Anda di halaman 1dari 18

RASTHRIYA PROJECT

06484

PROJECT No.:

SAFETY AND FIRE FIGHTING SYSTEM (UNIT 00)

PROCESS DATA SHEET


FIRE FIGHTING TANK
00-FB-301

00

22/11/2013

ISSUE FOR PROPOSAL

ABG

JLS

JRF

Rev. No:

DATE

DESCRIPTION

PREPARED BY

CHECKED BY

APPROVED BY

DOCUMENT TITLE
PROCESS CONDENSATE TANK DATA SHEET
DOCUMENT NUMBER

06484-00-120-DS-0003

REVISION
PAGE

OF

00

This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its
characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

SAFETY AND FIRE FIGHTING SYSTEM (00)


RCF-GAIL-CIL-FCIL

ABG

CLIENT

Checked

JLS

LOCATION TALCHER COMPLEX, ODISHA (INDIA)

Approved

JRF

Item N:

00-FB-301

Service:

FIRE FIGHTING TANK

Fluid:

SERVICE WATER (Note 1)

Nominal capacity:

1357

m3

Net Capacity:

1101

m3

Diameter (ID)

12000

mm

Height

12000

mm

8
9

TANK PRESSURE

Quantity:

06484-00-120-DS-0003
2 OF 3

ATM.

kg/cm g

Design

0,03

kg/cm2 g

-0,005

kg/cm2 g

Vacuum design

11

Operating

TANK
TEMPERATURE

Operating

10

12

DOC N
PAGE
REV

REV

Prepared

AMB

Design

80

C
kg/cm2 g

13

Operating Press.

14

Operating Temp.

15

Design Press.

kg/cm2 g

COIL

16

Design Temp.

17

Nom. Diameter

in

18

Length

MATERIAL

19
20

Shell / Roof

21

Cladding

22

Coil

CORR. ALLOW.

CS

1,5

mm

Nota 6

mm

mm

23
24

Type

25
26

X Conical Roof

Floating Roof

X API

Refrigerated

Bottom

27
28

Steam out Conditions:

kg /cm2 g

Short term maximum temperature:

kg /cm2 g

Flat

Short term minimun temperature:

kg /cm g

Conical Pointing Downwards

TANK VENTING DATA:

Conical Pointing Upwards

- Blanketing:

29

Code:

API STD.650

30

Stress Relieve for Process Reasons:

31

Insulation:

Type

Not Insulated

Thickness

32

mm

NO

- Max inbreathing rate (Note 4):

kg/h

- Max outbreathing rate (Note 4):

kg/h

- Emergency relief:

Flow (Note 4):

- Relieving conditions:

Temperature:

NOZZLES

33

kg/h

/MW:

C /Pressure:

kg/kmol
kg/cm2 g

NOZZLES

34

Quantity

Size

Service

Type

Quantity

Size

Service

Type

35

N1

4"

INLET

RF

M1

24"

MAN HOLE IN SHELL

API 650

M2

24"

MAN HOLE IN ROOF

API 650

36

N2

12"

OUTLET

RF

37

N3

6"

OVERFLOW

RF

38

N4

4"

DRAIN (Note 7)

RF

39

N5

12"

VENT (Note 2,3,4)

BW

40

N6

8"(Note 8)

LEVEL GAUGE

RF

41

N7

8"(Note 8)

LEVEL TRANSMITTER

RF

42

N8

2"(Note 8)

TEMP. GAUGE

RF

43

N9

8"(Note 9)

FIRE PUMP TESTING


HEADER

RF

44
45
46
47
48
49
50

See general notes on next page.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

SAFETY AND FIRE FIGHTING SYSTEM (00)

ABG

CLIENT

RCF-GAIL-CIL-FCIL

Checked

JLS

LOCATION

TALCHER COMPLEX, ODISHA (INDIA)

Approved

JRF

DOC N

06484-00-120-DS-0003

PAGE

3 OF 3

REV

Prepared

GENERAL NOTES FOR TANK:

00-FB-301

2
3

1. Liquid SG = 0,995 @ 32C

2. Swan neck and bird screen to be fitted. No other elements which may obstruct the flow area allowed.

3. To be confirmed by vendor

4. Maximum filling rate: 50 m3/h

Maximum pumpout rate: 318 m3/h

Tank Vendor to confirm vent size for 1,5 times indicated filling/pump out rates according API 2000. The open drain flow shall be considered.

