CLIENT
EPC CONTRACTOR
CONTRACTOR
DOCUMENT TITLE
EARTHING LAYOUT
22/02/2013
EARTHING CALCULATIONS
AJAY
RRK
RRK
DATE
Rev : NO
DESCRIPTION
DESIGNED
CHECKED
APPROVED
DOCUMENT NO : PU-13-02-007
Sheet 1 of 1
BLOCK1
33KV Switchyard
Reference Documents
a) Electrical resistivity test report at plant site for 132kv Switch Yard, Vishnupuram
b) IEEE80-2000
c) CBIP Manual on substation publication number : 223
14 M
EQUIVALENT
AREA
10.6 M
(Fig-1)
Switch yard
14
10.6
148.4
LC =
133.6 M
Sheet 1 of 1
1)
IEEE 80-2000
2)
1.0)
Conductor material
GI
(ii)
System Voltage
33
kV
(iii)
Fault Current, If
25
kA
(iv)
Fault Duration, tc
sec
(v)
620
(vi)
Ambient Temperature, Ta
50
(vii)
20
(viii)
Temperature, r
(ix)
o
0.0032 1/ C
20.1
/cm3
(x)
3.93
J/cm3/oC
(xi)
K0 = (1/r) -Tr
292.5
Conductor Size :As per Eq.37 of IEEE Std 80-2000, conductor size is given by
tc r r x 104
TCAP
A
If
Ko + Tm
ln
Ko + Ta
323
=
=
=
=
sq.mm
420.015758 mm2
900
mm2
L*B
75
12
GI FLAT
Sheet 1 of 1
2
2.1)
CALCULATIONS FOR TOLERABLE TOUCH VOLTAGE (Etouch ) AND STEP VOLTAGE( Estep)
Input Data :
(i)
System Voltage, Vs
33
kV
(ii)
25
KA
(iii)
sec
(iv.1)
14
metre
(iv.2)
10.6
metre
(iv.3)
148.4
sq.metre
(v)
900
sq.mm
(vi)
0.6
metre
(vii.1)
14
metre
(vii.2)
10.6
metre
(vii.3)
10
metre
144
metre
(vii.4)
157
metre
184.02
metre
119.39
metre
(ix)
10
-metre
(x)
Surface Resistivity, s
3000
-metre
(xi)
(xii)
(xiii)
metre
(xvi)
Thickness of Concrete , hs
0.15
metre
(xvii)
0.7
metre
Sheet 1 of 5
2.2)
a)
Cs
=
0.7700
tS = Duration of shock current in seconds =
0.5
( from clause 16.2.2 of IEEE Std 80-2000 )
Substituting the above values,
Tolerable Etouch50
=
732.48 Volts
b)
Tolerable Estep50
2437.76 Volts
=
R1 + R2 - 2Rm
Where,
R1
R2
Rm
k1 Lc
2 Lc
ln
Lc
- k2
+
a
'
Where,
Lc
=
=
Soil Resistivity in -m
Total length of all connected grid conductors in m
a'
2a
=
=
A
k1
=
=
a.2h
for conductors buried at depth h in m
Diameter of conductor in m
Area covered by conductors in m2
Coefficient from fig 25(a) of IEEE Std 80-2000
k2
10
144
ohm-m
m
0.3000 m
0.08 m
2
148.4 m
1.06
4.33
0.3341
Sheet 2 of 5
R2
4 LR
ln
2 k1 . Lr
( nR - 1 )2
-1 +
b
2 nRLR
Where,
Lr
2b
nR
=
=
=
2.75
0.08
5
LR
13.75
k1
R2
m
m
1.06
0.163
Mutual ground resistance between the grid and the rod bed, Rm
From eq.56 of IEEE Std 80-2000
Rm
k1 Lc
2 Lc
ln
- k2 + 1
Lc
Lr
Rm
=
0.3071
Subtituting the above values,
Rg
=
0.3403
2.4)
IG
IG x RG
Volts
17.5 KA
5954.71 Volts
Since, GPR > Estep50 (as per Figure 33 of IEEE Std 80-2000),calculate Attainable Emesh and Attainable
Estep voltages
2.5)
Lr
LM = Lc + 1.55+1.22
Lr
L2x + L2y
Where,
Lr
Lx
Ly
=
=
20
14
10.6
m
m
Sheet 3 of 5
IG
grid current
17.5
Ki
corrective Factor,
1.51
13.75
LR
=
Total length of ground rods
Subtituting the above values,
LM
184.02
As per Eq.81 of IEEE Std 80-2000, the Spacing Factor for Mesh Voltage,
D2
1
Km =
(D + 2h)2
ln
+
16hd
8Dd
(2n-1)
Kh
0.0339 metre
Kh
Where,
8
ln
4d
Kii
h
-
1.26
na nb nc nd (From eq.84 of IEEE Std 80-2000)
Lp
nb
=
4 A
0.7 A
Lx Ly
Lx Ly
nc
Dm
nd
I
L2x + L2y
A
Where,
Lp
Dm
5.84
nb
1.005
nc
nd
1.00
5.87
49.2
17.6
0.644 + ( 0.148 x n )
1.51
0.4251
611.23 Volts
Sheet 4 of 5
2.6)
As per Eq.94 of IEEE Std 80-2000, the Spacing Factor for Step Voltage,
1
Ks =
1
+
1
(1 - 0.5n-2)
+
D+h
2h
=
=
=
6
6
0.644 + ( 0.148 x n )
Ki
1.51
Ks
0.4527
Lc
0.75 Lc + 0.85 LR
LR
Ls
119.3875 m
1003.47 Volts
CONCLUSION :
Tolerable
Etouch
732.48 Volts
Attainable
Emesh
611.23 Volts
Tolerable
Estep
2437.76 Volts
Attainable
Estep
1003.47 Volts
SAFE
0.3403 ohms
SAFE
Grid Resistance =
SAFE
1)
From the above results,it can be seen that the Attainable Emesh and Voltages are less
2)
3)
Sheet 5 of 5