INTRODUCTION
Earthing is one of the most important design aspects of an
electric power system. Proper earthing contributes to the safety of
equipment and personnel as to proper operation of control and other
sensitive circuits. The primary reasons for earthing equipment and
neutral points of a power system are:
- To limit fundamental-frequency electric potential between all
uninsulated conducting objects in a local area.
- To limit touch and step potentials.
- To limit overvoltage on equipment and circuits for various
operation conditions.
- To limit system unbalances.
- To provide for relaying and subsequent isolation of faulted
equipment and circuits when phase to ground faults occur.
- To provide four-wire, three-phase power supply (low-voltage).
Any potential difference, if sufficiently high, between uninsulated
equipment or equipment and ground may damage equipment.
Similarly, such potential difference may set up a shock hazard to
personnel. Next to safety, isolating the faulted equipment or circuits
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
Why Earthing?
- Earthing protects human from danger of electrification caused by
any defect at consumers premises or at supply authority
premises.
- It protects the tall structures like towers against lightning
- Earthing increases the reliability of supply services, provides
stability of voltage condition and it is necessary for proper
functioning of certain equipment like 3-phase star wound
generator.
Ungrounded Systems
Historically, ungrounded systems were used initially because
the first line-to-ground fault would not cause interruption of power.
It did change the voltage to ground of the other two phases to full
line-to-line voltage to ground. Figure 2a shows the phasor
relationships to ground on an ungrounded system. When a second
line-to-ground fault occurs on another feeder, it causes a phase-tophase fault that interrupts two circuits instead of one.
It was discovered that there were multiple motor failures on this type
of system. When the system was analyzed, it was determined that
the distributed capacitance in parallel with a fault in an inductive
device or an arcing fault could be a resonant circuit where the
voltage could be several times normal (five or more times rated
system voltage). These transient overvoltages occurred on lowvoltage systems and caused multiple motor failures. To eliminate
this problem, grounding systems were developed and promoted.
Many ungrounded systems were the result of delta-connected lowvoltage windings. The transient overvoltages problem was
eliminated by grounding one phase of the delta winding. This
eliminated the high transient overvoltages, but still impressed full
line-to-line voltage on the other two phases.
A simple ground-fault detection system for ungrounded systems
consists of three lamps connected phase-to-ground. When all three
lamps have the same brightness, there are no grounds (faults)
present on the system. When one lamp goes out and the other two
are bright, that phase which has the lamp out has a ground fault.
These lamps are a resistance that is in parallel with the distributed
capacitance so it tends to damp some of the transient over voltages.
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
What is Earthing ?
- Earthing is a connection to the general mass of earth by means of
earth electrode, and this connection is achieved by embedding an
earth electrode in earth.
- The effectiveness of the earthing connection is qualified as Earth
Resistance which measured in ohms.
- There are some factors which affect the earthing resistance:
1- the earthing electrode
2- the composition of the soil
3- the temperature of the soil
4- the moisture content of the soil
5- methods of placing earth electrodes in soil
- all these factors effect to reduce the total earth resistance
Earthing Conductors
To limit the potential rise on all metalwork to which persons
and animals normally have access, to a safe value under normal and
abnormal circuit conditions. The bonding together of all normally
exposed metalwork, such as gas, water, central-heating pipe work
etc., and the connection of that bond to the earth terminal, will
prevent the possibility of a dangerous potential difference arising
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
Earth Electrodes
The earth electrode is the component of the earthing system
which is in direct contact with the ground and thus provides a means
of releasing or collecting any earth leakage currents. In earthed
systems it will normally be required to carry quite a large fault
current for a short period of time and so will need to have a crosssectional area large enough to be able to carry this safely. Electrodes
must have adequate mechanical and electrical properties to continue
to meet the demands on them over a relatively long period of time,
during which actual testing or inspection is difficult. The material
should have good electrical conductivity and should not corrode in a
wide range of soil conditions. Materials used include copper,
galvanized steel, stainless steel and cast iron. Copper is generally the
preferred material for reasons described later. Aluminum is
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
Driven Rods
These are the most common form of electrodes (Figure 4),
because they are relatively cheap to install and can be used to reach
into deeper, low resistivity soil with only limited excavation and
backfilling. They are available in a range of lengths, diameters and
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
materials.