5.- Drawoff Swamp.

6.- Full Epoxy Lining is required

10

7.- Tank should be 100% drainable.

11

8.- To be Confirmed by Instrument Deparment

12

9.- To be confirmed with final fire pumps

13

10.- Fire water capacity to be confirmed during detail desgin, after risk asessment.

14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

RASHTRIYA PROJECT
06484

PROJECT No.:

NITRIC ACID PLANT, 01

TANK PROCESS DATA SHEET


START-UP TANK
01-FB-001

00

22/11/2013

ISSUE FOR PROPOSAL

FJ

JLS

JR

Rev. No:

DATE

DESCRIPTION

PREPARED BY

CHECKED BY

APPROVED BY

DOCUMENT TITLE
START-UP TANK DATA SHEET
DOCUMENT NUMBER

06484-01-120-DS-0023

REVISION
PAGE

OF

00

This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its
characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

Prepared

FJ

JOB N

06484

UNIT

Nitric Acid Plant (unit 01)

CLIENT

RDF-GAIL-CIL-FCIL

LOCATION

Talcher Complex, Odisha (India)

JRF

DOC. N

06484-01-120-DS-0023

PAGE

2/3

REV

JLS

Approved

REV

Checked

Item N:

Service:

Fluid:

Nominal capacity:

Net Capacity:

Quantity:

01-FB-001

NITRIC ACID 60% (Note 1)


m3

198

m3

Diameter (ID)

6000

mm

Height

7000

mm

Operating

8
9

START-UP TANK

TANK PRESSURE

Design

Atm.

bar g

0.1

bar g

10

Vacuum design

-0.02

bar g

11

Operating

50

Design

80

12

TANK
TEMPERATURE

13

Operating Press.

14

Operating Temp.

15

Design Press.

bar g

16

Design Temp.

17

Nom. Diameter

in

18

Length

bar g

COIL

MATERIAL

19
20

Shell

CORR. ALLOW.

AISI 304L

mm

21

Cladding

mm

22

Roof

mm

23
24

Type

25

X Conical Roof

Floating Roof

Steam out Conditions:

kPa g

X API

Refrigerated

Short term maximum temperature:

kPa g

kPa g

26

Bottom

Flat

Short term minimun temperature:

27

NOTE (2)

Conical Pointing Downwards

TANK VENTING DATA:

Conical Pointing Upwards

- Blanketing:

28
29

Code:

30

Stress Relieve for Process Reasons:

API STD.650

31

Insulation:

Type

Not Insulated

Thickness

32

NO

- Max inbreathing rate :

kg/h

- Max outbreathing rate :

kg/h

- Emergency relief:
mm

kg/h

Flow :

- Relieving conditions: Temperature:

NOZZLES

33

/MW:

C /Pressure:

kg/kmol
kPa g

NOZZLES

34

Quantity

Size

Service

TYPE

Quantity

Size

Service

TYPE

35

N1

4''

ACID INLET DA-002

RF

N11

2"

DEMI WATER

RF

2''

ACID INLET FROM


FA-002

RF

N12

2"

SEAL DRAIN

RF

36

N2

37

N3

4''

RECIRCULATION

RF

N13

4"

SPARE

RF

38

N4

2''

DRAIN

RF

N14

2"

NITRIC ACID TO GA-016

RF

39

N5

4''

LEVEL

RF

M1

24"

MAN HOLE in Roof

RF

40

N6

2''

GA-011 RETURN

RF

M2

24"

MAN HOLE in Sheel

RF

41

N7

6''

ACID OUTLET

RF

42

N8

2''

T INSTRUMENT

RF

43

N9

10"

VENT

RF

N10

6"

OVERFLOW

RF

44
45
46

See general notes on next page.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

Nitric Acid Plant (unit 01)

CLIENT

RDF-GAIL-CIL-FCIL

FJ

Checked

JLS

LOCATION Talcher Complex, Odisha (India)

Approved

JRF

DOC. N

06484-01-120-DS-0023

PAGE

3/3

REV

Prepared

GENERAL NOTES FOR TANK:

