STANDARD TECHNIQUE: SD8B/3 (Part 3)
Relating to 33kV Underground Cable Ratings

Policy Summary
This document contains 33kV cable ratings of the various types of 33kV cables used within
Western Power Distribution South West and South Wales areas. It assumes that the cables
will be subjected to the cyclic load as given by the load curve shown in figure one. If other
load curves are required contact the Company Cable Engineer.
This Standard Technique should be used when designing any 33kV electricity distribution
network that has underground cables in it.

Western Power Distribution (South West) plc Produced All Rights Reserved 2009

ST:SD8B/3 (Part 3)

March 2009

- 1 of 159 -

1.0

INTRODUCTION
This Standard Technique replaces Standard Technique ST: SD 8B/2.
This Part 3 document of ST: SD 8B sets out the all the WPD, 33kV underground
cable Sustained ratings, Cyclic ratings and Distribution ratings for winter, spring,
summer and autumn which are to be applied. These ratings are based on Electrical
Network Association Engineering Recommendation P17, Crater for MV Cables,
ERA Report F/T 183 and manufacturers data.

2.0

UNDERGROUND CABLES
The main factors governing the rating of underground cables are: Maximum depth of lay;
Soil thermal resistivity Tr (g);
Ground ambient temperature (oC);
Air ambient temperature (oC);
Cyclic loading conditions;
Maximum permissible conductor temperature;
Proximity to other cables;
Whether the cable is laid direct in the ground, in ducts or in air.
Duct dimensions

3.0

CRITERIA

3.1

General criteria for 33kV cables (applies to Paper, EPR and XLPE cables)
A winter soil resistivity of 0.9oCm/W and a summer soil resistivity of 1.2oCm/W are
considered realistic for the South West and South Wales, although the possibility of
localised higher values may need to be taken into account. To control the thermal
resistivity of the surrounding medium then the best example would be to use cement
bound sand (CBS) backfill for a cable route, but this is expensive. Generally crushed
Limestone dust or crushed Granite dust 3mm to dust is suitable as this gives a Tr of
1.2oCm/W.
Ground ambient temperatures across the South West and South Wales vary between
7oC in the winter and 15oC in the summer. These values apply in most locations, but
winter ground temperatures in the city centres such as Bristol, Cardiff, Exeter,
Plymouth and Swansea will be about 2oC higher.

3.2

The current ratings quoted in this document are maximum values based on balanced
loads.

ST:SD8B/3 (Part 3)

March 2009

- 2 of 159 -

3.3

The current ratings quoted apply to cables supplying loads, during the requisite
season.

3.4

The current ratings specified are to be adjusted where the conditions are known to
vary from those quoted in this instruction i.e. high summer loads or grouping.

3.5

The maximum conductor temperature for MIND paper cable is 65oC. The maximum
conductor temperature for Oil filled and impregnated pressure gas cable is 85oC. The
maximum conductor temperature for EPR and XLPE cables is 90oC.

3.6

When two or more cables or trefoil groups are laid in the same trench then a derating
factor needs to be applied to both circuits. The amount of derating is dependant upon
the spacing of the circuits. All spacing distances quoted in this document are centreto-centre spacings of the cables or trefoil groups.

3.7

Only 33kV Ratings are now included in this document.

3.8

The ratings are detailed as Sustained - Winter, Spring, Summer and Autumn; Cyclic
- Winter, Spring, Summer and Autumn; Distribution - Winter, Spring, Summer and
Autumn; for each of the cable types included in this document.

3.9

Each cable type for which ratings have been generated the typical assumed
installation conditions are given in the formation shown below: Depth of lay 0.8m;
Soil resistivity of 0.9oCm/W;
Ground ambient temperature of 10oC;
Maximum conductor temperature of 65oC for 33kV for 3 core MIND paper
cables and 70oC for 33kV single core PILC cables. The maximum conductor
temperature for Oil filled and impregnated pressure gas cable is 85oC. All
polymeric cables e.g. EPR and XLPE have a maximum conductor
temperature of 90C.
No allowance made for grouping of cable circuits.

4.0

DEFINITIONS
All 33kV EPR triplex circuits, for the purpose of this document, have been assumed
to be three single-core polymeric cables laid touching, throughout their length, in
trefoil formation. That the copper wire screens or the lead sheaths of the cables have
been solidly bonded together and earthed at both ends of the circuit.
It should be noted that when triplex or single core cable, which has been laid in
trefoil, a maximum of 12% of the TOTAL ROUTE LENGTH, can be laid in flat
space configuration without affecting the trefoil rating. If more than 12% of the Total
Route Length is laid in flat space configuration then high circulating currents will
flow in the copper wire screens or the lead sheath of the single core cables. This must
be avoided. If the 12% cannot be achieved then contact the Company Cable Engineer
at Avonbank.

ST:SD8B/3 (Part 3)

March 2009

- 3 of 159 -

4.1

Sustained, Continuous or Steady-State rating


The sustained rating is the maximum current that can be carried, in defined
conditions, without the assumed maximum conductor temperature being exceeded.

4.2

Cyclic rating
A cyclic rating is the maximum current that maybe carried during the prolonged
application of a succession of identical 24-hour load cycles, without the assumed
maximum conductor temperature being exceeded.

4.3

Distribution rating
Distribution ratings are ratings calculated for stated conditions commonly occurring
on distribution systems. The tabulated ratings given are 3 to 5 day limited time cyclic
ratings.
The basis of the Distribution ratings is given below: Quantity and value assumed
in
calculating Distribution
Ratings
Assumed maximum
conductor temperature
Depth of Laying
0.8m
Soil Ambient Temp.
10C
Soil Thermal resistivity
for cables laid direct or in ducts
g = 0.9C.m/W
Soil Thermal Diffusivity
needed for transient conditions
0.5 x 10-6 m/s
Ambient conditions
Cables in Air
10C
Solar gain neglected
Other Heat Sources
None
Cyclic Loading
For cables laid direct or in ducts
24 hr load cycle.
Limited-time Rating
Normal conditions restored
after 3 5 days.

ST:SD8B/3 (Part 3)

March 2009

Conditions for which valid.

90C
Nominal laying depth, direct or in ducts.
Winter peak loads in UK.
(a) Summer load not greater than 75% of
winter load.
(b) Either special measures taken for difficult soils
OR increased risk accepted.
G = 0.9C.m/W
(a)Maximum load in winter.
(b) Heating from adjacent equipment not
excessive.
(c) Shielded from the sun.
No allowance made for grouping.
Daily cyclic load typical domestic/commercial
type.
Two-feeder open-ring operation.

- 4 of 159 -

4.4

Utilisation factor
The percentage of a cable's distribution rating which is not exceeded during its
normal operational condition. Distribution ratings are based on an initial cable
utilisation of 50%; if a circuit has a higher utilisation factor such as 75% then the
Distribution rating must be reduced by 2.5%.

4.5

Load Factor
The ratio of the number of units supplied during a given period, to the number of
units that would be supplied, had the maximum demand been maintained throughout
that period. This is usually expressed as a percentage.

4.6

Soil thermal conductivity


The soil thermal conductivity is the thermal transmission in unit time through unit
area of homogeneous soil of unit thickness, when unit difference of temperature is
established between its surfaces.

4.7

Soil thermal resistivity


The ratings given are calculated for a damp thermal resistivity, which is suitable for
rating cables for winter-peak loads.

4.8

Ground ambient temperature


Where a cable circuit carries a sustained load and does not have a seasonal variation
it should be rated for the maximum summer value of ground temperature.

4.9

Ducts
A duct up to 15m in length can be used without derating the cable. Two or more duct
lengths can be used on a section, provided that there is no more than 30m of duct in a
particular 250m cable section and that there is a minimum of 10m separation
between each duct length. See the example given below.
Example of two 15m-duct lengths in a 250m-cable section.
The correct duct rating shall be used if 15m or more of continuous duct is installed
on a particular 250m-cable section. This rating is dependant upon the type of ducting
used, for this reason the ratings given in the tables contain values for both smooth
walled PVC and Rigiduct (Rigiduct is a twin walled duct) type ducting.
The rating of the cable section can be restored if the ducts are bentonited after the
cables have been installed. To ensure the thermal equivalence to the direct buried
parts of the route, the ducts shall be completely filled with a bentonite-sand-cement
mixture.
The filling medium shall be prepared by adding 20 parts of sand and 8 parts of
cements, by weight, to 100 parts of a 10:1 water/bentonite mixture.

ST:SD8B/3 (Part 3)

March 2009

- 5 of 159 -

Note: - Provided the bentonite is sealed into the duct with duct seals, and then the
bentonite forms a gel, which is stabilized by the cement, and the addition of sand
increases the load-bearing properties of the mixture. Should it be necessary to
remove this mixture, it may be flushed out of the ducts by using high-pressure water
jets.
Ducts, which are filled with a bentonite mixture, shall be installed wherever possible
in a concrete surround but if not, any joints in the duct run must be effectively
sealed. At the duct ends, the gap around the cable must be effectively sealed to
prevent migration of the bentonite mixture and preserve its moisture content under
service conditions.
In general duct lengths of up to 100m can be filled where a standard 150mm nominal
bore duct is installed.
4.10

Cables exposed to the sun


To reduce the effect of solar radiation it is recommended that cables should be
shielded from direct rays of the sun without restriction of ventilation.

