Anda di halaman 1dari 8

Costumer:

Epli S.A.C.

Project:

SKID MOUNTED
SUBSTATION

Ttle:

Structural Calculation

Approval Control
Done
Rev.

Sign

Soproing

Checked
Date

Sign
Soproing

Notes
Date

INDEX
1.
1.1
1.2
1.3
1.4
1.5

GENERAL ................................................................................................... 3
REMARKS .................................................................................................................. 3
RELATIVE dOCUMENTATION .................................................................................. 3
SCOPE ....................................................................................................................... 3
DEFINITIONS AND ABBREVIATIONS ....................................................................... 3
SITE CONDITIONS .................................................................................................... 3

2.

INTRODUCTION ......................................................................................... 4

3.

OBJETIVES ................................................................................................. 4

4.

SKID MOVIL SUB STATION DESCRIPTION ............................................ 5

5.

UNITS .......................................................................................................... 5

6.

MATERIALS ................................................................................................ 5

7.

StandarDS AND REGULATIONS .............................................................. 6

8.

RESULT: ..................................................................................................... 7

8.1 Study Case ................................................................................................. 7

1. GENERAL
1.1 REMARKS
This structural analysis was conducted considering the most critical conditions or service, or
maneuvering or lifting.

1.2 RELATIVE DOCUMENTATION


This specification is relative and based on the following documents.
Doc.

Doc. No.
5550-SS-825

Descripcin
General Arragement
Data SHeet Skind Mounted Sub Station

1.3

SCOPE
The analysis and the result shown include service conditions and terms of hoisting frame
structure (called a platform) and all components required for each case.

1.4 DEFINITIONS AND ABBREVIATIONS


Name
MPa

Descripcin
Mega Pascal

ASTM

American Society for Testing and Materials

AISC

American Institute of Steel Construction

1.5 SITE CONDITIONS


Altitud:
Ssmic:

4500 m.a.s.l.
Reglamento Nacional de Construcciones, E.030,
zona 3

2.

INTRODUCTION
The mobile Sub-station consists of a structure that contains a single module.
Module has the following dimensions: 13 000 x 3 500 x 3 500 mm
The study should demonstrate that the structural deck profiles have a higher resistance than the
maximum permissible resistance indicated by the appropriate standard (ANSI / AISC 360-05 ASD).
Was used to calculate Solidworks.

3.

OBJETIVES
The frame of the mobile Sub-station will be analyzed based on one case studies.
LIFTING scenary is the most critical The mobile Unit Sub Station will be analysed considered:
-

Uniform load of 1000 Kg /m2 (10 kN), twice of specification (5 kN)


The result should shown that structural members will be enough resistance
The weight of enclosure and roo mis considered into the uniform load 10kN

Figura 1. Movil Sub Station

4.

SKID MOVIL SUB STATION DESCRIPTION


The mobil Sub Station consists of a main structure, are made of a frame of beams rigidly together
by welding and completely covered the walls and roof panels made of steel sheet cold forming.
The modules making up the main structure are joined together by bolts.
The main structure has the following general areas:
Length 13 000 mm,
Width 3 500 mm
Height 4 100 mm

Green Color C-beam (two elements) for Fused Load Break Switch (3 100 kg)
Violet Color C-beam (three elements) for transformer (6 850 kg)

5.

UNITS
The units used will correspond to the International System.

6.

MATERIALS
All profiles W, C, L and floor plate shall be ASTM A-36 steel.
The tubes square lattice walls and ceiling will LAC Steel ASTM A-36.
tem

Descripcin

ASTM A-36

Modulo de Elasticidad (MPa)

Limite de Fluencia (MPa)

250

Limite de Rotura (MPa)

400

Limite de Tensin (MPa)

2.1x105

7.

Coeficiente de Poisson

Densidad (kg/m3)
7850
Tabla 1.- Propiedades del material

0.3

STANDARDS AND REGULATIONS


Structural Analysis of the Electrical Room will be based on the following:
ANSI / AISC 360-05 - Method ASD

8.

RESULT:
8.1 STUDY CASE
The most critical scenary is when the complete unit is lifting, so this is our analisys
Model Loaded

Each C-beam is loaded with 2 700 kg (27 kN)


Stresses Diagram (maximun permited: 250 MPa)

The maximun stress is 103 MPa

Deflection Diagram
Maximun permited (L/240) 16.7 mm

According to the diagram the maximun is 11.5 mm.


Security Factor Diagram, minimun expected: 2

The minimum acoording to the diagram is 2.4


According to the results, the estructure is satisfactory