01-FB-001

2
3

1. Liquid SG = 1.38 @ 10C

2. Tank bottom with 0.5% slope to N4

3. Stainless steel bolt and nuts

4. The equipment 01-FA-008 is supported over the vent nozzle

5. Level connections sizes to be confirmed by instrument department

6, N1, N2, N3 with dip pipe and shyphon breaker

7, Wear plate at bottom, and dip pipes in inlet N1, N2, N3, N6

10

8. Equipment 01-FA-007 will be located above nozzle n9

11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44

RASTHRIYA PROJECT
06484

PROJECT No.:

AMMONIUM NITRATE SOLUTION STORAGE (UNIT 05)

VESSEL PROCESS DATA SHEET


AN SOLUTION TANKS
05-FB-101 A/B

00

22/11/2013

ISSUE FOR PROPOSAL

MSP

JLS

JRF

Rev. No:

DATE

DESCRIPTION

PREPARED BY

CHECKED BY

APPROVED BY

DOCUMENT TITLE
AN SOLUTION TANKS PROCESS DATA SHEET
DOCUMENT NUMBER

06484-05-120-DS-0001

REVISION
PAGE

OF

00

This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its
characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

AMMONIUM NITRATE SOLUTION STORAGE (05)

MSP

CLIENT

RCF-GAIL-CIL-FCIL

Checked

JLS

LOCATION

TALCHER COMPLEX, ODISHA (INDIA)

Approved

JRF

DOC N

06484-05-120-DS-0001

PAGE

2 OF 3

REV

Prepared

Item N:

05-FB-101 A/B

Service:

AMMONIUM NITRATE SOLUTION STORAGE TANK

Fluid:

Nominal capacity:

Net Capacity:

Diameter (ID)

Height

12

1220 (2)

m3

12000

mm

10800

mm

Operating

kg/cm2 g

Atm.

+0,1 / -0,02 kg/cm2 g

Design

TANK PRESSURE

Vacuum design

10
11

AMMONIUM NITRATE SOLUTION (96 %) (1)

8
9

Quantity:

TANK
TEMPERATURE

kg/cm g

Operating

140

Design

180

C
2

13

Operating Press.

5.1

kg/cm g

14

Operating Temp.

152

Design Press.

9/FV

kg/cm2 g

Design Temp.

200

15

COIL

16
17

Nom. Diameter

(Notes 4,5) 6 mm

18

Length

(Notes 4,5) 6 mm

19
20

Shell / Roof

21

Cladding

22

Coil / Internals

MATERIAL

CORR. ALLOW.

AISI 304L

mm

mm

AISI 304L

mm
REV

23
24

Type

25
26

Bottom

27
28

X Conical Roof

Floating Roof

Steam out Conditions:

kg/cm2 g

X API

Refrigerated

Short term maximum temperature:

kg/cm2 g

Flat

Short term minimun temperature:

kg/cm2 g

Conical Pointing Downwards

TANK VENTING DATA:

Conical Pointing Upwards

- Blanketing:

29

Code:

30

Stress Relieve for Process Reasons:

31

Insulation:

32

API STD.650
-

Type

Heat conservation

Thickness

100

mm

(19)

NO

- Max inbreathing rate :

(8)

kg/h

- Max outbreathing rate :

(8)

kg/h

- Emergency relief:

Flow :

- Relieving conditions:

Temperature:

NOZZLES

33
34

Quantity

Size

35

N1

6"

36

N2

37

N3

38

kg/h MW:
-

Pressure:

kg/kmol

kg/cm2 g

NOZZLES
Type

Quantity

Size

AN SOLUTION INLET (9) (14)

RF

N12

2"

BOTTOM COIL STEAM INLET

RF

2"

AMMONIA GAS (9) (18)

RF

N13 A/B

4"

KICKBACK LINES FROM PUMPS (9)

RF

2"

PROCESS CONDENSATE (9)

RF

N14

2"

BOTTOM COIL CONDENSATE OUTLET

RF

N4

4"

DRAIN (13)

RF

N15

2"

SHELL COIL STEAM INLET

RF

39

N5 A/B

6"

LEVEL (7)

RF

N16

2"

SHELL COIL CONDENSATE OUTLET

40

N6

2"

ANSOL SAMPLE RETURN (9)

RF

M1

24"

MANHOLE IN SHELL

API 650

41

N7

8"

AN SOLUTION OUTLET (14)

RF

M2

24"

MANHOLE IN ROOF

API 650

42

N8 A/B/C/D

2"

