierent hybrid lters with rectier load
iL
iS a
V PCC a
iS b
V PCC b
95.16
96.04
96.85
96.98
45.46
47.37
45.35
110.81
0.37
0.38
0.37
1.29
3.62
3.84
1.09
1.67
3.86
2.92
2.63
3.03
320
25
20
15
10
10
15
20
25
Harmonic Index
Fig. 8. Harmonic spectrum of load current, supply current with passive lter and with IHF, under distorted supply condition.
350
Voltage at PCC with Passive Filter alone
Voltage at PCC with Hybrid Filter
300
250
200
150
100
50
10
15
20
25
Harmonic Index
Fig. 9. Harmonic spectrum of voltage at PCC with passive lter and IHF under distorted supply condition.
7. Conclusion
The performance of IHF system has demonstrated its
ability to control and isolate the harmonics. It has been
observed that the system has a fast dynamic response and
is able to keep the THD of the supply current well below
the limit specied by the IEEE 519 Standard. The cost of
the system is very much reduced due to the use of tuned
passive lters which sinks the harmonic currents. The
scheme has the advantage of simplicity and is able to self
support its DC bus, through power transfer from line at
321