Plates
There are several types of plate used for earthing purposes,
but the only type which is generally considered as an electrode
would be solid and of substantial size. Lattice type plates, as
illustrated in Figure 5 are used for potential grading and would not
be expected to pass significant amounts of fault current. They are
normally made of copper or steel mesh (Figure 5).
Horizontal Electrodes
These are made from high conductivity copper strip or
stranded conductor. Strip is normally the preferred material as it has
a larger surface for a given cross section area and is considered to
have a superior performance at higher frequencies, due to a slightly
higher capacitance when installed in the soil. It can be more difficult
to connect (for example to vertical earth rods), so may involve a
slightly higher installation cost.
To reduce overall costs, strip is often used for the electrodes which
will be required to carry most current (i.e. the perimeter electrode
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
Buried Depth
This only provides a marginal reduction in impedance, but at
a relatively high cost, so is not normally considered. It should
however be remembered that the greater the burial depth, the smaller
the voltage gradients on the surface of the soil. Within a substation a
high voltage is required above the electrode, to minimize touch
voltages. However, if an earth electrode extends into a field, then a
low surface voltage is required to reduce step potentials. In some
cases it is advantageous to increase the depth of electrodes to reduce
the risk of electrocution to horses, cattle and other animals. They are
more susceptible to step voltages than humans because of the
distance between their front and rear legs. For rods, this can be
achieved by installing a plastic pipe around the top metre or two of
each rod.
Proximity Effect.
If two earth electrodes are installed close together, then their
zones of influence will overlap and the full benefit possible will not
be achieved. In fact, if two rods or horizontal electrodes are close
together, the combined earth impedance of the two can be virtually
the same as for one, meaning the second is redundant. Spacing,
position and soil characteristics are the dominant factors in this.
Figure 6-6 shows how the overall resistance of two five metre
vertical rods changes as the distance between them is increased.
From this it can be seen that the rods should be more than 4m apart
in uniform soil. Calculations of this type are the basis for the
established practice of installing electrodes at least the same distance
apart as their length.
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
Where:
R = resistance of rod (W)
r = soil resistivity (W m)
l = length of rod (m)
d = diameter of rod (m)
For a short, buried horizontal conductor, the formula is:
Where:
R = resistance of horizontal buried conductor ()
l = length of conductor (m)
d = diameter of conductor (m)
h = height below ground (m)
Q = 1.3 for circular conductors
Q = 1.0 for strip conductors
The above formula has been simplified to:
Resistivity (Ohm-metre)
Sea water
0.1 - 1
5 - 50
London clay
5 - 100
40 - 250
Porous chalk
30 - 100
Quartzite/crystalline limestone
300+
Rock
1,000 - 10,000
Dry concrete
2,000 - 10,000
Wet concrete
30 - 100
Ice
10,000 - 100,000
The two main factors which influence the soil resistivity value are
the porosity of the material and the water content. Porosity is a term
which describes the size and number of voids within the material,
which is related to its particle size and the pore diameter. It varies
between 80/90% in the silt of lakes, through 30/40% in sands and
unconsolidated clay to a few percent in consolidated limestone.
As mentioned previously, it is most unusual to find soil which can
be described as uniform for earthing purposes. We are interested in
soil to a significant depth as the earth fault currents flow deeply into
the ground. There may be thin layer of soil on the surface, with
layers of rock underneath. Each successive layer of rock would have
fewer cracks, be more solid and would be expected to have a higher
resistivity.
If an electrode was installed at the surface, then the distance,
thickness and actual resistivity of each of the layers would be
important factors influencing its eventual resistance value.
Temperature and water content have an important influence on the
soil resistivity and hence the performance of the earthing system. An
increase in water content causes a steep reduction in resistivity until
the 20% level is reached when the effect begins to level out.