TEMPERATURE (3)

RF

43

N9

12"

VENT (8)

RF

44

N10

6"

OVERFLOW

RF

45
46
47
48
49
50

See general notes on next page

Service

Service

Type

RF

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

AMMONIUM NITRATE SOLUTION STORAGE (05)

MSP

CLIENT

RCF-GAIL-CIL-FCIL

Checked

JLS

LOCATION

TALCHER COMPLEX, ODISHA (INDIA)

Approved

JRF

DOC N

06484-05-120-DS-0001

PAGE

3 OF 3

REV

Prepared

GENERAL NOTES FOR TANK: 05-FB-101 A/B

2
3

1. Liquid density at 140C = 1423,6 kg/m .

2. Total tank volume (approx) between top TL and bottom TL. Working volume: 1074 m3 (volume between HLL and LLL).

3. At different height. Two of them below LLL.

4. Bottom coil:

- Comprised of two independent coils with independent steam inlet and condensate outlet.

- The lenght of each coil will be minimum 50 m, the size 2".

- Both pipe coils will be placed at the bottom of tank with a proper support arrangement to be developed by vendor.

10

- Each coil will cover the complete surface of bottom.

11

- A clearance of minimum 300 mm from the floor shell shall be maintained while arranging the two pipes.

12

5. Shell coil:

13

- Two helicoidal coils of 40 mm diameter will be installed inside the tank to heat along shell from LLL to HHLL.

14

- Adequate arrangements shall be made to support helicoidal coils about 300 mm from shell inside.

15
16

- The minimum lenght shall be 70 m for each coil.


6. Stainless steel bolt and nuts.

17

7. Level connections sizes to be confirmed by Instrument department.

18

8. Maximum filling rate: 33 m3/h. Maximum pumpout rate: 90 m3/h. Preliminary vent size. Tank vendor to confirm vent size 1,5 times the indicated filling / pumpout rates

19

according to API 2000. Vent to be insulated to retain heat to prevent blockage due to crystallization.

20

9. Line with dip pipe and syphon breaker. Syphon breaker above HHLL.

21

10. Copper, tin, zinc and their alloys are not allowed in tank manufacturing.

22

11. Environmental conditions:

- Minimum air temperature: 12 C (dry bulb).


- Maximum wind speed: As per IS 875 Part 3

23
24

12. 4" nozzle to be used for dip pipe calibration of level instruments

25

13. Drain to be from the bottom of the tank and at the lowest end to ensure full drainage of the tank.

26

14. Nozzle N1 and nozzle N7 to be on opposite ends.

27

15. Mixing eductors to be close to tank floor ( to pump suction nozzle N7, on the same elevation) and supported off the floor of the tank. Eductors to be pointed tangential to

28

the tank wall angled upward at 15 to horizontal. Provide mechanical reinforcement to handle nozzle vibration. Mixing eductors to be supplied by vendor on kickback lines

29

as indicated. Tank design and eductors location shall ensure that there are no stagnant areas that can accumulate contaminants or pockets where ammonium nitrate

30

can be confined within the equipment or structural items within the tank.

31

16. It is considered a small sump at bottom for pump suction nozzle N7.

32

17. Approximated dimmensions.

33

18. Ammonia sparger: 2" diameter of downcomer, 40 m pipe in circular shape of 4000 mm diameter with 3 mm diameter holes separated 50 mm each other along an axis.

34

Sparger 350 mm below minimum level. Locate ammonia sparger near mixing eductor suction nozzle to provide an adequate ammonia mixing.

35

19. Insulation also on roof.

36

20. Both tank floor as well as sump must be isolated.

37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52

AMMONIA INJECTION DETAILS FOR TANK: 05-FB-101 A/B

RASTHRIYA PROJECT
06484

PROJECT No.:

AMMONIUM NITRATE SOLUTION STORAGE (UNIT 05)

VESSEL PROCESS DATA SHEET


PROCESS CONDENSATE TANK
05-FB-102

00

22/11/2013

ISSUE FOR PROPOSAL

MSP

JLS

JRF

Rev. No:

DATE

DESCRIPTION

PREPARED BY

CHECKED BY

APPROVED BY

DOCUMENT TITLE
PROCESS CONDENSATE TANK DATA SHEET
DOCUMENT NUMBER

06484-05-120-DS-0002

REVISION
PAGE

OF

00

This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its
characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