4.11

Effects of grouping of cables


No allowance has been made for grouping in the ratings listed in the tables. Use the
correction factors given in Table 1 for various grouping arrangements.
When two or more circuits of the same voltage are laid in close proximity the ratings
of the cables must be reduced by multiply the group-rating factor given in Table 1
with the relevant cable rating selected from this document. It should be noted that if
thermally independence of both the circuits is required, then the circuits need a
centre-to-centre spacing of 2.5m.
All spacing quoted in Table 1, are a centre-to-centre spacing for the relevant circuits.

4.12

Loading Conditions
All the ratings listed in this document are calculated for a particular typical
domestic/commercial daily load curve, having a loss load factor of 0.5. See Figure 1
for the load curve.
Ratings given for cables installed in air and clipped direct to a wall are the steadystate ratings. Cables installed in this manner do NOT have a Cyclic or Distribution
rating just their sustained or steady state rating.

5.0

FURTHER GUIDANCE
If required, further guidance should be sought from the Company Cable Engineer,
Policy Section, Avonbank, Feeder Road, Bristol where necessary.

ST:SD8B/3 (Part 3)

March 2009

- 6 of 159 -

5.1

INDEX

TABLE
Table 1
Figure 1
A1 win
A2 spr
A3 sum
A4 aut
B1 win
B2 spr
B3 sum
B4 aut
C1 win
C2spr
C3 sum
C4 aut
D1 win
D2 spr
D3 sum
D4 aut
E1 win
E2 spr
E3 sum
E4 aut
F1 win
F2 spr
F3 sum
F4 aut
G1 win
G2 spr
G3 sum
G4 aut

DESCRIPTION
Group Derating Factors for Circuits.
Typical Load Curve G.
33kV XLPE Lead Sheath and MDPE - WINTER Sustained, Cyclic & Distribution Current
Ratings.
33kV XLPE Lead Sheath and MDPE - SPRING - Sustained, Cyclic & Distribution Current
Ratings.
33kV XLPE Lead Sheath and MDPE - SUMMER - Sustained, Cyclic & Distribution Current
Ratings.
33kV XLPE Lead Sheath and MDPE - AUTUMN - Sustained, Cyclic & Distribution Current
Ratings.
33kV XLPE Cu. Wire Screen and MDPE - WINTER Sustained, Cyclic & Distribution
Current Ratings.
33kV XLPE Cu. Wire Screen and MDPE - SPRING - Sustained, Cyclic & Distribution
Current Ratings.
33kV XLPE Cu. Wire Screen and MDPE - SUMMER - Sustained, Cyclic & Distribution
Current Ratings.
33kV XLPE Cu. Wire Screen and MDPE - AUTUMN - Sustained, Cyclic & Distribution
Current Ratings.
33kV EPR Cu. Wire Screen and MDPE - WINTER Sustained, Cyclic & Distribution
Current Ratings.
33kV EPR Cu. Wire Screen and MDPE - SPRING - Sustained, Cyclic & Distribution Current
Ratings.
33kV EPR Cu. Wire Screen and MDPE - SUMMER - Sustained, Cyclic & Distribution
Current Ratings.
33kV EPR Cu. Wire Screen and MDPE - AUTUMN - Sustained, Cyclic & Distribution
Current Ratings.
33kV HSL MIND (Copper) metric & imperial - WINTER Sustained, Cyclic & Distribution
Current Ratings.
33kV HSL MIND (Copper) metric & imperial - SPRING - Sustained, Cyclic & Distribution
Current Ratings.
33kV HSL MIND (Copper) metric & imperial - SUMMER - Sustained, Cyclic & Distribution
Current Ratings.
33kV HSL MIND (Copper) metric & imperial - AUTUMN - Sustained, Cyclic & Distribution
Current Ratings.
33kV HSL MIND (Aluminium) metric & imperial - WINTER Sustained, Cyclic &
Distribution Current Ratings.
33kV HSL MIND (Aluminium) metric & imperial - SPRING - Sustained, Cyclic &
Distribution Current Ratings.
33kV HSL MIND (Aluminium) metric & imperial - SUMMER - Sustained, Cyclic &
Distribution Current Ratings.
33kV HSL MIND (Aluminium) metric & imperial - AUTUMN - Sustained, Cyclic &
Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) imperial - WINTER Sustained, Cyclic &
Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) imperial - SPRING - Sustained, Cyclic &
Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) imperial - SUMMER - Sustained, Cyclic
& Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) imperial - AUTUMN - Sustained, Cyclic
& Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) metric - WINTER Sustained, Cyclic &
Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) metric - SPRING - Sustained, Cyclic &
Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) metric - SUMMER - Sustained, Cyclic &
Distribution Current Ratings.
33kV H type MIND, SWA (Aluminium & copper) metric - AUTUMN - Sustained, Cyclic &
Distribution Current Ratings.

ST:SD8B/3 (Part 3)

March 2009

- 7 of 159 -

TABLE
H1 win
H2 spr
H3 sum
H4 aut
J1 win
J2 spr
J3 sum
J4 aut
K1 win
K2 spr
K3 sum
K4 aut
L1 win
L2 spr
L3 sum
L4 aut
M1 win
M2 spr
M3 sum
M4 aut
N1 win
N2 spr
N3 sum
N3 aut

DESCRIPTION
33kV single core PILC (copper) metric& imperial - WINTER Sustained, Cyclic &
Distribution Current Ratings.
33kV single core PILC (copper) metric & imperial - SPRING - Sustained, Cyclic &
Distribution Current Ratings.
33kV single core PILC (copper) metric & imperial - SUMMER - Sustained, Cyclic &
Distribution Current Ratings.
33kV single core PILC (copper) metric & imperial - AUTUMN - Sustained, Cyclic &
Distribution Current Ratings.
33kV single core PILC (Aluminium) metric & imperial - WINTER - Sustained, Cyclic &
Distribution Current Ratings.
33kV single core PILC (Aluminium) metric & imperial - SPRING - Sustained, Cyclic &
Distribution Current Ratings.
33kV single core PILC (Aluminium) metric & imperial - SUMMER - Sustained, Cyclic &
Distribution Current Ratings.
33kV single core PILC (Aluminium) metric & imperial - AUTUMN - Sustained, Cyclic &
Distribution Current Ratings.
33kV three core ducted Oil Filled Lead sheath (metric) cable - WINTER Sustained &
Cyclic Current Ratings.
33kV three core ducted Oil Filled Lead sheath (metric) cable - SPRING - Sustained & Cyclic
Current Ratings.
33kV three core ducted Oil Filled Lead sheath (metric) cable - SUMMER - Sustained &
Cyclic Current Ratings.
33kV three core ducted Oil Filled Lead sheath (metric) cable - AUTUMN - Sustained &
Cyclic Current Ratings.
33kV three core ducted Oil Filled Lead sheath (imperial) cable - WINTER Sustained &
Cyclic Current Ratings.
33kV three core ducted Oil Filled Lead sheath (imperial) cable - SPRING - Sustained &
Cyclic Current Ratings.
33kV three core ducted Oil Filled Lead sheath (imperial) cable - SUMMER - Sustained &
Cyclic Current Ratings.
33kV three core ducted Oil Filled Lead sheath (imperial) cable - AUTUMN - Sustained &
Cyclic Current Ratings.
33kV three core ductless Oil Filled CAS sheath cable - WINTER Sustained, Cyclic &
Distribution Current Ratings.
33kV three core ductless Oil Filled CAS sheath cable - SPRING - Sustained, Cyclic &
Distribution Current Ratings.
33kV three core ductless Oil Filled CAS sheath cable - SUMMER - Sustained, Cyclic &
Distribution Current Ratings.
33kV three core ductless Oil Filled CAS sheath cable - AUTUMN - Sustained, Cyclic &
Distribution Current Ratings.
33kV three core impregnated pressure gas cables - WINTER Sustained & Cyclic Current
Ratings.
33kV three core impregnated pressure gas cables - SPRING Sustained & Cyclic Current
Ratings.
33kV three core impregnated pressure gas cables - SUMMER Sustained & Cyclic Current
Ratings.
33kV three core impregnated pressure gas cables - AUTUMN Sustained & Cyclic Current
Ratings.

ST:SD8B/3 (Part 3)

March 2009

- 8 of 159 -

TABLE 1
GROUP DERATING FACTORS FOR CIRCUITS OF THREE SINGLE-CORE
CABLES, IN TREFOIL or LAID FLAT, HORIZONTAL FORMATION, LAID
DIRECT.
S

Spacing of Circuits Metre (S).