Dissolved minerals and salts in the water may help further to reduce
the resistivity, particularly where these are naturally occurring and
do not become diluted over time. The water content will vary
seasonally and is likely to cause variations in the impedance of the
earthing system. Whilst there is data on the effect this has on
individual rods, we are not yet aware of the effect on larger
substations which encompass a larger area. The very high resistivity
of ice (table 1) compared to water, shows why it is necessary to
install the electrodes beneath the freezing line. This is about 0.6
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
Figure 8
System Grounding
In industrial and commercial power systems, the system should
operate grounded. There are, however, other methods of operation
that have been used historically and have operated satisfactorily for
several years but not have all of the advantages of the operation of a
grounded system. Systems can be defined as:
Ungrounded (although these are grounded through the
distributed capacitance of the system)
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
Solidly grounded
Resistance grounded
Resistance
grounded with
grounding
transformer and
resistor
Reactance grounded
resistance grounded systems give the best service under both steady
state and transient conditions.
Other Considerations
In system grounding practices, the selection of grounding
points is important. There are several factors to be considered in
selecting the grounding points:
Grounding at each voltage level
Grounding at source, but not at load
Grounding at each major source bus
Number of sources
Reference ground during isolated operation
At least one grounding point at each voltage level is necessary. This
is achieved because most of the transformers have delta
(ungrounded on the high side) - star (grounded on the low side)
windings. Autotransformers have common neutrals. At every stepdown level, the transformer neutral is grounded on the low side.
Where delta-delta windings are used, or when isolated operation
creates a floating neutral conditions, a grounding transformer is
required.
Whenever impedance grounding is used, the impedance in neutral
should be applied properly. The five important factors are:
Limiting of line to ground fault current
Providing sufficient fault current for detection and relay
operation
Having proper thermal rating (I2 R)
Having proper voltage rating
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
The cost of this one ohm earth would be of the order of 25 using
galvanized mild-steel rods and bare-copper interconnecting
conductor. This is about the average cost of an earth with a
resistance of this order; the cost of higher resistance earth in average
conditions may be estimated on a proportional basis from this figure,
which is very much less than the cost of installing less efficient earth
electrodes.
the "step voltage". Vs < V touch which depends on the length of step
(on an average 80 cm.) and the distance from the human being up to
the earthing arrangement .
Factors to Consider
Low soil resistivity is to some extent tied to an electrolytic
mechanism with such characteristics as - chemicals composition,
soil ionization, homogenous grain size and even distribution, playing
a large determinant due to the effect on the retention of soil moisture
and packing density in contact with the electrode.
Obtaining a satisfactory earth resistance has always been a problem
in areas of poor soil conductivity. Most National and International
Lightning Protection codes require an earth resistance of 10 ohms or
less to be provided for a lightning protection installation.
The laying of copper grids, tapes and rods alone may not always
provide the desired result. Even if copper materials are used and the
specified resistance level is achieved, seasonal fluctuations in soil
moisture can cause variations in the resistance level. In dry periods it
is possible for the earth resistance to rise above the as installed level.
This variation is earth resistance can affect the integrity of the entire
lightning protection system. If suitable electrical resistance cannot
be simply and economically attained by the installation of a standard
earth grid, an application of earth improving compounds will assist.
Such compounds consist of chemical solutions of good electrical
conductivity which, when mixed with water and poured onto the
earthing grid and surrounding soil become a gelatinous mass,
forming an integral part of the overall earthing system. Field tests
have shown dramatic improvement in earth resistance when such
compounds are added to high resistivity soils such as shale or silica.
Soil resistivity
Making a Measurement
When designing an earthing system to meet safety and
reliability criteria, an accurate resistivity model of the soil is
required. The following sections outline the major practical aspects
of the measurement procedure and result interpretation.
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
1. Principles
Soil resistivity values vary widely depending on the type of
terrain, e.g., silt on a river bank may have resistivity value in the
order of 1.5 -m, whereas dry sand or granite in mountainous
country areas may have values higher than 10,000 -m. Factors that
affect resistivity may be summarized as: Type of earth (e.g., clay, loam, sandstone, granite).