AMMONIUM NITRATE SOLUTION STORAGE (05)

CLIENT

RCF-GAIL-CIL-FCIL

Checked

JLS

LOCATION

TALCHER COMPLEX, ODISHA (INDIA)

Approved

JRF

DOC N

06484-05-120-DS-0002

PAGE

2 OF 3

REV

MSP

REV

Prepared

Item N:

05-FB-102

Service:

PROCESS CONDENSATE TANK

Fluid:

PROCESS CONDENSATE (Note 1)

Nominal capacity:

106

m3

Net Capacity:

95

m3

Diameter (ID)

4500

mm

Height

7200

mm

8
9

TANK PRESSURE

Quantity:

Operating

ATM.

kg/cm2 g

Design

0,03

kg/cm2 g

-0,005

kg/cm2 g

10

Vacuum design

11

Operating

50

Design

100

12

TANK
TEMPERATURE

kg/cm2 g

13

Operating Press.

14

Operating Temp.

15

Design Press.

kg/cm2 g

COIL

16

Design Temp.

17

Nom. Diameter

in

18

Length

MATERIAL

19

CORR. ALLOW.

20

Shell / Roof

AISI 304L

mm

21

Cladding

mm

22

Coil

mm

23
24

Type

25
26

X Conical Roof

Floating Roof

Steam out Conditions:

X API

Refrigerated

Short term maximum temperature:

Flat

Short term minimun temperature:

Conical Pointing Downwards

TANK VENTING DATA:

Conical Pointing Upwards

- Blanketing:

Bottom

27
28
29

Code:

API STD.650

30

Stress Relieve for Process Reasons:

31

Insulation:

Type
Thickness

32

mm

kg /cm2 g

kg /cm2 g

kg /cm2 g

NO

- Max inbreathing rate (Note 4):

kg/h

- Max outbreathing rate (Note 4):

kg/h

- Emergency relief:

Flow (Note 4):

- Relieving conditions:

Temperature:

NOZZLES

33

kg/h

/MW:

C /Pressure:

kg/kmol
kg/cm2 g

NOZZLES

34

Quantity

Size

Service

Type

Quantity

Size

Service

Type

35

N2

4"

PROCESS CONDENSATE OUTLET

RF

M1

24"

MAN HOLE IN SHELL

API 650

36

N3

4"

OVERFLOW

RF

M2

24"

MAN HOLE IN ROOF

API 650

37

N4 22/11/2013

2"

MIN.FLOW RECYCLE

RF

38

N5

2"

DRAIN (Note 5)

RF

39

N6

3"

VENT (Note 2,3)

BW

40

N7

4"

LEVEL TRANSMITTER

RF

41

N8

2"

LEVEL TRANSMITTER

RF

42

N9

2"

TEMP. GAUGE

RF

43

N10

2"

CONDENSATE INLET

RF

44
45
46
47
48
49
50

See general notes on next page.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

AMMONIUM NITRATE SOLUTION STORAGE (05)


RCF-GAIL-CIL-FCIL

MSP

CLIENT

Checked

JLS

LOCATION

TALCHER COMPLEX, ODISHA (INDIA)

Approved

JRF

DOC N

06484-05-120-DS-0002

PAGE

3 OF 3

REV

Prepared

GENERAL NOTES FOR TANK:

05-FB-102

2
3

1. Liquid SG = 0,988 @ 50C

2. Swan neck and bird screen to be fitted. No other elements which may obstruct the flow area allowed.

3. To be confirmed by vendor

4. Maximum filling rate: 15 m3/h

Liquid SG= 1,00 @ T amb

7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

Maximum pumpout rate: 30 m3/h

Tank Vendor to confirm vent size for 1,5 times indicated filling/pump out rates according API 2000. The open drain flow shall be considered.
5. Drawoff Swamp.