Type of Cable No. of Circuits

Touching
Trefoil Laid Flat

33kV Cables

ST:SD8B/3 (Part 3)

0.15 0.20

0.3

0.45

0.78

0.80

0.81 0.82 0.85

0.88

0.66

0.69

0.71 0.73 0.76

0.80

0.60

0.63

0.65 0.67 0.72

0.76

0.55

0.58

0.61 0.63 0.68

0.73

March 2009

- 9 of 159 -

Figure 1

ST:SD8B/3 (Part 3)

March 2009

- 10 of 159 -

TABLE A1 - Win
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)

Winter SUSTAINED Current Ratings

SUSTAINED CURRENT RATINGS-AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

425
477
538
621
700
795
1004

No Ratings Available
No Ratings Available
357
334
400
374
451
421
521
486
587
546
666
618
841
775

508
575
656
766
877
1014
1331

486
549

No Ratings Available
407
380
460
428

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 11 of 159 -

TABLE A1 - Win
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

481
541
613
710
805
918
1173

No Ratings Available
No Ratings Available
392
362
440
406
498
458
577
529
653
597
744
678
948
855

508
575
656
766
877
1014
1331

555
630

No Ratings Available
451
414
511
468

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 12 of 159 -

TABLE A1 - Win
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

528
594
675
783
890
1019
1310

No Ratings Available
No Ratings Available
413
378
465
424
527
480
611
555
693
627
792
713
1015
904

508
575
656
766
877
1014
1331

612
696

No Ratings Available
478
434
543
491

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 13 of 159 -

TABLE A2 - Spr
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)

Spring SUSTAINED Current Ratings

SUSTAINED CURRENT RATINGS-AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

397
454
502
579
652
740
933

No Ratings Available
No Ratings Available
342
322
383
360
431
405
498
466
560
524
635
592
799
741

508
575
656
766
877
1014
1331

453
511

No Ratings Available
389
365
439
411

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 14 of 159 -

TABLE A2 - Spr
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

454
540
578
669
756
863
1100

No Ratings Available
No Ratings Available
381
353
427
395
483
445
559
514
631
579
719
657
913
828

508
575
656
766
877
1014
1331

522
593

No Ratings Available
437
402
495
454

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 15 of 159 -

TABLE A2 - Spr
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

502
598
640
743
843
964
1238

No Ratings Available
No Ratings Available
406
373
456
418
517
472
599
546
679
616
775
700
990
886

508
575
656
766
877
1014
1331

580
660

No Ratings Available
468
427
532
483

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05 oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 16 of 159 -

TABLE A3 - Sum
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)

Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

371
415
468
539
607
688
866

No Ratings Available
No Ratings Available
326
308
365
344
411
387
473
445
532
500
602
564
756
705

508
575
656
766
877
1014
1331

421
476

No Ratings Available
370
348
417
392

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2 C m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 17 of 159 -

TABLE A3 - Sum
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

427
480
543
628
710
809
1030

No Ratings Available
No Ratings Available
367
341
411
381
465
430
537
496
607
559
690
633
874
797

508
575
656
766
877
1014
1331

491
556

No Ratings Available
420
388
475
438

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2 oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 18 of 159 -

TABLE A3 - Sum
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

475
534
606
702
796
910
1167

No Ratings Available
No Ratings Available
396
364
445
408
503
461
583
533
660
601
752
682
959
862

508
575
656
766
877
1014
1331

549
624

No Ratings Available
456
416
517
471

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 19 of 159 -

TABLE A4 - Aut
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)

Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

391
437
493
569
640
726
915

No Ratings Available
No Ratings Available
339
319
379
356
427
401
493
462
554
519
628
586
789
733

508
575
656
766
877
1014
1331

445
502

No Ratings Available
385
361
434
507

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1 C m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 20 of 159 -

TABLE A4 - Aut
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

448
503
569
659
745
850
1083

No Ratings Available
No Ratings Available
378
351
424
393
479
443
555
511
627
576
713
653
905
822

508
575
656
766
877
1014
1331

515
584

No Ratings Available
434
400
491
451

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1 oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 21 of 159 -

TABLE A4 - Aut
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

469
558
633
734
832
952
1221

No Ratings Available
No Ratings Available
405
372
455
417
515
471
598
545
677
615
772
699
986
883

508
575
656
766
877
1014
1331

573
652

No Ratings Available
467
426
530
482

598
686

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 22 of 159 -

TABLE B1 - Win
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Winter SUSTAINED Current Ratings

SUSTAINED CURRENT RATINGS-AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

303
362
412
461
521
601
677
769
976

292
346
389
432
483
549
611
685
852

285
336
378
419
467
530
588
657
812

346
418
481
544
621
726
830
959
1263

236
471
532

200
399
451

189
343
420

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 23 of 159 -

TABLE B1 - Win
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

341
409
467
525
595
689
780
890
1142

323
384
435
484
543
620
693
781
981

313
371
418
465
520
592
660
741
923

346
418
481
544
621
726
830
959
1263

265
540
613

218
441
499

203
406
458

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 24 of 159 -

TABLE B3 - Win
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

373
448
513
577
655
761
863
989
1277

349
416
471
526
591
677
759
858
1085

336
399
452
503
564
643
718
809
1014

346
418
481
544
621
726
830
959
1263

290
596
678

228
466
529

211
424
480

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 25 of 159 -

TABLE B1 - Spr
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Spring SUSTAINED Current Ratings

SUSTAINED CURRENT RATINGS-AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

284
339
385
431
486
561
631
716
907

247
295
335
375
422
487
548
621
784

234
279
316
353
397
457
513
580
729

346
418
481
544
621
726
830
959
1263

221
440
496

192
382
431

182
358
403

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 26 of 159 -

TABLE B2 - Spr
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

323
387
441
495
561
649
734
837
1072

272
326
371
416
471
544
615
700
892

254
304
345
386
436
502
566
642
812

346
418
481
544
621
726
830
959
1263

251
509
577

212
427
483

198
394
445

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 27 of 159 -

TABLE B3 - Spr
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

356
427
488
549
623
722
819
937
1208

289
347
395
444
503
583
660
753
966

268
320
364
408
461
533
601
683
867

346
418
481
544
621
726
830
959
1263

276
566
643

225
457
519

208
418
472

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05 oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 28 of 159 -

TABLE B1 - Sum
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

266
317
360
403
454
523
588
666
843

236
282
320
357
402
463
521
589
742

224
267
302
338
380
436
490
553
694

346
418
481
544
621
726
830
959
1263

207
410
462

184
363
410

174
342
385

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2 C m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 29 of 159 -

TABLE B2 - Sum
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

304
364
415
466
527
610
689
785
1004

263
315
358
402
454
524
591
672
855

246
294
334
373
421
485
546
619
781

346
418
481
544
621
726
830
959
1263

237
478
541

205
411
465

192
381
429

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2 oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 30 of 159 -

TABLE B3 - Sum
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

338
405
462
520
589
683
774
885
1139

282
339
386
433
490
568
642
732
936

262
314
356
399
451
520
586
666
844

346
418
481
544
621
726
830
959
1263

262
536
608

220
445
505

204
408
461

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 31 of 159 -

TABLE B4 - Aut
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

280
334
379
424
478
551
620
703
890

245
292
332
371
418
482
542
574
775

232
276
313
350
393
453
508
574
721

346
418
481
544
621
726
830
959
1263

218
432
488

191
378
426

181
355
400

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1 C m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 32 of 159 -

TABLE B4 Aut
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

319
381
435
488
553
640
723
824
1055

271
324
369
414
468
541
611
695
885

253
302
343
384
433
500
562
638
807

346
418
481
544
621
726
830
959
1263

248
501
568

211
424
480

197
392
442

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1 oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 33 of 159 -

TABLE B4 - Aut
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

352
422
482
542
615
714
808
925
1192

288
346
394
443
502
581
658
751
962

268
320
364
408
460
532
599
681
865

346
418
481
544
621
726
830
959
1263

273
559
635

224
456
517

208
417
472

269
569
651

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 34 of 159 -

TABLE C1 - Win
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Winter SUSTAINED Current Ratings

SUSTAINED CURRENT RATINGS-AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240 mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

291
348
397
446
505
584
660
751
851
959

249
298
339
380
430
497
561
638
721
811

235
281
319
358
404
465
524
594
670
751

326
395
456
517
591
694
795
922
1064
1223

226
455
518

193
390
441

183
365
412

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 35 of 159 -

TABLE C1 - Win
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

324
390
446
503
571
664
753
863
983
1114

269
324
369
415
471
546
618
706
803
907

252
302
344
386
436
504
569
648
733
824

326
395
456
517
591
694
795
922
1064
1223

252
520
591

209
428
486

196
395
448

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 36 of 159 -

TABLE C3 - Win
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

351
424
487
549
625
729
829
954
1090
1240

281
338
386
436
495
575
653
748
853
967

261
314
257
402
455
527
596
679
770
868

326
395
456
517
591
694
795
922
1064
1223

273
570
651

218
451
513

203
413
468

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 37 of 159 -

TABLE C2 - Spr
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

274
328
373
418
473
547
617
702
794
893

240
287
326
365
412
476
536
609
688
772

227
272
308
345
389
448
504
570
643
719

326
395
456
517
591
694
795
922
1064
1223

213
428
485

186
373
422

177
351
396

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 38 of 159 -

TABLE C2 - Spr
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Spring CYCLIC Current Ratings
SIZE AND TYPE OF CABLE
CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