Stratification; layers of different types of soil (e.g., loam backfill
on a clay base).
Moisture content; resistivity may fall rapidly as the moisture
content is increased, however, after a value of about 20% the rate
of decrease is much less. Soils with moisture content greater than
40% do not occur very often.
Temperature; above freezing point, the effect on earth resistivity is
practically negligible.
Chemical composition and concentration of dissolved salt.
Presence of metal and concrete pipes, tanks, large slabs, cable
ducts, rail tracks, metal pipes and fences, etc.
Topography; rugged topography has a similar effect on resistivity
measurement as local surface resistivity variation caused by
weathering and moisture.
When defining the electrical properties of a portion of the
Earth, a distinction between the geoelectric and geologic model is
required. In the geoelectric model the boundaries between layers are
determined by changes in resistivity, being primarily dependent
upon water and chemical content, as well as texture. The geologic
model, based upon such criteria as fossils and texture, may contain
several geoelectric sections. The converse is also common.
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
with
testing
and
interpretation
techniques
Figure 13
(a) Test Method
Factors such as maximum probe depths, lengths of cables
required, efficiency of the measuring technique, cost (determined by
the time and the size of the survey crew) and ease of interpretation
of the data need to be considered, when selecting the appropriate test
type. Three common test types are shown in figure 14. The
Schlumberger array is considered more accurate and economic than
the Wenner or Driven Rod methods, provided a current source of
sufficient power is used.
that dont cover a wide area. It is simple to carry out and requires a
minimal amount of calculation to obtain a result.
This method is generally not suited to large earthing installations, as
the stake separations needed to ensure an accurate measurement can
be excessive, requiring the use of very long test leads.
Normally, the outer test electrode, or current test stake, is driven into
the ground 30 to 50 meters away from the earth system, and the
inner electrode, or voltage test stake, is then driven into the ground
mid-way between the earth electrode and the current test stake, and
in a direct line between them.
The Fall of Potential method incorporates a check to ensure that the
test electrodes are indeed positioned far enough away for a correct
reading to be obtained. It is advisable that this check be carried, as it
is really the only way of ensuring a correct result.
To perform a check on the resistance figure, two additional
measurements should be made; the first with the voltage test
electrode (P) moved 10% further away from the earth under test, and
the second measurement with the (P) electrode moved 10% closer to
the earth under test.
If these two additional measurements are in agreement with the
original measurement, within the required level of accuracy, then the
test stakes have been correctly positioned and the DC resistance
figure can be obtained by averaging the three results. However, if
there is substantial disagreement amongst any of these results, then
it is likely that the stakes have been incorrectly positioned, either by
being too close to the earth system being tested, too close to one
another or too close to other structures that are interfering with the
results. The stakes should be repositioned at a larger separation
distance or in a different direction and the three measurements
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim
the measurements with the inner test stake moved 10% of the earth
electrode-inner test stake separation distance, as before.
The main disadvantage with this method is that the theory on
which it is based relies on the assumption that the underlying soil is
homogeneous, which in practice is rarely the case. Thus, care should
be taken in its use and a soil resistivity survey should always be
carried out. Alternatively, one of the other methods should be
employed.
Other Test Methods
Many other methods exist for taking earth resistance
measurements. Many of these methods have been designed in an
attempt to alleviate the necessity for excessive electrode separations,
when measuring large earth systems, or the requirement of having to
know the electrical centre of the system.
Three such methods are briefly described below. Specific
details are not given here, but instead the reader is referred to the
relevant technical paper where these systems are described in detail.
(a) The Slope Method
This method is suitable for use with large earthing systems,
such as sub-station earthing. It involves taking a number of
resistance measurements at various earth systems to voltage
electrode separations and then plotting a curve of the resistance
variation between the earth and the current. From this graph, and
from data obtained from tables, it is possible to calculate the
theoretical optimum location for the voltage electrode and thus, from
the resistance curve, calculate the true resistance.
EARTHING Prepared by : Dr. Alaa Baiumy Abd Alazim