Dear Achim,

1)

UCTE Line:

a)
Current limit for real element should be positive (if not warn and Use
Zero)
Current limit for equivalent and busbar coupler element should be blank or posit
ive (if not warn and Use Zero)
b)
R and X should be positive for real element ( If not stop the module - F
ATAL. )
R and X can be both positive and negative) for equivalent element ( If not stop
the module - FATAL. )
B for real and equivalent element should not be blank (if blank Warn and use zer
o)
R and X and B value for busbar coupler should be Zero (If not it is warned and
use zero). In PSSE we need to keep a small reactance value (0.000100 pu).
Absolute value of X for both real and equivalent element must be greater than 0
.05. (if not warn and use 0.05)
2)
UCTE Transformers:
a)
Current limit for real element should be positive (if not warn and Use
Zero)
Current limit for equivalent should be blank or positive (if not Warn and use Ze
ro)
b)
R and X should be positive for real element ( If not stop the module - F
ATAL. )
R and X can be both positive and negative for equivalent element ( If not stop t
he module - FATAL. )
Absolute value of X for both real and equivalent element must be greater than 0
.05.
G for both real and equivalent element must be positive or zero (if not w
arn and use zero)
B for both real and equivalent element can be positive or negative (if bl
ank warn and use zero)
3)
UCTE Transformer regulation
a)
Delta V and Delta U Value should not be above 6 % or less than (Warn an
d use the same value)
b)
No of (Voltage and angle ) Taps should not be above 35 or below zero. (W
arn and use the same value)
c)
Absolute value of Angle cannot exceed 180 degree (Warn and use the same
value)
d)
Target voltage must be smaller than or equal to (Un + n * delta U *Un/
100) and greater than or equal to (Un - n * delta U *Un/100). (If not warn and
use the same value as given).
I assumed all these things should have been mentioned somewhere in Detail Specif
ication. Now I have to analyze all these things and spend my time on these thing
s.
With best regards,
Madhusudhan Srinivasan
Siemens plc
RC-GB EM SG PTI
Princess Road, Princess Parkway
Manchester M20 2UR, Grobritannien und Nordirland

Tel.: +44 1614 466850


Mobil: +44 7808 828529
mailto:madhusudhan.srinivasan@siemens.com
Siemens plc registered office: Faraday House, Sir William Siemens Square, Frimle
y, Camberley, GU16 8QD. Registered no: 727817, England.
This communication contains information which is confidential and may also be pr
ivileged. It is for the exclusive use of the addressee. If you are not the addre
ssee please note that any distribution, reproduction, copying, publication or us
e of this communication or the information is prohibited. If you have received t
his communication in error, please contact us immediately and also delete the co
mmunication from your computer.

Anda mungkin juga menyukai