307
370
423
476
540
627
711
813
926
1048

262
315
359
403
457
529
599
684
776
875

246
295
335
376
425
491
553
629
711
799

326
395
456
517
591
694
795
922
1064
1223

239
491
558

204
415
471

191
385
435

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 39 of 159 -

TABLE C2 - Spr
33kV SINGLE CORE E.P.R INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

336
406
465
524
596
694
789
906
1035
1176

277
333
381
429
486
565
641
734
835
945

258
310
353
396
448
519
586
668
757
852

326
395
456
517
591
694
795
922
1064
1223

261
543
619

215
443
503

201
407
461

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 40 of 159 -

TABLE C3 - Sum
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Summer SUSTAINED Current Ratings


SIZE AND TYPE OF CABLE
CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

257
307
350
392
442
511
576
654
740
831

229
274
311
349
393
454
511
579
653
732

218
260
295
330
372
428
481
545
613
686

326
395
456
517
591
694
795
922
1064
1223

200
400
453

178
356
402

170
336
379

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 41 of 159 -

TABLE C3 - Sum
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

291
350
399
449
509
591
669
765
870
984

254
304
347
389
441
510
577
658
745
840

238
285
324
364
411
474
535
607
686
770

326
395
456
517
591
694
795
922
1064
1223

226
463
526

197
400
433

185
372
420

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 42 of 159 -

TABLE C3 - Sum
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

320
386
442
498
566
658
748
858
979
1111

271
326
372
419
475
551
624
714
811
917

253
303
345
388
438
507
573
652
738
830

326
395
456
517
591
694
795
922
1064
1223

249
516
587

211
432
490

197
398
450

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 43 of 159 -

TABLE C4 - Aut
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)

Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTSAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

270
323
367
412
465
538
607
690
780
877

238
284
323
362
408
471
531
603
680
763

226
269
306
342
385
444
499
565
636
712

326
395
456
517
591
694
795
922
1064
1223

210
421
477

185
370
418

175
348
393

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 44 of 159 -

TABLE C4 - aut
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Winter CYCLIC Current Ratings
SIZE AND TYPE OF CABLE
CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

304
365
417
470
533
618
701
802
912
1032

261
313
357
401
454
526
595
679
770
869

245
293
334
374
422
488
550
626
707
794

326
395
456
517
591
694
795
922
1064
1223

236
484
550

203
412
468

190
383
433

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 45 of 159 -

TABLE C4 - aut
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric sizes
Copper conductors
70mm2 Copper
95mm2 Copper
120mm2 Copper
150mm2 Copper
185mm2 Copper
240mm2 Copper
300mm2 Copper
400mm2 Copper
500mm2 Copper
630mm2 Copper
Aluminium conductors
70mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS

333
402
460
519
590
686
780
895
1022
1161

276
333
380
428
485
564
639
731
832
941

258
310
352
396
448
518
585
667
755
850

326
395
456
517
591
694
795
922
1064
1223

259
537
612

215
370
502

201
406
460

253
543
623

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

90oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV polymeric cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 46 of 159 -

TABLE D1 - win
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

228
281
327
370
411
477
525

196
240
279
314
348
403
442

186
228
264
296
328
378
414

249
311
366
417
469
554
619

236
283
322
361
406
467
522

202
242
274
307
344
395
439

192
229
259
289
323
370
410

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 47 of 159 -

TABLE D1 - win
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

252
313
366
416
465
544
603

209
258
301
339
377
438
483

197
242
281
317
351
406
446

249
311
366
417
469
554
619

263
317
362
408
462
535
602

217
261
296
332
374
430
481

204
244
277
309
347
398
443

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 48 of 159 -

TABLE D1 - win

33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD


SHEATH & ARMOURED

Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

271
338
396
452
506
549
661

227
282
330
375
419
491
544

211
261
305
344
384
447
493

249
311
366
417
469
554
619

280
340
389
440
500
581
657

231
279
318
358
405
469
527

215
258
293
329
371
427
478

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 49 of 159 -

TABLE D2 -spr
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

214
264
307
347
385
446
490

188
230
267
300
333
384
421

179
218
253
284
314
361
395

249
311
366
417
469
554
619

222
266
302
338
380
436
486

194
232
262
293
328
376
418

184
220
248
277
309
353
392

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 50 of 159 -

TABLE D2 - spr
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

240
298
348
395
441
515
570

203
250
290
327
364
422
430

191
235
272
306
340
392
430

249
311
366
417
469
554
619

250
301
343
387
437
506
568

210
252
286
320
360
414
462

198
237
268
299
336
384
427

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 51 of 159 -

TABLE D2 - spr

33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD


SHEATH & ARMOURED

Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

259
323
378
431
482
565
628

221
274
321
363
406
475
526

206
254
296
335
373
433
477

249
311
366
417
469
554
619

268
324
370
419
475
552
622

224
271
309
347
392
454
509

209
251
285
320
360
414
463

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 52 of 159 -

TABLE D3 - sum
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

201
247
286
323
358
414
455

178
218
253
284
314
362
397

170
208
240
269
298
342
374

249
311
366
417
469
554
619

207
248
281
314
352
404
450

184
219
248
277
310
354
393

175
209
236
262
293
334
370

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 53 of 159 -

TABLE D3 - sum
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

227
281
328
372
415
484
535

194
239
278
313
347
402
442

183
225
261
293
325
375
411

249
311
366
417
469
554
619

236
284
323
363
410
474
531

201
241
273
306
344
395
440

190
227
256
286
321
367
408

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 54 of 159 -

TABLE D3 - sum

33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD


SHEATH & ARMOURED

Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

246
306
358
407
455
533
591

213
264
308
349
389
454
503

199
245
285
322
358
415
458

249
311
366
417
469
554
619

253
306
350
395
448
519
585

216
260
296
333
376
434
487

201
242
274
307
346
397
443

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 55 of 159 -

TABLE D4 - win
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

212
261
303
342
379
439
483

186
228
265
297
329
380
417

177
217
251
282
311
358
392

249
311
366
417
469
554
619

219
262
297
333
374
429
478

192
230
260
290
325
372
413

183
218
246
274
307
350
388

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 56 of 159 -

TABLE D4 - aut
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

238
295
345
391
436
510
564

202
248
289
325
362
419
461

190
234
271
305
338
390
428

249
311
366
417
469
554
619

247
298
340
383
432
500
561

209
251
285
319
358
412
459

197
235
267
298
334
382
425

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 57 of 159 -

TABLE D4 - aut

33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD


SHEATH & ARMOURED

Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2 Cu.
0.2 in2 Cu.
0.25 in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
Metric sizes
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu

CABLE IN
DUCTS
PVC
Rigiduct

257
320
375
427
478
560
621

220
273
319
362
404
472
523

205
254
285
334
371
431
475

249
311
366
417
469
554
619

265
321
367
415
470
546
615

224
270
307
346
390
451
506

208
250
284
319
359
413
461

257
313
358
406
462
540
612

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 58 of 159 -

TABLE E1 - win
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

177
219
256
324
380
422

152
188
219
276
322
356

145
178
207
259
302
334

194
243
286
369
439
494

221
252
283
320
371
417

189
215
241
272
314
352

179
203
227
256
294
329

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 59 of 159 -

TABLE E1 - win
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

196
244
287
367
432
483

163
202
235
298
349
388

154
189
221
278
324
359

194
243
286
369
439
494

247
283
320
363
424
479

204
232
260
295
342
385

191
217
243
274
317
355

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 60 of 159 -

TABLE E1 -win
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Winter DISTRIBUTION Current Ratings

DISTRIBUTION CURRENT RATINGS - AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

212
265
312
402
477
534

177
220
259
331
391
437

165
204
239
303
356
396

194
243
286
369
439
494

264
303
342
390
456
517

218
250
282
321
374
424

201
230
258
293
340
383

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 61 of 159 -

TABLE E2 - spr
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

167
206
241
304
355
394

146
180
209
263
306
339

139
171
198
248
289
319

194
243
286
369
439
494

208
236
265
299
346
388

181
206
230
259
299
334

172
195
217
245
281
314

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 62 of 159 -

TABLE E2 - spr
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

187
232
272
348
410
457

158
195
228
288
337
374

149
183
214
269
313
347

194
243
286
369
439
494

235
269
303
344
400
452

197
224
251
284
329
370

185
210
235
265
306
342

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 63 of 159 -

TABLE E2 - spr
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Spring DISTRIBUTION Current Ratings

DISTRIBUTION CURRENT RATINGS - AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

203
253
298
383
454
508

172
214
251
320
378
422

160
199
232
294
345
384

194
243
286
369
439
494

252
288
326
371
433
491

212
242
273
311
362
409

196
223
251
284
330
371

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 64 of 159 -

TABLE E3 - sum
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

156
193
224
283
330
366

135
166
193
249
289
320

132
162
188
236
273
302

194
243
286
369
439
494

193
220
246
278
321
360

171
195
217
245
282
315

163
185
206
232
266
297

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 65 of 159 -

TABLE E3 - sum
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

177
219
257
327
385
429

147
181
211
274
321
356

143
176
205
257
299
331

194
243
286
369
439
494

221
253
285
323
376
424

188
214
240
271
314
352

177
201
225
253
292
327

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2C m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 66 of 159 -

