Referring to rating & terminalmarking plate, identify the H.V and L.V terminal,
whichcorresponding to one phase. E.g. For a vector Group of Dyn-11,H.V
Terminal 1U, 1V &L.V terminal 2U,2N correspond to U phase. Apply 415V AC,
50Hz supply to H.V side and measure the voltageon the L.V side. Measure
these voltages on all taps and note them
Activity (8)
FILTERS
Add to collectionReviewAdd NoteLike
Reply
praveen added this note
excellent detials about commissioning
praveen liked this
1 hundred reads
Rahul Kumar liked this
Sharad_B_Patel liked this
lekanola liked this
Arvind Singh Rathore liked this
santoshkumar liked this
Similar to Commissioning Report for HT
Realistic Ct Specs
CG Power Transformers
Bushings
Testing Ppt[1]
METHOD STATEMENT
CircuitBreaker
Excel Formulas
135692909-Dobble
HV Circuit Breakers
micom p343
Power Transformer
More From This User
TU Package Options2
.TXT
DOWNLOAD
Recommended
Realistic Ct Specs
kapil
design and technical requirements for ehv current transformer in large switch...
CG Power Transformers
Hamayoun Murtaza
Power Transformer
.TXT
DOWNLOAD
ABOUT
Browse books
Browse documents
About Scribd
Meet the team
Our blog
Join our team!
Contact Us
SUPPORT
Help
FAQ
Press
Purchase help
AdChoices
PARTNERS
Publishers
Developers / API
LEGAL
o
Terms
Privacy
Copyright
MEMBERSHIPS
Join today
Invite Friends
Gifts
STAY CONNECTED
UPLOAD LIBRARY
BooksAudiobooks
DOWNLOAD
STANDARD VIEW
FULL VIEW
OF 50
1
8
Commissioning Report
for HT
Ratings:
(0)|Views: 1,673|Likes: 8
Published by rstephenraj
See more
STERLING &
WILSON LTD
HT
COMMISSIONING
48
STERLING
& WILSON
LTD
Ref.No
:Page.No:Date :
CLIENT
:PROJECT :
TEST REPORT
FOR OVER
CURRENT /
EARTH FAULT
RELAY-PRE
COMMISSIONI
NG
Date
:Phase/ PS Startin
g ClosingUnit (A)
T.M.S. Current Cur
rent(A)
(A)Operating
time (Sec)
atmultiples of
PS2 5 10
5
. Operating Cur
rent Check
(For
instantaneous
unit)i) O/C
UnitSetting Curre
nt (A)Operating C
a) Correct
operation of
appropriate
indicator / Aux.
relay
:b) Correct initiati
on of alarm conta
cts :c) Correct cir
cuit breaker tripp
ing contacts :
7. Service setti
ng
O/C(R) O/C(Y)
O/C(B)
E/FP.S. (A) :T.M.S :
Instantaneous un
it (A) :
8. Remarks
STERLING & WI
LSON STERLING
& WILSON CLIE
NT/CONSULTAN
T
(Testing
Engineer)
STERLING &
WILSON LTD
HT
COMMISSIONING
49
AP
PE
ND
IX
E
STERLING &
WILSON LTD
HT
COMMISSIONING
50
STERLING
& WILSON
LTD
Ref.No :Page.
No:Date
:CLIENT
:PROJECT :
COMMISSION
ING REPORT
FOR
ELECTRICAL
SYSTEM
1. System Ref.
Date:
Location
2. Check for
completeness
of installation
of Electrical
system
:
. Check
the following
points before
charging the
system
Clean the entire
system which is
going to be charg
ed :Plug the extra
side
Voltage:Check th
e Transformer par
ameters and othe
r conditions :Che
ck the LT side
voltagePhase to
Phase -Phase to
Earth
-Check the phase
r of Transformer
and check the LT
panel Bus section
is charged :Load
the Transformer s
lowly and check
all the parameter
s are OK :Check t
he Load manager
and other meters
are functioning pr
operly :Check the
relay setting for a
ll outgoing feeder
s and keep it min
imum :Close the
balance out goin
g feeders and giv
e the power to all
panels :Load all
ment which is mo
unted on panels :
4. Remarks
STERLING & WI
LSON STERLING
& WILSON CLIE
NT/CONSULTAN
T
(Testing
Engineer)
Activity (8)
FILTERS
CG Power Transformers
Bushings
Testing Ppt[1]
METHOD STATEMENT
CircuitBreaker
Excel Formulas
135692909-Dobble
HV Circuit Breakers
micom p343
Power Transformer
TU Package Options2
.TXT
DOWNLOAD
Recommended
Realistic Ct Specs
kapil
design and technical requirements for ehv current transformer in large switch...
CG Power Transformers
Hamayoun Murtaza
Power Transformer
Previous|NextPage 1 of 8
.TXT
DOWNLOAD
AB O UT
Browse books
Browse documents
About Scribd
Our blog
Contact Us
S UP P O R T
Help
FAQ
Press
Purchase help
AdChoices
PAR TNE RS
Publishers
Developers / API
L E G AL
Terms
Privacy
Copyright
ME MBE RS HI P S
Join today
Invite Friends
Gifts
CT SIZING
CALCULATION FOR
TRANSIENT OPERATION
Navigation
Project Home
INTRODUCTION
PROCEDURE
FUNDAMENTALS OF
CT
PRAG NOTES
RELAY CATALOGS
AND CT SIZING FILES
SIMULATION MODEL
OF CT
CT UNDER
SYMMETRICAL FAULT
CURRENT
CT UNDER
PROTECTION
STEPS FOR DOING
CT SIZING CALCULATION
FOR TRANSFORMER
EXAMPLE
Transformer details
PRACTICAL RESULTS
VB BASED TOOL
attachments
calender
Help
Sitemap
=385 A
Max feeder current on secondary side= (1.1xMVA rating x1000) / (1.73x Vs )
= (1.1 x120x1000) / (1.732x33)
=2309 A
CT ratio selected
IP(HV)
500
Selected tap
main CT at H
IP(LV)
2500
Selected tap
main CT at L
IS
Nominal sec
current
Primary side CT
Through fault MVA of transformer =MVA rating/% impedance at ve tap
=120/.1130=1062.417 MVA
Through fault current on primary side IPF(T)=fault MVA/1.732xVP
=1062.41/1.732 x 220=2.79 kA
Calculate total secondary resistance= RCT+Rlead+RB
=2.5+1.916+0.2 ohms
Calculate knee point voltage Vk( IPF(T)/N)(RCT+Rlead+RB)
Vk (2790/500) (2.5+1.916+0.2) V
Vk 25.75 V
Secondary side CT
Through fault MVA of transformer =MVA rating/% impedance at ve tap
=120/.1130=1062.417 MVA
Through fault current on primary side IPF(T)=fault MVA/1.732xVP
=1062.41/1.732 x 33=18.71 kA
Calculate total secondary resistance= RCT+Rlead+RB
=2.5+1.916+0.2 ohms
Calculate knee point voltage Vk ( IPF(T) /N)(RCT+Rlead+RB)
Vk (1871/500) (2.5+1.916+0.2) V
Vk 17.27 V