RASHTRIYA PROJECT
06484

PROJECT No.:

NITRIC ACID STORAGE, 06

TANK PROCESS DATA SHEET


NITRIC ACID STORAGE
06-FB-001 A/B

00

22/11/2013

ISSUE FOR PROPOSAL

FJ

JLS

JR

Rev. No:

DATE

DESCRIPTION

PREPARED BY

CHECKED BY

APPROVED BY

DOCUMENT TITLE
NITRIC ACID STORAGE DATA SHEET
DOCUMENT NUMBER

06484-06-120-DS-001

REVISION
PAGE

OF

00

This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its
characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

Prepared

JOB N

FJ

06484

UNIT

Nitric Acid Storage (unit 06)

CLIENT

RDF-GAIL-CIL-FCIL

LOCATION

Talcher Complex, Odisha (India)

JRF

DOC. N

06484-06-120-DS-001

PAGE

2/3

REV

JLS

Approved

REV

Checked

06-FB-001 A/B Quantity:

Item N:

Service:

Fluid:

Nominal capacity:

Net Capacity:

NITRIC ACID 60% (Note 1)


m3

3728

m3

Diameter (ID)

17500

mm

Height

15500

mm

Operating

8
9

NITRIC ACID STORAGE

TANK PRESSURE

Design

Atm.

bar g

0.1

bar g

10

Vacuum design

-0.02

bar g

11

Operating

50

Design

80

12

TANK
TEMPERATURE

13

Operating Press.

14

Operating Temp.

15

Design Press.

bar g

16

Design Temp.

17

Nom. Diameter

in

18

Length

bar g

COIL

MATERIAL

19
20

Shell

CORR. ALLOW.

AISI 304L

mm

21

Cladding

mm

22

Roof

mm

23
24

Type

25

X Conical Roof

Floating Roof

Steam out Conditions:

kPa g

X API

Refrigerated

Short term maximum temperature:

kPa g

kPa g

26

Bottom

Flat

Short term minimun temperature:

27

NOTE (2)

Conical Pointing Downwards

TANK VENTING DATA:

Conical Pointing Upwards

- Blanketing:

28
29

Code:

30

Stress Relieve for Process Reasons:

API STD.650

31

Insulation:

Type

Not Insulated

Thickness

32

NO

- Max inbreathing rate :

kg/h

- Max outbreathing rate :

kg/h

- Emergency relief:
mm

kg/h

Flow :

- Relieving conditions: Temperature:

NOZZLES

33

/MW:

C /Pressure:

kg/kmol
kPa g

NOZZLES

34

Quantity

Size

Service

TYPE

Quantity

Size

Service

TYPE

35

N1

6''

ACID INLET

RF

N11

2"

DEMI WATER

RF

36

N2

6''

RESERVE

RF

N12

2"

SEAL DRAIN

RF

37

N3

4''

RECIRCULATION

RF

N13

4"

SPARE

RF

38

N4

2''

DRAIN

RF

M1

24"

MAN HOLE in Roof

API 650

39

N5

4''

LEVEL

RF

M2

24"

MAN HOLE in Sheel

API 650

40

N6

2''

GA-002 RETURN

RF

41

N7

6''

ACID OUTLET

RF

42

N8

2''

T INSTRUMENT

RF

43

N9

10" (Note 6)

VENT (Note 4)

RF

N10

6"

OVERFLOW

RF

44
45
46

See general notes on next page.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

Nitric Acid Plant (unit 01)

CLIENT

RDF-GAIL-CIL-FCIL

FJ

Checked

JLS

LOCATION Talcher Complex, Odisha (India)

Approved

JRF

DOC. N

06484-01-120-DS-0023

PAGE

3/3

REV

Prepared

GENERAL NOTES FOR TANK:

06-FB-001 A/B

2
3

1. Liquid SG = 1.38 @ 10C

2. Tank bottom with 0.5% slope to N4

3. Stainless steel bolt and nuts

4. The equipment 06-FA-001A/B is supported over the vent nozzle

5. Level connections sizes to be confirmed by instrument department

6. To be confirmed

7. Equipment 06-FA-002 will be located above nozzle n9

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44

RASTHRIYA PROJECT
06484

PROJECT No.:

CONDENSATE POLISHING SYSTEM (UNIT 20)

VESSEL PROCESS DATA SHEET


POLISHING CONCENTRATE TANK
20-FB-101

00

22/11/2013

ISSUE FOR PROPOSAL

MSP

JLS

JRF

Rev. No:

DATE

DESCRIPTION

PREPARED BY

CHECKED BY

APPROVED BY

DOCUMENT TITLE
POLISHING CONCENTRATE TANK DATA SHEET
DOCUMENT NUMBER

06484-20-120-DS-0002

REVISION
PAGE

OF

00

This document contains confidential information property of TECNICAS REUNIDAS/ESPINDESA, any reproduction or use of its content, total or partial, including without limitation any of its
characteristics patented or able to be patented, it is forbidden and it cannot be reproduced or used without the permission of TECNICAS REUNIDAS and ESPINDESA.