TABLE E3 sum
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED (Cont.)
Summer DISTRIBUTION Current Ratings

DISTRIBUTION CURRENT RATINGS - AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

192
240
282
362
428
479

161
200
234
307
362
404

155
191
223
283
331
368

194
243
286
369
439
494

238
272
308
350
408
462

203
233
262
298
346
391

188
215
241
273
316
356

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 67 of 159 -

TABLE E4 - aut
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

165
204
237
300
350
388

145
178
207
261
303
336

138
170
197
246
286
316

194
243
286
369
439
494

205
233
261
295
341
382

179
204
228
257
296
331

170
193
215
243
279
311

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 68 of 159 -

TABLE E4 aut
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

185
230
270
344
405
452

157
194
226
286
334
371

148
183
213
267
311
345

194
243
286
369
439
494

233
266
300
340
396
447

196
223
250
283
327
367

184
206
234
264
304
340

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 69 of 159 -

TABLE E4 aut
33kV H.S.L. CABLES OIL IMPREGNATED PAPER INSULATED LEAD
SHEATH & ARMOURED (Cont.)
Autumn DISTRIBUTION Current Ratings

DISTRIBUTION CURRENT RATINGS - AMPS

SIZE AND TYPE OF CABLE


CONDUCTOR

CABLE IN
GROUND
Imperial Sizes
Aluminium conductors
0.1in2 Al
0.15in2 Al
0.2in2 Al
0.3in2 Al
0.4in2 Al
0.5in2 Al
Metric sizes
Aluminium conductors
95mm2 Al
120mm2 Al
150mm2 Al
185mm2 Al
240mm2 Al
300mm2 Al

CABLE IN
DUCTS
PVC
Rigiduct

201
251
296
380
449
503

171
213
250
319
376
420

160
198
231
293
344
382

194
243
286
369
439
494

249
286
323
367
429
486

211
241
272
309
360
407

195
223
250
283
328
369

244
280
318
363
427
486

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 70 of 159 -

TABLE F1 win
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

231
284
333
377
421
491
544

197
242
282
318
355
413
456

187
229
267
301
334
388
428

252
312
369
422
476
564
633

330
388
433

278
326
363

263
307
341

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 71 of 159 -

TABLE F1 win
33kV (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED CABLES
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

256
317
372
425
476
560
624

211
259
303
343
384
448
497

199
244
284
321
358
416
460

252
312
369
422
476
564
633

373
441
495

301
354
395

281
329
366

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 72 of 159 -

TABLE F1 win
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

273
338
399
457
574
607
679

224
276
325
370
415
489
545

208
256
301
341
381
446
495

252
312
369
422
476
564
633

403
479
539

325
385
432

299
352
394

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 73 of 159 -

TABLE F2 - spr
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

218
267
312
353
394
459
508

189
231
270
304
339
394
434

180
220
256
288
320
371
409

252
312
369
422
476
564
633

309
363
404

266
311
346

252
294
326

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 74 of 159 -

TABLE F2 spr
33kV (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED CABLES
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

244
301
354
402
451
529
589

204
251
293
332
370
432
478

193
236
275
311
346
402
444

252
312
369
422
476
564
633

353
417
468

290
341
380

272
318
354

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 75 of 159 -

TABLE F2 - spr
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

261
323
381
435
489
576
644

218
269
316
359
403
473
527

203
250
293
331
370
433
480

252
312
369
422
476
564
633

383
455
511

315
373
418

290
342
382

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 76 of 159 -

TABLE F3 sum
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

203
249
291
329
366
426
470

180
220
256
288
320
372
410

172
209
243
274
304
352
387

252
312
369
422
476
564
633

287
336
374

252
294
326

239
278
308

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 77 of 159 -

TABLE F3 sum
33kV (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED CABLES
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

230
284
333
378
423
496
552

196
240
281
317
354
412
456

185
227
264
298
331
385
424

252
312
369
422
476
564
633

332
392
438

277
326
363

260
304
338

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 78 of 159 -

TABLE F3 - sum
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

247
306
360
410
461
543
606

210
258
304
345
386
453
504

196
241
282
319
356
416
461

252
312
369
422
476
564
633

362
428
481

303
358
401

279
328
366

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 79 of 159 -

TABLE F4 aut
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

215
264
308
348
388
452
500

188
230
268
302
336
390
430

179
218
254
286
318
368
405

252
312
369
422
476
564
633

304
357
398

264
308
343

250
291
323

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 80 of 159 -

TABLE F4 - aut
33kV (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED CABLES
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

242
298
350
398
446
523
582

203
250
292
330
368
429
475

192
235
274
309
344
400
442

252
312
369
422
476
564
633

349
413
462

289
339
378

270
316
352

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 81 of 159 -

TABLE F4 aut
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Imperial Sizes
Copper conductors
0.1in2 Cu.
0.15in2Cu.
0.2in2Cu.
0.25in2Cu.
0.3in2Cu.
0.4in2Cu.
0.5in2Cu.
Aluminium conductors
0.3in2Al.
0.4in2Al.
0.5in2Al.

CABLE IN
DUCTS
PVC
Rigiduct

259
320
377
431
484
570
637

217
268
315
357
401
471
524

203
249
292
330
369
431
478

252
312
369
422
476
564
633

380
450
506

314
371
410

289
340
380

372
444
502

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 82 of 159 -

TABLE G1 win
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

237
285
324
364
411
474
532

200
240
273
305
344
396
444

190
228
258
288
324
372
416

257
313
359
406
463
543
618

222
322
374
421

187
270
312
351

177
254
294
330

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 83 of 159 -

TABLE G1 win
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

264
319
364
411
466
541
611

215
258
293
329
372
430
483

202
242
275
308
347
400
447

257
313
359
406
463
543
618

248
365
426
483

201
291
339
382

189
272
315
355

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 84 of 159 -

TABLE G1 win
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

280
340
386
440
501
584
662

227
274
313
353
401
467
528

211
254
290
325
368
426
480

257
313
359
406
463
543
618

265
394
462
526

214
315
368
418

198
289
337
381

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 85 of 159 -

TABLE G2 spr
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

223
267
303
340
384
442
496

192
230
261
292
328
378
422

183
219
247
276
310
356
398

257
313
359
406
463
543
618

208
301
349
393

179
258
298
335

170
244
281
315

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 86 of 159 -

TABLE G2 spr
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

251
302
345
389
440
511
576

208
249
284
318
359
414
465

196
235
266
298
335
386
432

257
313
359
406
463
543
618

235
345
402
456

194
281
327
368

183
263
304
342

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 87 of 159 -

TABLE G2 spr
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

267
324
370
419
476
554
627

221
267
304
343
389
452
511

206
247
282
316
358
414
465

257
313
359
406
463
543
618

253
374
438
498

208
305
357
405

193
281
327
369

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 88 of 159 -

TABLE G3 sum
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

208
249
282
316
356
410
459

183
218
247
276
310
357
399

174
208
235
262
294
338
376

257
313
359
406
463
543
618

194
279
323
364

170
244
281
316

162
231
266
298

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 89 of 159 -

TABLE G3 sum
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

236
284
324
365
413
479
539

199
239
271
304
343
395
443

188
225
255
285
321
369
413

257
313
359
406
463
543
618

221
323
377
426

186
269
312
351

175
252
291
327

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 90 of 159 -

TABLE G3 sum
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

253
306
349
395
448
521
589

212
256
293
329
373
433
489

198
238
271
304
344
398
446

257
313
359
406
463
543
618

239
352
412
468

200
293
342
388

186
270
314
354

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 91 of 159 -

TABLE G4 aut
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

220
264
299
335
378
436
488

191
228
259
289
325
374
418

182
217
246
274
308
353
394

257
313
359
406
463
543
618

205
296
343
386

178
255
295
332

169
242
279
313

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 92 of 159 -

TABLE G4 aut
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

248
299
341
384
435
505
569

207
248
282
316
357
412
462

195
234
265
296
334
384
430

257
313
359
406
463
543
618

233
341
397
450

193
280
325
366

182
262
303
340

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 93 of 159 -

TABLE G4 aut
33kV CABLES (H type cable) 3 CORE SCREENED, OIL IMPREGNATED PAPER
INSULATED, LEAD SHEATH AND ARMOURED
Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS - AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
95mm2 Cu
120mm2 Cu
150mm2 Cu
185mm2 Cu.
240mm2 Cu
300mm2 Cu
Aluminium conductors
95mm2 Al.
185mm2 Al.
240mm2 Al
300mm2 Al.

