as it would affect the protective system operation and thus, the system
security.
Contrary to measuring CTs - which have to maintain their accuracy only over
their measuring range, protective CTs will have to remain accurate for currents
many times in excess of their rated current, for, only then the protection
system would read the primary conditions exactly and would react accordingly.
Hence, a protection CT must remain stable - it must not saturate, for currents
that are many multiples of its rated current. This level of saturation in
protection CTs is denoted by a term called ALF - Accuracy Limiting Factor.
Typical ALFs are 5, 10, 15, 20 & 30.
A 5P10 CT means this is a protection CT with a composite error of +/- 5% and
this error will be maintained upto 10 times the rated primary current of the CT.
If the primary current is more than 10 times the rated primary current, then
this CT will saturate and will not reproduce secondary current linearly with the
primary current.
Now, for a given CT, the accuracy limit voltage (ALV) is fixed at the time of
designing the CT. That is,
ALV = ALF x ISec. Rated x (ZCT + ZExt.)
Where,
ALV = Accuracy Limit Voltage in Volts
ALF = Accuracy Limiting Factor for the protection core
I
Sec. Rated
Ext