STORAGE TANK
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

JOB N

06484

UNIT

CONDENSATE POLISHING SYSTEM

CLIENT

RCF-GAIL-CIL-FCIL

JLS

LOCATION

TALCHER COMPLEX, ODISHA (INDIA)

Approved

JRF

DOC. N

06484-20-120-DS-0002

PAGE

2 OF 3

REV

MSP

Checked

REV

Prepared

Item N:

20-FB-101

Service:

POLISHING CONCENTRATE TANK

Fluid:

AMMONIUM NITRATE SOLUTION (5 g/l)

Nominal capacity:

420

m3

Net Capacity:

390

m3

Diameter (ID)

7500

mm

Height

9900

mm

8
9

TANK PRESSURE

12

Operating

ATM

kg/cm2 g

0,03

kg/cm2 g

-0,005

kg/cm2 g

Operating

TANK
TEMPERATURE

Design
Vacuum design

10
11

Quantity:

AMB

Design

80

C
kg/cm2 g

13

Operating Press.

14

Operating Temp.

15

Design Press.

kg/cm2 g

16

Design Temp.

17

Nom. Diameter

in

18

Length

COIL

MATERIAL

19
20

Shell / Roof

21
22

CORR. ALLOW.

304 L

mm

Cladding

mm

Coil

mm

23
24

Type

25

X Conical Roof

Floating Roof

Steam out Conditions:

kg/cm2 g

X API

Refrigerated

Short term maximum temperature:

kg/cm2 g

kg/cm2 g

26

Bottom

Flat

Short term minimun temperature:

27

NOTE (2)

Conical Pointing Downwards

TANK VENTING DATA:

Conical Pointing Upwards

- Blanketing:

28
29

Code:

API STD.650

30

Stress Relieve for Process Reasons:

31

Insulation:

Type
-

mm

Quantity

Size

35

N1

2"

36

N2

2"

37

N3

8" (3)

VENT (4)

BW

38

N4

2"

MIN. FLOW RECYCLE


20-GA-001 A/B

RF

39

N5

4"

OVERFLOW

RF

40

N6

2"

TEMP. GAUGE

RF

41

N7

4"

DRAIN

RF

3"

POLISHING
CONCENTRATE
OUTLET

RF

N8

Service
POLISHING
CONCENTRATE
LP DEMI WATER
INLET

Service

Type

RF

M1

24"

MAN HOLE IN ROOF

API 650

RF

M2

24"

MAN HOLE IN SHELL

API 650

2"

LEVEL TRANSMITTER

RF

2"

LEVEL TRANSMITTER

RF

50

See general notes on next page.

kg/kmol
kg/cm2 g

Size

N9

45

/MW:

C /Pressure:

Quantity

N10

49

Temperature:

44

48

- Relieving conditions:

kg/h

Type

43

47

Flow:

NOZZLES

34

46

kg/h
(3)

- Emergency relief:

NOZZLES

33

42

kg/h

- Max outbreathing rate (3):

Not Insulated

Thickness

32

NO

- Max inbreathing rate (3):

STORAGE TANKS
PROCESS DATA SHEET
Rev.

00

Date

22/11/2013

Prepared

JOB N

MSP

06484

UNIT

CONDENSATE POLISHING SYSTEM

CLIENT

RCF-GAIL-CIL-FCIL

JLS

LOCATION

TALCHER COMPLEX, ODISHA (INDIA)

JRF

DOC. N

06484-20-120-DS-0002

PAGE

3 OF 3

REV

Checked
Approved

GENERAL NOTES FOR TANK:

20-FB-101

2
3

1. Liquid SG: Max. 1,00 @ 10C.

2. Tank bottom with 0,5% slope to N7

3. Maximum filling rate: 5,5 m3/h

Maximum pumpout rate: 4,4 m3/h

Vendor shall design the venting system based on 1,5 times these filling / pumpout rates shown, and verified that the design covers

the scenario of fire case.

10

4. Swan neck and bird screen to be fitted. No other elements which may obtruct the flow are allowed.

11

5. Tank should be 100% drainable.

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

Anda mungkin juga menyukai