CABLE IN
DUCTS
PVC
Rigiduct

265
321
367
414
471
548
620

220
266
303
341
387
450
508

205
247
281
315
356
412
463

257
313
359
406
463
543
618

250
370
433
493

207
304
355
403

192
280
326
368

243
363
427
488

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 94 of 159 -

TABLE H1 win
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION.
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

258
354
450
522
587
668
744
836

185
254
322
374
420
477
532
595

176
239
303
351
394
446
495
553

239
336
439
518
591
688
778
896

247
307
360
411
460
540
601
663
731
845

181
224
262
298
333
390
434
478
525
604

172
212
248
281
313
366
406
446
490
561

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 95 of 159 -

TABLE H1 win
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

287
398
511
596
672
770
861
975

200
275
351
409
461
526
588
662

188
257
326
379
426
484
540
604

239
336
439
518
591
688
778
896

273
342
403
462
519
613
686
761
843
983

195
242
284
324
363
427
476
526
581
672

183
227
266
301
337
395
440
484
533
613

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 96 of 159 -

TABLE H1 win
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

312
434
561
656
741
853
956
1087

208
287
368
429
485
556
623
703

194
266
339
394
444
506
565
634

239
336
439
518
591
688
778
896

295
371
439
505
569
674
756
840
935
1095

202
252
297
338
380
449
501
556
615
714

189
234
275
313
350
412
459
506
558
644

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 97 of 159 -

TABLE H2 spr
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION.
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

240
329
417
484
543
618
687
771

176
241
305
354
397
451
502
561

168
228
288
333
374
423
470
523

239
336
439
518
591
688
778
896

231
286
336
382
427
501
557
614
677
780

172
213
249
282
315
369
410
451
496
569

164
202
236
267
298
348
385
423
464
531

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 98 of 159 -

TABLE H2 spr
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

270
373
478
556
628
718
803
908

192
264
337
392
441
503
562
631

181
274
314
364
409
465
517
579

239
336
439
518
591
688
778
896

258
322
379
434
487
575
642
711
788
917

187
232
273
310
348
409
456
503
555
641

176
218
256
290
324
380
422
465
511
587

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 99 of 159 -

TABLE H2 spr
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

295
410
528
617
698
802
898
1020

202
279
357
417
471
538
603
679

189
259
330
384
432
492
549
615

239
336
439
518
591
688
778
896

281
352
416
478
538
637
713
792
880
1030

197
245
289
329
369
435
486
538
595
690

184
229
268
305
341
401
446
492
542
625

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 100 of 159 -

TABLE H3 sum
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION.
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

223
304
385
446
501
568
632
708

166
226
285
330
371
420
467
521

158
214
270
312
350
396
439
489

239
336
439
518
591
688
778
896

215
266
311
354
395
463
514
566
623
718

162
200
233
264
295
345
382
420
461
529

154
190
222
251
279
326
361
396
434
490

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 101 of 159 -

TABLE H3 sum
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

252
347
444
517
583
666
745
841

182
250
318
370
416
474
529
594

172
234
297
344
387
439
489
546

239
336
439
518
591
688
778
896

242
301
355
405
454
535
598
662
732
851

177
220
258
293
329
386
430
474
523
603

167
207
242
275
307
359
399
439
483
554

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 102 of 159 -

TABLE H3 sum
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

278
385
495
578
652
749
839
951

194
267
341
398
449
513
574
646

182
249
316
367
413
470
524
587

239
336
439
518
591
688
778
896

265
332
392
449
505
597
668
742
823
962

189
235
276
314
353
416
464
513
567
656

177
219
257
292
327
384
427
470
518
596

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 103 of 159 -

TABLE H4 aut
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION.
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

236
323
410
475
533
606
675
756

175
239
302
350
393
446
496
554

167
226
286
330
371
419
465
518

239
336
439
518
591
688
778
896

228
282
330
376
420
492
547
603
664
766

171
211
247
280
313
366
406
447
490
562

163
201
234
265
295
345
382
420
460
526

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 104 of 159 -

TABLE H4 aut
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

266
368
471
548
618
707
790
893

191
263
335
389
439
500
558
627

180
246
312
362
407
462
514
575

239
336
439
518
591
688
778
896

255
318
374
428
480
567
633
701
776
903

186
231
272
309
346
406
453
500
551
636

176
217
254
289
323
378
420
462
508
584

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 105 of 159 -

TABLE H4 aut
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Copper conductors
70mm2 Cu
120mm2 Cu
185mm2 Cu
240mm2 Cu
300mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu
Imperial
Copper conductors
0.1 in2 Cu.
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu.
0.3in2 Cu.
0.4in2 Cu.
0.5in2 Cu.
0.6in2 Cu.
0.75in2 Cu.
1.0in2 Cu.

CABLE IN
DUCTS
PVC
Rigiduct

292
406
522
609
689
791
886
1006

202
279
357
416
469
537
601
677

189
259
330
383
432
491
548
614

239
336
439
518
591
688
778
896

278
349
412
472
531
629
704
782
869
1016

197
245
288
328
368
434
485
537
593
688

184
229
268
305
341
400
445
491
541
623

230
290
345
397
450
538
608
681
763
907

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 106 of 159 -

TABLE J1 win
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

351
409
462

252
293
331

237
275
310

342
406
464

193
240
282
322
361
425
475
528

141
175
205
233
260
307
343
381

133
165
193
219
245
288
321
356

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/w

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 107 of 159 -

TABLE J1 win
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

399
466
528

274
321
364

255
297
336

342
406
464

213
267
316
363
408
484
543
606

152
189
222
253
284
336
377
420

142
176
207
235
264
311
348
386

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 108 of 159 -

TABLE J1 win
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Winter DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

437
513
583

287
337
383

265
309
350

342
406
464

231
290
344
396
446
532
598
670

157
197
232
265
297
353
397
443

147
182
215
244
274
324
363
404

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 109 of 159 -

TABLE J2 spr
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

326
379
427

239
278
313

225
262
295

342
406
464

180
224
263
299
335
395
441
489

134
166
195
221
248
291
325
361

128
158
184
209
234
274
306
338

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/w

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 110 of 159 -

TABLE J2 - spr
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

373
436
494

263
307
348

245
285
323

342
406
464

201
252
297
340
382
453
508
567

146
181
213
243
273
323
362
402

137
170
200
227
254
300
335
372

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 111 of 159 -

TABLE J2 - spr
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Spring DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

412
483
549

279
327
371

258
301
341

342
406
464

219
276
326
375
422
502
565
631

153
191
226
257
290
343
386
430

144
178
210
239
268
316
354
393

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 112 of 159 -

TABLE J3 sum
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

301
349
394

223
259
292

211
245
276

342
406
464

167
207
242
276
309
363
406
450

126
155
182
206
231
271
303
335

120
148
173
196
219
256
286
316

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/w

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 113 of 159 -

TABLE J3 sum
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

347
405
458

249
290
328

232
270
305

342
406
464

188
234
276
316
355
420
471
525

138
171
201
229
257
304
340
378

130
161
189
214
240
283
316
350

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 114 of 159 -

TABLE J3 sum
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Summer DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

386
452
513

267
312
354

247
288
326

342
406
464

206
258
305
350
394
468
527
589

146
183
215
245
276
327
367
409

137
171
201
228
256
302
338
375

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 115 of 159 -

TABLE J4 aut
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

320
372
420

236
275
310

232
259
292

342
406
464

177
220
258
294
329
388
433
481

133
165
193
219
245
288
322
357

127
156
183
207
232
272
303
335

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/w

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 116 of 159 -

TABLE J4 - aut
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

367
429
486

261
305
346

244
284
321

342
406
464

199
248
293
336
377
447
501
559

145
180
212
242
271
321
359
400

137
170
199
226
253
298
333
370

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 117 of 159 -

TABLE J4 aut
33kV SINGLE CORE OIL IMPREGNATED PAPER INSULATED LEAD SHEATH
CABLES IN TREFOIL FORMATION
Autumn DISTRIBUTION Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

DISTRIBUTION CURRENT RATINGS-AMPS


CABLE IN
GROUND

Metric
Aluminium conductors
185mm2 Al.
240mm2 Al.
300mm2 Al.
Imperial
Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.4in2 Al.
0.5in2 Al.
0.6in2 Al

CABLE IN
DUCTS
PVC
Rigiduct

407
429
542

279
326
370

258
301
340

342
406
464

217
273
323
370
417
496
558
623

153
191
225
257
289
343
385
429

143
178
210
238
268
316
353
393

179
227
270
312
353
425
482
543

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

65oC

This is a 3 to 5 Day Rating ONLY.


Ratings based on Crater for MV paper cables.

ST:SD8B/3 (Part 3)

March 2009

CABLE IN
AIR

- 118 of 159 -

TABLE K1 win
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

382
428
486
561
584
634
677
714
795
880

315
355
403
466
487
529
565
598
666
745

299
336
380
439
458
496
530
559
622
693

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

297
333
379
439
459
498
535
566
638
726

245
276
315
365
382
415
446
474
535
609

232
261
297
343
360
390
418
444
500
567

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 119 of 159 -

TABLE K1 win
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

437
492
562
651
680
742
793
839
938
1057

343
388
443
513
536
585
626
663
742
834

322
363
412
477
498
542
578
612
682
764

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

340
382
438
509
534
582
626
665
753
864

267
301
345
402
421
459
494
526
596
682

250
282
322
373
391
425
457
486
548
624

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 120 of 159 -

TABLE K2 Spr
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

356
400
453
522
544
590
630
664
739
825

303
341
387
446
465
505
539
570
635
708

288
323
366
422
439
476
508
536
596
663

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

277
310
353
409
428
463
497
527
593
674

235
265
301
349
366
397
426
452
510
579

224
251
285
330
345
374
401
425
478
542

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 121 of 159 -

TABLE K2 spr
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

412
464
529
613
640
698
746
789
882
993

334
377
429
497
520
566
605
641
716
804

313
353
401
463
483
525
561
593
661
739

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

321
360
413
480
503
548
589
626
708
812

259
293
335
389
408
444
478
509
575
658

244
274
313
363
380
412
443
471
531
604

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 122 of 159 -

TABLE K3 sum
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

332
372
422
486
506
549
585
617
686
765

289
325
368
425
443
480
512
541
601
670

275
309
349
402
419
454
484
511
567
630

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

258
289
329
380
398
431
462
490
551
626

225
252
287
332
348
377
405
429
453
548

214
240
272
315
329
356
382
405
455
515

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 123 of 159 -

TABLE K3 sum
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

388
436
497
576
601
655
700
740
827
931

322
363
413
479
500
544
581
615
687
770

303
341
387
447
466
506
540
571
636
710

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

301
339
388
450
472
514
553
587
664
761

250
282
322
374
393
427
459
488
552
630

236
265
302
350
366
397
427
453
511
581

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 124 of 159 -

TABLE K4 aut
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

350
393
445
513
535
580
618
653
726
810

300
337
383
442
461
500
534
564
627
700

285
320
363
418
435
472
503
531
590
656

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

272
305
347
401
420
455
489
518
583
662

233
262
299
346
362
393
422
448
504
573

222
249
283
327
342
370
398
421
474
537

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 125 of 159 -

TABLE K4 aut
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

407
458
522
604
631
688
735
778
869
978

332
375
427
494
516
562
601
637
711
798

312
351
399
461
481
522
558
590
657
734

372
424
490
575
603
666
715
763
864
993

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

316
355
407
473
496
540
581
617
698
800

258
291
333
387
406
441
475
505
571
653

243
273
311
361
378
410
441
468
528
600

289
329
382
450
474
522
564
605
693
811

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 126 of 159 -

TABLE L1 win
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

275
342
398
455
505
555
590
627
657
688
728

228
283
330
378
419
461
492
524
549
575
608

217
269
312
356
395
434
463
491
515
539
569

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

100
138
171
227
276
323
362
405
469
521
526

83
114
142
189
229
268
302
338
392
436
440

79
108
134
178
216
252
284
317
368
409
411

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 127 of 159 -

TABLE L1 win
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

312
391
455
525
584
645
686
733
768
807
857

247
309
360
414
460
508
543
579
607
638
676

232
289
337
386
429
472
504
536
562
589
623

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

113
157
196
262
319
375
420
473
548
612
619

90
124
155
207
252
295
333
374
433
484
489

84
116
145
193
235
274
309
346
401
447
450

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 128 of 159 -

TABLE L2 spr
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

258
320
371
424
471
517
550
584
611
640
676

219
272
316
362
402
441
471
500
524
549
580

209
259
300
343
380
417
444
471
494
516
545

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

94
129
160
212
257
301
337
377
436
485
489

80
110
136
181
220
257
289
323
374
416
419

76
104
129
171
208
242
273
304
352
392
394

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 129 of 159 -

TABLE L2 spr
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

295
369
430
495
550
607
646
690
723
759
805

240
300
349
402
446
492
526
560
588
617
653

226
282
328
375
417
458
489
520
545
571
604

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

107
148
185
247
301
353
396
445
516
576
582

87
121
150
200
244
286
322
362
419
468
472

82
113
141
187
228
266
300
336
389
433
437

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 130 of 159 -

TABLE L3 sum
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

241
298
346
395
438
481
511
543
568
595
628

210
260
302
345
383
420
448
475
498
521
550

200
248
287
328
363
398
424
449
471
492
519

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

87
120
149
197
240
279
314
350
406
451
454

76
105
130
172
209
244
275
307
355
395
398

73
100
124
163
199
231
260
290
336
373
375

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 131 of 159 -

TABLE L3 sum
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

278
347
404
465
517
570
607
647
679
712
755

232
289
337
387
430
473
506
538
565
592
627

219
272
317
362
402
442
472
501
525
550
581

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

101
140
174
232
283
331
372
418
484
540
546

84
116
145
193
235
275
310
348
403
449
453

80
110
136
181
220
257
289
324
375
417
420

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 132 of 159 -

TABLE L4 aut
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

254
315
365
417
463
508
540
574
601
629
664

217
270
314
359
398
437
466
495
519
543
574

207
257
298
340
377
413
440
467
489
512
540

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

92
127
157
208
253
295
331
370
429
477
480

79
109
135
179
218
254
286
320
370
412
415

75
103
128
170
206
240
270
302
349
388
390

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 133 of 159 -

TABLE L4 aut
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTED.
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

291
364
424
488
542
599
637
680
713
748
794

239
298
347
399
444
489
522
556
584
612
648

225
280
326
373
415
456
486
517
542
568
600

261
333
390
457
510
569
611
657
691
731
781

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

106
146
182
244
297
348
391
439
508
567
574

87
120
149
199
243
284
320
359
417
464
469

82
113
140
186
227
265
298
334
387
431
434

95
134
168
228
279
331
374
424
493
554
564

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 134 of 159 -

TABLE M1 win
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

274
336
394
449
503
548
589
621
650
678
713

226
278
326
371
415
454
487
515
541
565
595

215
278
326
371
415
454
487
515
541
565
595

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

99
136
170
224
275
319
361
401
464
514
515

82
112
140
185
227
264
299
332
386
428
430

78
106
133
175
215
249
281
313
363
402
403

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 135 of 159 -

TABLE M1 win
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

309
354
450
515
580
634
684
722
757
791
832

244
302
355
403
455
498
536
567
597
624
658

230
284
333
379
424
464
499
527
554
578
609

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

112
155
194
257
317
368
419
466
540
600
601

89
121
153
202
249
289
329
366
425
473
475

84
114
143
189
232
270
306
340
395
438
440

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 136 of 159 -

TABLE M2 spr
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

256
316
368
419
468
511
548
578
605
631
664

217
268
313
356
398
435
467
493
517
540
569

207
255
298
338
377
411
441
465
488
509
536

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

93
127
158
209
256
297
336
373
432
478
479

79
108
135
178
218
253
286
318
369
409
411

75
102
128
169
206
239
270
300
348
386
387

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 137 of 159 -

TABLE M2 spr
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

293
363
425
486
546
597
644
680
713
745
784

238
293
345
393
441
483
520
549
578
604
637

224
277
324
369
413
451
484
512
537
561
591

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

106
146
183
242
299
347
395
439
508
564
566

86
118
148
196
241
281
318
355
412
458
460

82
111
139
184
226
262
297
330
383
425
427

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 138 of 159 -

TABLE M3 sum
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

239
295
343
390
436
475
509
537
563
587
617

208
256
299
340
379
414
444
469
492
513
540

199
244
285
323
360
393
421
444
466
486
511

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

87
118
148
194
238
276
312
347
401
445
446

76
103
129
169
207
241
272
303
351
389
390

72
98
123
161
197
228
258
287
332
368
369

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 139 of 159 -

TABLE M3 sum
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

276
341
400
457
513
561
604
637
669
699
736

230
283
333
379
425
465
500
529
556
580
612

217
268
313
356
398
435
467
493
518
541
570

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

100
137
172
228
280
326
370
411
477
529
531

83
114
143
189
232
270
306
341
396
440
442

79
108
135
178
218
253
286
318
369
410
411

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 140 of 159 -

TABLE M4 aut
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

252
311
362
411
460
502
538
567
595
620
652

216
265
311
353
394
431
462
488
512
534
563

206
253
295
335
374
408
437
461
484
504
531

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

92
125
156
205
252
292
330
366
424
470
471

78
107
134
176
216
250
283
315
365
405
406

75
102
127
167
204
237
268
298
345
382
383

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 141 of 159 -

TABLE M4 aut
33kV THREE CORE OIL FILLED LEAD SHEATHED DUCTLESS.
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.55in2 Cu.
0.6in2 Cu

289
358
419
479
539
589
634
670
702
734
772

236
292
343
391
439
480
516
546
574
600
632

224
275
323
367
411
449
482
509
534
558
588

257
322
383
442
501
552
600
637
672
706
746

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.55in2 Al.
0.6in2 Al

105
144
180
239
294
342
389
432
501
556
557

86
117
148
195
240
279
316
352
409
455
457

81
111
139
183
224
261
295
328
381
423
424

93
129
165
221
274
321
367
411
479
535
538

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 142 of 159 -

TABLE N1 - win
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

384
431
484
553
575
620
662
692
762
835

317
356
399
459
477
514
549
575
635
696

299
336
376
431
448
482
514
538
593
648

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

299
336
379
436
456
491
529
557
622
696

247
277
313
362
378
407
439
463
518
581

234
262
295
340
355
382
411
433
484
541

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 143 of 159 -

TABLE N1 win
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Winter CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

441
498
561
645
672
727
779
817
904
998

346
390
439
506
526
569
609
639
709
781

323
364
408
469
488
526
562
589
651
714

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

344
388
440
508
532
576
622
656
737
830

270
304
344
398
417
451
487
514
578
651

252
284
320
370
387
417
449
474
531
596

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 144 of 159 -

TABLE N2 spr
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

358
401
450
515
535
576
614
643
707
774

304
341
382
439
456
491
524
548
605
662

288
323
362
414
430
462
493
515
567
620

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

279
313
353
406
424
457
491
517
577
645

237
266
300
346
361
389
419
441
494
552

225
252
284
326
341
367
394
415
463
517

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 145 of 159 -

TABLE N2 spr
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

416
469
528
607
632
683
731
767
849
935

336
378
425
490
509
550
589
617
684
752

315
354
397
456
474
510
545
571
630
691

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

324
366
414
478
500
541
584
616
692
779

262
295
333
386
404
436
470
497
558
627

246
276
311
359
375
405
436
459
515
576

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 146 of 159 -

TABLE N3 sum
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

333
373
419
478
497
534
570
596
656
717

290
325
364
417
433
466
497
520
573
626

276
309
345
395
410
441
469
491
540
589

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

260
291
328
377
394
424
456
479
535
598

226
253
286
329
343
370
398
419
468
523

215
241
271
312
325
350
375
395
441
492

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 147 of 159 -

TABLE N3 sum
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

390
440
495
569
592
639
685
718
794
874

324
364
409
471
490
528
565
593
656
720

304
341
383
439
457
492
525
549
606
664

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

304
343
388
448
469
507
547
577
647
728

253
284
321
371
388
419
452
477
535
601

237
266
300
346
362
390
420
442
495
554

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 148 of 159 -

TABLE M4 aut
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

352
394
442
505
525
565
603
631
594
759

301
338
379
434
451
486
518
542
598
654

286
320
359
410
426
458
488
510
562
613

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

274
308
347
398
416
448
482
507
567
633

235
263
297
342
358
385
414
437
488
546

223
250
281
324
338
363
390
411
459
512

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 149 of 159 -

TABLE M4 aut
33kV THREE CORE OIL FILLED LEAD CORRUGATED ALUMINIUM
SHEATHED DUCTLESS.
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Metric
Copper conductors
120mm2 Cu
150mm2 Cu
185mm2 Cu
240mm2 Cu
260mm2 Cu
300mm2 Cu
350mm2 Cu
400mm2 Cu
500mm2 Cu
630mm2 Cu

410
462
520
598
622
672
720
755
836
921

334
376
423
486
506
546
585
613
679
746

313
352
395
453
471
507
542
567
626
686

377
430
488
570
595
649
701
740
831
932

Aluminium conductors
120mm2 Al.
150mm2 Al.
185mm2 Al.
240mm2 Al.
260mm2 Al.
300mm2 Al.
350mm2 Al.
400mm2 Al.
500mm2 Al.
630mm2 Al.

319
360
408
471
492
533
575
607
681
766

260
293
331
384
401
433
467
493
554
622

244
274
310
357
373
402
433
457
511
578

294
335
382
448
471
514
559
594
676
774

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings based on Crater for oil filled cables.

ST:SD8B/3 (Part 3)

March 2009

- 150 of 159 -

TABLE O1 win
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Winter SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

257
316
377
429
480
519
559
594
613
677

217
267
317
361
404
437
472
502
521
573

207
255
301
342
382
413
445
473
491
539

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

199
245
293
334
375
411
439
469
488
544

168
207
247
281
316
346
371
396
413
460

161
198
234
266
298
327
350
373
389
432

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 151 of 159 -

TABLE O1 win
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Winter CYCLIC Current Ratings
SIZE AND TYPE OF CABLE
CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

285
354
425
487
547
594
641
684
709
789

235
291
348
398
448
487
526
561
584
646

222
275
327
373
419
455
492
524
544
601

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

222
274
330
379
427
470
504
539
562
632

182
225
270
309
349
385
414
442
462
517

172
213
254
290
327
359
386
412
430
480

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

0.9oC m/W

Ground Ambient Temperature

10oC

Air Ambient Temperature

10oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 152 of 159 -

TABLE O2 spr
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Spring SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

242
298
354
402
449
486
523
556
577
636

209
257
305
347
387
419
452
481
499
547

200
246
290
329
367
397
428
454
471
515

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

188
231
275
313
351
385
411
439
457
509

162
200
237
270
303
332
355
379
395
439

155
191
226
257
287
315
336
358
373
414

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 153 of 159 -

TABLE O2 spr
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Spring CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

272
336
403
462
518
562
607
648
673
748

228
283
338
386
434
471
509
543
565
624

217
268
318
363
407
442
477
508
527
581

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

211
261
314
360
405
445
477
510
532
597

177
219
262
300
338
373
400
428
446
499

168
208
247
282
317
349
374
400
417
465

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.05oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 154 of 159 -

TABLE O3 sum
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Summer SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

228
279
331
376
420
454
488
519
538
592

200
246
291
331
369
399
430
457
474
521

192
236
278
315
351
379
408
433
449
493

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

176
217
257
293
328
359
384
409
426
474

155
191
227
258
289
316
338
361
376
417

149
183
216
246
275
300
321
342
356
394

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 155 of 159 -

TABLE O3 - sum
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Summer CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

258
319
381
436
489
530
573
610
634
703

221
273
326
372
418
453
490
522
542
599

210
259
308
350
393
426
459
489
508
560

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

200
247
296
339
382
420
450
481
502
562

171
212
253
289
326
359
385
411
429
479

163
201
239
273
306
336
361
385
402
447

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.2oC m/W

Ground Ambient Temperature

15oC

Air Ambient Temperature

15oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 156 of 159 -

TABLE O4 aut
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Autumn SUSTAINED Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

SUSTAINED CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

239
293
348
396
442
478
515
547
567
625

207
255
302
344
384
415
448
476
494
543

199
244
288
327
364
394
424
450
467
513

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

185
228
271
308
345
378
405
432
449
500

161
198
235
268
300
329
352
375
391
435

154
189
224
255
285
312
333
355
370
410

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 157 of 159 -

TABLE O4 aut
33kV THREE CORE IMPREGNATED PRESSURE GAS CABLES.
Autumn CYCLIC Current Ratings

SIZE AND TYPE OF CABLE


CONDUCTOR

CYCLIC CURRENT RATINGS-AMPS


CABLE IN
GROUND

CABLE IN
DUCTS
PVC
Rigiduct

CABLE IN
AIR

Copper conductors
0.1 in2 Cu
0.15in2 Cu.
0.2in2 Cu.
0.25in2 Cu
0.3in2 Cu.
0.35in2 Cu
0.4in2 Cu
0.45in2 Cu
0.5in2 Cu
0.6in2 Cu

269
333
399
456
512
555
600
639
664
738

227
282
336
384
431
468
506
539
561
621

216
267
317
361
405
439
474
505
524
578

246
307
373
430
487
532
578
619
645
726

Aluminium conductors
0.1 in2 Al.
0.15in2 Al.
0.2in2Al.
0.25in2 Al.
0.3in2 Al.
0.35in2 Al.
0.4in2 Al.
0.45in2 Al
0.5in2 Al.
0.6in2 Al

209
258
310
355
400
439
471
504
525
590

176
218
261
299
336
370
398
425
443
495

167
207
246
281
316
347
372
398
415
462

191
238
290
335
381
421
454
488
511
580

Parameters
Maximum depth of lay

1m

Soil Thermal Resistivity (g)

1.1oC m/W

Ground Ambient Temperature

12oC

Air Ambient Temperature

12oC

Maximum Conductor Temperature

85oC

Ratings taken from Crater for Gas cables.

ST:SD8B/3 (Part 3)

March 2009

- 158 of 159 -

APPENDIX A
SUPERSEDED DOCUMENTATION
This document supersedes ST:SD8B/2 dated September 2003 which should now be
withdrawn.

APPENDIX B
ASSOCIATED DOCUMENTATION
ST: CA6A/2 -

Relating to the Installation of Underground Cables

APPENDIX C
IMPACT ON COMPANY POLICY
This Standard Technique has been updated to add all four seasons to the cable rating
document instead of just having one season as given in the previous document. In addition
the document has been broken up into manageable parts, with each part being for a
particular voltage level.

APPENDIX D
IMPLEMENTATION OF POLICY
This Standard Technique shall be communicated to all relevant WPD Planning and Control
staff at the next Team Briefing by the relevant Team Manager.

APPENDIX E
KEY WORDS
33kV Group Derating, Sustained Rating, Cyclic Rating, Distribution Rating, Laid Direct